ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : UPS Room Ground floor /10-09-2023


2. Board Name / Panel No. : Testing Panel -2
3. Feeder Name / No. : INCOMER

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6436 Accuracy Class 1.0
SR. No. 34140233717
Rated Voltage 400 V-600 V AC
CT Ratio 400/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


15.10 15.00 0.662251656

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : UPS Ground floor Burning Room /10-09-2023


2. Board Name / Panel No. : Plant Distribution Panel
3. Feeder Name / No. : INCOMER

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6436 Accuracy Class 1.0
SR. No. 540420080566
Rated Voltage 400 V-600 V AC
CT Ratio 100/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


20.10 20.00 0.497512438

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : UPS Ground floor Burning Room /10-09-2023


2. Board Name / Panel No. : Plant Distribution Panel
3. Feeder Name / No. : Outgoing -1

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6436 Accuracy Class 1.0
SR. No. 540420080563
Rated Voltage 400 V-600 V AC
CT Ratio 100/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


20.15 20.00 0.744416873

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : UPS Ground floor Burning Room /10-09-2023


2. Board Name / Panel No. : Plant Distribution Panel
3. Feeder Name / No. : Outgoing -3

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6436H Accuracy Class 1.0
SR. No. 540420080565
Rated Voltage 400 V-600 V AC
CT Ratio 100/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


20.15 20.07 0.397022333

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : UPS Ground floor Burning Room /10-09-2023


2. Board Name / Panel No. : Plant Distribution Panel
3. Feeder Name / No. : Outgoing -4

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6436H Accuracy Class 1.0
SR. No. 540420080564
Rated Voltage 400 V-600 V AC
CT Ratio 100/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


20.08 20.00 0.398406375

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : UPS Ground floor /10-09-2023


2. Board Name / Panel No. : MCB Line Panel UPS Ground Floor
3. Feeder Name / No. : VTPN-5

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6400NG Accuracy Class 1.0
SR. No. 340160001117
Rated Voltage 400 V-600 V AC
CT Ratio 150/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


25.10 25.00 0.398406375

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : First floor /10-09-2023


2. Board Name / Panel No. : Production Panel
3. Feeder Name / No. : Outgoing to BBT-1 (1ST Floor)

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6400NG Accuracy Class 1.0
SR. No. 340160001091
Rated Voltage 400 V-600 V AC
CT Ratio 150/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


25.18 25.10 0.31771247

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : First floor /10-09-2023


2. Board Name / Panel No. : Production Panel
3. Feeder Name / No. : Outgoing to VTPN BBT

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6400NG Accuracy Class 1.0
SR. No. 340160001078
Rated Voltage 400 V-600 V AC
CT Ratio 150/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


30.00 29.84 0.533333333

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 11/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : First floor /10-09-2023


2. Board Name / Panel No. : Burn in Panel First Floor
3. Feeder Name / No. : Testing area

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6400NG Accuracy Class 1.0
SR. No. 340160001075
Rated Voltage 400 V-600 V AC
CT Ratio 200/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


30.00 29.79 0.7

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 10/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : First floor /10-09-2023


2. Board Name / Panel No. : Burn in Panel Ground Floor
3. Feeder Name / No. : Incomer

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6436 Accuracy Class 1.0
SR. No. 340160001075
Rated Voltage 400 V-600 V AC
CT Ratio 600/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


25.00 24.85 0.6

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 10/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : Shop Floor /10-09-2023


2. Board Name / Panel No. : GRIR Clearing I/C SSB-1
3. Feeder Name / No. : I/C SSB-1

4. Specification:
Make Multispan Aux voltage 44-300V AC/DC
Model No. AVH13N Accuracy Class 1.0
SR. No. 200318415
Rated Voltage 400 V-600 V AC
CT Ratio 400/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


20.00 19.85 0.75

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 10/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : Compressor Room /10-09-2023


2. Board Name / Panel No. : Compressor Panel
3. Feeder Name / No. : Incomer

4. Specification:
Make Schneider Aux voltage 44-300V AC/DC
Model No. EM6436 Accuracy Class 1.0
SR. No. 340160001079
Rated Voltage 400 V-600 V AC
CT Ratio 400/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


25.00 24.85 0.6

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 10/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : Shop Floor /10-09-2023


2. Board Name / Panel No. : MLSB- DTA -1
3. Feeder Name / No. : Incomer

4. Specification:
Make Multispan Aux voltage 44-300V AC/DC
Model No. AVH13N Accuracy Class 1.0
SR. No. 200318408
Rated Voltage 400 V-600 V AC
CT Ratio 400/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


30.00 29.87 0.433333333

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 10/09/2023
ENERGY METER CALIBRATION - TEST REPORT

1. Location /Date : Shop Floor /10-09-2023


2. Board Name / Panel No. : SSB-2 (Engg Control Room)
3. Feeder Name / No. : Incomer

4. Specification:
Make Multispan Aux voltage 44-300V AC/DC
Model No. AVH13N Accuracy Class 1.0
SR. No. 200318421
Rated Voltage 400 V-600 V AC
CT Ratio 400/5

5. Meter Calibration :-

Applied KiloWatt Hour Measured KiloWatt Hour % of Error


35.00 34.85 0.428571429

6. Remarks : Calibration satisfactory

Tested BY Dated Signature


Name S.Ashok Kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : HVAC Panel -2
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123171
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 412.1 413.5 415 412 413.1 414.3 0.024266 0.096735 0.168675

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Shop Floor Sub Lightning Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123177
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 415 414.2 415 414.8 414 412 0.048193 0.048286 0.722892

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Shop Floor Power Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123173
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 416 417 415 415.8 417.1 416.1 0.048077 -0.02398 -0.26506

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : MCB Line Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123176
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 415 416 417 415.8 416.5 416.2 -0.19277 -0.12019 0.191847

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : HVAC Panel-1
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34143912940
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 416 419 418 415.8 418 417.5 0.048077 0.238663 0.119617

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Power Panel admin (option -A)
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 3414523264
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 416 420 420.7 416.1 420.2 420 -0.02404 -0.04762 0.166389

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Main Lightning Panel (option -A)
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123170
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 417 417.3 419.9 416.5 417 419 0.119904 0.071891 0.214337

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : UPS Panel admin
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123170
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 398 397 398 397.5 396 396 0.125628 0.251889 0.502513

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : Ground Floor /10-09-2023


2. Board Name / Panel No. : Substation Aux Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123170
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 419 416 421 418 415 418.2 0.238663 0.240385 0.665083

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Admin Sub Lightning
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123179
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 411 405 408 410 406 409 0.243309 -0.24691 -0.2451

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : HVAC Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901170872
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 411.8 410.9 414 411.2 410.8 413.5 0.145702 0.024337 0.120773

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Production Panel 1st floor
3. Feeder Name / No. : Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901170832
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 409.7 409.4 413 408.6 409 413.5 0.268489 0.097704 -0.12107

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : UPS -2 Panel 1st floor
3. Feeder Name / No. : Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901175671
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 393 393.3 392.1 392.5 393.2 391 0.127226 0.025426 0.280541

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : First Floor change over panel
3. Feeder Name / No. : Stabilizer -1 Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901061700
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 389.1 388 392 389.5 389 391.2 -0.1028 -0.25773 0.204082

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : First Floor change over panel
3. Feeder Name / No. : Stabilizer -2 Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901170845
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 389.5 388.6 392.5 388.2 388.4 391.2 0.333761 0.051467 0.33121

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : From Substation Main lt panel-2
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901061705
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 414.1 414.2 416.8 413.9 414.3 416.9 0.048298 -0.02414 -0.02399

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : New Burn in Panel
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901170870
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 390.2 388 392 390.3 388.2 392.3 -0.02563 -0.05155 -0.07653

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : UPS -1 Panel FF
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901175669
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 393.6 393.8 393.6 393 393 393 0.152439 0.203149 0.152439

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : Burn in Panel
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901170831
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 414 414 416 413.8 412.8 415.2 0.048309 0.289855 0.192308

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor DTA -1 OFFICE /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : DTA UPS Panel
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123174
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 415 416 419 414.2 415.2 418 0.192771 0.192308 0.238663

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor DTA -1 OFFICE /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : DTA Power Panel
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123175
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 415 416 419 417 417 418 -0.48193 -0.24038 0.238663

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
VOLT METER - TEST REPORT

1. Location /Date : First Floor DTA -1 OFFICE /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : DTA Sub Lightning Panel
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3210 Accuracy Class 1.0
SR. No. 34145123172
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied voltage Measured Voltage % of Error
Volt RY YB BR RY YB BR RY YB BR
meter 415 416 419 416 415.2 418.5 -0.24096 0.192308 0.119332

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : HVAC Panel -2
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144023186

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 7.13 6.14 7.15 7.11 6.1 7.18 0.280505 0.651466 -0.41958

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Shop Floor Sub Lightning Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34143930829

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 2.19 2.15 0 2.18 2.14 0 0.456621 0.465116 **

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use, B-Phase CT to be Check

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Shop Floor Power Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34145123173

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 5.1 5.5 6.3 5.2 5.2 6.25 -1.96078 5.454545 0.793651

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : MCB Line Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34145123176
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 5 5.2 5.2 4.97 5.21 5.19 0.6 -0.19231 0.192308

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : HVAC Panel-1
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34143912940
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 50 53 50 49.8 52.74 50.1 0.4 0.490566 -0.2

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Power Panel admin (option -A)
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144431170

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 3.4 8.1 3.3 3.38 8.04 3.28 0.588235 0.740741 0.606061

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : Main Lightning Panel (option -A)
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144023182
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 4.9 5.6 7.3 4.89 5.58 7.28 0.204082 0.357143 0.273973

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : UPS Ground Floor /10-09-2023


2. Board Name / Panel No. : UPS Panel admin
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144023189

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 1.11 2 1.8 1.1 1.98 1.79 0.900901 1 0.555556

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : Ground Floor /10-09-2023


2. Board Name / Panel No. : Substation Aux Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144511567

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 2.5 1.4 2.2 2.48 1.39 2.19 0.8 0.714286 0.454545

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Admin Sub Lightning
3. Feeder Name / No. : Incomer
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144023193
Rated Voltage 400 V-600 V AC

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 0 0 0 0 0 0 #DIV/0! #DIV/0! #DIV/0!

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Not working.

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : HVAC Panel
3. Feeder Name / No. : Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244355

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 6.2 5.5 9.7 6.18 5.48 9.68 0.322581 0.363636 0.206186

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Production Panel 1st floor
3. Feeder Name / No. : Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244374

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 6.3 5.5 9.7 6.28 5.48 9.68 0.31746 0.363636 0.206186

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : UPS -2 Panel 1st floor
3. Feeder Name / No. : Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244356

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 3.2 1.7 1.37 3.18 1.69 1.38 0.625 0.588235 -0.72993

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : First Floor change over panel
3. Feeder Name / No. : Stabilizer -1 Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244370

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 5 5 5 4.96 4.98 4.98 0.8 0.4 0.4

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : First Floor change over panel
3. Feeder Name / No. : Stabilizer -2 Incomer
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244362

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 5 5 5 4.97 4.98 4.96 0.6 0.4 0.8

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : From Substation Main lt panel-2
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244371

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 22 20.07 25.59 21.91 20.01 25.51 0.409091 0.298954 0.312622

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : New Burn in Panel
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244378

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 24.21 24.21 25.36 24.18 24.11 25.31 0.123916 0.413052 0.197161

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : UPS -1 Panel FF
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244367

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 3.3 2.5 2.4 3.29 2.48 2.38 0.30303 0.8 0.833333

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : Burn in Panel
4. Specification:

Make Rishab Aux voltage 44-300V AC/DC


Model No. EINE Accuracy Class 1.0
SR. No. 1901244361

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 13.6 13.93 13.01 13.58 13.92 12.95 0.147059 0.071788 0.461184

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor DTA -1 OFFICE /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : DTA UPS Panel
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144431181

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 13.6 13.93 13.01 13.58 13.92 12.95 0.147059 0.071788 0.461184

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor DTA -1 OFFICE /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : DTA Power Panel
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34143930831

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 15 15 15 14.89 14.85 14.89 0.733333 1 0.733333

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : First Floor DTA -1 OFFICE /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : DTA Sub Lightning Panel
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34144023187

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 15 15 15 14.91 14.92 14.93 0.6 0.533333 0.466667

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023
AMMETER - TEST REPORT

1. Location /Date : Substation - 1 /10-09-2023


2. Board Name / Panel No. : Sub Panel
3. Feeder Name / No. : Compressor main LT-1
4. Specification:

Make Schneider Aux voltage 44-300V AC/DC


Model No. DM3110 Accuracy Class 1.0
SR. No. 34143742774

5. Secondary Injection Test:-


Test Unit Applied Current Measured Current % of Error
AMMETE R Y B R Y B R Y B
R 15.36 15.91 15.57 15.29 15.84 15.47 0.455729 0.439975 0.642261

6. Operational Checks:-
a. Correct Programming of meter Yes
b. Correct Button Operation Yes

7. Remarks:- Fit for use

Tested BY Dated Signature


Name S.Ashok kumar 10/09/2023