1. Packaged Refrigeration Chiller


a. Estimated Capacity of Packaged Water-cooled Chiller
b. Packaged Chiller Data Selected
c. Estimated Flow for Chilled and Cooling Water in gallons
per minute
d. Schematic Diagram of the Chiller showing the different
parameters
e. High Lighted Selected Data on the Brochure
f. Specification of the Chiller
WEST Building
Ground & Other Floors
Total Computed Cooling Load in
Floor Tons
74 F 78 F
Room Temp. Room Temp.
Ground (Rooms/Offices) 30
Corridors (AHUs) 10
Second (Rooms/Offices) 25 -
Corridors (AHU) 15
Total Capacity
North/ North West Building
Ground & Other Floors
Total Computed Cooling Load in
Floor Tons
74 F 78 F
Room Temp. Room Temp.
Ground (Rooms/Offices) 30
Corridors (AHUs) 10
Second (Rooms/Offices) 25 -
Corridors (AHU) 15
Total Capacity
South/South West Building
Ground & Other Floors
Total Computed Cooling Load in
Floor Tons
74 F 78 F
Room Temp. Room Temp.
Ground (Rooms/Offices) 30
Corridors (AHUs) 10
Second (Rooms/Offices) 25 -
Corridors (AHU) 15
Total Capacity
Summary for all the Buildings
Total Computed Cooling Load in
Buildings Tons
74 F 78 F
Room Temp. Room Temp.
North/North West 30 12

South/South West 36 32

West Building 47 54

Total 113 44

Total Capacity 157 (157 x 1.1 = 172.7)


Packaged Chiller Data Selected
Type of Chiller/Model/Size Packaged Water-cooled Chiller
Quantity of Chillers 1
Capacity in Tons per Chiller 165
Compressor Type Centrifugal/Screw/Rotary/Reciprocating
Number of Compressors 2
Chiller Efficiency in kW per ton 0.716 kW per ton

Chiller Refrigerant R-134a


Condenser Type Water-cooled Shell and Tube Type
Condenser Water Flow in gallons per minute 495
Condenser Entering/Leaving Water Temp 88 F/ 98 F
Condenser Water Pressure Drop, feet (Loss)

Chiller Type (Evaporator) Shell and Tube Type


Chilled Water Flow in gallons per minute 396
Chiller Entering/Leaving Water Temperature 54 F / 44 F
Chiller Water Pressure Drop, feet (Loss)
Estimated Flow for Chilled and Cooling Water
Gallons per Minute

Chilled Water Flow = (12000 x 165) / (500 x (54-44))

Condenser Water Flow = (15000 x 165) / (500 x (98-88))


Schematic Diagram Of Packaged Chiller

COOLING
TOWER

98˚F

BASIN

ΔP condenser = 12 ft

495 GPM
CONDENSER
44 ˚F
88˚F

CONDENSER CHILLER
WATER
PUMP
ΔPchiller = 8 ft
54 ˚F

COMPRESSOR 1 COMPRESSOR 2

396 GPM

CHILLER WATER
PUMP
2. Air Handling Units

a. AHU Selection Data


b. AHU Selected Data
c. Schematic Diagram of the AHU showing the different
parameters
d. High Lighted Selected Data on the Brochure
e. Specification of the AHUs
Air Handling Units Selection Data
Air-handling Units
ITEM AHU 11 AHU 12 AHU 13

Capacity in Tons (Grand Total Heat or Total 15 15 12


Capacity – TC)
Sensible Capacity (Room Sensible Heat +
Outdoor Air Heat) SC
Entering Dry Bulb / Entering Wet Bulb in F

Leaving Dry Bulb / Leaving Wet Bulb in F

Dehumidified CFM 6100

External Static Pressure in inch water gage

Chilled Water Flow in gallons per minute 36 36 29

Entering / Leaving Chilled Water Temp. F 44 / 54 44 / 54 44 / 54


Estimated Flow for Chilled
Gallons per Minute for AHU

Chilled Water Flow = (12000 x 15) / (500 x (54-44)) For AHU 11

Chilled Water Flow = (12000 x 15) / (500 x (54-44)) For AHU 12

Chilled Water Flow = (12000 x 12) / (500 x (54-44)) For AHU 13


Air Handling Units Selected Data
ITEM AHU 11 AHU 12 AHU 13
Unit Model / Size
Fan CFM (with reference to Dehumidified CFM) 6150
Type of Fan (Forward, Backward or Aerofoil curve Blades) Forward Backward Aerofoil
Selected Motor Brake Horsepower
Motor Revolution per minute
Total Static Pressure
External Static Pressure (Air Distribution Losses in inch water gage)
Internal Static Pressure (Losses in the AHU in inch water gage)
a. Dampers (Face/Bypass Damper)
b. Mixing Box
c. Flat Filter
d. Bag Type or high efficiency filters
e. Cooling Coil (Air Side)
f. Unit Casing Losses
Cooling Coil Model
Cooling Coil Capacity in BTU per hour
a. Face Area in Square Feet
b. Face Velocity in Feet per minute 500 550 600
c. Number of Rows per coil
d. Cooling Coil Entering Dry and Wet Bulb Air Temperature in F
e. Cooling Coil Leaving Dry and Wet Bulb Air Temperature in F
Cooling Coil Chilled Water Flow in gallons per minute
Cooling Coil Entering and Leaving Chilled Water Temperature in F 44 / 54 44 / 54 44 / 54
Cooling Coil Chilled Water Pressure Drop in feet
Cooling Coil Chilled Water Flow, GPM = (Tons x 12000) / (500 x Temperature Rise)
Air Handling Units Selected Data
ITEM AHU 1 AHU 2
LPC-AC 08-E-J LPC-AC 10-E-J
Unit Model / Size
Size 8 Size 10
Fan CFM (with reference to Dehumidified CFM) 3200 5500
FAN
Type of Fan (Forward, Backward or Aerofoil curve Blades) Forward Forward
Selected Motor Brake Horsepower 2 5
Motor Revolution per minute 1064.9 1086
External Static Pressure
0.4647 0.4647
(Air Distribution Losses in inch water gage)
Internal Static Pressure
1.11 1.73
(Losses in the AHU in inch water gage)
TOTAL STATIC
Dampers (Face/Bypass Damper) 0.19 0.35
PRESSURE
Mixing Box 0.10 0.15
Flat Filter 0.27 0.39
Cooling Coil (Air Side) 0.55 0.84
Total Static Pressure 1.5747 2.1947
Cooling Coil Model Size 8 Size 10
Cooling Coil Capacity in BTU per hour 91000 186320
Face Area in Square Feet 5.98 11.05
Air Face Velocity in Feet per minute 430 565
Side Number of Rows per coil 4 4
Cooling Cooling Coil Entering Dry and Wet Bulb Air Temperature in F 80/67 80/67
Coil
Cooling Coil Leaving Dry and Wet Bulb Air Temperature in F 58.4/ 58.1 54.78/ 54.43
Cooling Coil Chilled Water Flow in gallons per minute 36 48
Water
Cooling Coil Entering and Leaving Chilled Water Temperature in F 44 / 54 44 / 54
Side
Cooling Coil Chilled Water Pressure Drop in feet 1.30 2.77
Dcfm = 3200 CFM

Total Static Pressure = 1.5747 in. Wg


Schematic Diagram

AHU 1 - LPC-AC 08 –E-J / SIZE 8 Fan Model/Size = LPC-AC 08 –E-J / SIZE 8


Fan BHP = 2 HP
Fan RPM = 1064.9 rpm

RETURN LDB = 58.4˚F


AIR LWB= 58.1˚F

Pressure Coil= 1.3 in. Wg (Water Side)

OUTSIDE MIXING
AIR BOX EDB = 80˚F
EWB= 67˚F

INTERNAL STATIC PRESSURE = 1.11 in. wg


44˚F 54˚F
Mixing Box = 0.10 in. Wg 36 GPM
Flat Filters = 0.27 in. Wg
Cooling Coil = 0.55 in. Wg
Dampers (Face/Bypass Damper) = 0.19 in. Wg
CHILLED WATER
PUMP
Dcfm = 5500 CFM

Total Static Pressure = 2.1947 in. Wg


Schematic Diagram

AHU 2 - LPC-AC 10 –E-J / Size 10 Fan Model/Size = LPC-AC 10 –E-J / Size 10

Fan BHP = 5 HP

Fan RPM = 1086 RPM

RETURN LDB = 56.7˚F


AIR LWB= 56.1˚F

Pressure Coil= 2.77 in. Wg. (Air Side)

OUTSIDE MIXING
AIR BOX EDB = 80˚F
EWB= 67˚F

INTERNAL STATIC PRESSURE = 1.73 in. wg 44˚F 54˚F


48 GPM
Mixing Box = 0.15 in. Wg
Flat Filters = 0.39 in. Wg ΔP coil = 8 ft
Cooling Coil = 0.84 in. Wg
Dampers (Face/Bypass Damper) = 0.35 in. Wg CHILLED WATER
PUMP