You are on page 1of 7

Space for Stamp: IP/OE

RETURN CODE

Issued for Construction


Revision History
Rev. Revision Issued by Checked by Released by Brief Description
Date

Description current Revision

Owner

Owner’s Engineer: Contractor:

Project:
TAMBAK LOROK COMBINED CYCLE
POWER PLANT BLOCK 3 PROJECT
WITH NET DEPENDABLE CAPACITY OF 600 – 850 MW.
SEMARANG – CENTRAL JAVA
Subject: C902 Generator Technical Data

Issue Purpose: Responsible Dept:

Originator:

Originator Document no: Document Status: Originator Rev: C


128T0741 Released
Project Document No.: Rev: Sheet.:

TBL/31/G/MKA---GA71/DS/001 1 0/6

Issue date: 2023-05-24

Information Class, if applicable, on pg. 1 et sqq


Doc Name : 128T0741 Rev C Released Date : 2023/05/24 Page 1 of 6

General Electric 128T0741


Responsible department: Derived from: Replaces: MLI No.

9706 TG16-1075 rev. A C902


Prepared: Checked: Approved: Revision: Page:

2023-05-22 M. Sklodowski 2023-05-22 W. Furmański 2023-05-22 Ch. Xu C 1/6

Plant: TAMBAK LOROK

Generator-Type: W88 (50WT25E-138)

Generator Serial Number: PL100191

Technical Data for Generator


W88 (50WT25E-138) with Static Excitation
995.0 MVA 24000 V 50 Hz cos = 0.85 Tcg = 40°C Tcdw = 43°C pH2 = 4.5 bar(g)

Content: Page
1. Generator main data 2
2. Generator reactances and resistances 3
3. Time constants 3
4. Miscellaneous (electrical) 4
5. Torque and inertia 4
6. Generator losses at rated load 4
7. Generator efficiency 5
8. Generator hydrogen cooler data 5
9. Stator winding cooling water system 5
10. Generator stator 6
11. Generator rotor 6
12. Synchronising requirements 6

The information contained herein is General Electric proprietary information and has been disclosed in confidence to the
designated party for specified purposes only. Any use, disclosure or reproduction contrary thereto is a violation of General
Electric’s right. © General Electric Company and/or its Affiliates, 2017-2023. All rights reserved.

GE Non-Public- Class II - (Non Critical) NLR


Doc Name : 128T0741 Rev C Released Date : 2023/05/24 Page 2 of 6

Revision: Page:

C 2/6
128T0741

Technical Data for Generator W88 (50WT25E-138) with Static Excitation


995.0 MVA 24000 V 50 Hz cos = 0.85 Tcg = 40°C Tcdw = 43°C pH2 = 4.5 bar(g)

1. Generator main data Sym. Value Dim.


1.1 Standards IEC 60034
1.2 Temperature rise according to IEC 60034 Cl. 130(B)
1.3 Rated apparent power Sn 995.0 MVA
1.4 Rated active power Pn 845.8 MW
1.5 Rated terminal voltage (+5.0% / -5.0%) Un 24000 V
1.6 Rated phase current In 23936 A
1.7 Rated power factor lagging cosn 0.85 -
(at rated active power) leading cos 0.9 -
1.8 Rated frequency (+2.0% / -2.0%) fn 50 Hz
1.9 Rated speed nn 3000 rpm
1.10 Cold gas inlet temperature Tcg 40 °C
1.11 Minimum cold gas inlet temperature Tcgmin 10 °C
1.12 Hydrogen pressure (gauge) pH2 4.5 bar
1.13 Hydrogen purity 98.0 %
1.14 Stator winding deionized cooling water inlet temperature Tcdw 43 °C
1.15 Temperature of cooling water for hydrogen, deionized water, seal Tcw 35 °C
oil and brush gear coolers
1.16 Min. temperature of cooling water for hydrogen coolers Tcwmin 5 °C
1.17 Generator air-gap field current at no load and rated terminal Ifδ 1957 A
voltage
1.18 Generator field current at no load and rated terminal voltage Ifo 2082 A
1.19 Generator field voltage at no load and rated terminal voltage Ufo 230 V
at 95°C
1.20 Generator field current at rated conditions Ifn 5759 A
1.21 Generator field voltage at rated conditions at 110°C (temperature Ufn 655 V
limit for 6 outlet regions)
1.22 Generator field current at 995MVA and cos = 1 4499 A
1.23 Generator field current at rated armature current at short circuit Ifk3 3847 A
1.24 Ceiling current 2.0 x 5759 A
1.25 Ceiling voltage 2.0 x 655 V
1.26 Ceiling time 10 s
1.27 Short-circuit ratio SCR 0.54 -
1.28 Generator output with one hydrogen cooler out of service 100 %

GE Non-Public- Class II - (Non Critical) NLR


Doc Name : 128T0741 Rev C Released Date : 2023/05/24 Page 3 of 6

Revision: Page:

C 3/6
128T0741

Technical Data for Generator W88 (50WT25E-138) with Static Excitation


995.0 MVA 24000 V 50 Hz cos = 0.85 Tcg = 40°C Tcdw = 43°C pH2 = 4.5 bar(g)

2. Generator reactances and resistances Sym. Value Dim.


2.1 Rated impedance Zn 0.579 
2.2 Direct-axis synchronous reactance (unsaturated) xd 1.97 p. u.
2.3 Direct-axis transient reactance (unsaturated) x'd 0.28 p. u.
2.4 Direct-axis subtransient reactance (unsaturated) x"d 0.22 p. u.
2.5 Direct-axis synchronous reactance (saturated) xdv 1.85 p. u.
2.6 Direct-axis transient reactance (saturated) x'dv 0.27 p. u.
2.7 Direct-axis subtransient reactance (saturated) x"dv 0.19 p. u.
2.8 Quadrature-axis synchronous reactance (unsaturated) xq 1.93 p. u.
2.9 Quadrature-axis transient reactance (unsaturated) x'q 0.45 p. u.
2.10 Quadrature-axis subtransient reactance (unsaturated) x"q 0.23 p. u.
2.11 Quadrature-axis synchronous reactance (saturated) xqv 1.93 p. u.
2.12 Quadrature-axis transient reactance (saturated) x'qv 0.41 p. u.
2.13 Quadrature-axis subtransient reactance (saturated) x"qv 0.20 p. u.
2.14 Negative-sequence reactance (unsaturated) x2 0.22 p. u.
2.15 Zero-sequence reactance (unsaturated) xo 0.090 p. u.
2.16 Negative-sequence reactance (saturated) x2v 0.19 p. u.
2.17 Zero-sequence reactance (saturated) xov 0.080 p. u.
2.18 Potier reactance xP 0.34 p. u.
2.19 Leakage reactance (stator) x 0.19 p. u.
2.20 Zero-sequence resistance at 95°C ro 0.00163 p. u.
2.21 Stator winding resistance per phase at 95°C Ra 0.946 m
2.22 Rotor winding resistance at 95°C Rf 0.1080 
2.23 Stator impedance without rotor Xtotal 0.33 

3. Time constants (unsaturated at 95°C) Sym. Value Dim.


3.1 Direct-axis transient short-circuit time constant T'd 0.75 s
3.2 Direct-axis subtransient short-circuit time constant T"d 0.017 s
3.3 Quadrature-axis transient short-circuit time constant T'q 0.17 s
3.4 Quadrature-axis subtransient short-circuit time constant T"q 0.017 s
3.5 Direct-axis transient open-circuit time constant T'do 5.26 s
3.6 Direct-axis subtransient open-circuit time constant T"do 0.022 s
3.7 Quadrature-axis transient open-circuit time constant T'qo 0.73 s
3.8 Quadrature-axis subtransient open-circuit time constant T"qo 0.034 s
3.9 Short-circuit time constant of armature winding Ta 0.42 s

GE Non-Public- Class II - (Non Critical) NLR


Doc Name : 128T0741 Rev C Released Date : 2023/05/24 Page 4 of 6

Revision: Page:

C 4/6
128T0741

Technical Data for Generator W88 (50WT25E-138) with Static Excitation


995.0 MVA 24000 V 50 Hz cos = 0.85 Tcg = 40°C Tcdw = 43°C pH2 = 4.5 bar(g)

4. Miscellaneous (electrical) Sym. Value Dim.


4.1 Continuous unbalanced load, maximum I2 0.059 p. u.
4.2 Short time capability for unbalanced faults, maximum I22t 5.0 p. u. s

4.3 Voltage increase at sudden load rejection and cos = 0.85 41 %


(without AVR action)
4.4 Voltage increase at sudden load rejection and cos = 1.00 31 %
(without AVR action)
4.5 3-phase short-circuit current (peak value) ip3 317 kA
4.6 3-phase steady-state symmetrical short-circuit current (r.m.s.) Ik3 35.8 kA
4.7 3-phase transient symmetrical short-circuit current (peak value) I’k3 140 kA
4.8 3-phase subtransient symmetrical short-circuit current (peak value) I”k3 195 kA
4.9 Three-phase stator winding capacitance (3 x CPhase to ground) C 0.86 F
4.10 Limit of acceptable peak to peak field voltage including
commutation overvoltage peaks:
- in fully balanced and symmetrical systems 3000 Vp-p
- in not fully balanced and unsymmetrical systems 1500 Vp-p

5. Torque and inertia Sym. Value Dim.


5.1 Nominal torque MN 2692 kNm
5.2 Synchronous pull-out torque Mmax 4734 kNm
5.3 Maximum two-phase short-circuit torque at rated voltage Mk2 21388 kNm
5.4 Inertia moment J 15429 kgm2
5.5 Inertia constant (H = Jω2/(2Sn)) H 0.765 s

6. Generator losses at rated load Sym. Value Dim.


6.1 Stator core losses 694 kW
6.2 Stator winding I2R losses 1626 kW
6.3 Stray load losses 979 kW
6.4 Rotor winding I2R losses 3582 kW
6.5 Excitation system losses + brush contact losses 147 kW
6.6 Windage losses 803 kW
6.7 Bearing losses 703 kW
6.8 Total losses 8534 kW

GE Non-Public- Class II - (Non Critical) NLR


Doc Name : 128T0741 Rev C Released Date : 2023/05/24 Page 5 of 6

Revision: Page:

C 5/6
128T0741

Technical Data for Generator W88 (50WT25E-138) with Static Excitation


995.0 MVA 24000 V 50 Hz cos = 0.85 Tcg = 40°C Tcdw = 43°C pH2 = 4.5 bar(g)

7. Generator efficiency (all losses were considered) Sym. Value Dim.


7.1 At rated cos = 0.85 - full load  4/4 99.00 %
- 3/4 load  3/4 99.04 %
- 2/4 load  2/4 98.97 %
- 1/4 load  1/4 98.48 %
7.2 At cos = 1.00 - full load  4/4 99.31 %
- 3/4 load  3/4 99.29 %
- 2/4 load  2/4 99.17 %
- 1/4 load  1/4 98.63 %

8. Generator hydrogen cooler data (without glycol) Value Dim.


8.1 Design capacity (total) 6020 kW
(*)
8.2 Number of coolers 4 x 33 %
3
8.3 Cooling water flow (total) 510 m /h
8.4 Cooling water inlet temperature 35 °C
8.5 Cooling water outlet temperature 45 °C
8.6 Cooling water pressure drop 510 mbar
8.7 Max. operating pressure of cooling water (gauge) 4.0 bar
8.8 Tube material CuNi10Fe
8.9 Cooling water pH reaction 6.0 to 9.5
(*)
referring to generator output with one cooler out of service on water side

9. Stator winding cooling water system Value Dim.


9.1 Design capacity of coolers (total) 2140 kW
9.2 Number of coolers 3 x 50 %
3
9.3 Stator winding deionized cooling water flow (total) 138 m /h
9.4 Pressure drop in the stator winding 1.85 bar
9.5 Max. operating pressure of stator winding deionized cooling water (gauge) 4.0 bar
9.6 Max. operating pressure of cooling water (gauge) to stator winding 3.5 bar
deionized water coolers

GE Non-Public- Class II - (Non Critical) NLR


Doc Name : 128T0741 Rev C Released Date : 2023/05/24 Page 6 of 6

Revision: Page:

C 6/6
128T0741

Technical Data for Generator W88 (50WT25E-138) with Static Excitation


995.0 MVA 24000 V 50 Hz cos = 0.85 Tcg = 40°C Tcdw = 43°C pH2 = 4.5 bar(g)

10. Generator stator Value Dim.


10.1 Class of insulation 155(F)
10.2 Main insulation system MICADUR
10.3 Method of cooling stator winding directly
10.4 Winding coolant Deionized water
10.5 Core coolant H2

11. Generator rotor Value Dim.


11.1 Class of insulation 155(F)
11.2 Method of cooling rotor winding directly
11.3 Winding coolant H2

12. Synchronising requirements Sym. Value Dim.


12.1 Max. fault angle between generator and system (grid)  ± 15 deg.
12.2 Max. frequency deviation (slip) between generator and system s ± 0.5 %
(grid)
12.3 Max. voltage deviation between generator and system (grid) U ± 5.0 %
12.4 Generator voltage and frequency as well as system (grid) voltage
(relative to generator voltage) and frequency have to be within the
upper and lower limits of the generator permissible voltage and
frequency range.

GE Non-Public- Class II - (Non Critical) NLR