CL-6A Quik-Study Car d

Voltage Limiter High Status Check


Out-Of-Band High with Metering-PLUS™
Out-Of-Band Low Feature
Voltage Limiter Low
+
Tapping Blocked
Edit /
Function
Reverse Power Reset

1 2 3 4
Voltage Reduction
* Comp
*Load
*Load
* Tap
Voltage Voltage Current Position
Escape Enter
5 6 7 8

Settings Features Counters Metering

Comp Voltage 125.0 9 0 Tap Position 8


Band 119.0-121.0 Alarms / Diag-
Using Func 1-5 Events nostics SOFT-ADD-AMP -8, 8
- P.I. ADD-AMP -16, 16

Load Voltage 115.0 Load Current 600 Fwd


Limiter 114.0-126.0 Current Threshold 12
Mode Bi-directional
Blocked: Cntrl Switch

Flash Card Active


Write FC 350
Flash Card Port
Flash card used to
Flash Card save, write, and load
information to and
Flash Card Active
from control.
Save/Load FC 351–354

Enter Security Code: Navigation Edit/Change Parameter


9 9
Function > > > Enter (key in numeric
Alarms / Alarms / Edit /
Events Events Reset > value or scroll > Enter
through options)
(key in the
Use Function Code: Function > > Enter
function code #)
(key in the
Function > >
5 6 7 8 function code #) Enter
Use Menu or or or > Enter
Structure: Settings Features Counters Metering

Language/Idioma/Langue Function > *Comp1 > * Tap 4 > *Comp1 > Enter
Voltage Position Voltage
Main Menu Sub-Menu FC Sample Parameters Factory Setting
Forward Direction 001 Forward Set Voltage 120.0
002 Forward Bandwidth 2.0
5
003 Forward Time Delay 45
Settings 004 Forward Line Drop Compensation R 0.0
005 Forward Line Drop Compensation X 0.0
Reverse Direction 051 Reverse Set Voltage 120.0
052 Reverse Bandwidth 2.0
053 Reverse Time Delay 45
054 Reverse Line Drop Compensation R 0.0
055 Reverse Line Drop Compensation X 0.0
Configuration 040 Regulator Identification panel serial number
140 Regulator Type per nameplate
049 Tap-Changer Type* per nameplate
041 Regulator Configuration per nameplate
042 Control Operating Mode Sequential
043 System Line Voltage per nameplate
044 Overall P.T. Ratio per nameplate
045 C.T. Primary Rating per nameplate
046 Demand Time Interval 15.0
144 P.I. ADD-AMP High Limit 16
145 P.I. ADD-AMP Low Limit -16
146 Vin P.T. Configuration Vdiff Mode
Calendar/Clock
Menu System

Auto-Block Status 069 Auto Operation Blocking Status* Normal


5 Reverse Power Mode 056 Reverse Sensing Mode Locked Forward
Source-Side Voltage Calculation 039 Source-Side Calculation On
Settings
Voltage Limiter 080 Voltage Limiter Mode Off
Voltage Reduction 070 Voltage Reduction Mode Off
Tap-to-Neutral
SOFT-ADD-AMP™ Feature
Communications
Calibration
Compact Flash 350 Data Writer NA
Turn Display Off 351 Load Custom Configuration NA
6 352 Load Standard Configuration NA
Operations Counter 353 Save Custom Configuration NA
Features 354 Save Standard Configuration NA
355 Format Compact Flash Card NA
8
Instantaneous
Forward Demand * For quick troubleshooting, check
Metering Reverse Demand FC 49 Tap Changer Type and
Master Reset + FC 69 Auto Block Status.
Edit /
Function
Reset
9 Alarms Active Unacknowledged
1 2 3 4
Alarms / Alarms Active Acknowledged *Comp
*Load
*Load
* Tap
Events Events Escape
Voltage Voltage Current Position
Enter
5 6 7 8

Settings Features Counters Metering


0
Control
9 0
Communications
Diag- Alarms / Diag-

nostics Maintenance Events nostics

Metering-PLUS™ Feature -

©2004 Cooper Power Systems, Inc.


Metering-PLUS™ and SOFT-ADD-AMP™ 1045 Hickory Street
are trademarks of Cooper Industries, Inc. Pewaukee, WI 53072
www.cooperpower.com
Bulletin 04008 • April 2004 • New Issue