BS EN 50525-2-21:2011

BSI Standards Publication

Electric cables — Low voltage


energy cables of rated voltages
up to and including 450/750 V
(U0/U)
Part 2-21: Cables for general applications
— Flexible cables with crosslinked
elastomeric insulation

NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW

raising standards worldwide™


BS EN 50525-2-21:2011 BRITISH STANDARD
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

National foreword
This British Standard
Standard isis the
theUK
UKimplementation
implementationof ofEN
EN50525-2-21:2011.
50525-2-21:2011. It partially supersedes BS6500:2000 and
In the UK, the BS EN 50525 series of standards contain complex
BS7919:2001.
supersession details. The table below best summarizes the relationship
between
The these standards:
UK participation in its preparation was entrusted to Technical
Committee GEL/20/17, Electric Cables - Low voltage.
Part 1 together with Supersedes
A list of organizations represented on this committee can be
2-81
obtained on request to its secretary. BS 638-4:1996
2-41, 2-42 BS 6007: 2006
This publication does not purport to include all the necessary
2-11 (in part),
provisions of a2-12, 2-21 (in
contract. part),
Users are2-71 BS 6500:2000
responsible for its correct
application.
2-11 (in part), 2-21 (in part), 2-51 (in part), 2-83, 3-21 BS 7919:2001
2-31,
© BSI 2-51
2011(in part) BS 6004:2000
3-41 978 0 580 64364 4
ISBN BS 7211:1998
2-22, 2-72, 2-82, 3-11, 3-31 None
BS EN 50525-2-21:2011 ICS 29.060.20 BRITISH STANDARD
NOTE All British Standards will remain current until they are
Compliance
withdrawn on with a British Standard
31 December cannot
2012. British confer
Standards inimmunity from
bold are only
legal obligations.
partially superseded, and new editions of BS 6004 and BS 7211 will be
National
introducedforeword
on 1 January 2013.
This British Standard was published under the authority of the
Standards
This BritishPolicy and is
Standard Strategy
the UK Committee on 30of
implementation September
EN 2011.
50525-2-21:2011.
National Annex NA It partially supersedes
(informative) BS6500:2000onand
gives information the origins
Amendments issued since publication
BS7919:2001.
and identification of particular cable types.
Date Text affected
The UK participation in its preparation was entrusted to Technical
Committee GEL/20/17, Electric Cables - Low voltage.
A list of organizations represented on this committee can be
obtained on request to its secretary.
This publication does not purport to include all the necessary
provisions of a contract. Users are responsible for its correct
application.
© BSI 2011
ISBN 978 0 580 64364 4
ICS 29.060.20
Compliance with a British Standard cannot confer immunity from
legal obligations.
This British Standard was published under the authority of the
Standards Policy and Strategy Committee on 30 September 2011.
Amendments issued since publication
Date Text affected
BS EN 50525-2-21:2011

EUROPEAN STANDARD EN 50525-2-21


Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

NORME EUROPÉENNE
EUROPÄISCHE NORM May 2011

ICS 29.060.20 Supersedes HD 22.4 S4:2004, HD 22.10 S2:2007, HD 22.11 S2:2007, HD 22.12 S2:2007, HD
22.16 S2:2007

English version

Electric cables -
Low voltage energy cables of rated voltages up to and including 450/750 V
(U0/U) -
Part 2-21: Cables for general applications -
Flexible cables with crosslinked elastomeric insulation

Câbles électriques - Kabel und Leitungen -


Câbles d’énergie basse tension de tension Starkstromleitungen mit Nennspannungen
assignée au plus égale à 450/750 V bis 450/750 V (U0/U) -
(U0/U) - Teil 2-21: Starkstromleitungen für
Partie 2-21: Câbles pour applications allgemeine Anwendungen -
générales - Flexible Leitungen mit vernetzter
Câbles souples isolés en matériau Elastomer-Isolierung
élastomère réticulé

This European Standard was approved by CENELEC on 2011-01-17. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 50525-2-21:2011 E


BS EN 50525-2-21:2011
EN 50525-2-21:2011 -2-
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Foreword

This European Standard was prepared by the Technical Committee CENELEC TC 20, Electric
cables.

The text of the draft was submitted to the formal vote and was accepted by CENELEC as
EN 50525-2-21 on 2011-01-17.

This document, which is one of a multipart series, supersedes HD 22.4 S4:2004,


HD 22 10 S2:2007, HD 22.11 S2:2007, HD 22.12 S2:2007, HD 22.16 S2:2007.

Attention is drawn to the possibility that some of the elements of this document may be the
subject of patent rights. CEN and CENELEC shall not be held responsible for identifying any
or all such patent rights.

The following dates were fixed:

– latest date by which the EN has to be implemented


at national level by publication of an identical
national standard or by endorsement (dop) 2012-01-17

– latest date by which the national standards conflicting


with the EN have to be withdrawn (dow) 2014-01-17

_______________
BS EN 50525-2-21:2011
-3- EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Contents
Page
1 Scope .............................................................................................................................. 5 
2 Normative references ....................................................................................................... 5 
3 Terms and definitions ....................................................................................................... 6 
4 General purpose cables ................................................................................................... 6 
4.1  Ordinary duty cables – H05RR-F ............................................................................. 6 
4.2  Ordinary duty cables – H05RN-F ............................................................................. 7 
4.3  Heavy duty cables – H07RN-F ................................................................................ 8 
4.4  Heavy duty multicore cables – H07RN-F ................................................................. 9 
5 Water resistant cables .................................................................................................... 10 
5.1  Heavy duty cables – H07RN8-F ............................................................................ 10 
5.2  Heavy duty multicore cables – H07RN8-F ............................................................. 12 
6 Heat resistant cables (90 °C) ......................................................................................... 13 
6.1  Ordinary duty cables – H05BB-F ........................................................................... 13 
6.2  Heavy duty cables – H07BB-F ............................................................................... 14 
6.3  Ordinary duty cables – H05BN4-F ......................................................................... 16 
6.4  Heavy duty cables – H07BN4-F............................................................................. 16 
6.5  Heavy duty multicore cables – H07BN4-F ............................................................. 18 
7 Heat resistant cables – TPU sheathed (90 °C) ............................................................... 19 
7.1  Ordinary duty cables – H05BQ-F ........................................................................... 19 
7.2  Heavy duty cables – H07BQ-F .............................................................................. 20 
8 Heat resistant EVA cables (110 °C) - Ordinary duty cables – H05GG-F and
H05GGH2-F ................................................................................................................... 21 
8.1  Construction ......................................................................................................... 21 
8.2  Requirements ....................................................................................................... 22 
Annex A (normative) Tests for cables to EN 50525-2-21 ...................................................... 23 
Annex B (normative) General data ....................................................................................... 27 
Annex C (normative) Requirements for compatibility test ..................................................... 33 
C.1  Cables with a 60 °C temperature rating ................................................................. 33 
C.2  Cables with a 90 °C temperature rating ................................................................. 33 
C.3  Cables with a 110 °C temperature rating ............................................................... 34 
Annex D (normative) Water resistance test for H07RN8-F flexible cables – Electrical
test ................................................................................................................................ 35 
D.1  Voltage pre-test on completed cables ................................................................... 35 
D.2  Voltage test on completed cable at 50 °C .............................................................. 35 
D.3  Insulation resistance test after pre-voltage test ..................................................... 35 
Annex E (normative) Water resistance test for H07RN8-F flexible cables – Mechanical
properties of sheath after water immersion ..................................................................... 37 
E.1  General ................................................................................................................. 37 
E.2  Procedure ............................................................................................................. 37 
E.3  Requirements ....................................................................................................... 37 
Annex F (normative) Special national conditions ....................................................................... 39 
Bibliography ......................................................................................................................... 40 
BS EN 50525-2-21:2011
EN 50525-2-21:2011 -4-
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Tables
Table A.1 − 60 °C cables ...................................................................................................... 23 
Table A.1 − 60 °C cables (concluded) ................................................................................... 24 
Table A.2 − 90 °C and 110 °C cables ................................................................................... 25 
Table B.1 .............................................................................................................................. 27 
Table B.2 .............................................................................................................................. 28 
Table B.3 .............................................................................................................................. 31 
Table B.4 .............................................................................................................................. 32 
Table C.1 ............................................................................................................................. 33 
Table C.2 ............................................................................................................................. 33 
Table C.3 ............................................................................................................................. 34 
Table E.1 − Requirements for tensile strength and elongation at break ....................................... 38 
BS EN 50525-2-21:2011
-5- EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

1 Scope

EN 50525-2-21 applies to flexible cables, insulated with crosslinked elastomeric compound,


and sheathed with either crosslinked elastomeric compound or thermoplastic polyurethane
(TPU).

The cables are of rated voltages U 0 /U up to and including 450/750 V.

The cables are intended for a variety of applications where appliances or equipment,
including heavy industrial equipment, require a flexible connection to the power supply.

The maximum conductor operating temperatures for the cables in this standard are 60 °C (R
types), 90 °C (B types) and 110 °C (G types).

The following particular cable types are included:

- General purpose cables (RR and RN types);


- Water-resistant cables (RN8 types);
- General purpose cables (BB and BN4 types);
- TPU sheathed cables (BQ types);
- Heat resistant cables (GG types)
NOTE HD 516 contains extensive guidance on the safe use of cables in this standard.

This EN 50525-2-21 should be read in conjunction with EN 50525-1, which specifies general
requirements.

2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.

NOTE One or more references to the standards below are in respect of a specific sub-division of that standard,
for instance a clause, a table, a class or a type. Cross-references to these standards are undated and, at all times,
the latest version applies.

EN 50363-1 Insulating, sheathing and covering materials for low voltage


energy cables - Part 1: Cross-linked elastomeric insulating
compounds
EN 50363-2-1 Insulating, sheathing and covering materials for low voltage
energy cables - Part 2-1: Cross-linked elastomeric sheathing
compounds
EN 50363-10-2 Insulating, sheathing and covering materials for low voltage
energy cables - Part 10-2: Miscellaneous sheathing compounds -
Thermoplastic polyurethane
EN 50395 Electrical test methods for low voltage energy cables
EN 50396 Non electrical test methods for low voltage energy cables
EN 50525-1 Electric cables - Low voltage energy cables of rated voltages up
to and including 450/750 V (U 0 /U) - Part 1: General requirements
EN 60228 Conductors of insulated cables (IEC 60228)
BS EN 50525-2-21:2011
EN 50525-2-21:2011 -6-
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions -
Part 1-2: Test for vertical flame propagation for a single insulated
wire or cable - Procedure for 1 kW pre-mixed flame
(IEC 60332-1-2)

EN 60811-1-1 Insulating and sheathing materials of electric and optical cables -


Common test methods - Part 1-1: General application -
Measurement of thickness and overall dimensions - Tests for
determining the mechanical properties (IEC 60811-1-1)

EN 60811-1-2 Insulating and sheathing materials of electric and optical cables -


Common test methods - Part 1-2: General application - Thermal
ageing methods (IEC 60811-1-2)

EN 60811-1-4 Insulating and sheathing materials of electric and optical cables -


Common test methods - Part 1-4: General application - Tests at
low temperature (IEC 60811-1-4)

3 Terms and definitions

For the purposes of this document, the terms and definitions given in Clause 3 of EN 50525-1
apply.

4 General purpose cables

4.1 Ordinary duty cables – H05RR-F

4.1.1 Construction

4.1.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

4.1.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- 2 and 5 core – 0,75 mm to 4 mm ;

2 2
- 3 and 4 core – 0,75 mm to 6 mm .

4.1.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 4 to EN 50363-1,


applied around each conductor.

4.1.1.4 Assembly

The cores shall be twisted together.

NOTE 1 A centre filler may be used.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

4.1.1.5 Sheath

The sheath shall be a cross-linked elastomeric compound of Type EM 3 to EN 50363-2-1.


BS EN 50525-2-21:2011
-7- EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

The sheath shall fill the spaces between the cores.

The colour of sheath is not specified.

NOTE If black is used, the requirement in EN 50363-2-1 for EM 3 to have a minimum level of carbon black will
apply.

4.1.1.6 Marking

The cable shall be marked with the CENELEC code H05RR-F. The marking shall comply with
Clause 6 of EN 50525-1.

4.1.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.1, column 6.

The dimensions of the cables shall conform to Table B.1 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.1.

4.2 Ordinary duty cables – H05RN-F

4.2.1 Construction

4.2.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

4.2.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- 2, 3 and 4 core – 0,75 mm and 1 mm .

4.2.1.3 Insulation
The insulation shall be a cross-linked elastomeric compound, Type EI 4 to EN 50363-1,
applied around each conductor.

4.2.1.4 Assembly

The cores shall be twisted together.

NOTE 1 A centre filler may be used.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

4.2.1.5 Sheath
The sheath shall be a cross-linked elastomeric compound of Type EM 2 to EN 50363-2-1.

The sheath shall fill the spaces between the cores.


BS EN 50525-2-21:2011
EN 50525-2-21:2011 -8-
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

4.2.1.6 Marking

The cable shall be marked with the CENELEC code H05RN-F. The marking shall comply with
Clause 6 of EN 50525-1.

4.2.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.1, column 7.

The dimensions of the cables shall conform to Table B.1 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.1.

4.3 Heavy duty cables – H07RN-F

4.3.1 Construction

4.3.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

4.3.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- Single core – 1,5 mm to 630 mm ;

2 2
- 2 and 5 core – 1,0 mm to 95 mm ;

2 2
- 3 and 4 core – 1,0 mm to 300 mm .

4.3.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 4 to EN 50363-1,


applied around each conductor.

NOTE It is permitted to apply a tape on each core.

Where the insulation is covered with a tape, it shall be applied in such a manner that it can be
removed without damage to the insulation.

4.3.1.4 Assembly

The cores of cables having two to five cores shall be twisted together.

NOTE 1 A centre filler may be used.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

4.3.1.5 Sheath
The cores shall be covered with a sheath.

a) For cables with a specified sheath thickness up to and including 2,4 mm:
BS EN 50525-2-21:2011
-9- EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

1) sheath in a single layer, cross-linked elastomeric compound of type EM 2 to


EN 50363-2-1.
b) For cables with a specified sheath thickness greater than 2,4 mm:
1) sheath either in a single layer, cross-linked elastomeric compound of type EM 2 to
EN 50363-2-1;
2) or in two layers, with the inner layer made of one of the cross-linked elastomeric
compounds type EM 2 or EM 3 to EN 50363-2-1 and the outer layer of the cross-
linked elastomeric compound type EM 2 to EN 50363-2-1.

The sheath applied in a single layer or the inner layer of the sheath in two layers shall, for
cables with two to five cores, fill the spaces between the cores. Where a tape of suitable
material is applied around the core assembly (see NOTE 2 to 4.3.1.4) this requirement shall
not apply, provided that the finished cables shall not have any substantial cavity in the outer
interstices between the cores.

4.3.1.6 Marking

The cable shall be marked with the CENELEC code H07RN-F. The marking shall comply with
Clause 6 of EN 50525-1.

4.3.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.1, column 8.

NOTE For non-electrical tests on sheaths in two layers see EN 50525-1, 5.7.2.3, c).

The dimensions of the cables shall conform to Table B.2 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.1.

4.4 Heavy duty multicore cables – H07RN-F

4.4.1 Construction

4.4.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

4.4.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- 6, 7, 12, 18, 24 and 36 core – 1,5 mm and 2,5 mm ;

2
- 6, 7, 12 and 18 core – 4 mm .

NOTE The number of cores given here is preferred. Other numbers of cores are permitted up to the maximum
number stated in the table for the given size of conductor, subject to agreement between the purchaser and
manufacturer. See also footnote c to Table B.3.

4.4.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 4 to EN 50363-1


applied around each conductor.

The identification of each core shall be in accordance with Annex D of EN 50525-1.


BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 10 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

4.4.1.4 Assembly

The cores shall be twisted together. A single core in the centre is not permitted. A protective
conductor, if any, shall be applied in the outer layer. A centre filler shall be used for cables
having 6, 7, 18, and 36 cores, and also for 19 cores when this non-preferred size is used.

NOTE 1 A centre filler may be used for other sizes.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

4.4.1.5 Sheath

The core assembly shall be covered with a sheath. The sheath shall be applied either in a
single layer, cross-linked elastomeric compound EM 2 to EN 50363-2-1, or in two layers, with
the inner layer made of one of the cross-linked elastomeric compounds EM 2 or EM 3 to
EN 50363-2-1 and the outer layer of cross-linked elastomeric compound EM 2 to
EN 50363-2-1.

The sheath in a single layer or the inner layer of the sheath in two layers shall fill the spaces
between the cores. Where a tape of suitable material is applied around the core assembly
(see NOTE 2 to 4.4.1.4) this requirement shall not apply, provided that the finished cables
shall not have any substantial cavity in the outer interstices between the cores.

4.4.1.6 Marking

The cable shall be marked with the CENELEC code H07RN-F. The marking shall comply with
Clause 6 of EN 50525-1.

4.4.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.1, column 9.

NOTE For non-electrical tests on sheaths in two layers see EN 50525-1, 5.7.2.3, c).

The dimensions of the cables shall conform to Table B.3 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.1.
5 Water resistant cables

5.1 Heavy duty cables – H07RN8-F

5.1.1 Construction

5.1.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

Where an optional separator is applied around each conductor it shall be non-hygroscopic.

5.1.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- Single core – 1,5 mm to 630 mm ;

2 2
- 2 and 5 core – 1,0 mm to 25 mm ;
BS EN 50525-2-21:2011
- 11 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

2 2
- 3 and 4 core – 1,0 mm to 300 mm .

5.1.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 4 to EN 50363-1


applied around each conductor.

NOTE It is permitted to apply a tape on each core.

Where the insulation is covered with a tape, it shall be non-hygroscopic and shall be applied
in such a manner that it can be removed without damage to the insulation.

5.1.1.4 Assembly

The cores of cables having two to five cores shall be twisted together.

NOTE 1 A centre filler may be used.

NOTE 2 A non-hygroscopic tape may be applied around the core assembly before
application of the sheath.

5.1.1.5 Sheath
The cores shall be covered with a sheath.

a) For cables with a specified sheath thickness up to and including 2,4 mm:
1) sheath in a single layer, cross-linked elastomeric compound of type EM 2 to
EN 50363-2-1.
b) For cables with a specified sheath thickness greater than 2,4 mm:
1) sheath either in a single layer, cross-linked elastomeric compound of type EM 2 to
EN 50363-2-1;
2) or in two layers, with the inner layer made of one of the cross-linked elastomeric
compounds type EM 2 or EM 3 to EN 50363-2-1 and the outer layer of the cross-
linked compound type EM 2 to EN 50363-2-1.

The sheath applied in a single layer or the inner layer of the sheath in two layers shall, for
cables with two to five cores, fill the spaces between the cores. Where a non-hygroscopic
tape of suitable material is applied around the core assembly (see NOTE 2 to 5.1.1.4) this
requirement shall not apply, provided that the finished cables shall not have any substantial
cavity in the outer interstices between the cores.

5.1.1.6 Marking

The cable shall be marked with the CENELEC code H07RN8-F. The marking shall comply
with Clause 6 of EN 50525-1.

5.1.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.
Testing shall be in accordance with Table A.1, column 10.

NOTE For non-electrical tests on sheaths in two layers see EN 50525-1, 5.6.2.3, c).

The dimensions of the cables shall conform to Table B.2 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.1.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 12 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

The requirements to be met for the water resistance tests shall be as given in Annexes D
and E.

5.2 Heavy duty multicore cables – H07RN8-F

5.2.1 Construction

5.2.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

Where an optional separator is applied around each conductor it shall be non-hygroscopic.

5.2.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- 6, 7, 12, 18, 24 and 36 core – 1,5 mm and 2,5 mm ;

2
- 6, 7, 12 and 18 core – 4 mm .

NOTE The number of cores given here is preferred. Other numbers of cores are permitted up to the maximum
number stated in the table for the given size of conductor, subject to agreement between the purchaser and
manufacturer. See also footnote c to Table B.3.

5.2.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 4 to EN 50363-1,


applied around each conductor.

The identification of each core shall be in accordance with Annex D of EN 50525-1.

5.2.1.4 Assembly

The cores shall be twisted together. A single core in the centre is not permitted. A protective
conductor, if any, shall be applied in the outer layer. A centre filler shall be used for cables
having 6, 7, 18, and 36 cores, and also for 19 cores when this non-preferred size is used.

NOTE 1 A centre filler may be used for other sizes.

The centre filler shall consist of a non-hygroscopic material.

NOTE 2 A non-hygroscopic tape may be applied around the core assembly before application of the sheath.
BS EN 50525-2-21:2011
- 13 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

5.2.1.5 Sheath

The core assembly shall be covered with a sheath. The sheath shall be applied either in a
single layer, cross-linked elastomeric compound EM 2 to EN 50363-2-1, or in two layers, with
the inner layer made of one of the cross-linked elastomeric compounds EM 2 or EM 3 to
EN 50363-2-1 and the outer layer of cross-linked elastomeric compound EM 2 to
EN 50363-2-1.

The sheath in a single layer or the inner layer of the sheath in two layers shall fill the spaces
between the cores. Where a non-hygroscopic tape of suitable material is applied around the
core assembly (see NOTE 2 to 5.2.1.4) this requirement shall not apply, provided that the
finished cables shall not have any substantial cavity in the outer interstices between the
cores.

5.2.1.6 Marking

The cable shall be marked with the CENELEC code H07RN8-F. The marking shall comply
with Clause 6 of EN 50525-1.

5.2.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.1, column 11.

NOTE For non-electrical tests on sheaths in two layers see EN 50525-1, 5.7.2.3, c).

The dimensions of the cables shall conform to Table B.3 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.1.

The requirements to be met for the water resistance tests shall be as given in Annexes D
and E.

6 Heat resistant cables (90 °C)

6.1 Ordinary duty cables – H05BB-F

6.1.1 Construction

6.1.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

6.1.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- 2 and 5 core – 0,75 mm to 2,5 mm ;

2 2
- 3 and 4 core – 0,75 mm to 6 mm .

6.1.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 6 to EN 50363-1,


applied around each conductor.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 14 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

6.1.1.4 Assembly

The cores shall be twisted together.

NOTE 1 A centre filler may be used.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

6.1.1.5 Sheath

The sheath shall be a cross-linked elastomeric compound of Type EM 6 to EN 50363-2-1.

The sheath shall fill the spaces between the cores.

The colour of sheath is not specified.

NOTE If black is used, the requirement in EN 50363-2-1 for EM 6 to have a minimum level of
carbon black will apply.

6.1.1.6 Marking

The cable shall be marked with the CENELEC code H05BB-F. The marking shall comply with
Clause 6 of EN 50525-1.

6.1.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.2, column 6.

The dimensions of the cables shall conform to Table B.1 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.2.

6.2 Heavy duty cables – H07BB-F

6.2.1 Construction

6.2.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

6.2.1.2 Sizes of cable

The sizes of cable shall be:


2 2
- Single core – 1,5 mm to 630 mm ;
2 2
- 2 core – 1,0 mm to 25 mm ;
2 2
- 3, 4 and 5 core – 1,0 mm to 300 mm .

6.2.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 6 to EN 50363-1,


applied around each conductor.
BS EN 50525-2-21:2011
- 15 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

NOTE It is permitted to apply a tape on each core.

Where the insulation is covered with a tape, it shall be applied in such a manner that it can be
removed without damage to the insulation.

6.2.1.4 Assembly

The cores of cables having two to five cores shall be twisted together.

NOTE 1 A centre filler may be used.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

6.2.1.5 Sheath

The cores shall be covered with a sheath.

a) For cables with a specified sheath thickness up to and including 2,4 mm:
1) sheath in a single layer, cross-linked elastomeric compound of type EM 6 to
EN 50363-2-1.
b) For cables with a specified sheath thickness greater than 2,4 mm:
1) sheath either in a single layer, cross-linked elastomeric compound of type EM 6 to
EN 50363-2-1;
2) or in two layers, with both layers made of cross-linked elastomeric compound of
type EM 6 to EN 50363-2-1.

The sheath applied in a single layer or the inner layer of the sheath in two layers shall, for
cables with two to five cores, fill the spaces between the cores. Where a tape of suitable
material is applied around the core assembly (see NOTE 2 to 6.2.1.4) this requirement shall
not apply, provided that the finished cables shall not have any substantial cavity in the outer
interstices between the cores.

The colour of sheath is not specified.

NOTE If black is used, the requirement in EN 50363-2-1 for EM 6 to have a minimum level of carbon black will
apply.

6.2.1.6 Marking

The cable shall be marked with the CENELEC code H07BB-F. The marking shall comply with
Clause 6 of EN 50525-1.

6.2.2 Requirements

Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.2, column 7.

NOTE For non-electrical tests on sheaths in two layers see EN 50525-1, 5.7.2.3, c).

The dimensions of the cables shall conform to Table B.2 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.2.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 16 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

6.3 Ordinary duty cables – H05BN4-F

6.3.1 Construction

6.3.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

6.3.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- 2 and 3 core – 0,75 mm and 1 mm .

6.3.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 7 to EN 50363-1


applied around each conductor.

6.3.1.4 Assembly

The cores shall be twisted together.

NOTE 1 A centre filler may be used.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

6.3.1.5 Sheath

The sheath shall be a cross-linked elastomeric compound of Type EM 7 to EN 50363-2-1.

The sheath shall fill the spaces between the cores.

6.3.1.6 Marking

The cable shall be marked with the CENELEC code H05BN4-F. The marking shall comply
with Clause 6 of EN 50525-1.

6.3.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.2, column 8.

The dimensions of the cables shall conform to Table B.1 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.2.

6.4 Heavy duty cables – H07BN4-F

6.4.1 Construction

6.4.1.1 Conductor

The conductor shall be class 5, according to EN 60228.


BS EN 50525-2-21:2011
- 17 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

6.4.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- Single core – 1,5 mm to 630 mm ;

2 2
- 2 and 5 core – 1,0 mm to 25 mm ;

2 2
- 3 and 4 core – 1,0 mm to 300 mm .

6.4.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 7 to EN 50363-1


applied around each conductor.

NOTE It is permitted to apply a tape on each core.

Where the insulation is covered with a tape, it shall be applied in such a manner that it can be
removed without damage to the insulation.

6.4.1.4 Assembly

The cores of cables having two to five cores shall be twisted together.
NOTE 1 A centre filler may be used.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

6.4.1.5 Sheath

The cores shall be covered with a sheath.

a) For cables with a specified sheath thickness up to and including 2,4 mm:
1) sheath in a single layer, cross-linked elastomeric compound of type EM 7 to
EN 50363-2-1.
b) For cables with a specified sheath thickness greater than 2,4 mm:
1) sheath either in a single layer, cross-linked elastomeric compound of type EM 7 to
EN 50363-2-1;
2) or in two layers, with the inner layer made of one of the cross-linked elastomeric
compounds type EM 7 or EM 6 to EN 50363-2-1 and the outer layer of the cross-
linked elastomeric compound type EM 7 to EN 50363-2-1.

The sheath applied in a single layer or the inner layer of the sheath in two layers shall, for
cables with two to five cores, fill the spaces between the cores. Where a tape of suitable
material is applied around the core assembly (see NOTE 2 to 6.4.1.4) this requirement shall
not apply, provided that the finished cables shall not have any substantial cavity in the outer
interstices between the cores.

6.4.1.6 Marking

The cable shall be marked with the CENELEC code H07BN4-F. The marking shall comply
with Clause 6 of EN 50525-1.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 18 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

6.4.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.2, column 9.

NOTE For non-electrical tests on sheaths in two layers see EN 50525-1, 5.7.2.3, c).

The dimensions of the cables shall conform to Table B.2 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.2.

6.5 Heavy duty multicore cables – H07BN4-F

6.5.1 Construction

6.5.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

6.5.1.2 Sizes of cable

The sizes of cable shall be:


2 2
- 6, 7, 12, 18, 24 and 36 core – 1,5 mm and 2,5 mm ;

2
- 6, 7, 12 and 18 core – 4 mm .

NOTE The number of cores given here is preferred. Other numbers of cores are permitted up to the maximum
number stated in the table for the given size of conductor, subject to agreement between the purchaser and
manufacturer. See also footnote c to Table B.3.

6.5.1.3 Insulation
The insulation shall be a cross-linked elastomeric compound, Type EI 7 to EN 50363-1,
applied around each conductor.

The identification of each core shall be in accordance with EN 50525-1, Annex D.

6.5.1.4 Assembly
The cores shall be twisted together. A single core in the centre is not permitted. A protective
conductor, if any, shall be applied in the outer layer. A centre filler shall be used for cables
having 6, 7, 18, and 36 cores, and also for 19 cores when this non-preferred size is used.

NOTE 1 A centre filler may be used for other sizes.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

6.5.1.5 Sheath
The core assembly shall be covered with a sheath. The sheath shall be applied either in a
single layer, cross-linked elastomeric compound EM 7 to EN 50363-2-1, or in two layers, with
the inner layer made of one of the cross-linked elastomeric compounds EM 7 or EM 6 to
EN 50363-2-1 and the outer layer of cross-linked elastomeric compound EM 7 to
EN 50363-2-1.

The sheath in a single layer or the inner layer of the sheath in two layers shall fill the spaces
between the cores. Where a tape of suitable material is applied around the core assembly
BS EN 50525-2-21:2011
- 19 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

(see NOTE 2 to 6.5.1.4) this requirement shall not apply, provided that the finished cables
shall not have any substantial cavity in the outer interstices between the cores.

6.5.1.6 Marking

The cable shall be marked with the CENELEC code H07BN4-F. The marking shall comply
with Clause 6 of EN 50525-1.

6.5.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.1, column 10.

NOTE For non-electrical tests on sheaths in two layers see EN 50525-1, 5.7.2.3, c).

The dimensions of the cables shall conform to Table B.3 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.2.

7 Heat resistant cables – TPU sheathed (90 °C)

7.1 Ordinary duty cables – H05BQ-F

7.1.1 Construction

7.1.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

7.1.1.2 Sizes of cable

The sizes of cable shall be:


2 2
- 2, 3, 4 and 5 core – 0,75 mm and 1 mm .

7.1.1.3 Insulation
The insulation shall be a cross-linked elastomeric compound, Type EI 6 to EN 50363-1,
applied around each conductor.

7.1.1.4 Assembly

The cores shall be twisted together.

NOTE A centre filler may be used.

The twisted cores shall be covered by either:

a) an extruded inner covering of a non-crosslinked rubber or plastic compound, or by a


separating tape of suitable material, which may be combined with separate fillers;
or

b) the sheath shall fill the spaces between cores.


BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 20 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

7.1.1.5 Sheath

The sheath shall be thermoplastic polyurethane of type TMPU to EN 50363-10-2 applied


around the completed assembly.

The sheath shall fit closely but not adhere to the inner covering, or, where there is no
separate inner covering, shall not adhere to the cores.

7.1.1.6 Marking

The cable shall be marked with the CENELEC code H05BQ-F. The marking shall comply with
Clause 6 of EN 50525-1.

7.1.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.2, column 11.

The dimensions of the cables shall conform to Table B.1 for the relevant size.

NOTE Where an inner covering is used it should have an approximate thickness of 0,3 mm, but there is no
requirement for this to be measured.

The requirements to be met for the compatibility test shall be as given in Table C.2.

7.2 Heavy duty cables – H07BQ-F

7.2.1 Construction

7.2.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

7.2.1.2 Sizes of cable

The sizes of cable shall be:

2 2
- 2, 3, 4 and 5 core – 1,0 mm to 16 mm .

7.2.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 6 to EN 50363-1,


applied around each conductor.

7.2.1.4 Assembly

The cores shall be twisted together.

NOTE A centre filler may be used.

The twisted cores shall be covered by either:

a) an extruded inner covering of a non-crosslinked rubber or plastic compound, or by a


separating tape of suitable material, which may be combined with separate fillers;
or
BS EN 50525-2-21:2011
- 21 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

b) the sheath shall fill the spaces between cores.

7.2.1.5 Sheath

The sheath shall be thermoplastic polyurethane of type TMPU to EN 50363-10-2 applied


around the completed assembly.

The sheath shall fit closely but not adhere to the inner covering, or, where there is no
separate inner covering, shall not adhere to the cores.

7.2.1.6 Marking

The cable shall be marked with the CENELEC code H07BQ-F. The marking shall comply with
Clause 6 of EN 50525-1.

7.2.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.2, column 12.

The dimensions of the cables shall conform to Table B.4 for the relevant size.

NOTE Where an inner covering is used it should have an approximate thickness of 0,3 mm, but there is no
requirement for this to be measured.

The requirements to be met for the compatibility test shall be as given in Table C.2.

8 Heat resistant EVA cables (110 °C) - Ordinary duty cables – H05GG-F and
H05GGH2-F

8.1 Construction

8.1.1 Conductor

The conductor shall be class 5, according to EN 60228.

A separator of suitable material shall be applied around each conductor if the conductors are
plain.

NOTE If the conductors are tinned the use of a separator is optional.

8.1.2 Sizes of cable

The sizes of circular cable shall be:

2 2
- 2 and 5 core – 0,75 mm to 2,5 mm ;

2 2
- 3 and 4 core – 0,75 mm to 6 mm ;

2
- for flat cable the only size is 2 core, 0,75 mm .

8.1.3 Insulation

The insulation shall be a cross-linked elastomeric compound, Type EI 3 to EN 50363-1,


applied around each conductor.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 22 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

8.1.4 Assembly

The cables shall be assembled as follows:

- circular cable: the cores shall be twisted together;


- flat cable: the cores shall be laid parallel.

NOTE 1 A centre filler may be used for circular cables.

NOTE 2 A tape may be applied around the core assembly before application of the sheath.

8.1.5 Sheath

The sheath shall be a cross-linked elastomeric compound of Type EM 4 to EN 50363-2-1.


The sheath shall fill the spaces between the cores.

8.1.6 Marking

The cable shall be marked with the CENELEC code H05GG-F for circular cables, or
H05GGH2-F for flat cables. The marking shall comply with Clause 6 of EN 50525-1.

8.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.

Testing shall be in accordance with Table A.2, column 13.

The dimensions of the cables shall conform to Table B.1 for the relevant size.

The requirements to be met for the compatibility test shall be as given in Table C.3.
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

- 23 - EN 50525-2-21:2011

Annex A
(normative)

Tests for cables to EN 50525-2-21


Table A.1 − 60 °C cables

1 2 3 4 5 6 7 8 9 10 11
a
Ref Tests Category Test Method described in Applicability of test – Subclause
No. of test
EN Clause 4.1 4.2 4.3 4.4 5.1 5.2

H05RR
H05RN
H07RN
H07RN
H07RN8
H07RN8

multicore
multicore

b
1 Electrical tests
1.1 Resistance of conductors T, S 50395 5 X X X X X X
1.2.1 Voltage test at 2 500 V T, S 50395 6 - - X X X X
1.2.2 Voltage test at 2 000 V T, S 50395 6 X X - - - -
1.3 Voltage test on cores according to
specified insulation thickness
1.3.1 at 1 500 V up to and including 0,6 mm T 50395 7 X X - - - -
1.3.2 at 2 000 V exceeding 0,6 mm T 50395 7 X - - - - -
1.3.3 at 2 500 V T 50395 7 - - X X X X
1.4 Absence of faults in insulation R 50395 10 X X X X X X
1.5 Surface resistance of sheath T 50395 11 X X X X X X
2 Constructional and dimensional tests
2.1 Checking of compliance with constructional T, S 50525-1 Inspection and X X X X X X
provisions manual tests
2.2 Measurement of thickness of insulation T, S 50396 4.1 X X X X X X
2.3 Measurement of thickness of sheath T, S 50396 4.2 X X X X X X
2.4 Measurement of overall diameter
2.4.1 Mean value T, S 50396 4.4 X X X X X X
2.4.2 Ovality T, S 50396 4.4 X X X X X X
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

EN 50525-2-21:2011 - 24 -

Table A.1 − 60 °C cables (concluded)

1 2 3 4 5 6 7 8 9 10 11
a
Ref Tests Category Test Method described in Applicability of test – Subclause
No. of test
EN Clause 4.1 4.2 4.3 4.4 5.1 5.2

H05RR
H05RN
H07RN
H07RN
H07RN8
H07RN8

multicore
multicore

2.5 Solderability test (plain conductors) T 50396 8.2 X X X X X X


c
3 Insulation material tests T 50363-1 - X X X X X X
c, d
4 Sheath material tests T 50363-2-1 X X X X X X
5 Compatibility test T 60811-1-2 8.1.4 X X X X X X
e e
6 Impact test at - 25 °C T 60811-1-4 8.5 X X X X X X
7 Mechanical strength of completed cable
Flexing test f followed, after immersion in
water, by a voltage test on cores
7.1 - at 1 500 V on cores with specified T 50396 6.2 X X - - - -
insulation thickness up to and including
0,6 mm 50395 7

7.2 - at 2 000 V on cores with specified T 50396 6.2 X - X X X X


insulation thickness exceeding 0,6 mm
50395 7
8 Test under fire conditions T 60332-1-2 - - X X X X X
9 Water resistance tests
9.1 Electrical test T This EN Annex D - - - - X X
9.2 Mechanical test on sheath T This EN Annex E - - - - X X
a
The order given does not imply a sequence of testing.
b
Particular test conditions and requirements are given in Table 1 of EN 50525-1.
c
This EN includes all the test methods and requirements for the material. Material to be tested is taken from the finished cable.
d
The requirement for resistance to ozone is not applicable to the inner layer of two layer sheath.
e
Not applicable to cables having conductors greater than 16 mm².
f
Not applicable to single core cables, nor to multicore cables having conductors greater than 4 mm², nor to cables with more than 18
cores laid up in more than two concentric layers.
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

- 25 - EN 50525-2-21:2011

Table A.2 − 90 °C and 110 °C cables

1 2 3 4 5 6 7 8 9 10 11 12 13
a
Ref Tests Category Test method described in Applicability of test – Subclause
No. of test
EN Clause 6.1 6.2 6.3 6.4 6.5 7.1 7.2 8

H05BB
H07BB
H05BQ
H07BQ
H05GG

H05BN4
H07BN4
H07BN4
multicore
b
1 Electrical tests
1.1 Resistance of conductors T, S 50395 5 X X X X X X X X
1.2.1 Voltage test at 2 500 V T, S 50395 6 - X - X X - X -
1.2.2 Voltage test at 2 000 V T, S 50395 6 X - X - - X - X
1.3 Voltage test on cores according to specified
insulation thickness
1.3.1 at 1 500 V up to and including 0,6 mm T 50395 7 X - X - - X - X
1.3.2 at 2 000 V exceeding 0,6 mm T 50395 7 X - - - - - X X
1.3.3 at 2 500 V T 50395 7 - X - X X - - -
1.4 Absence of faults in insulation R 50395 10 X X X X X X X X
1.5 Surface resistance of sheath T 50395 11 X X X X X X X X
2 Constructional and dimensional tests
2.1 Checking of compliance with constructional T, S 50525-1 Inspection X X X X X X X X
provisions and
manual
tests
2.2 Measurement of thickness of insulation T, S 50396 4.1 X X X X X X X X
2.3 Measurement of thickness of sheath T, S 50396 4.2 X X X X X X X X
2.4 Measurement of overall diameter
2.4.1 Mean value T, S 50396 4.4 X X X X X X X X
2.4.2 Ovality T, S 50396 4.4 X X X X X X X X
2.5 Solderability test (plain conductors) T 50396 8.2 X X X X X X X X
3 Insulation material tests T 50363-1 - X X X X X X X X
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

EN 50525-2-21:2011 - 26 -

Table A.2 − 90 °C and 110 °C cables (concluded)


1 2 3 4 5 6 7 8 9 10 11 12 13
a
Ref Tests Category Test method described in Applicability of test – Subclause
No. of test
EN Clause 6.1 6.2 6.3 6.4 6.5 7.1 7.2 8

H05BB
H07BB
H05BQ
H07BQ
H05GG

H05BN4
H07BN4
H07BN4
multicore
c d
4 Sheath material tests T 50363-2-1 X X X X X X X X
5 Compatibility test T 60811-1-2 8.1.4 X X X X X X X X
6 Impact test
e
6.1 at - 40 °C T 60811-1-4 8.5 X X - - - X X -
e
6.2 at - 25 °C T 60811-1-4 8.5 - - X X X - - -
6.3 at - 5 °C T 60811-1-4 8.5 - - - - - - - X
7 Mechanical strength of completed cable
Flexing test f followed, after immersion in
water, by a voltage test on cores
7.1 - at 1 500 V on cores with specified T 50396 6.2 X - X - - X - X
insulation thickness up to and including
0,6 mm 50395 7

7.2 - at 2 000 V on cores with specified T 50396 6.2 X X - X X - X X


insulation thickness exceeding 0,6 mm
50395 7
8 Test under fire conditions T 60332-1-2 - - - X X X - - -
a
The order given does not imply a sequence of testing.
b
Particular test conditions and requirements are given in Table 1 of EN 50525-1.
c
This EN includes all the test methods and requirements for the material. Material to be tested is taken from the finished cable.
d
The requirement for resistance to ozone is not applicable to the inner layer of two layer sheath.
e
Not applicable to cables having conductors greater than 16 mm².
f
Not applicable to single core cables, nor to multicore cables having conductors greater than 4 mm², nor to cables with more than 18 cores laid up in more
than two concentric layers.
BS EN 50525-2-21:2011
- 27 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Annex B
(normative)

General data

NOTE The overall dimensions of cables have been calculated in accordance with EN 60719.

Table B.1

1 2 3 4 5
Number and nominal Thickness of insulation Thickness of sheath Mean overall diameter
cross-sectional area
of conductors a Specified value Specified value

Lower limit Upper limit


mm² mm mm mm mm
2 x 0,75 0,6 0,8 5,7 or 7,4 or
3,7 x 6,0 4,7 x 7,4
2x1 0,6 0,9 6,1 8,0
2 x 1,5 0,8 1,0 7,6 9,8
2 x 2,5 0,9 1,1 9,0 11,6
2x4 1,0 1,2 10,6 13,7

3 x 0,75 0,6 0,9 6,2 8,1


3x1 0,6 0,9 6,5 8,5
3 x 1,5 0,8 1,0 8,0 10,4
3 x 2,5 0,9 1,1 9,6 12,4
3x4 1,0 1,2 11,3 14,5
3x6 1,0 1,4 12,8 16,3

4 x 0,75 0,6 0,9 6,8 8,8


4x1 0,6 0,9 7,1 9,3
4 x 1,5 0,8 1,1 9,0 11,6
4 x 2,5 0,9 1,2 10,7 13,8
4x4 1,0 1,3 12,7 16,2
4x6 1,0 1,5 14,2 18,1

5 x 0,75 0,6 1,0 7,6 9,9


5x1 0,6 1,0 8,0 10,3
5 x 1,5 0,8 1,1 9,8 12,7
5 x 2,5 0,9 1,3 11,9 15,3
5x4 1,0 1,4 14,6 18,6
a
Not all cable types are specified in all the sizes given here. See the specific clause of the standard, and also
Clause 1 of EN 50525-1.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 28 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Table B.2

1 2 3 4 5 6 7
Number & Thickness of Thickness of sheath Mean overall diameter
nominal insulation
cross Specified value
sectional Specified
value One layer Two layers Lower Upper
area of limit limit
a
conductors Inner Outer
layer layer
mm² mm mm mm mm mm mm
1 x 1,5 0,8 1,4 - - 5,7 7,1
1 x 2,5 0,9 1,4 - - 6,3 7,9
1x4 1,0 1,5 - - 7,2 9,0
1x6 1,0 1,6 - - 7,9 9,8
1 x 10 1,2 1,8 - - 9,5 11,9
1 x 16 1,2 1,9 - - 10,8 13,4
1 x 25 1,4 2,0 - - 12,7 15,8
1 x 35 1,4 2,2 - - 14,3 17,9
1 x 50 1,6 2,4 - - 16,5 20,6
1 x 70 1,6 2,6 1,0 1,6 18,6 23,3
1 x 95 1,8 2,8 1,1 1,7 20,8 26,0
1 x 120 1,8 3,0 1,2 1,8 22,8 28,6
1 x 150 2,0 3,2 1,3 1,9 25,2 31,4
1 x 185 2,2 3,4 1,4 2,0 27,6 34,4
1 x 240 2,4 3,5 1,4 2,1 30,6 38,3
1 x 300 2,6 3,6 1,4 2,2 33,5 41,9
1 x 400 2,8 3,8 1,5 2,3 37,4 46,8
1 x 500 3,0 4,0 1,6 2,4 41,3 52
1 x 630 3,0 4,1 1,6 2,5 45,5 57

2x1 0,8 1,3 - - 7,7 10,0


2 x 1,5 0,8 1,5 - - 8,5 11,0
2 x 2,5 0,9 1,7 - - 10,2 13,1
2x4 1,0 1,8 - - 11,8 15,1
2x6 1,0 2,0 - - 13,1 16,8
2 x 10 1,2 3,1 1,2 1,9 17,7 22,6
2 x 16 1,2 3,3 1,3 2,0 20,2 25,7
2 x 25 1,4 3,6 1,4 2,2 24,3 30,7
2 x 35 1,4 3,8 1,5 2,3 27,2 34,3
2 x 50 1,6 4,2 1,7 2,5 31,6 39,8
2 x 70 1,6 4,6 1,8 2,8 35,8 45,1
2 x 95 1,8 5,0 2,0 3,0 40,2 51
BS EN 50525-2-21:2011
- 29 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Table B.2 (continued)

1 2 3 4 5 6 7
Number & Thickness of Thickness of sheath Mean overall diameter
nominal insulation
cross Specified value
sectional Specified
value Two layers
area of
conductors One layer Inner Outer Lower Upper
layer layer limit limit
mm² mm mm mm mm mm mm
3x1 0,8 1,4 - - 8,3 10,7
3 x 1,5 0,8 1,6 - - 9,2 11,9
3 x 2,5 0,9 1,8 - - 10,9 14,0
3x4 1,0 1,9 - - 12,7 16,2
3x6 1,0 2,1 - - 14,1 18,0
3 x 10 1,2 3,3 1,3 2,0 19,1 24,2
3 x 16 1,2 3,5 1,4 2,1 21,8 27,6
3 x 25 1,4 3,8 1,5 2,3 26,1 33,0
3 x 35 1,4 4,1 1,6 2,5 29,3 37,1
3 x 50 1,6 4,5 1,8 2,7 34,1 42,9
3 x 70 1,6 4,8 1,9 2,9 38,4 48,3
3 x 95 1,8 5,3 2,1 3,2 43,3 54
3 x 120 1,8 5,6 2,2 3,4 47,4 60
3 x 150 2,0 6,0 2,4 3,6 52 66
3 x 185 2,2 6,4 2,5 3,9 57 72
3 x 240 2,4 7,1 2,8 4,3 65 82
3 x 300 2,6 7,7 3,1 4,6 72 90

4x1 0,8 1,5 - - 9,2 11,9


4 x 1,5 0,8 1,7 - - 10,2 13,1
4 x 2,5 0,9 1,9 - - 12,1 15,5
4x4 1,0 2,0 - - 14,0 17,9
4x6 1,0 2,3 - - 15,7 20,0
4 x 10 1,2 3,4 1,4 2,0 20,9 26,5
4 x 16 1,2 3,6 1,4 2,2 23,8 30,1
4 x 25 1,4 4,1 1,6 2,5 28,9 36,6
4 x 35 1,4 4,4 1,7 2,7 32,5 41,1
4 x 50 1,6 4,8 1,9 2,9 37,7 47,5
4 x 70 1,6 5,2 2,0 3,2 42,7 54
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 30 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Table B.2 (concluded)

1 2 3 4 5 6 7
Number & Thickness of Thickness of sheath Mean overall diameter
nominal insulation
cross Specified value
sectional Specified
value Two layers
area of
conductors One layer Inner Outer Lower Upper
layer layer limit limit
mm² mm mm mm mm mm mm
4 x 95 1,8 5,9 2,3 3,6 48,4 61
4 x 120 1,8 6,0 2,4 3,6 53 66
4 x 150 2,0 6,5 2,6 3,9 58 73
4 x 185 2,2 7,0 2,8 4,2 64 80
4 x 240 2,4 7,7 3,1 4,6 72 91
4 x 300 2,6 8,4 3,3 5,1 80 101

5x1 0,8 1,6 - - 10,2 13,1


5 x 1,5 0,8 1,8 - - 11,2 14,4
5 x 2,5 0,9 2,0 - - 13,3 17,0
5x4 1,0 2,2 - - 15,6 19,9
5x6 1,0 2,5 1,0 1,5 17,5 22,2
5 x 10 1,2 3,6 1,4 2,2 22,9 29,1
5 x 16 1,2 3,9 1,5 2,4 26,4 33,3
5 x 25 1,4 4,4 1,7 2,7 32,0 40,4
5 x 35 1,4 4,6 1,8 2,8 35,7 45,1
5 x 50 1,6 5,2 2,1 3,1 41,8 53
5 x 70 1,6 5,7 2,3 3,4 47,5 60
5 x 95 1,8 6,3 2,5 3,8 54 67
5 x 120 1,8 6,3 2,5 3,8 58 73
5 x 150 2,0 6,8 2,7 4,1 64 80
5 x 185 2,2 7,4 3,0 4,4 71 89
5 x 240 2,4 8,1 3,2 4,9 80 100
5 x 300 2,6 8,8 3,5 5,3 88 111
a
Not all cable types are specified in all the sizes given here. See the specific clause of the
standard, and also Clause 1 of EN 50525.
BS EN 50525-2-21:2011
- 31 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Table B.3

1 2 3 4 5 6 7
b c
Number & Thickness Thickness of sheath Mean overall diameter
nominal of
cross insulation Specified value Lower Upper
sectional limit limit
Specified One layer Two layers
area of
conductors a value
Inner layer Outer
layer

mm 2 mm mm mm mm mm mm
6 x 1,5 0,8 2,5 1,0 1,5 13,4 17,2
7 x 1,5 0,8 2,6 1,0 1,6 14,7 18,7
12 x 1,5 0,8 2,9 1,2 1,7 17,6 22,4
18 x 1,5 0,8 3,2 1,3 1,9 20,7 26,3
24 x 1,5 0,8 3,5 1,4 2,1 24,3 30,7
36 x 1,5 0,8 3,8 1,5 2,3 27,8 35,2

6 x 2,5 0,9 2,7 1,1 1,6 15,7 20,0


7 x 2,5 0,9 2,8 1,1 1,7 17,1 21,8
12 x 2,5 0,9 3,1 1,2 1,9 20,6 26,2
18 x 2,5 0,9 3,5 1,4 2,1 24,4 30,9
24 x 2,5 0,9 3,9 1,6 2,3 28,8 36,4
36 x 2,5 0,9 4,3 1,7 2,6 33,2 41,8

6x4 1,0 2,9 1,2 1,7 18,2 23,2


7x4 1,0 3,1 1,2 1,9 20,1 25,5
12 x 4 1,0 3,5 1,4 2,1 24,4 30,9
18 x 4 1,0 3,9 1,6 2,3 28,8 36,4
a
The number of cores given here is preferred.
b
The sheath thicknesses (e g ) of the cables have been calculated by the fictitious calculation
method according to IEC 60502-1, Annex A, using the following formula:
e g = 0,11 D + 1,5 mm
where D is the diameter over laid up cores.
c
Where “non-preferred” numbers are manufactured, the sheath thickness, for one layer or for two
layer constructions, shall be for the next highest preferred number of cores.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 32 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Table B.4

1 2 3 4 5
Number and nominal Thickness of insulation Thickness of sheath Mean overall diameter
cross-sectional area
of conductors Specified value Specified value

Lower limit Upper limit


mm² mm mm mm mm
2x1 0,8 0,9 6,9 9,0
2 x 1,5 0,8 1,0 7,6 9,8
2 x 2,5 0,9 1,1 9,0 11,6
2x4 1,0 1,2 10,6 13,7
2x6 1,0 1,3 11,8 15,1
2 x 10 1,2 2,0 15,6 19,9
2 x 16 1,2 2,1 17,9 22,8

3x1 0,8 0,9 7,3 9,5


3 x 1,5 0,8 1,0 8,0 10,4
3 x 2,5 0,9 1,1 9,6 12,4
3x4 1,0 1,2 11,3 14,5
3x6 1,0 1,4 12,8 16,3
3 x 10 1,2 2,1 16,8 21,4
3 x 16 1,2 2,3 19,5 24,7

4x1 0,8 1,0 8,2 10,7


4 x 1,5 0,8 1,1 9,0 11,6
4 x 2,5 0,9 1,2 10,7 13,8
4x4 1,0 1,3 12,7 16,2
4x6 1,0 1,5 14,2 18,1
4 x 10 1,2 2,2 18,6 23,6
4 x 16 1,2 2,3 21,3 27,0

5x1 0,8 1,1 9,2 11,9


5 x 1,5 0,8 1,1 9,8 12,7
5 x 2,5 0,9 1,3 11,9 15,3
5x4 1,0 1,4 14,1 17,9
5x6 1,0 1,6 15,7 20,0
5 x 10 1,2 2,3 20,4 25,9
5 x 16 1,2 2,5 23,7 30,0
BS EN 50525-2-21:2011
- 33 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Annex C
(normative)

Requirements for compatibility test

C.1 Cables with a 60 °C temperature rating

C.1.1 Test conditions


The sample shall be aged for seven days at (80 ± 2) °C in accordance with the designated
test method.

C.1.2 Requirements

At the conclusion of the ageing period the insulation and sheath shall meet the requirements given in
Table C.1 below.

Table C.1

Parameter Units Insulation Sheath


EI 4
EM 2 EM 3

Tensile strength - median, min. N/mm 2 4,2 - -


a b
- variation , max. % ± 25 - 15 ± 30
Elongation at break - median, min. % 200 250 -
- variation a , max. % ± 25 - 25 b
± 30
a
The variation is the difference between the respective values obtained prior to and after heat treatment,
expressed as a percentage of the former.
b
No limit for the positive tolerance.

C.2 Cables with a 90 °C temperature rating

C.2.1 Test conditions


The sample shall be aged for seven days at (100 ± 2) °C in accordance with the designated
test method.

C.2.2 Requirements
At the conclusion of the ageing period the insulation and sheath shall meet the requirements
given in Table C.2 below.
Table C.2

Parameter Units Insulation Sheath


EI 6 EI 7 EM 6 EM 7 TMPU
2
Tensile strength - median, min. N/mm 5,0 5,0 7,0 - -
a
- variation , max. % ± 30 ± 30 - ± 30 ± 30
Elongation at break - median, min. % - - 200 - 300
a
- variation , max. % ± 30 ± 30 - ± 40 ± 30
a
The variation is the difference between the respective values obtained prior to and after heat treatment, expressed as a
percentage of the former.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 34 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

C.3 Cables with a 110 °C temperature rating

C.3.1 Test conditions


The sample shall be aged for seven days at (135 ± 2) °C in accordance with the designated
test method.

C.3.2 Requirements
At the conclusion of the ageing period the insulation and sheath shall meet the requirements
given in Table C.3 below.

Table C.3

Parameter Units Insulation Sheath


EI 3 EM 4

Tensile strength - median, min. N/mm 2 - -


a
- variation , max. % ± 30 ± 30
Elongation at break - median, min. % - -
a
- variation , max. % ± 30 ± 30
a
The variation is the difference between the respective values obtained prior to and after heat treatment,
expressed as a percentage of the former.
BS EN 50525-2-21:2011
- 35 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Annex D
(normative)

Water resistance test for H07RN8-F flexible cables – Electrical test

D.1 Voltage pre-test on completed cables


The sample shall consist of at least 20 m of the complete cable to be tested. The sample shall be
immersed in potable tap water at (20 ± 5) °C for at least one hour. Then the a.c. voltage test shall be
carried out according to EN 50395, Clause 6.

D.2 Voltage test on completed cable at 50 °C


A 5 m sample shall be taken from the 20 m length tested in D.1 and immersed in potable tap water at
(50 ± 2) °C for a period of 100 days. During this immersion period an a.c. test-voltage of 1 kV shall be
applied between one conductor connected to the water and all others connected together in the case of
multicore cable, and between the conductor and the water in the case of single core cable. If the cable
contains a circuit protective conductor this shall be the conductor connected to the water.

No electrical breakdown shall occur.

D.3 Insulation resistance test after pre-voltage test

D.3.1 General

Three samples of core each 5 m long shall be taken from the sample length of complete cable tested in
D.1.

The three samples shall be subjected to all the following tests of D.3

D.3.2 Voltage test on cores

The three samples shall be immersed in potable tap water at (50 ± 2) °C for at least 24 h.
Then an a.c. test voltage of 2 500 V shall be applied between each conductor and the water
for a period of 5 min.

No electrical breakdown shall occur.

Immediately after this test the insulation resistance shall be measured in accordance with
EN 50395, 8.1 at a temperature of (50 ± 2) °C.

The value of volume resistivity calculated from the formula given in EN 50395, Annex A, shall
12
be ≥ 10 Ω ·cm.

D.3.3 Voltage test on cores at 50 °C

The three samples tested in D.3.2 shall be immersed in potable tap water at (50 ± 2) °C for a
period of 14 days. During this period an a.c. test voltage of 1 000 V shall be applied between
each conductor and the water.

No electrical breakdown shall occur.

Immediately after this test the insulation resistance shall be measured in accordance to 8.1 of
EN 50395, at a temperature of (50 ± 2) °C.
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

11
BS EN 50525-2-21:2011
EN 50525-2-21:2011

shall be ≥ 10 Ω · cm.
- 36 -

The value of volume resistivity, calculated from the formula given in EN 50395, Annex A,
BS EN 50525-2-21:2011
- 37 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Annex E
(normative)

Water resistance test for H07RN8-F flexible cables – Mechanical


properties of sheath after water immersion

E.1 General
This test shall be carried out on samples taken from:

a) the sheath when applied as a single layer; or

b) the inner and outer layers of sheath when applied in two layers.

E.2 Procedure
Four sets of three dumb bell samples shall be taken from each layer of the sheath of the
cable as manufactured as described in EN 60811-1-1, 9.2.3, and conditioned for seven days
at a temperature of (20 ± 5) °C and a relative humidity of (50 ± 5) %. At the end of the
conditioning period the sets shall be used as follows:

a) One set shall be weighed to 0,1 mg. The samples shall then be immersed in potable tap
water at (50 ± 2) °C for 100 days.

After removal from the potable tap water, surface water shall be removed by wiping lightly
with a filter paper and the samples conditioned for 16 h at a temperature of (20 ± 5) °C and a
relative humidity of (50 ± 5) %.

The samples shall then be re-weighed and the weights determined to 0,1 mg as soon as
possible after removal from the conditioning chamber.

b) Three sets shall be used for determination of tensile strength and elongation at break
as follows:

1) Without immersion;
2) After immersion in potable tap water at (50 ± 2) °C for 28 days;
3) After immersion in potable tap water at (50 ± 2) °C for 100 days.

E.3 Requirements
a) Increase in mass

The increase of mass after immersion for 100 days shall not be greater than 40 % of the
mass before immersion.

b) Tensile strength and elongation at break

The tensile strength and elongation at break, as described in EN 60811-1-1, 9.2.7, after
immersion for 100 days shall be greater than or equal to the values given in Table E.1.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 38 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Table E.1 − Requirements for tensile strength and elongation at break

Parameter Units Inner layer Single layer/


outer layer
2
Tensile strength N/mm 5 7
Elongation at % 175 200
break

Variation between 28 days immersion and 100 days immersion:

TS 28 - TS 100
- 0,15 ≤ ≤ + 0,15
TS 28

EB 28 - EB100
- 0,2 ≤ ≤ + 0,2
EB 28
BS EN 50525-2-21:2011
- 39 - EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Annex F
(normative)

Special national conditions

Special national condition: National characteristic or practice that cannot be changed even over a long
period, e.g. climatic conditions, electrical earthing conditions. If it affects harmonization, it forms part of
the European Standard.

For the countries in which the relevant special national conditions apply these provisions are normative,
for other countries they are informative.

Clause Special national condition

Table B.1 Ireland, United Kingdom

Add:

3 x 1,25 0,8 1,0 7,8 10,2

NOTE This cable is intended for use on appliances fitted with 13 A plugs conforming to
BS 1363-1 or I.S. 401.
BS EN 50525-2-21:2011
EN 50525-2-21:2011 - 40 -
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

Bibliography

EN 50334 Marking by inscription for the identification of cores of electric


cables

EN 60719 Calculation of the lower and upper limits for the average outer
dimensions of cables with circular copper conductors and of rated
voltages up to and including 450/750 V (IEC 60719)

HD 516 Guide to use of low voltage harmonized cables

IEC 60502-1 2004 Power cables with extruded insulation and their accessories for
rated voltages from 1 kV (Um = 1,2 kV) up to
30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV
(Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
BRITISH STANDARD NA to BS EN 50525-2-21:2011
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

National Annex (informative) Origins and identification of the particular cable types
As an aid to users, the table below shows, in respect of BS EN 50525-2-21:
—— the identification of the particular cable types from BS 6500 and BS 7919 that are now included in
BS EN 50525-2-21;
—— the location of the cables within BS EN 50525-2-21;
—— any applicable United Kingdom and CENELEC cable codings (see also National Informative Annex B
to BS EN 50525-1).

Pre-existing BS Clause in BS EN 50525-2-21 Cable type – Coding


Number Table United Kingdom CENELEC
(if applicable)
BS 6500 12 4.1 3182/3/4/5 H05RR-F
BS 6500 13 4.2 3182/3P H05RN-F
BS 6500 15 6.1 – H05BB-F
BS 6500 16 6.3 – H05BN4-F
BS 7919 10 4.1 3182/3 H05RR-F
BS 7919 11 6.1 – H05BB-F
BS 7919 12 6.2 – H07BB-F
BS 7919 13 8.1 – H05GG-F
– H05GGH2-F
BS 7919 14 4.3 6381/2/3/4/5P H07RN-F
BS 7919 15 4.4 6386/12/18/24/36P H07RN-F
BS 7919 16 6.4 – H07BN4-F
BS 7919 17 6.5 – H07BN4-F
BS 7919 20 5.1 – H07RN8-F
BS 7919 21 5.2 – H07RN8-F
BS 7919 23 7.1 – H05BQ-F
BS 7919 24 7.2 – H07BQ-F

© BSI 2011 • 41
Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

42 • © BSI 2011
NA to BS EN 50525-2-21:2011
BRITISH STANDARD

This page deliberately left blank


Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

This page deliberately left blank


Bought by Mr DAVID GOMEZ, Documail, on 17/12/2012 19:39 Latest version. Not to be distributed/networked. For multi-user access www.bsigroup.com/license © BSI

British Standards Institution (BSI)


BSI is the independent national body responsible for preparing British Standards
and other standards-related publications, information and services.
It presents the UK view on standards in Europe and at the international level.
It is incorporated by Royal Charter.

Revisions Information on standards


British Standards are updated by amendment or revision. Users of British Stan- BSI provides a wide range of information on national, European
dards should make sure that they possess the latest amendments or editions. and international standards through its Knowledge Centre.
It is the constant aim of BSI to improve the quality of our products and serv- Tel: +44 (0)20 8996 7004 Fax: +44 (0)20 8996 7005
ices. We would be grateful if anyone finding an inaccuracy or ambiguity while Email: knowledgecentre@bsigroup.com
using this British Standard would inform the Secretary of the technical com-
mittee responsible, the identity of which can be found on the inside front Various BSI electronic information services are also available which
cover. give details on all its products and services.
Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001 Tel: +44 (0)20 8996 7111 Fax: +44 (0)20 8996 7048
Email: info@bsigroup.com
BSI offers Members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards. BSI Subscribing Members are kept up to date with standards
Tel: +44 (0)20 8996 7669 Fax: +44 (0)20 8996 7001 developments and receive substantial discounts on the purchase price
Email: plus@bsigroup.com of standards. For details of these and other benefits contact Membership Ad-
ministration.
Buying standards Tel: +44 (0)20 8996 7002 Fax: +44 (0)20 8996 7001
Email: membership@bsigroup.com
You may buy PDF and hard copy versions of standards directly using a
credit card from the BSI Shop on the website www.bsigroup.com/shop. Information regarding online access to British Standards via British
In addition all orders for BSI, international and foreign standards publications Standards Online can be found at www.bsigroup.com/BSOL
can be addressed to BSI Customer Services.
Further information about BSI is available on the BSI website at www.bsi-
Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001 group.com/standards
Email: orders@bsigroup.com

In response to orders for international standards, it is BSI policy to Copyright


supply the BSI implementation of those that have been published
Copyright subsists in all BSI publications. BSI also holds the copyright,
as British Standards, unless otherwise requested.
in the UK, of the publications of the international standardization bodies. Ex-
cept as permitted under the Copyright, Designs and Patents Act 1988 no ex-
tract may be reproduced, stored in a retrieval system or transmitted in any
form or by any means – electronic, photocopying, recording or otherwise –
without prior written permission from BSI. This does not preclude the free
use, in the course of implementing the standard of necessary details such as
symbols, and size, type or grade designations. If these details are to be used
for any other purpose than implementation then the prior written permission
of BSI must be obtained. Details and advice can be obtained from the Copy-
right & Licensing Manager.
Tel: +44 (0)20 8996 7070
Email: copyright@bsigroup.com

BSI Group Headquarters


389 Chiswick High Road London W4 4AL UK
Tel +44 (0)20 8996 9001
Fax +44 (0)20 8996 7001
www.bsigroup.com/standards

raising standards worldwide™

You might also like