Q1.

A balanced three-phase, star-connected load of 100 kW takes a leading current of 80 A, when


connected across a 3-phase 1100-V, 50-Hz supply. Find the circuit constants of the load per phase.

Solution: Approximate time : [4 mins] 3M

Q2. A three-phase supply feeds a load consisting of three equal resistors. By how much percentage is the
load reduced if one of the resistors is removed when the load is in i) Star ii) Delta

Solution: Approximate time : [5 mins] 2M


Q3. For the circuit shown below, determine the total current and the power factor of the circuit.

Approximate time : [4 mins] 2M


Solution:

Q4. For the circuit shown below, calculate the average power absorbed by the resistor and inductor.

Approximate time : [4 mins] 2M

Solution:
Q5. An iron ring of crosssectional area 6 cm2 is wound with a wire of 100 turns and has a saw cut of 2
mm. Calculate the magnetising current required to produce a flux of 0·1 mWb if mean length of magnetic
path is 30 cm and relative permeability of iron is 470. ( assume flux density in the air gap is equal to the
flux density in the core) Approximate time : [4 mins] 2M

Solution:
Q6. Calculate the effective value of inductance for the circuit shown below

Approximate time : [2 mins] 2M

Solution: