Ss.40477 (Distribution SS) Ss.40474 (Distribution SS) : Notes
Ss.40477 (Distribution SS) Ss.40474 (Distribution SS) : Notes
GOLF
310
DISTRICT
GDW-01
GOLF
580.326
COURSE
WEST
213593.8
GCR-01
RESIDEN
06
TIAL
T 1/6 R50
T 1/6 R50
RESIDENTIAL
WFR-03
WATERFRONT
212097.142
T 1/6 R50
T 1/6 R50
WATERFRONT092.967
211
WFR-02
RESIDENTIAL
GSD-03 DISTRICT
T 1/6 R50
GOLF
GSD-03
030.712
612
GOLF
T 1/6 R50
611GDS-02
DISTRICT
233.550
T 1/6 R50
FOX
412
FXH-05
HILLS
321.987
WATERFRONT
210046.655
WFR-01
RESIDENTIAL
GOLF
610 DISTRIC
GDS-01
485.738
T
T 1/6 R50
R50
1/6
T
EDUCATION
510 844.130
EDD-03
MEDICAL
DISTRICT
312 728.251
MEC-01
DISTRICT
T 1/6 R50
R50
1/6
T
T 1/6 R50
T 1/6 R50
FOX
411
FXH-04
HILLS
843.970
T 1/6 R50
DISTRICT
EDUCATION
EDD-02
313 342.335
WATERFR
TCL = 10345kVA
112 WFC-04
ONT
416.575
T 1/6 R50
COMMER
T 1/6 R50
CIAL
411
FOX
FXH-03
337.899
HILLS
MDL = 6522 kVA
05R 6/1 T
MDL = 6554 kVA
SS.40477 (DISTRIBUTION SS)
EDUCATION
T 1/6 R50
314 176.193
EDD-01
05R 6/1 T
DISTRICT
SS.40474 (DISTRIBUTION SS)
WATERFRONT
111 799.483
WFC-03
CENTRAL
810 000.000
COMMERCIAL
PZC-01
PZC-01
PLAZA
NORTH
BLN-01
BOULEVARD
810 921.731
T 1/6 R50
T 1/6 R50
410 850.520
FOX HILLS
FXH-02
NORTH
BLN-02
BOULEVARD
264.678
811
810 911.858
BLS-01
SOUTH
BOULEVARD
T 1/6 R50
811 254.805
T 1/6 R50 BLS-02 SOUTH
BOULEVARD
T 1/6 R50
T 1/6 R50 T 1/6 R50
05R 6/1 T
05R 6/1 T
T 1/6 R50
T 1/6 R50
R50
1/6
T
WATER
T
1/6
R50
T
6/
1
05R 6/1 T
05
R
T 1/6 R50
FRONT
111
WFC-02
COMME
196.254
RCIAL
05R 6/1 T
410 355.752
FOX HILLS
FXH-01
TCL = 5736 kVA TCL = 4609 kVA TCL = 5400 kVA
05R 6/1 T
WATERF
ENERGY
RONT
512 678.033
EC2-01
110
WFC-01
COMME
786.935
CITY
RCIAL
MDL = 3631 kVA MDL = 2923 kVA MDL = 3428 kVA
QATAR
ENTERTAINMEN
110
QEC-02
231.879
T CITY
NOTES:
- THE LOCATION OF PRIVATE SUBSTATIONS ARE
INDICATIVE ONLY. THE EXACT LOCATION SHALL BE
FINALIZED DURING RESPECTIVE BP PROCESSING.
- ALL 11KV CABLES ARE 3C-300mm² XLPE+ FO CABLES.
THE 3C-300mm² CABLES ARE LAID AT A SPACING OF
50CM THUS REDUCING THE CURRENT CARRYING
CAPACITY TO THAT OF 3C-240mm².
- IN ALL SECONDARY SUBSTATION FEEDER BREAKERS
SHALL BE PROVIDED WITH DIRECTIONAL
OVER CURRENT AND DIRECTIONAL EARTH FAULT
PROTECTION (TYPE4).
- THE LOCATION OF ALL ELECTRICAL EQUIPMENT SUCH
AS FEEDER PILLAR, KWHR METER, SERVICE CABINET,
TCL = 9770 kVA TCL = 9934 kVA
MDL = 6206 kVA MDL = 6304 kVA MINI PILLAR ETC, ARE INDICATIVE ONLY. THE EXACT
SS.40476 (DISTRIBUTION SS) SS.40473 (DISTRIBUTION SS) LOCATION WILL BE AS PER THE AS-BUILT DRAWINGS.
TCL = 5392 kVA TCL = 4378 kVA TCL = 4830 kVA TCL = 5104 kVA - IN CASE DETAILS/ MATERIALS ON THE DRAWINGS
MDL = 3434 kVA MDL = 2772kVA MDL = 3066 kVA MDL = 3238 kVA
CONTRADICT WITH KM STANDARDS AND
SPECIFICATION, THEN THE LATER SHALL PREVAIL.
- COMPLETE DISTRIBUTION DESIGN RESPONSIBILITY TO
THE INFRASTRUCTURE CONSULTANT.
- CLIENT TO APPOINT A KM APPROVED
CONTRACTOR TO EXECUTE WORK AT SITE.
- TARIFF METERING FOR ALL LUSAIL PROJECTS ARE AT
THE LV SIDE, EXCEPT OTHERWISE STATED.
- LV CABLES ARE LAID AT A SPACING OF 40CM.
- ALL PERMANENT SECONDARY SUBSTATIONS ARE
INDOOR TYPE.
- ALL 11KV SWITCHGEARS SHOULD BE KM STANDARD
WITH 31.5 KA/3SEC FAULT RATING.
- THIS SCHEME IS SUBJECT TO ALL CONDITIONS
MENTIONED IN THE APPROVAL LETTER REF.NO.
EP/MO/3378/2023. DATED: 24-09-2023.
- ALL DISTRIBUTION SUBSTATIONS ARE STANDARD
DOUBLE INDOOR TYPE WITH 4x 1600 KVA OIL TYPE Tx,
4x 6W FSFP, WITH NATURAL VENTILATION,
STANDALONE AT GROUND FLOOR.
INFRASTRUCTURE PROJECT.
TCL = 10245 kVA TCL = 10717 kVA ALL MATERIAL & LABOR BY CLIENT.
MDL = 6524 kVA MDL = 6824 kVA ALL COST TO CLIENT. NO COST TO KM.
SS.40472 (DISTRIBUTION SS) SS.40467 (DISTRIBUTION SS)
TCL = 5185 kVA TCL = 5060 kVA TCL = 5271 kVA TCL = 5446 kVA
MDL =3312 kVA MDL = 3212 kVA MDL = 3355 kVA MDL = 3469 kVA * A DIVERSITY OF (0.8x0.8) IS APPLIED
FOR TRANSFORMER SIZING PURPOSE.