Professional Documents
Culture Documents
Abstract—Both Standards EN 50522 and IEEE 81 propose the EPR Earth Potential Rise.
fall of potential method (FPM) to carry out the measurement of ES Earthing System.
the resistance to earth (RES ) of an earthing system (ES). However, FEM Finite Element Method.
in urban areas, the recommended distances between the ES and
auxiliary electrodes are not easy to respect, due to the presence FPM Fall of Potential Method.
of buildings and tarmac. Furthermore, unknown buried metallic FPM/Clamp Fall of potential/clamp-on method.
parts and interconnections among ESs could modify the earth po- GES Global Earthing System.
tential profile of the area, affecting the measurement results. In HV High Voltage.
this paper, the key-issues that influence the measured RES when I Test current.
the FPM is used in an urban environment are presented. A para-
metric analysis, carried out with Comsol Multiphysics, quantifies LV Low voltage.
the errors due to wrong positioning of the auxiliary electrodes and MV Medium voltage.
due to the presence of interconnected ESs in the proximity of the P Voltage probe.
ES under test. In addition, a real case of field measurement is de- RES Resistance to earth.
scribed, emphasizing the main aspects that could compromise the
V Voltage between the earthing system under test
results. Finally, practical suggestions to reduce errors are provided.
and the voltage probe.
Index Terms—Earth, Grounding, resistance measurement, ur- r Relative percentage error.
ban areas, fall of potential, MV/LV substation.
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
2338 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 3, MAY/JUNE 2019
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
COLELLA et al.: FALL OF POTENTIAL MEASUREMENT OF THE EARTH RESISTANCE IN URBAN ENVIRONMENTS: ACCURACY EVALUATION 2339
Fig. 2. Error due to interconnection among ESs. The dashed blue line and Fig. 3. Error due to the presence of BPs, interconnected to the ES. The dot-
the continuous green line represent the EPP for the scenario with and without dash red line and the continuous green line represent the EPP for the scenario
interconnection, respectively. with and without the BP, respectively.
presented in [13], in addition to the reduction of the earth current The effects of the interconnection among ESs are also pre-
similar to that described before for MV cable sheaths, the high sented in the discussion of the parametric analysis in Section IV.
number and the proximity of the earth rods have an impact also
on the potential distribution on the soil surface: The voltage C. Presence of BPs
probe can be placed where the soil potential is far from zero. Another point that should be considered in earth resistance
As a consequence, the measurement error increases and RES is measurements is the presence of buried metallic parts, which
underestimated. can either belong to the earthing network (e.g., bare buried
If the MV/LV substation is under construction, a simple so- conductors) or not (e.g., water and gas pipes). These objects are
lution is the disconnection of the ES under test from other ESs. commonly widespread in urban areas and usually have a large
Vice versa, if the MV/LV substation is already in operation, extension. Generally, no information about them is available
other strategies should be adopted. In fact, in order to carry during RES measurements. They can be interconnected to the
out the measurement safely, before disconnecting the ES from ES or kept floating. According to their interconnection level
the cable sheaths, the whole MV feeder shall be powered OFF, and to their distance from the ES under test, they can modify
with a consequent service interruption that is generally con- the current field and the earth potential profile (EPP) [9]. An
sidered unacceptable by distribution system operators (DSOs). unfavorable condition happens when the voltage probe P is
An alternative solution suggested by EN 50522 is to use high placed over a metallic object interconnected to the ES as shown
frequency earth testers, which are commonly adopted to de- in Fig. 3. In this case, the reference potential given by P is far
couple transmission tower earth wires; the frequency shall be from zero and both EPR and RES are underestimated.
sufficiently high to make the impedance of the interconnection
conductors relevant, representing a practically negligible shunt
III. PARAMETRIC ANALYSIS
circuit to the earthing of the single ES [1].
Another approach to take into account the interconnection As discussed in the aforementioned section, standards EN
among ESs is to measure the portion of the current that flows 50522 and IEEE Std. 81 provide suggestions for the position-
into the ES under test only. This method is proposed by the IEEE ing of auxiliary electrodes [see (1) and (2)] [1], [7]. However,
Std. 81 by the name of “Fall of potential/clamp-on method” the recommended distances are not easy to be respected in ur-
(FPM/Clamp) [7]. However, this method cannot always be ban environments due to the presence of buildings and tarmac.
adopted, because earthing conductors could be not easily acces- Moreover, the interconnection among ESs and the presence
sible and current clamps could not be installed. Furthermore, of BPs significantly affects the measurement as described in
even if this technique is adopted, the measurement error due to Section III.
the perturbation of the soil surface potential due to LV neutrals In order to quantify the error caused by an incorrect position-
distributed groundings is not eliminated. ing of current electrode and voltage probe, and by the presence
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
2340 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 3, MAY/JUNE 2019
TABLE I
EXAMINED SCENARIOS
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
COLELLA et al.: FALL OF POTENTIAL MEASUREMENT OF THE EARTH RESISTANCE IN URBAN ENVIRONMENTS: ACCURACY EVALUATION 2341
TABLE II
GEOMETRICAL AND ELECTRICAL DETAILS
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
2342 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 3, MAY/JUNE 2019
TABLE III
PARAMETRIC ANALYSIS RESULTS
Fig. 9. Percentage error r of R ES for scenario 3 (dC = 40 m), according to Fig. 10. Percentage error r of R ES for scenario 4 (dC = 20 m), according
the position of the voltage probe (FPM). to the position of the voltage probe (FPM).
areas [north (y > 0), south (y < 0), east (x > 0), west (x < 0)],
two asymmetries can be noticed. The first one between the west
and east portions of ground with reference to the ES; the sec-
ond one between the north and west areas. Both are due to the
presence of the auxiliary current electrode, which modifies the
electric potential profile of the ground with reference to the case
in which only the ES is present. According to these results,
contrary to what might be thought, it could be more convenient
to place the voltage probe along the north or south directions,
rather than on the west side. The common practice of placing
the voltage probe on the opposite side of the ES with respect to
the auxiliary current electrode should be avoided.
From a practical point of view, errors lower than 20% could
be considered acceptable, provided that the conditions reported
by standards for the observance of permissible touch voltages
are largely satisfied [1], [24].
In Figs. 9 and 10, the isolines of the relative percentage error
defined by the position of the voltage probe are reported for Fig. 11. Percentage error r of R ES for scenario 3 (dC = 40 m), according
scenarios 3 and 4 when the FPM is adopted. It can be noticed that to the position of the voltage probe (FPM/Clamp).
for the considered case, the position of the voltage probe does
not significantly influence the accuracy of the measurement, In particular, the effects of BPs in the test area are described.
which is mainly affected by the distribution of the test current.
Small percentage errors can be obtained in the proximity of
A. Measurement Description
the auxiliary current electrode. This result cannot be considered
always valid, since in real field measurements it is impossible A satellite image of the field measurement site is reported in
to evaluate if RES is under- or overestimated. Fig. 13. For confidentiality issues, all geographical references
If the FPM/Clamp is adopted, the isolines are modified as and labels were deleted.
shown in Figs. 11 and 12. At the same distance from the ES A soil resistivity of 250 Ωm was measured, according to the
under test, the percentage errors are significantly lower, even if Wenner four-electrode configuration method.
still rather high. In this case, the error is due to the modification To measure RES , a three terminal ground resistance tester,
of the EPP produced by the ESs 7 and 9. specifically designed for FPM, was used.
The ES of the substation under test is formed by a ground ring
electrode with a diameter of 5 m, buried at a depth of 0.75 m.
IV. FIELD MEASUREMENTS
Its maximum extension d is 5 m.
In order to provide practical examples of the issues reported In Fig. 13, the MV/LV substation is highlighted with a pink-
in Section III, the resistance to earth of an MV/LV substation in white oblique lines hatch, while the location of auxiliary elec-
a city was measured with the FPM. trodes is reported with colored circles. To evaluate how the
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
2344 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 3, MAY/JUNE 2019
TABLE IV
MEASUREMENT RESULTS
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
COLELLA et al.: FALL OF POTENTIAL MEASUREMENT OF THE EARTH RESISTANCE IN URBAN ENVIRONMENTS: ACCURACY EVALUATION 2345
can be higher in real scenarios due to the presence of the LV [7] Guide for Measuring Earth Resistivity, Ground Impedance, and Earth
earthing network, not considered in the simulations presented Surface Potentials of a Grounding System, IEEE Standard 81, Dec. 2012.
[8] E. Pons, P. Colella, R. Napoli, and R. Tommasini, “Impact of MV ground
in this paper, which can modify both the fault current and the fault current distribution on global earthing systems,” IEEE Trans. Industry
potential distribution on the soil surface. The disconnection of Appl., vol. 51, no. 6, pp. 4961–4968, Nov./Dec. 2015.
the ESs for each periodic measurement is not a practicable so- [9] E. Pons et al., “Global earthing system: Can buried metallic structures
significantly modify the ground potential profile?” IEEE Trans. Industry
lution, as it generally requires to power OFF the whole MV Appl., vol. 51, no. 6, pp. 5237–5246, Nov./Dec. 2015.
feeder, which is considered unacceptable for DSOs. Moreover, [10] P. Colella et al., “Currents distribution during a fault in an MV network:
disconnecting any earth bonds is contrary to best maintenance Methods and measurements,” IEEE Trans. Industry Appl., vol. 52, no. 6,
pp. 4585–4593, Nov./Dec. 2016.
practice. Therefore, if technically possible, the best option to [11] P. Colella, E. Pons, R. Tommasini, E. R. Sanseverino, M. L. Di Silvestre,
reduce measurement error is to compute RES considering the and G. Zizzo, “Earth resistance measurements in urban contexts: Problems
current that flows through the ES under test only (FPM/Clamp). and possible solutions,” in Proc. IEEE Int. Conf. Environ. Elect. Eng. IEEE
Ind. Commercial Power Syst. Eur., 2017, pp. 1–6.
Otherwise, if not possible, the FPM with high frequency tester [12] A. Campoccia, E. R. Sanseverino, and G. Zizzo, “Analysis of intercon-
can be employed to decouple the ES under test. However, even nected earthing systems of MV/LV substations in urban areas,” in Proc.
if these techniques are adopted, the measurement error due to 43rd Int. Universities Power Eng. Conf., 2008, pp. 1–5.
[13] G. Cafaro et al., “Influence of LV neutral grounding on global earthing
the perturbation of the soil surface potential is not eliminated. systems,” IEEE Trans. Industry Appl., vol. 53, no. 1, pp. 22–31, Jan./Feb.
Another alternative is to measure RES twice when the MV 2017.
feeder is out of service for a scheduled maintenance, keeping [14] G. F. Tagg, “Measurement of earth-electrode resistance with particular ref-
erence to earth-electrode systems covering a large area,” Elect. Engineers,
constant the test current: in the first measure, the ES is dis- Proc. Institution, vol. 111, no. 12, pp. 2118–2130, 1964.
connected from the earthing network and RES can be measured [15] J. Ladanyi and B. Smohai, “Influence of auxiliary electrode arrangements
with a small error, allowing to verify that the ES is adequately on earth resistance measurement using the fall-of-potential method,” in
Proc. 4th Int. Youth Conf. Energy, 2013, pp. 1–6.
designed and installed; in the second measure, the ES is inter- [16] E. Curdts, “Some of the fundamental aspects of ground resistance mea-
connected. The obtained value can therefore be associated to surements,” Trans. Amer. Inst. Elect. Eng., I, Commun. Electron., vol. 77,
that of the disconnected configuration. In this way, it is possible no. 5, pp. 760–767, 1958.
[17] P. Colella, E. Pons, and R. Tommasini, “MV ground fault current distribu-
to monitor just the “interconnected” RES value over the time; if tion: An analytical formulation of the reduction factor,” in Proc. IEEE Int.
no significant changes are observed on this value, the efficacy Conf. Environ. Elect. Eng./IEEE Ind. Commercial Power Syst. Europe,
of the ES can be considered preserved. 2017, pp. 1–6.
[18] A. Mujezinovic, A. Muharemovic, I. Turkovic, and Z. Bajramovic, “Ap-
Finally, according to the simulation results of the isolated plication of finite element method in calculation of large and complex
ES (scenario 1 and 2), and keeping in mind that the presence grounding systems,” in Proc. Int. Conf. Expo. Elect. Power Eng., 2012,
of buried electrodes in the proximity of the ES under test can pp. 688–692.
[19] V. Cataliotti and A. Campoccia, Impianti di Terra. Turin, Italy: TNE, 2013.
play a significant role in modifying the EPP, when the criterion [20] J. Li, T. Yuan, Q. Yang, W. Sima, and C. Sun, “Finite element modeling
suggested by EN 50522 is adopted, it is more convenient to of the grounding system in consideration of soil nonlinear characteristic,”
place the voltage probe not along the direction that connects the in Proc. Int. Conf. High Voltage Eng. Appl., 2010, pp. 164–167.
[21] O. Zienkiewicz, C. Emson, and P. Bettess, “A novel boundary infinite
ES with the current electrode, due to the non symmetric electric element,” Int. J. Numer. Methods Eng., vol. 19, no. 3, pp. 393–404, 1983.
potential profile, but along a perpendicular direction. [22] P. Colella, E. Pons, and R. Tommasini, “Dangerous touch voltages in
Even if the suggestions summarized in this manuscript can buildings: The impact of extraneous conductive parts in risk mitigation,”
Elect. Power Syst. Res., vol. 147, pp. 263–271, 2017.
minimize the measurement error, the RES evaluation through [23] A. Stohchniol, “A general transformation for open boundary finite element
the FPM remains difficult in particular contexts, such as for method for electromagnetic problems,” IEEE Trans. Magn., vol. 28, no. 2,
example the urban one. Considering the issues reported in this pp. 1679–1681, Mar. 1992.
[24] IEEE Guide for Safety in AC Substation Grounding. IEEE Standard 80,
paper and that an ES plays only a small part in ensuring safety 01 2000.
for staff and public in the event of an MV earth fault condition,
a more convenient approach is represented by GES.
REFERENCES
[1] Earthing of Power Installations Exceeding 1 kV a.c. EN 50522, Jul. 2011.
[2] G. Cafaro et al., “The global grounding system: Definitions and guide-
lines,” in Proc. IEEE 15th Int. Conf. Environ. Elect. Eng., 2015, pp. 537–
541.
[3] P. Colella, E. Pons, and R. Tommasini, “A comparative review of the
methodologies to identify a global earthing system,” IEEE Trans. Industry
Appl., vol. 53, no. 4, pp. 3260–3267, Jul./Aug. 2017.
[4] P. Colella, E. Pons, and R. Tommasini, “The identification of global earth- Pietro Colella (S’15–M’16) received the M.Sc. and Ph.D. degrees in electri-
ing systems: A review and comparison of methodologies,” in Proc. IEEE cal engineering from the Politecnico di Torino, Turin, Italy, in 2012 and 2016,
16th Int. Conf. Environ. Elect. Eng., 2016, pp. 1–6. respectively.
[5] G. Parise et al., “A practical method to test the safety of HV/MV substation He is currently an Assistant Professor with the Politecnico di Torino. His
grounding systems,” in Proc. IEEE 15th Int. Conf. Environ. Elect. Eng., research interest includes power systems, traction electrification systems, and
2015, pp. 502–506. electrical safety.
[6] G. Parise, L. Martirano, L. Parise, S. Celozzi, and R. Araneo, “Simplified Dr. Colella is a member of the AEIT - Associazione Italiana di Elettrotecnica,
conservative testing method of touch and step voltages by multiple auxil- Elettronica, Automazione, Informatica e Telecomunicazioni. He is a Registered
iary electrodes at reduced distance,” IEEE Trans. Industry Appl., vol. 51, Professional Engineer in Italy. He received the Italian Electrotechnical Com-
no. 6, pp. 4987–4993, Nov./Dec. 2015. mittee Best Thesis Award in 2011.
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.
2346 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 55, NO. 3, MAY/JUNE 2019
Enrico Pons (M’15) received the master’s degree in electrical engineering and Eleonora Riva Sanseverino has been an Associate Professor of electrical power
the Ph.D. degree in industrial safety and risk analysis from Politecnico di Torino, systems since 2002 with the University of Palermo, Palermo, Italy, and affiliated
Turin, Italy, in 2004 and 2008, respectively. as Full Professor by the Italian Ministry of Education since 2013. Since 2002, she
He is currently an Associate Professor with the Politecnico di Torino, where has been working with the Department of Energy, Information Engineering and
he teaches electrical installations. He has coauthored more than 70 publica- Mathematical Models, the University of Palermo. She is a scientific coordinator
tions, published in international conferences proceedings and in international of various research projects with research organizations and companies. She
journals. His research interests include complexity in energy systems, power is also responsible of various teaching cooperation agreements with foreign
systems security, complex networks methodologies for the analysis of power institutions. She has authored more than 250 papers on international journals,
systems vulnerability, real-time simulation of power systems, integration of edited books and book chapters, and conference proceedings. She is the Rector’s
renewable generation in distribution networks, smart metering, traction electri- delegate of the European Charter and code for Researchers at the University of
fication systems, and electrical safety. Palermo.
Riccardo Tommasini received the master’s and Ph.D. degree in electrical en-
gineering from the Politecnico di Torino, Turin, Italy, in 1984 and 1990, respec-
tively.
He was an Assistant Professor with the Politecnico di Torino. His research
interests include power systems and electrical safety.
Prof. Tommasini was a member of the Italian Electrotechnical Committee
where he worked in the 31 Committee, dealing with the evaluation of hazards
due to the risk caused by explosive atmospheres and in committee 81, dealing
with the protection against lightning. Unfortunately, he passed away on January
2017.
Maria Luisa Di Silvestre received the M.S. and Ph.D. degrees in electrical Gaetano Zizzo (SM’17) received the M.S. and Ph.D. degrees from the Univer-
engineering from the University of Palermo, Palermo, Italy, in 1993 and 1998, sity of Palermo, Palermo, Italy, in 2002 and 2006, respectively.
respectively. He is an Assistant Professor of Electrical Power Systems with the University
Since 2000, she has been an Assistant Professor with the University of of Palermo. Since 2006, he has been with the Department of Energy, Informa-
Palermo. Since 1999, she has been with the DEIM of the University of Palermo. tion Engineering and Mathematical Models, University of Palermo. His current
She was a Grant Holder from 1999 to 2000. Her research interests include research interests include electrical safety, power systems design, management,
analysis and modeling of complex grounding systems, optimization methods for and optimization, smart grids and stability analysis.
electrical distribution systems design, operation, and planning, optimal power Dr. Zizzo became a member of the Industry Application Society in 2017. He
flow. is involved in the activities of the IEEE Standard Association.
Authorized licensed use limited to: Universiti Malaysia Perlis. Downloaded on November 19,2023 at 01:49:58 UTC from IEEE Xplore. Restrictions apply.