Professional Documents
Culture Documents
HOLDS
ABBREVIATIONS
Abbreviation Description
BS British Standards
CE European Conformity
EN European Norm
HP High Pressure
IS Intrinsically Safe
LV Low Voltage
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
MV Medium Voltage
CONTENTS
ABBREVIATIONS ............................................................................................ 3
CONTENTS................................................................................................... 5
1 INTRODUCTION .................................................................................... 8
1.1 Scope of Supply ................................................................................... 8
9 EARTHING ......................................................................................... 31
9.1 Panel Earthing Requirements.................................................................. 31
9.2 Mechanical Package / Skid Earthing Requirements ........................................ 31
10 LIGHTING .......................................................................................... 32
10.1 Interface Connection Requirements ......................................................... 32
10.2 Standardisation of Lighting Design ........................................................... 32
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
11 JUNCTION BOXES................................................................................. 35
11.1 General Requirements .......................................................................... 35
11.2 Instrument & Intrinsically Safe Junction Boxes ............................................ 35
11.3 Segregation of Systems ......................................................................... 35
13 MOTORS ............................................................................................ 37
13.1 Requirements and Compliance ................................................................ 37
1 INTRODUCTION
The Greater Stella Area Development consists of three fields:-
The Stella field which will produce both a rich gas condensate and black oil
The Harrier field which will produce gas condensate.
The Hurricane field which will produce volatile oil.
The Stella and Harrier fields are located in the Central North Sea within the UK
Block 30/6a. The Hurricane field is located in UK Block 29/10b, approximately
10 km west of the Stella field.
The FPF1 floating production vessel is being refurbished and upgraded after
more than 30 years of operation in the North Sea to receive and process the
reservoir fluids from each of the three fields. The FPF1 will be located
approximately 2 km north west of the Stella Main Drill Centre and 1.5 km south
of the Stella Northern Drill Centre. The Stella fields will be tied back to the
FPF1 via subsea manifolds. The Harrier field will be tied-back to the main Stella
manifold and then tied back to the FPV. The Hurricane field, when developed,
will be tied directly back to the FPV.
Oil from the FPF1 will be exported to the Forties system and gas to CATS system.
1.1 Scope of Supply
This specification together with the referenced documents defines the minimum
requirement for design, manufacture installation and testing for electrical
equipment which are provided as part of a package.
Requirements relating to deviations to specification, spares, special tools,
packing and shipping are contained within the procurement documents
associated with the requisition package.
It is incumbent on the SUPPLIER to comply with all national legislation
applicable to the project in which this Specification is applied.
It shall be the SUPPLIER‟s responsibility to furnish all the items essential for the
safe and satisfactory operation of the equipment, notwithstanding the inclusion
or omission of same from this specification or the associated requisition and its
data sheets or the purchase order.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
IEC 60258 Direct acting recording electrical measuring instruments and their
accessories
IEC 60304 Standard Colours for Insulation for Low Frequency Cables and
Wires
IEC 60309 Plugs socket outlets and couplers for industrial and explosive gas
atmospheres
IEC 60446 Basic and safety principles for man-machine interface, marking
and identification - Identification of conductors by colours or
numerals
IEC 60502 Extruded solid dielectric insulated power cables for rated voltages
from 1kV up to 30kV
IEC 60898 Circuit breakers for overcurrent protection for household and
similar installations
ATEX Directive Minimum requirements for improving the safety and health
(99/92/EC) protection of workers potentially at risk from explosive
atmospheres
3.3.2 CE Marking
The SUPPLIER shall ensure that the equipment supplied meets with the
requirements of United Kingdom of Great Britain and all relevant EU Directives.
The SUPPLIER shall be responsible for obtaining CE markings and certification
from each sub-supplier as necessary and shall certify and CE mark the complete
package as a whole. All certification necessary for the installation and operation
of the complete Package within the EU shall be included in the certification
dossier.
3.4 Order of Precedence of Documents
The order of precedence of Project Documents, Codes, Standards and
Regulations applicable to the Material Requisition shall be as follows:
Government Regulations
Material Requisition
Equipment Data Sheets
This Specification
Project Specific Specifications
British Standards
International Standards
In the event of any conflict or ambiguity between this specification, datasheets,
other related documents, national standards, or any of the applicable codes and
regulations, the SUPPLIER shall inform the CONTRACTOR before proceeding with
the work.
3.5 Health, Safety and Environmental Requirement
Health, Safety and Environmental consideration is of foremost importance.
Hence, in case of a local regulation whose specification and requirements are
more stringent than this specification, in such case the more stringent will
apply. If the MANUFACTURER has a standard proven and approved design of their
equipment/system but still in case of any doubt whether it meets the local
regulations, they shall through the CONTRACTOR negotiate with the local
Authority for approval.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
4 DESIGN REQUIREMENTS
4.1 Equipment Utilisation Voltages
The CONTRACTOR shall provide power to all the packaged equipments from the
FPF1 distribution system. The Electrical equipment shall be designed for
operation at the following voltages, from the FPF1 distribution system. The
tolerances shall be ±10% for voltage (unless noted otherwise) and ±5% for
frequency.
Table 4.1 – Project Utilisation Voltages
TOPSIDES
MV Utility Voltage – 6.6kV
Switchgear
Motor Control 110V AC, 60Hz, single phase & neutral
Protection & Trip Supplies 110V DC ±1%
VCB Motor Spring Charging 110V AC, 60Hz, single phase & neutral
Switchboard Anti- 110V AC, 60Hz, single phase & neutral
Condensation Heaters
Motor Anti-Condensation 110V AC, 60Hz, single phase & neutral
Heaters
Low Voltage (LV) Power Distribution 440V 60Hz, 3-phase, 4 wire TN-S system
LV Utility Voltage – 440V Switchgear
Motor Control 110V AC, 60Hz, single phase & neutral
Protection & Trip Supplies 110V DC ±1%
Circuit Breaker Closing & 110V AC, 60Hz, single phase & neutral
Control Supply
Switchboard Anti-
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
Circuit Breaker Closing & 110V AC, 60Hz, single phase & neutral
Control Supply
Switchboard Anti- 110V AC, 60Hz, single phase & neutral
Condensation Heaters
Motor Anti-Condensation 110V AC, 60Hz, single phase & neutral
Heaters
Motors with rating up to and 480V 60Hz, 3-phase, 3 wire
including 200kW
ACCOMMODATION
Low Voltage (LV) Power Distribution 400V 60Hz, 3-phase, 4 wire TN-S system
Utility Voltage – 400V Switchgear
Motor Control 110V AC, 60Hz, single phase & neutral
Circuit Breaker Closing & 110V AC, 60Hz, single phase & neutral
Control Supply
Switchboard Anti-
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
GENERAL
Socket outlets:
Instrumentation:
The selection and installation of electrical equipment for use in hazardous areas
shall be in accordance with IEC60079 suitable for Gas Group IIB T3. Areas will
generally be classified Zone 2, However Zone 1 requirements will exist for
certain areas and certain equipments. Equipment shall be certified for use in the
specified area over the specified operating ambient temperature range by an
internationally recognised test authority in accordance with ATEX Directive
94/9/EC.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
The SUPPLIER‟s scope of supply shall include a schedule of all supplied and/or
installed certified equipment.
4.7 Electrical Installations
Electrical equipment shall be installed in accordance with project Specification
for Electrical Installations, Doc No: FPF1-ST-G00001-E-SPE-0020.
4.8 Electromagnetic Compatibility
In order to comply with the requirements of IEC61000 all electrical equipment
shall meet the current applicable levels of “emission” and “immunity”. All
applicable equipment shall be designed so that the Electromagnetic disturbance
it generates does not exceed a level allowing telecommunications equipment
and other relevant apparatus to operate as intended.
The design of equipment shall be of an adequate standard to maintain its
performance during its operational life in its installed environment.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
5 SERVICE CONDITIONS.
5.1 Site Conditions and Utilities Data
The site conditions and utility data are outlined in project specification FPF1-ST-
G00001-M-SPE-0003 Environmental, Vessel Motion and Utility Data.
Unless dual indicator lamps are specified or one lamp is always on; all lamps
shall have a lamp test facility, either integral in the holder, or as part of a total
lamp test facility.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
Pushbuttons shall be of the manual fleeting type fitted with suitably rated
contacts configured for the application. Pushbutton actuators shall be of the
fully shrouded type and coloured in accordance with the following table:
Table 6.2 – Push Button Actuator Colour
Emergency stop push-buttons shall have an actuator of the stay-put type and
shall be protected by either a cover or a shroud.
Each motor shall be provided with a stay-put type emergency stop pushbutton
located within 1 metre of the motor, operable in all circuit configurations. For
larger more complex packages, additional emergency stop pushbuttons may be
required for safety reasons to ensure that a stop facility is always conveniently
accessible.
Automatic process initiated starting of a motor shall be prevented in the field by
operation of the emergency stop pushbutton.
All control, protection, indication and other auxiliary circuits shall be protected
by either suitably rated HRC control fuses according to IEC60269 or MCBs
according to IEC60898 or MCCBs according to IEC60947.
A control circuit test switch shall be provided to enable the complete control
circuit to be tested live with the main power circuits disconnected. Suitable
interlocks shall be incorporated to ensure the main switch cannot be switched
on with the test switch remaining in the test position.
No voltmeters or ammeters are to be directly connected. Voltmeters shall be
connected to a suitably rated voltage transformer with a 110V AC secondary
winding and fitted with a phase selector switch. Ammeters shall be connected
to a suitably rated current transformer and fitted with a line selector switch.
Alternatively, a solid state power metering device is acceptable instead of
voltmeters and ammeters.
All measuring instruments shall be equal to the requirements defined in
IEC60051. Meters shall be square flush mounting type and shall have a scale
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
7.2 Trunking
All wiring shall run in trunking, blue for intrinsically safe signals and grey for all
other wiring. Trunking shall have 25% spare capacity once installed.
7.3 Terminals
All terminating wiring shall have stranded cores fitted with blade type crimps
complete with securing lips. Terminals shall be of the rail mounted pinch plate
type, of Weidmuller manufacture or approved equal, suitable for a maximum
conductor size of 2.5mm². Only one conductor shall be terminated in each
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
terminal. Fused indicating terminals shall be used for power. All IS field cables
shall terminate at blue terminals. Panels shall have an installed terminal spare
capacity of 20%.
Terminals shall be mounted together to form terminal strips and shall always be
mounted on DIN rails. Where run between trunking, the interface shall be
mounted on stand-offs such that the terminals are within 10mm of the top
surface of the trunking. Each terminal rail shall be individually numbered; the
number shall be included on a label carrier mounted at the beginning of the
strip. Terminal strips shall be supplied with end plates and partition plates. All
terminals shall be consecutively numbered using “Weidmuller Dekafix” system or
equal. Fused indicating terminals shall be used for power and digital outputs.
Terminals associated with external current monitoring signals shall be provided
with easily removable shorting plugs.
Terminal blocks shall be arranged and installed to facilitate accessibility for
cable core termination and inspection of terminal identification numbers. The
proximity of terminals and gland plates shall be such that ample space is
available for terminating the cores of external cables. In general, at least
300mm clearance shall be allowed between the gland plate and any internal
equipment to permit easy cable installation and connection.
Terminal blocks shall be logically grouped, indelibly marked and, for voltages
greater than 50V, shall be provided with removable plastic shrouds. Adequate
segregation shall be provided between the instrument analogue signals, the
instrument digital signals and the AC power wiring. Segregation shall additionally
be provided for the IS and non-IS instrument signals.
7.4 General and Warning Labels
Terminal blocks associated with voltages greater than 24V shall be fully
shrouded and fitted with a danger warning label. The warning label shall be
mounted on clear plastic. Warning labels shall use international standard
warning signs and symbols.
All components shall be labelled with the component number. Labelling shall be
Traffolyte material, black letters on white background and shall not be mounted
on the device.
Terminal blocks associated with external sources of supply shall be fully
shrouded and fitted with a danger warning label.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
The package unit shall be complete with all interconnecting cables, cable glands
and associated cable support system for all electrical equipment.
The cables connecting the package unit to the main power supply source will be
provided by others. The SUPPLIER shall provide suitably sized terminal boxes
having terminals and tapped holes (for EEx‟d‟ Zone 1 equipment) to suit
cables/cable glands provided by others.
Power, control and instrumentation circuits shall be terminated in separate
junction boxes suitable for the plant environmental conditions.
All cables that run within the package unit shall be adequately supported on
heavy duty ladder rack or tray. Ladder rack or tray shall be 316 Stainless Steel.
All cables shall be protected against mechanical damage.
Where cables supplied and installed by others are run to the package unit, the
SUPPLIER shall provide suitable space and supports for installing and terminating
the cables.
Terminal blocks shall be of Weidmuller type SAK make, or equivalent.
Wiring shall be clearly identified by means of ferrules if not colour-coded as
Section 7.1.
Generally all instrumentation and communications cables shall be run in
separate ladders from all electrical power and control cables
Electrical control and low-voltage power cables can be installed in the same
cable ladder.
The cable ladders shall be routed so as to maintain a minimum 300 mm
separation between ladders for electrical control and LV power and ladders for
instrumentation and communications.
Cable ladders for medium voltage cables shall be routed so as to maintain a
minimum 300 mm separation between ladders from ladders for electrical control
and LV power and 600 mm separation from ladders for instrumentation and
communications.
Instrument cables serving common equipment with power cables, e.g. motors
with RTD's, shall maintain the separation as far as possible with bearing and
winding RTD‟s being brought out to dedicated separate junction boxes located
away from the main terminal box.
Mechanical equipment, pipes, etc. shall not obstruct access to electrical
equipment and instrumentation.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
Process and utility piping shall not be used to support electrical equipment and
cables.
Cable entries shall be from below wherever possible.
8.4 Cable Construction
Cable construction and service details are provided in project Specification for
Electrical Power and Control, Instruments and Telecommunications Cables, Doc
No: FPF1-ST-G00001-E-SPE-0009.
Cables shall be HOFR (Heat and Oil Resistant, Flame retardant) LSOH (Low
smoke zero halogen) in accordance with IEC60331 and IEC60332.
Where applicable, cables will be protected from direct solar exposure with cable
tray covers. The construction of the covers will ensure that earthing of them to
racks and structures eliminates static discharge.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
9 EARTHING
9.1 Panel Earthing Requirements
An electrical equipment earth bar shall be provided the full length of the panel,
located on the inside rear face. All metallic non-current-carrying parts shall be
bonded together and connected to this earth bar.
Process control and instrumentation systems shall be provided with their own
dedicated earth bar(s), which shall be electrically isolated from the electrical
equipment earth system.
Each earth bar shall be clearly marked to distinguish between them.
All doors shall be bonded to the main panel enclosure by means of a flexible
2.5mm2 green/yellow LSOH insulated cable arranged so that it cannot be
trapped as the door is opened or closed.
An external M10 earth stud shall be provided to facilitate connection of the
electrical equipment earth to the mechanical package earth bar or to the
installation earthing system.
9.2 Mechanical Package / Skid Earthing Requirements
Skid mounted package units containing more than one item of electrical
equipment shall be provided with a tinned copper earth bar securely fixed to the
side of the skid. All electrical equipment and enclosures on the skid shall be
directly bonded to the earth bar with a minimum size of 16mm2 green/yellow
LSOH insulated cable.
Where applicable, up to two additional earth bars shall be installed for
collecting instrumentation clean and intrinsically safe earthing conductors.
Package baseplate(s) comprising vessels and structures firmly bolted or welded
down shall be treated as an integrally bonded unit and shall be provided with at
least two diagonally opposed M10 points of connection to the plant earthing
system for connection by others.
If non conductive vessels, supports and containers are employed, the methods
used to eliminate static discharge shall be described in the bid.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
10 LIGHTING
10.1 Interface Connection Requirements
Where outdoor lighting is within the SUPPLIER‟s scope of supply, he shall supply
a dedicated junction box for feeding outdoor lighting circuits. The CONTRACTOR
will provide a power supply to this junction box.
Indoor and equipment/panel lighting within the SUPPLIER‟s scope of supply shall
be supplied from separate junction boxes. The SUPPLIER shall provide switching
facilities for each circuit as required for maintenance and operational use.
Where emergency lighting is required, the SUPPLIER shall provide a dedicated
junction box for the electrical supply to the emergency lighting circuits.
10.2 Standardisation of Lighting Design
Three groups of package lighting, which shall be categorised according to the
security of their power supply as follows:
Normal lighting
Emergency lighting – Category 1
Essential lighting – Category 2
Normal lighting shall be supplied from the normal services distribution boards
fed from the main power supply only.
Emergency/Essential lighting shall be provided in all process and utility plant
areas and in all buildings as required split into two (2) categories:
Outdoor lighting shall be controlled by a time switch or photo electric cell with
an override switch controlling a supply contactor. Lighting within buildings shall
be controlled by wall switches.
Normal Illumination levels shall be as per Table 10.1 below:
Table 10.1 Normal Illumination Levels
NORMAL LIGHTING
11 JUNCTION BOXES
11.1 General Requirements
Junction boxes shall in all respects be suitable for the service conditions and
hazardous area classification stated and selected in accordance with Section 4.6
and comply with the following:
Junction box enclosures shall be either 316 stainless steel or industrial grade
plastic construction with a minimum ingress protection of IP56. Cables shall
access from the bottom via undrilled gland plates. Top entry is not permitted.
An internal and external M10 earthing stud shall be provided to facilitate
connection of the junction boxes to the main earth system. For non – metallic
junction boxes, a metal adapter plate and connection stud, mounted inside the
enclosure shall be provided to ensure earth continuity between cable glands and
the internal earth system.
Each junction box shall be provided with the requisite number of terminals to
terminate all cores cable(s) and have an additional 20% terminals spare. A
minimum distance of 100mm shall be allowed between any terminal face and
gland plate or entry.
11.2 Instrument & Intrinsically Safe Junction Boxes
For details of Instrument & Intrinsically Safe (IS) junction boxes, refer to the
General Instrument Specification Doc No: FPF1-ST-G00001-J-SPE-0004.
11.3 Segregation of Systems
Separate junction boxes shall be supplied for instrument and electrical systems.
For details refer to the General Instrument Specification Doc No: FPF1-ST-
G00001-J-SPE-0004.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
13 MOTORS
13.1 Requirements and Compliance
Low voltage induction motors shall be totally enclosed fan cooled type, with
squirrel cage rotor and selected in accordance with Section 4.6 of this document
and in accordance with project specification FPF1-ST-G00001-E-SPE-0007
Specification for LV Motors.
Unless otherwise stated, motors shall be provided by the Package Equipment
SUPPLIER. The CONTRACTOR may define a list of acceptable motor SUPPLIERS
and/or establish frame agreements.
The main power supply cable termination box on all motors shall be adequately
sized to allow termination of the cable type and size specified by CONTRACTOR.
Aluminium framed motors shall not be acceptable.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER:
When specified in the Purchase Order the SUPPLIER shall provide representatives
to assist the CONTRACTOR during installation, commissioning and initial startup
of the package.
PROJECT: PROJECT NO: COMPANY: DOCUMENT NUMBER: