You are on page 1of 2

7SJ600 Inverse Time

Over Current IP >(ph) I/In 0.1 - 4.0 (in steps 0.1)


Earth Fault IEP >(Earth) I/In 0.1 - 4.0 (in steps 0.1)
Time Multiplier above IP/IEP 0.05 - 3.20 S (in steps 0.1)
High Set I>> (ph) I/In 0.1 - 25.0 (in steps 0.1)
High Set IE>> (ph) I/In 0.1 - 25.0 (in steps 0.1)
Delay Time for I>>, IE>> 0.00 - 60.0 S (in steps 0.01)
High Set Inst I>>> (ph) I/In 0.3 - 12.5 (in steps 0.1)

3WN6 ACB

Over Current IP >(ph) I/In 0.4 - 1.0 In (5% grade, 10 S)


Earth Fault IEP >(Earth) I/In 0.2-0.6 (0.1-0.5 S)
High Set I>> (ph) I/Ir 1.25 - 12 Ir (0.02-0.4 S)
High Set Inst I>>> (ph) I/In 1-15 In

3VL MCCB - ETU22

Over Current IP >(ph) I/In 0.4 - 1.0 In (Fixed 10s)


Earth Fault IEP >(Earth) I/In 0.2-1.0 (01-0.5 S)
High Set I>> (ph) I/Ir 1.5 - 10 Ir (0-0.5 S)
High Set Inst I>>> (ph) I/In 11 In
Definite Time

0.1 - 4.0 (in steps 0.1)


0.1 - 4.0 (in steps 0.1)
0.00 - 60.0 S (in steps 0.01)
0.1 - 25.0 (in steps 0.1)
0.1 - 25.0 (in steps 0.1)
0.00 - 60.0 S (in steps 0.01)
0.3 - 12.5 (in steps 0.1)