Professional Documents
Culture Documents
ACS 1000
Medium Voltage Drives
315 to 5000 kW
400 to 6700 hp
User’s Manual
Frequency Converter
12-pulse and 24-pulse Air-Cooled Version
Issued: 25-10-2005
General Information
Contact Information
Related Documentation
Quality Certificates and Applicable Standards
Contact Information
Related Documentation
Document
Title
Number
Troubleshooting Manual
The user’s manual addresses personnel who are responsible for the
installation, operation and maintenance of the converter. The personnel
must be qualified and fully acquainted with medium voltage equipment.
Operating Personnel The operating personnel include all persons who operate the converter as
required for the application using the control panel(s) of the converter or a
supervisory control system. Operating the converter does not require
special knowledge of converter technology. However, the operator must
know the functions of the control panel.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 1-1 (4)
Chapter 1 - Safety ABB
DANGER!
Indicates an imminent hazardous situation. If not observed, it will lead to
death or life-threatening injury.
WARNING!
Indicates a potentially dangerous situation. If not observed, it could result
in death or life-threatening injury.
CAUTION!
NOTICE!
Indicates important information related to personal safety and protection
of property.
IMPORTANT!
1-2 (4) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 1 - Safety
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 1-3 (4)
Chapter 1 - Safety ABB
High voltage!
Do not remove any bolted walls or plates
when converter is energized or before
converter is grounded. Hot equipment inside the converter
1-4 (4) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Chapter 2 - Transportation, Storage and Disposal
2.1 Transportation
1000
ACS
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 2-1 (6)
Chapter 2 - Transportation, Storage and Disposal ABB
3 Compare the complete delivery with the purchase order and the
packing list.
4 If parts are missing or damaged, immediately inform the shipping
company and the ABB service organization.
It is recommended to photograph the damages.
CAUTION!
! Do not lift and move the converter or a transport unit using a forklift. The
frame of the cabinets could be damaged. If a crane is not available contact
ABB for instructions on other means of moving. See section General
Information for contact address.
CAUTION!
CAUTION!
! When transporting the converter ensure that no dirt enters. Keep doors
closed. Metallic dust in particular may cause damage and lead to
malfunction when the converter is powered up.
2-2 (6) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 2 - Transportation, Storage and Disposal
2.2 Storage
2.2.2 Storage
If the converter is taken out of service for a longer time proceed as follows:
1 Water cooled converters: drain the cooling circuit completely
(contact the ABB service organization for information) or add the
appropriate amount of glycol for frostproofing, if the converter is to be
stored in ambient temperatures below 0 °C (32 °F).
See Appendix A - Additional Manuals for information on frostproofing.
2 Remove the batteries (if applicable).
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 2-3 (6)
Chapter 2 - Transportation, Storage and Disposal ABB
3 Cover all cable inlets and ventilation slots with an impermeable plastic
or aluminum foil and a wooden panel.
4 Add the desiccant of the appropriate quality: 1 unit desiccant (30g)
absorbs 6g water vapor. The following quantity is needed when using
a polyethylene foil:
• 10 units/sqm foil
5 Close and lock the doors of the converter.
6 Use polyethylene or equivalent for packaging:
• 0,3 g/sqm/24h water vapor diffusion
7 Attach humidity indicators to the packaging.
The storage conditions and the packaging should be checked regularly.
Any damages which occur during the storage period should be repaired
immediately.
Inspect the spare parts immediately after receipt for damages. Report any
damage to the shipping company and the ABB service organization.
Observe the following to maintain spare parts in good condition and to
keep the warranty valid during the warranty period:
• Keep spare parts in their original packaging.
• Store printed circuit boards in antistatic bags or boxes.
• Storage temperature range: -5 °C to + 55 °C (23 °F to 131 °F)
• Storage place requirements:
• Free of vibration and shock.
• Protected against dust, sand, vermin and insects.
• Free of corrosive gases, salt or other impurities that
could damage electronic equipment.
• Dry; no condensation
Relative air humidity: 5 to 85 %
If in doubt if the maximum allowed humidity is
exceeded, protect spare parts by an external heater.
• Apply static-sensitive precautions when handling printed circuit
boards. Static electricity can damage these components.
• Do not touch a component without wearing a wrist
grounding strap.
• Put the component on a grounded working surface
protected against electrostatic discharges.
• Hold the component only at the edge.
2-4 (6) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 2 - Transportation, Storage and Disposal
At the end of the life time of the converter dispose of the following
components according to local regulations:
• Batteries
• Capacitors
• Printed circuit boards
• Electronic devices
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 2-5 (6)
Chapter 2 - Transportation, Storage and Disposal ABB
2-6 (6) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Chapter 3 - Mechanical Installation
NOTICE!
All installation work must be carried out by qualified personnel in
compliance with local regulations.
See Chapter 1 - Safety for explanation on how the safety messages are
categorized and used in this manual.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 3-1 (4)
Chapter 3 - Mechanical Installation ABB
The maximum allowable overall unevenness is ≤ 5 mm / 5 m. If the
mounting surface is uneven, the cabinet doors become misaligned and do
not open or close properly.
Cable ducts must be of non-flammable material with non-abrasive
surface.
Suitable fire protection measures must be applied to prevent fire from
spreading into the converter.
All cable entries and exits must be protected to prevent dust, humidity and
animals from entering into the converter.
See Layout Drawing in Appendix C - Mechanical Drawings for exact
dimensions, if holes and channels for cables and water pipes have to be
cut into the floor and mounting holes have to be drilled.
CAUTION!
! When installing the converter ensure that no dirt enters. Always close the
doors when work is discontinued and completely cover openings. Metallic
dust in particular may cause malfunction when the converter is powered
up and cause damage.
Proceed as follows:
1 Drill the floor fixing holes before moving the converter to the final
location.
2 Be careful when moving the converter.
See Chapter 2 - Transportation, Storage and Disposal, 2.1 Transpor-
tation for information to be observed.
3-2 (4) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 3 - Mechanical Installation
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 3-3 (4)
Chapter 3 - Mechanical Installation ABB
5 Assemble and mount the air exhaust hood.
A B
C D
3-4 (4) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Chapter 4 - Electrical Installation
NOTICE!
All installation work must be carried out by qualified personnel in
compliance with local regulations.
See Chapter 1 - Safety for explanation on how the safety messages are
categorized and used in this manual.
Power must not be applied to the drive system without the consent of the
ABB commissioning staff.
DANGER!
Hazardous voltage!
To ensure safety, the converter must be installed in accordance with the
instructions in this manual. Improper work can lead to life-threatening
injury or death.Take appropriate measures to prevent that mains and
auxiliary power can be switched on.
4.1 Overview
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 4-1 (10)
Chapter 4 - Electrical Installation ABB
4.2 Cables
Power Cables See Power Cable Specification for information on suitable power cables
(incoming feeder cables, motor cables, braking resistor cables) or contact
ABB.
Auxiliary Power Cable A 3-phase cable is required for the auxiliary power supply. A neutral
connector is not required. Type and rating is to be selected according to
local regulations.
Control Cables Control cables should be provided in accordance with Table 4-1. Either
single or multiple twisted pair cables may be used.
Control cables should not be laid in parallel to the power cables. If this
cannot be avoided, a minimum distance of 30 cm (12 in) must be
maintained between control and power cables. Control and power cables
should be crossed at an angle of 90°.
Table 4-1 Control Cable Requirements
Speed Encoder Twisted pair cable with overall shield 0.5 mm2
and separately shielded pairs 4 x (2+1)
4-2 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 4 - Electrical Installation
Figure 4-1 Ground Cable and Phase Conductor in one EMC Sleeve
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 4-3 (10)
Chapter 4 - Electrical Installation ABB
PE Transformer
System a1 b1 c1 a2 b2 c2
ground
Armouring
Shielding
System
ground 1U1 1V1 1W1 2U1 2V1 2W1
U2 V2 W2 Converter
PE
2V1
Terminal section
2W1
2U1 2U1
2V1 2V1
2W1 2W1
U2 U2
V2 V2
W2 W2
1U1 1U1
1V1 1V1
1W1 1W1
4-4 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 4 - Electrical Installation
PE Transformer
System a1 b1 c1 a2 b2 c2 a3 b3 c3 a4 b4 c4
ground
Armouring
Shielding
System
ground 1U1 1V1 1W1 2U1 2V1 2W1 3U1 3V1 3W1 4U1 4V1 4W1
U2 V2 W2 Converter
PE
V
U W
PE
Motor
Minimum Creepage When using spacers for cable connection to a busbar, the minimum
Distance required creepage distance must be observed. Depending on the
Comparative Tracking Index (CTI) of the insulation material of the cable
the following Minimum Creepage Distances (MCD) apply:
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 4-5 (10)
Chapter 4 - Electrical Installation ABB
Table 4-2 Creepage Distance
MCD in mm CTI
63 600
71 400....600
80 175....400
If the CTI value of the insulation material is unknown, the values in row
three of the table apply.
NOTICE!
Do not cut cables inside the terminal section. Make sure that waste from
cable cutting and stripping cannot enter the converter. Any waste which
accidentally dropped into the converter must be retrieved. The waste
could cause damage or malfunction.
2 Enter the conductors through the EMC sleeves of the entry plate as
shown in Figure 4-4 and Figure 4-5:
• Strip the cable insulation at the point of entry. Tighten
the EMC sleeve on the stripped part of the cable with
cable ties.
• If necessary, remove the entry plate and slide it onto
the cable. Fasten the entry plate, after the ground
connections have been made.
• IP 42: Remove the rubber grommets from the entry
plates and cut them to adequate diameter for the
transformer and the motor cables (Figure 4-5). To
ensure proper sealing, cut along the diameter
marking that corresponds to the cable diameter. Slide
the grommet onto the cable (Figure 4-4). The
grommet must fit tight to prevent water from entering
the cabinet. If necessary, seal the junctions with
silicone rubber.
4-6 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 4 - Electrical Installation
Outer sheath
Entry plate
EMC sleeve
Outer sheath
A B C
3 Check the insulation of each cable before connection and verify that
the results are within the specifications of the cable manufacturer.
NOTICE!
Do not drill inside the terminal section. Make sure that waste from drilling
cannot enter the converter. Any waste which accidentally dropped into the
converter must be retrieved. The waste could cause damage or
malfunction.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 4-7 (10)
Chapter 4 - Electrical Installation ABB
Approx. 60 mm
5 mm
80 mm
CAUTION!
! High voltages will be present in the terminal section. High voltages can
cause flashover between the potential of a phase conductor and ground.
A minimum clearance of 20 mm must be maintained between each cable
and the terminals of any other phase.
IMPORTANT!
! All provided screws must be mounted and tightened to achieve best EMC.
Cable entry is through the roof or through the bottom of the control unit.
Proceed as follows:
1 Enter the cables through the EMC slot of the entry plate that leads to
the front area of the control unit.
• Shielded cables: Remove the outer cable sheath in
the entry area. The conductive cushions of the EMC
4-8 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 4 - Electrical Installation
Screw holes
Base plate
Entry plate
Copper foil
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 4-9 (10)
Chapter 4 - Electrical Installation ABB
2 Connect the cables. For easy identification, it is recommended to
mark each conductor appropriately before connection.
Auxiliary power cable:
Connect the auxiliary power cable according to Appendix D - Elec-
trical Diagrams.
To identify the terminals see Figure 4-9 and Location Drawings in
Appendix C - Mechanical Drawings.
If a shielded cable is used connect the cable shield to PE.
Control cables:
Connect the control cables to terminals X300, X301 and to the IOEC
boards (see Figure 4-9).
For identification, see Figure 4-9 and Appendix C - Mechanical Draw-
ings. For connection details see Appendix D - Electrical Diagrams.
IOEC board 2
IOEC board 3
IOEC board 4
4-10 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Chapter 5 - Information on Commissioning
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 5-1 (2)
Chapter 5 - Information on Commissioning ABB
5-2 (2) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Chapter 6 - Operation
NOTICE!
Only qualified personnel shall operate the drive system, i.e. personnel
who are familiar with the machine and the operation of the drive system
and the hazards involved.
See Chapter 1 - Safety for explanation on how the safety messages are
categorized and used in this manual.
This chapter outlines the local operation of the converter using the CDP
control panel and the control switches as illustrated in section 6.1 Control
Panel after the converter has been installed and commissioned. If the
control interface has been modified to accommodate project-specific
requirements see the applicable Operating Instructions in Appendix A -
Additional Manuals.
Remote control of the converter via a PLC or remote stations is not
described in this chapter. If the converter is controlled from remote, see
the applicable manuals for information.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 6-1 (10)
Chapter 6 - Operation ABB
Control Panel
• used to start and stop the motor
• displays status messages of the converter
• displays alarm and fault messages
• used to reset alarm and fault messages
Illuminated Pushbuttons
• OFFline opens main circuit breaker
• ONline closes main circuit breaker
6-2 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 6 - Operation
6.2 Starting
DANGER!
High Voltage!
All bolted covers must be fitted to prevent unintended touching of
energized components.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 6-3 (10)
Chapter 6 - Operation ABB
4 Check that the grounding switch is in position “not grounded”.
6-4 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 6 - Operation
9 Press the ONLlNE button to close the main circuit breaker. After the
main circuit breaker has been closed, the DC link of the converter is
charged. The status line of the display changes to Charging:
10 Enter a setpoint.
See Chapter 7 - CDP Control Panel for information on entering a
setpoint.
11 Press the button of the CDP control panel to start the motor.
First, the motor is magnetized:
After the motor has been magnetized, the motor speed is ramped up
to the setpoint. As soon as the motor starts to turn, the display
indicates that the motor is Running:
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 6-5 (10)
Chapter 6 - Operation ABB
6.3 Stopping
As long as the main circuit breaker has not been opened, the motor
can be started again.
6-6 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 6 - Operation
DANGER!
Hazardous voltage!
Do not try to gain access to the converter transformer, the medium voltage
units of the converter nor the motor as long as the drive system is
energized and not grounded.
To disconnect the converter from the main power supply, do the following:
1 Stop the motor as described in the previous section.
2 Press the Offline button to disconnect the converter from the main
power supply. The following happens:
• Main circuit breaker opens.
• DC link discharges.
• Offline button lights up.
After the DC link has been discharged, the display shows:
IMPORTANT!
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 6-7 (10)
Chapter 6 - Operation ABB
After the grounding switch is in position “grounded”, the CDP control
panel displays:
The emergency off button is located on the control section of the converter
(see also Figure 6-1).
6-8 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 6 - Operation
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 6-9 (10)
Chapter 6 - Operation ABB
6-10 (10) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Chapter 7 - CDP Control Panel
7.1 Overview
The CDP control panel is the basic user interface for operating, controlling
and monitoring the converter.
The panel messages and parameter settings used in this chapter are
typical examples to illustrate the related instructions and display functions.
They may differ from the actual messages and parameter settings in your
converter.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 7-1 (12)
Chapter 7 - CDP Control Panel ABB
Keypad Modes The CDP control panel provides the following modes:
• Identification mode
• Actual Signal Display mode, selected by the ACT button
• Parameter mode, selected by the PAR button
• Function mode, selected by the FUNC button
• Drive Selection mode, selected by the DRIVE button.
After the converter has been energized or after the panel has been
connected to the converter for which the auxiliary voltage has been
switched on already, the identification display appears showing the panel
version and then the ID-number of the converter. When the control panel
is being initialized the display changes as follows:
........
After 2-3 seconds:
ID-NUMBER 1
After another few seconds, the display changes to the Actual Signal
Display mode.
7-2 (12) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 7 - CDP Control Panel
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 7-3 (12)
Chapter 7 - CDP Control Panel ABB
When in Actual Signal Display mode, the fast UP/DOWN buttons allow
to toggle between Actual Signal Display and Fault History Display.
Button to be
Step Function Display
pressed
Button to be
Step Function Display
pressed
4. to select a parameter
group 1 L -> 600.0 rpm 0
2 Actual Signals
01 Excitation Cur
7-4 (12) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 7 - CDP Control Panel
Button to be
Step Function Display
pressed
Button to be
Step Function Display
pressed
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 7-5 (12)
Chapter 7 - CDP Control Panel ABB
Table 7-3 Displaying a Fault and Resetting Fault History (Continued)
Button to be
Step Function Display
pressed
Button to be
Step Function Display
pressed
NOTICE!
Parameters must only be set by qualified personnel. Do not change any
parameter, if the meaning of the parameter and the effects of the change
are not fully understood. Running the drive system with incorrect data can
result in improper operation, reduction of control accuracy and damage of
equipment.
Selecting Parameters The Parameter mode is used to check and change parameters. When this
mode is entered for the first time after the auxiliary voltage of the converter
has been switched on, the display will show the first parameter of
parameter group 11. The next time, the Parameter mode is entered, the
previously selected parameter is shown.
7-6 (12) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 7 - CDP Control Panel
** Warning **
Write Access Denied
Parameter Setting
Not Possible
Button to be
Step Function Display
pressed
2. to select a different
group 1 L -> 600.0 rpm 0
75 OPTION MODULES
01 IOEC3 OptionBoard
YES
3. to select a parameter
1 L -> 600.0 rpm 0
75 OPTION MODULES
02 IOEC4 OptionBoard
NO
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 7-7 (12)
Chapter 7 - CDP Control Panel ABB
Table 7-5 Selecting a Parameter and Changing the Value (Continued)
Button to be
Step Function Display
pressed
Setting the Display The Function mode is used to set the contrast of the display.
Contrast
Button to be
Step Function Display
pressed
7-8 (12) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 7 - CDP Control Panel
Button to be
Step Function Display
pressed
2. to select a function (a
blinking cursor indicates 1 L -> 0.0 rpm 0
the selected function) UPLOAD <= <=
DOWNLOAD => =>
CONTRAST 4
Local Control When the panel is switched to LOCAL, operation via the pushbuttons on
the front door of the COU and the CDP control panel is possible. Control
commands from remote have no effect. LOCAL can only be selected
when the converter has been stopped and no remote run command is
active. Switching from LOCAL to REMOTE while the converter is running
stops the converter.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 7-9 (12)
Chapter 7 - CDP Control Panel ABB
Remote Control When the panel is switched to REMOTE, the pushbuttons on the front
door of the control section and the operational buttons of the control panel
are disabled. Operational commands and reference value from a remote
control station are transmitted via fieldbus or remote I/O to the converter.
Switching from REMOTE to LOCAL while the converter is running is not
possible.
Table 7-7 Selecting Local/Remote
Button to be
Step Function Display
pressed
When the direction of rotation is changed while the motor is running, the
speed will automatically ramp to zero and the motor will accelerate in
opposite direction to the preset speed. The direction of the arrow on the
display changes to the new direction when the motor has reached zero
speed.
7-10 (12) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 7 - CDP Control Panel
Button to be
Step Function Display
pressed
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 7-11 (12)
Chapter 7 - CDP Control Panel ABB
7-12 (12) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Chapter 8 - Maintenance and Troubleshooting
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 8-1 (4)
Chapter 8 - Maintenance and Troubleshooting ABB
DANGER!
Hazardous voltage!
Do not try to gain access to the converter transformer, the high voltage
unitss of the converter nor the motor as long as the drive system is
energized and not grounded.
DANGER!
Voltages from external control circuits may be present inside the
converter, even if mains and auxiliary power are shut off. Take appropriate
measures before working on the converter: de-energize and disconnect all
external devices!
DANGER!
The driven machine can cause the motor to rotate! Always disconnect,
short-circuit or block the motor before work is started.
NOTICE!
Before power is applied to the converter, check that:
• Mains and motor connections are ok
• Auxiliary power and control cable connections are ok
• No tools or other foreign objects are left in the cabinet
• All doors of the power sections are properly closed
NOTICE!
The cooling system may start automatically as soon as the auxiliary
voltage is switched on.
8-2 (4) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB Chapter 8 - Maintenance and Troubleshooting
8.2.1 Cleaning
Dust on electrical components and wiring can cause malfunction and
damage the components.
Proceed as follows:
1 De-energize the drive system according to Chapter 6 - Operation.
2 Carefully clean compartment floors with the vacuum cleaner fitted
with a soft nozzle to prevent component damage.
3 When finished, restart the drive system as described in Chapter 6 -
Operation.
IMPORTANT!
Proceed as follows:
1 Do not switch off the auxiliary voltage or try to reset a fault message
before all essential information at the time of the occurance of the
fault condition has been saved.
ACS 1000 User’s Manual 3BHS213401 ZAB E01 Rev. - 8-3 (4)
Chapter 8 - Maintenance and Troubleshooting ABB
2 Call up the Fault History Display on the CDP control panel. See
Chapter 7 - CDP Control Panel for further information.
Do not clear the fault buffer now!
3 Identify the fault and make a logbook entry.
4 Save the content of the data logger, when a PC is available which has
the DriveWindow or DriveDebug tool installed.
The data logger provides useful information (e.g. waveforms of
voltage, current, torque etc.) for efficient troubleshooting.
5 Try to rectify the fault following the Troubleshooting Manual.
6 Contact ABB service if a fault cannot be rectified.
When calling ABB service, it is recommended to have the following
data available at the time when the fault occurred:
• Operating, ambient and load conditions
• Unusual events
• In case of water-cooled converters:
Conductivity, temperature, pressure and water level
of the cooling water
After the fault has been rectified, start the converter as described in
Chapter 6 - Operation.
8-4 (4) 3BHS213401 ZAB E01 Rev. - ACS 1000 User’s Manual
ABB
Maintenance Schedule
Start-up P
Cooling
Aging
Improvements
SW / HW upgrade I I I I I I I I I I I I
Based on product notes I I I I I I I I I I I I
Measurements
Spare Parts
Spare parts I I I I I I I I I I I I
Legend:
Replacement of component R
Inspection (visual inspection, correction and replacement if needed) I
Performance of on-site work (commissioning, tests, measurements, etc.) P