Line-000-Ca-4-0016 - Specification For Reinforcing Bar Work - Rev. 0
Line-000-Ca-4-0016 - Specification For Reinforcing Bar Work - Rev. 0
Document Category
SPECIFICATION
Project Name :
LINE Project
Site Location :
Cilegon, Indonesia
Document Title :
SPECIFICATION FOR
REINFORCING BAR WORK
Document No. :
LINE-000-CA-4-0016
Rev.
Page Paragraph Description Remarks
No.
A - - First Issue
TABLE OF CONTENTS
1. GENERAL............................................................................................................................... 4
1.1 Scope ........................................................................................................................................................4
1.2 Related Standards ...................................................................................................................................4
1.3 Priority of Requirements .........................................................................................................................4
2. MATERIAL .............................................................................................................................. 4
2.1 Reinforcing Bar ........................................................................................................................................4
2.2 Welded Steel Wire Fabric ........................................................................................................................5
2.3 Accessories ..............................................................................................................................................5
5. INSPECTION .......................................................................................................................... 8
5.1 Before Installation ....................................................................................................................................8
5.2 During Installation ...................................................................................................................................8
5.3 After Installation .......................................................................................................................................8
1. GENERAL
1.1 Scope
This construction specification covers general requirement for Reinforcing Bar for concrete
which also includes Mild Steel and Deformed Reinforcing Bar.
This specification does not cover the construction of Pre-Stressed P.C steel wires.
2. MATERIAL
2.1.2 The Contractor may select any particular chemical analysis or composition of steel so
long as the specified mechanical properties are met. However, Mill certificates including
both mechanical properties and chemical composition shall be submitted to LCI prior to
SPECIFICATION FOR Doc. No. : LINE-000-CA-4-0016
Rev. No. : 0
REINFORCING BAR WORK Page : 5 of 8
2.3 Accessories
Accessories, bar supports and etc., are used in placing the reinforcing bars to assure that the
bars are correctly positioned in relation to the forms. The varied accessories all serve the
basic function of supporting the reinforcing steel, in proper vertical position, enabling the bar
setters to space and position the bars accurately. The bar supports shall be heavy enough
and numerous enough to support the bars properly.
3.1 General
3.1.1 Reinforcing bar shall be free from loose rust, scale, mud, oil, grease, paint or other
coatings that may prevent or reduce the bond.
3.1.2 Welding of cross bars shall not be permitted for the assembly of reinforcement unless
authorized by LCI. Spacer blocks shall be either Precast concrete or of cement mortar or
made out of PVC as approved by LCI.
3.1.3 Random length straight bars shall be identified with a metal tag to show the number of
bars, diameter and length.
3.3.1 Reinforcing bars shall be fabricated in the shop located at site. At this shop, benders,
cutters and work benches shall be used to execute all bending and cutting. The
fabricated reinforcing bars shall be transported to the appropriate work areas.
3.3.3 Bars bent incorrectly shall not be rebent without LCI approval.
3.4 Workmanship
3.4.1 Placing of rebar shall be carried out strictly in accordance with the detailed drawing. The
bars shall be securely fastened with tie wire. The center to center distance (spacing)
between consecutive bars shall be in accordance with the detailed drawings.
3.4.2 Reinforcing bars used in slabs, footings, rafts and etc. shall conform to the bar size,
dimensions, number and spacing as shown on the schedule and the detailed Drawings.
Pins used for beam reinforcement shall also have similar functions like chairs.
Bars intended to be in contact at the crossing points shall be securely wired together at
all such points with tie wire.
Two tie rods of at least 10 mm diameter shall be provided in the tip of all concrete
beams to fasten stirrups where no tip bar occurs.
Full continuity shall be provided over supports for all continuous slabs, beams and joints
unless otherwise noted.
All reinforcing bar within the limits of a day's pour shall be in place and firmly wired or
clipped in sufficient time to permit inspection before pouring concrete.
Reinforcement in structures shall not be welded except where approved by LCI. All
welding procedures shall be subject to the prior approval of LCI in written.
Bar Lapped splice shall be strictly in accordance with the standard drawings indicating
length and diameter of the bars
Splices shall be avoided from at the points of maximum stress. They shall be staggered
and shall be designed to develop the strength of the bar without exceeding the allowable
unit bond stress. All bar splices shall be approved by LCI.
Splices in welded wire fabric shall be made by lapping minimum of one spacing of
SPECIFICATION FOR Doc. No. : LINE-000-CA-4-0016
Rev. No. : 0
REINFORCING BAR WORK Page : 7 of 8
Placed reinforcing bar shall inspected and approved by LCI. The Contractor shall submit
an Inspection Request Form 1 day prior to the desired day of inspection. This inspection
of the reinforcing bars must take place prior to the pouring of concrete.
3.4.8 All intersections of reinforcing bars shall be bound tight with black annealed tie wire
similar to the splice (Laps).
Any leftover piece of bar after cutting, and which cannot be utilized and which is less
than 1.0 meter long shall be treated as scrap.
5. INSPECTION
For placing prefabricated reinforcing bar at heights, adequate scaffolding shall be provide for
the workmen to work safely and for temporarily supporting long vertical bars to prevent their
displacement and sagging during concrete placing and vibration.