Professional Documents
Culture Documents
MAINTENANCE
Ref. No. : AH-MS-220111-TR Date: 14.08.2023
REV. No. 00 Page 1 of 7
Approved By:
Client METHOD STATEMENT FOR TRANSFORMER Contractor
MAINTENANCE
Ref. No. : AH-MS-220111-TR Date: 14-08-2023
REV. No. 00 Page 2 of 7
REVISION RECORD
This cover page is a record of all revisions of the document identified above by number and title. All previous
cover pages are hereby superseded and are to be destroyed.
Approvals
Rev. No. Date By Chkd. Description and Page Numbers of Revisions
HMR
00 14/08/2023 AR VK AM 1st Submission
Client METHOD STATEMENT FOR TRANSFORMER Contractor
MAINTENANCE
Ref. No. : AH-MS-220111-TR Date: 14-08-2023
REV. No. 00 Page 3 of 7
CONTENTS
1. PURPOSE
2. SCOPE
3. REFERENCES
4. DEFINITIONS
5. RESPONSIBILITIES
8. HSE REQUIREMENTS
9. WORK PROCEDURE
1. PURPOSE
The purpose of generating this method statement is to define the procedure step by step to
implement the correct practices for DRY Type Tranformer Maintenance through the guidelines
contained here in so as to ensure that the job execution complies with specification and serves
the intended function to satisfactory level where applicable in the building of the M/s TDGISERV.
2. SCOPE
This method statement covers all processes related to following:
SR
MAINTENANCE WORK IN TRANSFORMER
NO
1 Check for Visual Inspection
2 Check for External damages
3 Clean the Transformer
4 Insulation Resistance Test
5 Winding Resistance Test
6 Transformer Ratio Test
7 Check for abnormal Noise
8 Check Tap Position
9 Check Winding Temperature
10 Check LV Cable tightness
11 Check the Earthing system
12 Check the Cooling system
13 Record the date of test
14 Preparation of test reports
Client METHOD STATEMENT FOR TRANSFORMER Contractor
MAINTENANCE
Ref. No. : AH-MS-220111-TR Date: 14.08.2023
REV. No. 00 Page 5 of 7
3. REFERENCE
The works will all be undertaken in accordance with the following documents:
a) ISO 9001:2008.
b) Electrical Standards.
c) M/s TDGISERV HSE Standards and requirements.
d) Project Quality Plan
e) Project HSE Plan
f) Manufacturer’s Data sheets.
g) Manufacturer’s recommendations.
h) Regulation of the local Electrical Authority, KAHRAMAA
i) Electrical standards for LV Panels
4. DEFINITIONS
COMPANY : TDGISERV
Contractor : Arrowhead Switchgear
QCP : Quality Control Procedure
HSE : Health, Safety and Environment
MS : Method of Statement
LOA : Limitation of Access
5. RESPONSIBLITIES
Responsibilities for ensuring that the steps in this procedure shall be carried out are specified at
relevant steps in the procedure:
- Testing Engineer / Site Engineer
- Kahramaa approved LOA Holder
- Site Supervisor/Technician
8. HSE REQUIREMENTS
General HSE Instructions:
1. No maintenance shall be carried out unless there is valid PTW is authorized by permit issuer.
2. Look Think Do LTD assessment shall be carried out prior to each activity.
3. Only competent persons shall carry out the maintenance tasks.
4. Task performer shall ensure that all hand-tools & equipment which are required to carry out the
maintenance are in good condition and that he knows how to use them safely.
5. Safety shoes must be worn; dust mask and hand gloves shall be provided and must be used when
required. In case of chemical use then the PPE stated by Safety data sheet shall be provided and
used.
6. Job performer shall be trained on how to carry out safe manual handling. In case of heavy load,
mechanical aids shall be used.
7. Defective tool / equipment shall be immediately taken out of use.
8. Task performer shall be trained on how to use ladder safely.
9. Before the use of any chemicals read the container label / SDS to know the hazards and the required
PPE. All required PPEs shall be provided and used when required. If you don’t know what PPE are
required ask supervisor.
10. Use Green chemicals as practicable. Never handle chemicals in unlabelled container & never mix
chemicals.
11. Never leave equipment or tools unattended in publicly accessible areas.
12. In case of any need to work in electricity energized parts, then power shall be adequately isolated,
locked-out and tagged-out and permit shall be taken before start of work. No work shall be carried
out on energized parts / systems.
13. In case maintenance resulted in waste, clean the task site and take waste to the right waste
collection area.
14. Housekeeping shall be maintained throughout the task.
Below mentioned PPE shall be used during the task as applicable:
9. WORK PROCEDURE
All maintenance activities and its frequency will be executed according the contract requirement
and obligation, standards, codes, engineering best practice and specialist recommendation.
As applicable the planned preventive maintenance shall follow;
• Visual inspection.
• Mechanical/ Electrical inspection, Cleaning, and Lubrication.
• Functional verification test.
• Insulation Resistance test
• Turns Ratio test
• Winding Resistance test
CONNECTIONS
The turns-ratio test detects shorted turns, which indicate insulation failure. Shorted turns may result
from short circuits with high currents or insulation failures. The voltage ratio obtained by the test is
compared to the name plate voltage ratio. The ratio obtained from the field test should agree with the
factory value to within 0.5%. New transformers normally compare to the name plate within 0.1%. With the
described test system, it is additionally possible to measure the ratio with magnitude and phase angle over
a wide frequency range.
Since the winding resistances are very small; the test set is connected in 4-wire configuration. It has
to be observed that the contact resistances of the connection clamps do not falsify the measuring result. A
constant current source is used to feed a direct current into the winding. The test current should be at least
1% of the rated current to bring the core into saturation. On the other hand, it should not exceed 15% of
the rated current to avoid temperature rise during measurement. A relatively high no-load voltage enables
a quick saturation of the core and a final value with only minor fluctuations is reached. Therefore, in most
cases the charging time per tap is distinctly less than 30 seconds. By pressing one button on the test system,
all values are logged and a test report is automatically generated. The resistance values are automatically
corrected to the reference temperature by automatic calculation utilizing the following formula:
Where,
Rm = Measured value of Resistance
Tm = Temp. During measurement
Client METHOD STATEMENT FOR TRANSFORMER Contractor
MAINTENANCE
Ref. No. : AH-MS-220111-TR Date: 14.08.2023
REV. No. 00 Page 12 of 7
More FURTHER CONTROLS (Elimination, Substitution, Engineering Controls, PPE REQUIRED (other than
HAZARD/RISK Who May Be Harmed EXISTING CONTROLS
L S R Required? Signage) site mandatory) L S R
Manual handling, Operatives involved in Work area to be fully controlled by M Use mechanical aids instead of manual lifting.Specific job training shall be given
actvity
Rigger Hand Gloves
Other Contractors
e to the workers before starting the task.Correct manual handling tecniques to be
specialist and competent gang.All L
working close by d
3 3 9 YES followed by all operatives, Firm grip, Good communication. Noise level must be 1 1 1 O
Visitors personnel associated with the task must i
assessed and precuations to be taken.Hearing protection to be provided if W
u
Dust, Noise wear the site mandatory PPE m necessary Dust Mask
Emergency rescue Operatives involved in Alarm / Siron Report to immediate responsible supervisoror safety officer.All emergency
actvity M
Other Contractors e contact number will be provided.Emergency response procedure , safety training
working close by Escape route L
d
Visitors 2 4 8 YES and induction will be given to all prior to commence the work.All activities will 1 1 1 O
i
Assembly point Tool Box W
Emergency Response u be preceded by a safety induction conducted by client. All activities will be
m
procedure Team Talk excuted in accordance with the Client's HSE guidelines and instruction.
Risk Assessment Prepared By: Signature: Date: 14-08-2022 Supervisor Responsible for Implementation: Signature:
Arunagiri R
Risk Assessment Approved By: Signature: Date: 14-08-2022 Periodical Review to Take Place On:
Abid