Professional Documents
Culture Documents
SPECIFICATION FOR
ELECTRIC HEAT TRACING
TABLE OF CONTENTS
1.0 GENERAL........................................................................................................................... 4
2.0 SCOPE................................................................................................................................ 4
1.0 GENERAL
This specification is to establish the quality of work and technical requirements for the
supply, installation, testing and documentation for Electric Heat Tracing.
The SUPPLIER shall use this specification together with other documents provided in
the requisition to establish the detail design and final installation of the system.
2.0 SCOPE
SUPPLIER shall perform heat demand calculations for OWNER’s review. The
calculations shall be based on temperature range and warm up time based on project
specific requirements.
SUPPLIER shall provide training manual, video and/or sample material for training the
OWNER’s operating and maintenance personnel.
SUPPLIER shall meet or exceed the requirements of the latest edition of the following
codes, regulations and standards, except as superseded herein. In cases where more
than one code, regulation or standard apply to the same condition, the most stringent
shall be followed. In the event of a conflict between this specification and other
specifications or correspondence, the OWNER shall be consulted and a ruling, in
writing, shall be obtained before any fabrication can start.
The Electric Heat Tracing Equipment shall be in accordance with the following
minimum IEC standards or Equivalent:
IEC 60540 Test Methods for Insulation and Sheaths of Electric Cables and Cords
IEC 60332-3 Flame retardant characteristics of electric cables. Part 3 Test on bundled
wires or cables.
The SUPPLIER shall ensure that the equipment supplied will work properly under the
site conditions.
The equipment and installation shall be suitable for the minimum environment
conditions, unless otherwise specified.
For details about Site Conditions, please refer the Project Site Data.
The Electric Heat Tracing shall be utilized to maintain temperature of fluid (oil) in pipes,
instruments or instrument bundles.
The heat race cable shall be suitable for the continuous surface temperature as
indicated.
All the necessary parameter like temperature etc shall be indicated in the line list and
P&IDs.
The overall responsibility for the heating system shall rest with the SUPPLIER.
The design shall be based on the specific requirements, stated on the P&IDs,
drawings, Isometrics and Line lists.
5.2 Safety
For safe and reliable application of electrical heating systems, the climatic,
environmental and operating conditions shall be taken into consideration.
For installations in Zone 1 and Zone 2 areas, the following types of protection shall be
used:
The heating cable shall be suitable for Zone 1 and Temperature Class T3.
For standardization, material as specified for Zone 1 and 2 areas should also be used
in non-hazardous areas.
However the control panel installed in outdoor safe area shall be weather proof with
IPW 55 degree of protection.
The AC supply to the heating system shall be symmetrical 3-phase + neutral, sub-
divided into single phase with a nominal voltage and frequency as indicated in the
requisition. The supply variations at the distribution board, under steady-state
conditions, shall be limited to:
The design of initial spare or over-capacity of the heating system shall be considered if
for critical applications the power output is not allowed to drop below the design values.
A minimum of 20% additional design heat requirement shall be taken into account.
This may not be applicable if self-regulating cable is used.
The safety factor used in the design shall be stated in the heat balance calculation.
All electrical equipment subject to operating and maintenance activities shall be easily
accessible and shall allow for safe and convenient performance of such activities.
For winterizing and compensation heating the following heater types may be used, in
order of preference:
In the case of welded pipelines (i.e. without flanges) the system of skin electric current
tracing heaters shall be considered.
The heaters shall vary the power output in response to the sensed temperature at
every point of the surface. As the temperature increases, the heater output shall
decrease automatically and vice versa. The natural reduction in heat output by
increasing temperatures shall be at least so much that the heater will not be damaged
due to overheating as result of e.g. overlapping, irrespective of the application.
Constant wattage parallel heaters may be utilized when the required heat output or the
operating temperature is beyond the capabilities of self-regulating/ self-limiting heaters.
A constant wattage parallel heating cable shall consist of two insulated copper
conductors. Heating elements (wires or other types of elements) are connected to the
two conductors at certain distances, forming heated zones. The maximum length of a
heating zone shall not be more than 1 metre.
The conductor and the heating elements shall be provided with one or more layers of
insulating material. All insulating material shall be heat resistant and non-hygroscopic
and shall be covered with a braided metal screen covering for at least 70% of the
surface together with a polymer outer jacket. The electrical conductivity of the braided
metal screen shall not be less than the conductivity of one of the conductors.
The heating pad shall have an external metal earth screen or foil over the entire
surface for mechanical and personnel protection.
The heaters (both, cables and pads) shall provide a constant power output regardless
of the operating temperature.
Mineral Insulated Heaters may be used, if the required temperatures are beyond the
capabilities of the constant wattage parallel heaters.
Mineral insulated heating cable shall consist of a metal outer tube with a concentric
heating conductor inside, insulated with compressed magnesium oxide powder. The
cable shall have a constant power output per meter which shall be determined by the
specific conductor resistance, the total length of the cable and the applied voltage.
The cable shall be prefabricated for the required length and provided at both ends with
proper seals, cold connection leads and metal cable glands.
Heating pads with mineral insulated heating cable shall consist of a metal plate on
which the cable is fixed, to guarantee heat transfer over the entire length of the heating
cable.
The SR heating cable shall vary its power out relative to the temperature of the surface
of the pipe. Also unlike mineral insulated (MI) and constant wattage (CW) cables, SR
cable can be overlapped during installation without fear of burnout.
Self-regulating heating cable shall be designed for useful life of 20 years or more with
“power on” continuously, based on the following useful life criteria:
• Retention of at least 90 percent of rated power after 1000 hours of operation at the
maximum published intermittent exposure temperature. The testing shall conform
to UL 7468, IEC 60214-1 Part 1.
All cables shall be warranted against manufacturing defects for a period of 10 years.
All cables shall be capable of passing a 2.5 kV dielectric test for one minute after
undergoing a 0.5 kg-m impact.
Each heat tracing circuit should be, controlled by a pipe temperature monitoring device
or a RTD temperature sensor. RTD’s should be 100 ohm platinum type (PT-100).
Each circuit shall be fitted with earth leakage circuit breaker (30 mA). At least one
spare circuit shall be installed for each section of piping. Easy inspection of supply
points shall be made possible.
Internal wiring within the panel shall be PVC insulated 600/1000V grade, stranded
copper conductors, minimum size 2.5 mm2.
Wiring shall be securely held in position (either loomed or run in conduit / trunking). If
wiring corridors, conduits and flexible conduits are used they shall be, adequately
sized to accommodate future additions (6 conductors minimum) by others.
Wiring identification shall be by numbered and/or lettered ferrules of insulating material
and located adjacent to the terminals.
Wiring connections to door mounted equipment shall be loomed, wrapped at both ends
to prevent movement at terminations.
All wiring for external connections shall be brought out to individual terminals on a
readily accessible terminal block. Sufficient spare ways (4 minimum) shall be allowed
for future use.
Plug and socket connections shall be of robust construction and include a location pin
or similar device to prevent the interconnection being made incorrectly.
Incomers shall be provided with Voltmeters and Ammeters. Relays shall be flush
mounting and fitted on the front of the equipment. All meters shall be of square pattern
type 96 x 96mm and mounted at a suitable height for easy reading from the front.
Potential free “Normally Closed” contact shall be provided to indicate failure of the heat
tracing system. This shall also include tripping of individual circuit breaker feeders.
SUPPLIER shall provide a canopy for control panel to protect against direct sunrays
and rain.
7.0 INSTALLATION
The electric heat tracing system shall be installed in accordance with manufacturer’s
instructions and recommendation. The location of the main Electric Heat Tracing
Panel shall preferably be in the substation. The control panel based on the system
requirements and design can be located in field at suitable location. The panel shall
be either with IPW-65 ingress protection when kept in a safe area or Ex-d as per area
class, if located in an hazardous area (It is preferable to locate the panel in a safe area
as far as possible).
RTD’s shall be located away from heating cable to obtain accurate measurement of
the fluid temperature, so as to avoid cold spots.
Heaters shall be distributed and grouped logically in order to minimize the number of
switches, thermostats and power cables.
Through connections or ‘Tee-offs’ shall not be made underneath the pipe insulation;
only end-seals and ‘cold-lead’ connections may be used. All other connections shall be
made in connection boxes. Sufficient heater capacity shall be installed to ensure that,
towards the end of the heating cable, the output does not drop below the minimum
design value owing to the voltage drop in the heater conductors.
Temperature controller shall be provided for each circuit in distribution panel. The
temperature controller shall be connected to the RTO and shall control the contactor
and its circuit.
Temperature controller shall make sure the temperature maintained in the pipe is the
true temperature or temperature listed in line list by switching on and off the contactor.
Short pipes carrying the same liquid can be grouped under one circuit and one
temperature controller shall be provided for this circuit. RTD for the same shall be
located at the biggest pipe.
Electronic Temperature Controller with PT-100 sensor should be used for temperature
control. The contacts of the controller used for direct switching shall have a minimum
rated capacity of 16 A.
Power Junction Boxes shall be used for connections between supply cable and heater
cables; The power Junction Box Should have two power cable entrances at least with
ingress protection IP65.
Extreme care shall be taken to prevent heater cables and pads absorbing water during
transport as well as during and after installation. During transportation to the site, the
ends of the cables or the connection leads shall be suitably sealed by heat shrinkable
adhesive end-seals, which shall remain fitted until the final connection is made in the
junction box, switch. etc..
The heater cables or the cold leads shall be terminated in the junction boxes, switches,
etc. in such a manner that any ingress of water through the cores, braiding or in
between insulation layers due to the capillary effect is excluded.
Heater shall be installed in accordance with the SUPPLIER’s instructions. All heaters
shall be fixed to ensure continuous and permanent contact with the surface to be
heated over the entire (hot) length.
Entry kits shall be used where heating cables, cold leads or temperature leads enter
the thermal insulation to prevent damage and to ensure weatherproofing. The entry
kits shall be fixed to the bottom part of the pipeline.
Heating cable fixed to pumps, valves, flanges etc. shall allow easy removal of the
equipment without damaging the cables. To obtain good contact between heater and
heated surface, additional metal tape or foil shall be provided on both sides of the
pumps, valves, flanges etc. to avoid loosening of the heater from the associated pipes.
Special measures shall be taken to prevent sharp edges or rough surfaces damaging
the heaters.
Fixing materials for heaters shall ensure continuous and permanent contact between
heater and heated surface. They shall be non-corrosive and suitable for the relevant
operating temperature, and shall not damage the heater mechanically or chemically.
Junction boxes and wiring devices shall not be attached to the insulation, but shall be
mounted on brackets fabricated of angle, channel or other material of sufficient
strength to support equipment mounted on them. Brackets shall not be mounted on
pipes but rather, on separate supports.
8.0 IDENTIFICATION
Electrically heat traced piping and equipment shall be clearly identified with suitable
durable weatherproof caution signs, to read “Electrically Traced”, visible from all sides.
Signs on traced pipelines shall not be more than 5 metres apart and positioned on
alternate sides of the sheathing/ cladding.
The elements of a circuit such as local switches, thermostats, connection boxes and
heaters shall be provided with permanent labels, which shall consistently indicate the
number of the circuit to which the elements are connected.
The labels shall be fixed on a non-removable part; for heaters the labels shall be fixed
on the sheathing of the associated pipelines or equipment.
The “Type” testing of the trace heaters shall be done in accordance with section 5.1 of
IEC 62086-1.
The “Routine” testing of the trace heater shall be done in accordance with section 5.2
of IEC 62086-1.
Before leaving the SUPPLIER’s works, each length of cable or panel shall be subject
to inspection, dielectric testing and verification of rated output. Results shall be
recorded in test reports, which shall be distributed as specified in the purchasing
documents.
9.2 Commissioning
Heating cables and surface heaters should be visually checked for damage incurred
during shipping and handling. Continuity and insulation tests may be made as a final
quality check.
Prior to the application of thermal insulation, the insulation resistance of the heating
cable shall be measured under normal dry conditions and before associated wiring or
control equipment is connected. The measured value should not be less than 20 MΩ
AT 500 V (dc).
For heating devices provided with a non-metallic over jacket, an insulation resistance
test should be performed between the metallic covering and ground at 500V (dc) after:
Installation of the heating device on the pipe/ vessel, and Installation of the thermal
insulation. These tests are used to detect damage to the over jacket during the
installation process. It is recommended that the insulation resistance of the entire
branch circuit, after the thermal insulation is complete, should not be less than 10 MΩ
measured at 500V (dc).