Transformer Connections
Transformer Connections
25-02-2021 4
Set under test:
Three nos. single phase transformer
each of 50 Hz, 1-phase, 1 kVA,
220/110 V (Divided in two equal
halves)
25-02-2021 5
OBJECT OF THE EXPERIMENT
1. Six-phase connections of transformers (Delta/Double Star,
Delta/Double Delta) to obtain six-phase supply from three-
phase source
2. Zig-zag connection of transformers (Delta/Zigzag) to obtain
three-phase supply suitable for unbalanced loads by
interconnecting different phases.
APPARATUS REQUIRED
25-02-2021 6
V = V1 + V2 V = V1 - V2
A.C. POLARITY TEST
+
V1 V2
25-02-2021
When V = V1 - V2 , a2 is (-) and a1 is (+) 7
Transformer terminals
SUPPLY
25-02-2021 8
EXPERIMENT DESK
POLARITY TEST RESULTS
+ - - + - +
+ - + - - +
+ - + - + -
a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
A1 B1 C1 A2 B2 C2
+ + + - - - - - - + + + - - - + + +
25-02-2021 9
THE LABORATORY SET-UPS
25-02-2021 11
Transformer windings and terminal markings
A1 A2
+ -
B1 B2
+ -
C1 + - C2
a1 - + a2 a3 - + a4
b2 + - b1 b3 - + b4
c2 + - c1 c4 + - c3
25-02-2021 12
A1 B1 C1 A2 B2 C2
+ + + - - -
C1 A2
C A
C2
A1
B1 B B2
25-02-2021 13
(A) DELTA-DOUBLE STAR a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
(Neutrals not connected)
- - - + + + - - - + + +
4 5
a4 c1
1
4
n(+) n’ (-) b4
3 6
b1 (a2,b2,c2) (a3,b3,c3)
6
c4 3
a1
2 1
n 2 n’
5
SECONDARY (DOUBLE STAR CONNECTION)
Neutrals not connected SECONDARY WINDINGS
Neutrals not connected
25-02-2021 14
(A) DELTA-DOUBLE STAR a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
(Neutrals not connected)
- - - + + + - - - + + +
C1 A2
4 5
a4 c1
n(+) n’ (-)
3 6
V b1 (a2,b2,c2) (a3,b3,c3) b4
c4 a1
C2 2 1
For 220 V/110 V
A1 transformer
SECONDARY
B1 PRIMARY B2
V1n = V3n = V5n = V2n’ = V4n’ = V6n’ = V
For 1:1 turns ratio, and two
secondaries having same number of V12 = V23 = V34 = V45 = V56 = V61 = 0
turns, V14 = V25 = V36 = 0
25-02-2021
V13 = V51 = V35 = V24 = V46 = V62 = 3 V15
LABORATORY SET UP: MAIN SWITCH
25-02-2021 16
SWITCH FUSE UNIT
SWITCH FUSE UNIT
25-02-2021 FUSE 17
TRANSFORMER TERMINALS
SUPPLY
EXPERIMENT DESK
25-02-2021 18
MEASURING INSTRUMENT USED
A.C. VOLTMETER
25-02-2021 19
(B) DELTA-DOUBLE STAR a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
(Neutrals connected)
- - - + + + - - - + + +
C1 A2
a4 4 5
c1
n
3 6
V b1 (a2,b2,c2) (a3,b3,c3)
b4
a1
c4 For 220 V/110 V
C2 2 1 transformer
A1 SECONDARY
B1 PRIMARY B2 V1n = V2n = V3n = V4n = V5n = V6n = V
For 1:1 turns ratio, and two V12 = V23 = V34 = V45 = V56 = V61 = V
secondaries having same number of
V14 = V1n + Vn4 = V + V = 2V
turns,
Similarly, V25 = V36 = 2V
25-02-2021 V13 = V35 = V51 = V24 = V46 = V62 = 3 V20
(C) DELTA-DOUBLE DELTA a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
(without 6-phase
resistive load) - - - + + + - - - + + +
C1 A2
c1, a2 5
a4, b3 b4, c3
4 6
b1, c2
C2 1
3
A1 a1, b2
a3, c4
B1 PRIMARY B2 2
For 220 V/110 V
transformer
For 1:1 turns ratio, and two SECONDARY
secondaries having same number of V31 = V15 = V53 = V24 = V46 = V62 = V
turns,
V12 = V23 = V34 = V45 = V56 = V61 = 0
25-02-2021 21
V14 = V25 = V36 = 0
DELTA-DOUBLE DELTA a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
(with 6-phase resistive
load) - - - + + + - - - + + +
5 4
C1 5
A2
4 6
B1 A1 2
B2
PRIMARY SECONDARY 2 1
25-02-2021 22
(D) DELTA-DOUBLE DELTA a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
(with 6-phase resistive
load) - - - + + + - - - + + +
C1 A2
c1, a2 5
a4, b3 b4, c3
4 6
b1, c2
C2 1
3
A1 a1, b2
a3, c4
B1 PRIMARY B2 2 For 220 V/110 V
transformer
25-02-2021 24
(E) DELTA- ZIGZAG a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
- - - + + + - - - + + +
C1 A2 1
a4
a3, c1 4
6 n
a2, b2 , c2
V c3, b1
3 b4 2
c4 a1, b3
C2 5
For 220 V/110 V
A1 transformer
SECONDARY
B1 PRIMARY B2
V12 = V23 = V31 = 3V
For 1:1 turns ratio, and two V1n = V2n = V3n = 3V
secondaries having same number of V4n = V5n = V6n = V
turns,
V16 = V24 = V35 = 2V
25-02-2021 25
REPORT
25-02-2021 26