8620 MKII Configuration Page 1 of 47

8620 MKII Configuration


Module
Module Options
Description

1
2
3
4

LED Indicators

Insert Card Text


1 Not Used Lit
2 Not Used Lit
3 Not Used Lit
4 Not Used Lit

Miscellaneous Options

Enable Fast Loading Feature No


Audible Alarm Prior to Starting No
All Warnings are Latched No
Enable Sleep Mode No
Enable Manual Fuel Pump Control No
Support Right-To-Left Languages in Module Strings No
Inhibit retransfer to mains No
Power Up in Mode Stop
Enable Cool Down in Stop Mode No
Enable Maintenance Reset on Module Front Panel No
Show Active DTC
Show Inactive DTC
Filter Generator Voltage Display
Filter Constant 30
Filter Mains Voltage Display
Filter Constant 30

Breaker Control

Enable Alternative Breaker Button Control


Enable Manual Breaker Control
Active

Configurable Status Screens


Home Page

Home Page Mode

Displayed Pages

Page 1 Summary Screen Page 6 Not Used


Page 2 Not Used Page 7 Not Used
Page 3 Not Used Page 8 Not Used
Page 4 Not Used Page 9 Not Used

about:blank 15/01/2024
8620 MKII Configuration Page 2 of 47

Page 5 Not Used Page 10 Not Used

Event Log
Display Options

Module display Date and time

Logging Options

Log the following events to the event log

Power-Up Yes Log Fuel Level Yes


Mains Fail Yes Log Fuel Level At Rest No
Mains Return Yes Engine starts Yes
ECU Shutdown alarms Yes Engine stops Yes

'Repeat SMS' requires a GSM modem to be configured on the


Communications/Basic page
Shutdown Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Electrical Trip Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Latched warnings Yes
Unlatched warnings Yes
Repeat SMS No
Repeat delay 12h
Repeats 2

Maintenance Alarms Yes


Repeat SMS No
Repeat delay 12h
Repeats 2

Data Logging
Configuration
Data Logging

Logged data Log Interval


1 -2147483384 1 minute
2 1536 1 second
3 1044 1 second
4 1032 1 second
5 1060 1 second
6 -1 1 second
7 -1 1 second
8 -1 1 second
9 -1 1 second
10 -1 1 second

about:blank 15/01/2024
8620 MKII Configuration Page 3 of 47

11 -1 1 second
12 -1 1 second
13 -1 1 second
14 -1 1 second
15 -1 1 second
16 -1 1 second
17 -1 1 second
18 -1 1 second
19 -1 1 second
20 -1 1 second

Options
Data Log Options

Only Log When Engine is Running Yes


Log to USB drive No
Keep Oldest Data No

about:blank 15/01/2024
8620 MKII Configuration Page 4 of 47

Application
ECU (ECM) Options

Engine Type Conventional Diesel


Enhanced J1939 No
Alternative Engine Speed No
Modbus Engine Comms Port RS485 Port

about:blank 15/01/2024
8620 MKII Configuration Page 5 of 47

Inputs
Analogue Input Configuration
ECU (ECM) Options

Use Module to Measure Oil Pressure


Use Module to Measure Coolant Temperature

Input Configuration

Analogue Input A Oil Sensor


Temperature
Analogue Input B
Sensor
Analogue Input C Fuel Sensor
Analogue Input D Flexible Analogue
'Flexible Analogue' selections are configured on the
'Inputs/Analogue Inputs' pages
'Digital Input' selections are configured on the 'Inputs/Digital
Inputs' pages
Oil/Temperature/Fuel selections are configured on the
'Engine' pages

Analogue Inputs
Analogue Inputs

Analogue
Inputs

Flexible Sensor A
The Analogue Input is currently configured as a Oil Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor B
The Analogue Input is currently configured as a Temperature Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor C
The Analogue Input is currently configured as a Fuel Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor D
Sensor Description

Sensor Name Flexible Sensor D

Input Type

Not used

Sensor Alarms

Alarm Arming Always

Low Alarm Enable No


Action None
Low Alarm 0

Low Pre-alarm Enable

about:blank 15/01/2024
8620 MKII Configuration Page 6 of 47

Low Pre-alarm Trip 0


Low Pre-alarm Return 0
Low Alarm String Flexible Sensor D Low

High Pre-alarm Enable


High Pre-alarm Return 0
High Pre-alarm Trip 0

High Alarm Enable No


Action None
High Alarm 0

High Alarm String Flexible Sensor D High

Digital Inputs
Digital Inputs

Digital
Inputs

Digital Inputs A - C
Digital Input A

Function Generator Closed Auxiliary


Polarity Close to Activate
Action
Arming
LCD Display Digital Input A
Activation Delay 0s

Digital Input B

Function User Configured


Polarity Close to Activate
Action Shutdown
Arming Always
LCD Display Digital Input B
Activation Delay 0s

Digital Input C

Function User Configured


Polarity Close to Activate
Action Indication
Arming Always
LCD Display Digital Input C
Activation Delay 0s

about:blank 15/01/2024
8620 MKII Configuration Page 7 of 47

Digital Inputs D - F
Digital Input D

Function Remote Start In Island Mode


Polarity Close to Activate
Action
Arming
LCD Display Digital Input D
Activation Delay 0s

Digital Input E

Function User Configured


Polarity Close to Activate
Action Electrical Trip
Arming From Safety On
LCD Display Digital Input E
Activation Delay 0s

Digital Input F

Function Paralleling Inhibit


Polarity Close to Activate
Action
Arming
LCD Display Digital Input F
Activation Delay 0s

about:blank 15/01/2024
8620 MKII Configuration Page 8 of 47

Digital Inputs G - I
Digital Input G

Function Mains Load Inhibit


Polarity Close to Activate
Action
Arming
LCD Display Digital Input G
Activation Delay 0s

Digital Input H

Function Mains Closed Auxiliary


Polarity Close to Activate
Action
Arming
LCD Display Digital Input H
Activation Delay 0s

Digital Input I

Function Volts Lower


Polarity Close to Activate
Action
Arming
LCD Display Digital Input I
Activation Delay 0s

about:blank 15/01/2024
8620 MKII Configuration Page 9 of 47

Digital Inputs J - L
Digital Input J

Function Volts Raise


Polarity Close to Activate
Action
Arming
LCD Display Digital Input J
Activation Delay 0s

Digital Input K

Function Speed Lower


Polarity Close to Activate
Action
Arming
LCD Display Digital Input K
Activation Delay 0s

Digital Input L

Function Speed Raise


Polarity Close to Activate
Action
Arming
LCD Display Digital Input L
Activation Delay 0s

Analogue Inputs A - C
Analogue Input A (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input B (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input C (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input D
Analogue Input D (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

about:blank 15/01/2024
8620 MKII Configuration Page 10 of 47

Outputs
Digital Outputs
Relay Outputs (Supplied From Emergency Stop Input)

Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise

Relay Outputs (Volts Free)

Source Polarity
Output C (N/C) Close Mains Output Energise
Output D Open Gen Output Pulse Energise

Digital Outputs (DC Supply Out)

Source Polarity
Output E Close Gen Output Energise
Output F Open Gen Output Pulse Energise
Output G Audible Alarm Energise
Output H System In Auto Mode Energise
Output I Fuel Pump Control Energise
Output J Fuel Level Low Alarm Energise
Output K Not Used Energise
Output L Not Used Energise

Virtual LEDs
LED Configuration

Source Polarity
LED 1 Not Used Lit
LED 2 Not Used Lit
LED 3 Not Used Lit
LED 4 Not Used Lit
LED 5 Not Used Lit
LED 6 Not Used Lit
LED 7 Not Used Lit
LED 8 Not Used Lit
LED 9 Not Used Lit
LED 10 Not Used Lit
LED 11 Not Used Lit
LED 12 Not Used Lit
LED 13 Not Used Lit
LED 14 Not Used Lit
LED 15 Not Used Lit
LED 16 Not Used Lit
LED 17 Not Used Lit
LED 18 Not Used Lit
LED 19 Not Used Lit
LED 20 Not Used Lit

about:blank 15/01/2024
8620 MKII Configuration Page 11 of 47

Timers
Start Timers
Start Delay

Remote Start Off Load 0s


Remote Start On Load 0s
Telemetry Start 5s
Mains Fail 0s

Start Timers

Mains Transient Delay 2.0s


Engage Attempt 2.0s
Engage Rest 1.6s
Delay Crank 0.5s
Cranking 10s
Cranking Rest 10s
Smoke Limiting 0s
Smoke Limiting Off 0s
DPF Ramp 5.0s
Safety On Delay 10s
Warming 0s
Sensor Fail Delay 2.0s

Load/Stopping Timers
Load Timers

Transfer Time / Load Delay 0.7s


Breaker Close Pulse 0.5s
Breaker Trip Pulse 0.5s
Parallel Run Time 0s

Stopping Timers

Return Delay 0s
Cooling 1m
Cooling at Idle 0s
ETS Solenoid Hold 0s
Fail to Stop Delay 30s
Generator Transient Delay 0.0s

Module Timers
Interface Timers

Page 5m
Scroll 2s
Sleep Timer 5m

about:blank 15/01/2024
8620 MKII Configuration Page 12 of 47

Generator
Generator Options
Generator Options

Alternator Fitted Yes


Poles 4
AC System 3 Phase, 4 Wire
VT fitted No
Primary 111 V PhPh Secondary 110 V PhPh

Generator Phase Rotation

Enable Yes
Phase Rotation L1-L2-L3

Breaker Control

Enable Breaker Alarms Yes


Fail to Open Delay 1.0s
Fail to Close Delay 1.0s

Generator Voltage
Under Voltage Alarms

Alarm Yes
Action Shutdown
Trip 318V PhPh 80.0%
Pre-Alarm Yes
Trip 339V PhPh 85.2%

Loading Voltage

Loading Voltage 358V PhPh 90.0%


Enable Alarm Yes
Action Electrical Trip

Nominal Voltage

398V PhPh

Over Voltage Alarms

Pre-Alarm Yes
Return 439V PhPh 110.4%
Trip 458V PhPh 115.2%
Alarm
Trip 479V PhPh 120.4%

Generator Sequence Alarms


Zero Sequence Alarm

Enable Zero Sequence should be set to a third of the required NVD value.

about:blank 15/01/2024
8620 MKII Configuration Page 13 of 47

Action
Arming Never
Trip 39.8V PhPh 10.0% 39.8V PhPh
Delay 0.0s

Positive Sequence Alarm

Enable
Action
Arming Never
Trip 358.5V PhPh 90.0% 358.5V PhPh
Delay 0.0s

Negative Sequence Alarm

Enable
Action
Arming Never
Trip 39.8V PhPh 10.0% 39.8V PhPh
Delay 0.0s

Asymmetry Alarm

Enable
Action
Arming Never
Trip 39.8V PhPh 10.0% 39.8V PhPh
Delay 0.0s

about:blank 15/01/2024
8620 MKII Configuration Page 14 of 47

Generator Frequency
Under Frequency Alarms

Alarm Yes
Action Shutdown
Trip 40.0 Hz 80.0%
Pre-Alarm Yes
Trip 42.0 Hz 84.0%

Loading Frequency

Loading Frequency 45.0 Hz 90.0%


Enable Alarm Yes
Action Electrical Trip

Nominal Frequency

50.0 Hz 100.0 %

Over Frequency Alarms

Pre-Alarm Yes
Return 54.0 Hz 108.0%
Trip 55.0 Hz 110.0%
Alarm Yes
Trip 57.0 Hz 114.0%

Generator Current
Generator Current

Generator
Current

Generator Current Options


Generator Current Options

CT Primary (L1,L2,L3,N) 1200 A


CT Secondary 5 Amp
Full Load Rating 938 A
Earth CT Primary 500 A

about:blank 15/01/2024
8620 MKII Configuration Page 15 of 47

Generator Current Alarms


Overcurrent Alarm

Immediate Warning Yes


IDMT Alarm Yes
Trip 100 % 938 A
Time Multiplier 1
Action Electrical Trip

Negative Phase Sequence

Enable No
Action Shutdown
Trip Level 20 %
Delay 0s

Short Circuit

Enable Yes
Action Electrical Trip
Trip 110 % 1031.8 A
Time Multiplier 0.01

Earth Fault

Enable Yes
Action Shutdown
Trip Level 10 % 93.8 A
Time Multiplier 0.5

about:blank 15/01/2024
8620 MKII Configuration Page 16 of 47

Generator Power
Generator Rating
Generator Rating

kW Rating 520kW 541kVA


-kVAr Rating -150kVAr -0.96pf
kVAr Rating 150kVAr 0.96pf

Overload Protection
Overload Protection

Pre-Alarm Yes
Trip 90 % 468 kW
Return 80 % 416 kW
Delay 5s
Alarm Yes
Action Shutdown
Trip 100 % 520 kW
Delay 5s

Load Control
Dummy Load Control

Enable No
Outputs in Scheme 1

Trip 20 % 104 kW
Trip Delay 5s

Return 50 % 260 kW
Return Delay 5s

Load Shedding Control

Enable No
Outputs in Scheme 1
Outputs at Start 1
Trip 80 % 416 kW
Trip Delay 5s
Return 70 % 364 kW
Return Delay 5s
Transfer Time / Load Delay 0.7s

Reverse Power
Reverse Power Alarm

Enabled Yes
Action Electrical Trip
Trip 35 kW
Delay 2.0s

Low Load

about:blank 15/01/2024
8620 MKII Configuration Page 17 of 47

Low Load Alarm

Enabled No
Description Low Load
Trip 30 %
Delay 1m

Synchronising
Synchronising

Sync

Sync Options
Options

Enable Synchronising Yes


Persistent Governor Output
Persistent AVR Output

Governor

Interface Internal Analogue


Output Reversed No
Action Adjust To Nominal Frequency

AVR

Output Internal Analogue


Output Reversed No
Action Adjust To Nominal Voltage

Check Sync
Check Sync

Low Frequency -0.1 Hz


High Frequency 0.2 Hz
Voltage 3V PhPh
Phase Angle 5°

Fail To Sync Alarm

Action Electrical Trip


Delay 1m

Load Control
Load Options

Load Control Mode kW Control


Reactive Load Control Mode kVAr Fixed Export

Ramp

Ramp Up Rate 3.0 % %/s


Ramp Down Rate 3.0 % %/s

Insufficient Capacity

about:blank 15/01/2024
8620 MKII Configuration Page 18 of 47

Action None
Delay 1s

AVR
Loss Of Excitation

Arming Active from Parallel


Pre-Alarm No
Trip 25.0 % %
Return 20.0 % %
Alarm No
Action Shutdown
Trip 35.0 % %
Delay 1s

AVR Trim Alarm

Action None
Delay 0s

Power Control
Constant Power Mode (Default)

No additional settings are required

Frequency-Power Mode

Frequency Rolling Average 1.0s


Control Curve RfG GB LFSM_O

Voltage-Power Mode

Voltage Rolling Average 1.0s


Control Curve Power Against Voltage

Power Ramp on Setpoint Change

Ramp Rate 50.0 % %/s

Voltage and Reactive Power Control


Constant Power Factor Mode

Limit Power Factor to Generator Rating


Power Rolling Average 1.0s

Voltage-Reactive Power Mode

Limit Power Factor to Generator Rating


Power Rolling Average 1.0s
Voltage Rolling Average 1.0s
Control Curve Reactive Power Against Voltage

Power-Power Factor Mode

about:blank 15/01/2024
8620 MKII Configuration Page 19 of 47

Power Rolling Average 1.0s


Control Curve Power Factor Against Power

Constant Reactive Power Mode (Default)

Limit Power Factor to Generator Rating

Reactive Power Ramp on Setpoint Change

Ramp Rate 50.0 % %/s

Mains
Mains

Mains

Mains Options
Mains Options

Mains Failure Detection Yes


Immediate Mains Dropout No
AC System 3 Phase, 4 Wire
VT fitted No
Primary 111 V PhPh 110 V PhPh

Mains Phase Rotation

Enable Yes
Phase Rotation L1-L2-L3

Breaker Control

Enable Breaker Alarms Yes


Fail to Open Delay 1.0s
Fail to Close Delay 1.0s

Phase Offset

Phase Offset 0

Mains Voltage Alarms


Under Voltage Alarms

Enable Yes
Trip 318V PhPh
Return 358V PhPh

Nominal Voltage

398V PhPh 398V PhPh

Over Voltage Alarms

Enable Yes
Return 438V PhPh

about:blank 15/01/2024
8620 MKII Configuration Page 20 of 47

Trip 478V PhPh

Mains Sequence Alarms


Zero Sequence Alarm

Enable No Zero Sequence should be set to a third of the required NVD value.
Action
Trip 39.8V PhPh 10.0% 39.8V PhPh
Delay 0.0s

Positive Sequence Alarm

Enable No
Action
Trip 358.5V PhPh 90.0% 358.5V PhPh
Delay 0.0s

Negative Sequence Alarm

Enable No
Action
Trip 39.8V PhPh 10.0% 39.8V PhPh
Delay 0.0s

Asymmetry Alarm

Enable No
Action
Trip 39.8V PhPh 10.0% 39.8V PhPh
Delay 0.0s

Mains Frequency Alarms


Under Frequency Alarms

Enable Yes
Trip 45.0 Hz
Return 48.0 Hz

Over Frequency Alarms

Enable Yes
Return 52.0 Hz
Trip 55.0 Hz

Mains Current
Mains Current Options

CT Enabled Yes
CT Primary (L1) 1200 A
CT Secondary 5 Amp
Full Load Rating 520 kW
Full KVAr Rating 150kVAr

about:blank 15/01/2024
8620 MKII Configuration Page 21 of 47

Export Power

Enable No
Action None
Trip 0 kW
Delay 0s

about:blank 15/01/2024
8620 MKII Configuration Page 22 of 47

Mains Decoupling
Options

Alarm Action Electrical Trip

R.O.C.O.F. Alarm

Enable No
Trip 0.13 Hz/s

Vector Shift Alarm

Enable No
Trip 6.0 °

Voltage Alarms

Under Voltage No
Trip 361V PhPh
Delay 0s
Over Voltage No
Trip 438V PhPh
Delay 0s

Frequency Alarms

Under Frequency No
Trip 47.0 Hz
Delay 0s
Over Frequency No
Trip 50.5 Hz
Delay 0s

about:blank 15/01/2024
8620 MKII Configuration Page 23 of 47

Engine
Engine Protection
Water In Fuel

Action Warning
Arming Always
Activation Delay 0s

Fuel Tank Bund

Action Warning

Oil Pressure
Input Type

Not used

Sensor Open Circuit Alarm

Enable Alarm

Low Oil Pressure Alarms

Shutdown
Engine manufacture standard minimum oil pressure at 200
Trip 0 kPA.
Pre-Alarm Not configured on DSE but standard inside ECM.
Trip 0
Return 0

Coolant Temperature
Coolant Temperature

Coolant
Temperature

Coolant Temperature Alarm


Input Type

Not used

Sensor Open Circuit Alarm

Enable Alarm

Low Coolant Temperature Alarms

Pre-Alarm
Trip 0
Return 0

High Coolant Temperature Alarms

Pre-Alarm Engine manufacture standard maximum top tank temp at


103 degree C.
Return 0
Not configured on DSE but standard inside ECM.
Trip 0
Electrical Trip

about:blank 15/01/2024
8620 MKII Configuration Page 24 of 47

Trip 0

Shutdown

Trip 0

Coolant Temperature Control


Coolant Heater Control

Enable No
On 50 °C, 122 °F
Off 55 °C, 131 °F

Coolant Cooler Control

Enable No
Off 70 °C, 158 °F
On 75 °C, 167 °F

Disable when set not available No

Fan Control

Fan Overrun Delay 0s

Fuel Level
Fuel Level

Fuel Control and Monitoring


Input Type

Not used

Fuel Pump Control

Enable No
On 25 %
Off 75 %

Fuel Monitoring

Fuel Tank Size 1000


Litres
Logging Interval 8h
Dial Out On Logging No
SMS Enabled Yes
SMS interval every 1 logs
Stable Timer 0.5s
Change Indicating Filling 1%
Change Indicating Stable 1%

Fuel Alarms
Low Fuel Level Alarms

about:blank 15/01/2024
8620 MKII Configuration Page 25 of 47

Alarm
Action None
Trip 0
Delay 0s

Pre-Alarm
Trip 0
Return 0
Delay 0s

High Fuel Level Alarms

Pre-Alarm
Return 0
Trip 0
Delay 0s
Alarm
Action None
Trip 0
Delay 0s

Fuel Usage Alarm

Enable No
Mode Standard Mode
Action Warning Always Latched
Running Rate 10 % / Hr 10 % / Hr
Stopped Rate 10 % / Hr 10 % / Hr

Fuel Use and Efficiency


Engine Efficiency Curve

Engine Type Not used


Specific Gravity 0.89

Instrumentation Sources

Instantaneous Fuel Consumption Not Used


Trip Average Fuel Consumption Not Used
Trip Fuel Usage Not Used
Accumulated Fuel Usage Not Used
Instantaneous Efficiency Not Used
Trip Average Efficiency Not Used
Estimate Run Time to Empty Not Used

Run Time Until Empty

Fuel Tank Run Time 8h 0m 8h 0m


Fuel Tank Run Time Load Level Percentage 100 %

DEF Level
Level Alarms

about:blank 15/01/2024
8620 MKII Configuration Page 26 of 47

Low Alarm Enable No


Action None
Trip 10 %
Delay 0s

Low Pre-alarm Enable No


Trip 30 %
Return 40 %
Delay 0s

Engine Options
ECU (ECM) Options

Engine Type Conventional Diesel


Enhanced J1939 No
Alternative Engine Speed No
Modbus Engine Comms Port RS485 Port
Disable ECM Speed Control No

Miscellaneous Options

J1939-75 Instrumentation Enable No


J1939-75 Alarms Enable No
CAN source address (instrumentation) 44

Startup Options

Start Attempts 3

Pre-heat

Enabled Yes
On 50 °C 122 °F
On 50 °C 122 °F
Duration 0s

Post-heat

Enabled Yes
On 50 °C 122 °F
On 50 °C 50 °C
Duration 0s

ECU (ECM) Options


Engine Hours

Module to Record Engine Hours No

DPF Regeneration Control

Allow Non-Mission Regeneration No

Speed Switch

about:blank 15/01/2024
8620 MKII Configuration Page 27 of 47

Enable 0: Default Dataset ECU

ECU Wakeup

Enable No
Periodic Wakeup Time 1h
Coolant Measurement Persistence No

Engine CAN Termination

Engine CAN Termination Disable

Droop

Enable No
4.0 %

DTC Ignore List

DTC
1
2
3
4
5

DTC
6
7
8
9
10

Miscellaneous

CAN source address (engine messages) 0

about:blank 15/01/2024
8620 MKII Configuration Page 28 of 47

ECU (ECM) Alarms


ECU (ECM) Data Fail
ECU (ECM) Data Fail

Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s

DM1 Signals
ECU Amber

Action Warning
Arming Always
Activation Delay 0s

ECU Red

Action Shutdown
Arming From Safety On
Activation Delay 0s

ECU Malfunction

Action Warning
Arming Always
Activation Delay 0s

ECU Protect

Action Warning
Arming From Safety On
Activation Delay 0s

Advanced
DPTC Filter

Enabled Yes
Action Warning
Arming From Safety On

HEST Active

Enabled Yes
Action Warning
Arming From Safety On

DEF Level

Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s

SCR Inducement

about:blank 15/01/2024
8620 MKII Configuration Page 29 of 47

Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s

Message Failure
ECU CAN Message Timeouts

Enabled Timeout Multiplier


Engine Speed 3
Oil Pressure 3
Coolant Temperature 3
Other Messages 3

Gas Engine Options


Gas Engine Timers

Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s

Cranking
Options

Crank Disconnect on Oil Pressure No


Check Oil Pressure Prior to Starting Yes

Crank Disconnect

Generator Frequency 21.0 Hz


Engine Speed 600 RPM
Oil Pressure 2 Bar
Delay 0.0s
Charge Alternator No
6.0 V DC
Generator Voltage No
322V PhPh

Manual Crank

Hold Start Button To Crank No


Manual Crank Limit 30s

Speed Sensing
Options

Disable ECM Speed Sensing No


Magnetic Pickup Fitted No
Flywheel Teeth 190
Enable Multiple Engage Attempts No
Engage Attempts 2
Loss of Sensing Signal Shutdown
Disable Under Speed Alarms If Sensor Fails No

about:blank 15/01/2024
8620 MKII Configuration Page 30 of 47

Magnetic Pickup Open Circuit Shutdown

Speed Settings
Under Speed

Alarm No
Action Shutdown
Trip 1200 RPM
Pre-Alarm No
Trip 1260 RPM
Return 1350 RPM

Over Speed

Pre-Alarm No
Return 1620 RPM
Trip 1650 RPM
Alarm
Trip 1710 RPM

Overspeed Options

Overspeed Overshoot 0 %
Overshoot Delay 0s

Plant Battery
Voltage Alarms

Under Voltage Yes


Pre-Alarm 10.0 V DC
Return 10.5 V DC
Delay 1m
Over Voltage Yes
Return 29.5 V DC
Pre-Alarm 30.0 V DC
Delay 1m

Charge Alternator Alarm

Use Module for Charge Alternator No


Alarm Disabled
Trip 4.0 V DC
Delay 5s
Pre-Alarm Enabled
Trip 6.0 V DC
Delay 5s

about:blank 15/01/2024
8620 MKII Configuration Page 31 of 47

Inlet Temperature
Inlet Temperature Alarms

Alarm No
Action Shutdown
Trip 95 °C, 203 °F
Pre-Alarm No
Trip 85 °C, 185 °F
Return 80 °C, 176 °F

about:blank 15/01/2024
8620 MKII Configuration Page 32 of 47

Communications
Communications Options
Module Identification

Site Identity
Genset Identity

RS232 Port
Basic
Serial Port Configuration

Server ID 10
Baud Rate 115200
Port Usage No Modem

Modem Settings

Alarm numbers

GSM Modem No
SMS Message centre number
SMS Recipient numbers

Send extended instrumentation No


Send as flash message No

Advanced
Initialisation Strings

Init (not auto answer) E0S7=60S0=0&S0&C1&D3


Init (auto answer) E0S7=60S0=2&S0&C1&D3
Hangup H0

Connection Settings

Client inactivity timeout 5s


Connect delay 60s
Retries 4
Retry delay 5s
Repeat cycle delay 10s
Inter-frame delay 0 ms

SMS Control
SMS Module Control

Require PIN No
PIN prefix : 0 0 0 0
Enabled commands

Start off load (code 1) No


Start on load (code 2) No
Cancel (code 3) No

about:blank 15/01/2024
8620 MKII Configuration Page 33 of 47

Stop mode (code 4) No


Auto mode (code 5) No
Start in Island Mode (code 6) No

RS485 Ports
RS485 Port 1

Server ID 10
Baud Rate 115200
Client inactivity timeout 5s
Inter-frame delay 0 ms

Ethernet Port
Dynamic Host Configuration Protocol

Obtain IP Address Automatically Yes

Names

Domain Name
Host Name
Vendor Name

IP Addresses

IP address
0 . 0 . 0 . 0

Subnet Mask
255 . 255 . 255 . 0

Gateway Address
0 . 0 . 0 . 0

DNS Address
0 . 0 . 0 . 0

Preferred Connection Address


0 . 0 . 0 . 0

Modbus

Modbus Port Number 502

Notifications
Notifications

Notifications

SNMP
SNMP Settings

Enable No

about:blank 15/01/2024
8620 MKII Configuration Page 34 of 47

Device Name
Manager 1 Address
Manager 2 Address
Manager Port 161
Notification Port 162
Read Community String public
Write Community String private

SMTP
SMTP Server

Enable SMTP No
Server Address
Server Port 25
Require Authentication No
Domain
User Name
Password

Sender

Name
Email

Recipient A

Name
Email

Recipient B

Name
Email

Notifications
Notifications

SNMP Trap
Named Alarms No
Unnamed Alarms No
Mode Change No
Power Up No
Engine Starts No
Engine Stops No
Mains Fail No
Mains Return No
ECU Lamps No
Fuel Level Monitoring No
Bus Off Load No
Bus On Load No
Incorrect Password Entered No
Application Switched Multi Set No
Application Switched Single Set No

about:blank 15/01/2024
8620 MKII Configuration Page 35 of 47

Application Switched Mains No


Application Switched Group No
Generator Breaker Opened No
Generator Breaker Closed No
Mains Breaker Opened No
Mains Breaker Closed No
Group Starts No
Group Stops No

about:blank 15/01/2024
8620 MKII Configuration Page 36 of 47

Scheduler
Scheduler

Scheduler

Scheduler Options
Scheduler Options

Enable Exercise Scheduler

Bank 1
Bank 1

Schedule Period Weekly


Week Day Run Mode Start Time Duration
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00

Bank 2
Bank 2

Schedule Period Weekly


Week Day Run Mode Start Time Duration
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00

Maintenance Alarm
Maintenance Alarm 1

Enable No
Description Maintenance Alarm 1
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Maintenance Alarm 2

about:blank 15/01/2024
8620 MKII Configuration Page 37 of 47

Enable No
Description Maintenance Alarm 2
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Maintenance Alarm 3

Enable No
Description Maintenance Alarm 3
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Configurable CAN Instrumentation


Received Instrumentation (1-10)
Instrumentation Configuration

Enabled On Module
Description

1 Configurable CAN 1
2 Configurable CAN 2
3 Configurable CAN 3
4 Configurable CAN 4
5 Configurable CAN 5
6 Configurable CAN 6
7 Configurable CAN 7
8 Configurable CAN 8
9 Configurable CAN 9
10 Configurable CAN 10

Received Instrumentation (11-30)


Instrumentation Configuration

Enabled On Module
Description

11 Configurable CAN 11
12 Configurable CAN 12
13 Configurable CAN 13
14 Configurable CAN 14
15 Configurable CAN 15
16 Configurable CAN 16

about:blank 15/01/2024
8620 MKII Configuration Page 38 of 47

17 Configurable CAN 17
18 Configurable CAN 18
19 Configurable CAN 19
20 Configurable CAN 20
21 Configurable CAN 21
22 Configurable CAN 22
23 Configurable CAN 23
24 Configurable CAN 24
25 Configurable CAN 25
26 Configurable CAN 26
27 Configurable CAN 27
28 Configurable CAN 28
29 Configurable CAN 29
30 Configurable CAN 30

Transmitted Instrumentation
Instrumentation Configuration

Enabled Source

1 -1

2 -1

3 -1

4 -1

5 -1

6 -1

7 -1

8 -1

9 -1

10 -1

about:blank 15/01/2024
8620 MKII Configuration Page 39 of 47

Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options

Default Configuration Main Configuration

Advanced
Advanced

Advanced

Advanced Options
Protections

Disable No
Protections Are Disabled Never
Protections Disabled Alarm Action Indication
Coolant Level Protection Override Disabled

Out Of Sync

Action Electrical Trip


Out Of Sync Angle 16 °
Out Of Sync Timer 0.2s

Other Timers

Synchronisation Delay 3s
Mains Decoupling Supervision 1.0s
Interlock Override Off 0.1s

Test mode

Run Mode Island Mode

Ramp

Alternative ramping scheme No

Reset Electrical Trip


Reset Electrical Trip

Enable
Enable by Input
Enable by Front Panel
Number of Resets 1
Time Period 5m
Inhibit Engine Stop

PLC
PLC Logic
PLC Functions 1-4
Function 1

Function User Configured


Polarity Close to Activate

about:blank 15/01/2024
8620 MKII Configuration Page 40 of 47

Action Warning
Arming Always
LCD Display PLC Function 1
Activation Delay 0s

Function 2

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 2
Activation Delay 0s

Function 3

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 3
Activation Delay 0s

Function 4

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 4
Activation Delay 0s

PLC Functions 5-8


Function 5

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 5
Activation Delay 0s

Function 6

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 6

about:blank 15/01/2024
8620 MKII Configuration Page 41 of 47

Activation Delay 0s

Function 7

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 7
Activation Delay 0s

Function 8

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 8
Activation Delay 0s

PLC Functions 9-12


Function 9

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 9
Activation Delay 0s

Function 10

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 10
Activation Delay 0s

Function 11

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 11
Activation Delay 0s

Function 12

about:blank 15/01/2024
8620 MKII Configuration Page 42 of 47

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 12
Activation Delay 0s

PLC Functions 13-16


Function 13

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 13
Activation Delay 0s

Function 14

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 14
Activation Delay 0s

Function 15

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 15
Activation Delay 0s

Function 16

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 16
Activation Delay 0s

PLC Functions 17-20


Function 17

Function User Configured


Polarity Close to Activate

about:blank 15/01/2024
8620 MKII Configuration Page 43 of 47

Action Warning
Arming Always
LCD Display PLC Function 17
Activation Delay 0s

Function 18

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 18
Activation Delay 0s

Function 19

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 19
Activation Delay 0s

Function 20

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 20
Activation Delay 0s

Module Display
Displayed Pages

Page 1 Not Used Page 5 Not Used


Page 2 Not Used Page 6 Not Used
Page 3 Not Used Page 7 Not Used
Page 4 Not Used Page 8 Not Used

Configurable Gencomm Pages


Configurable Gencomm Pages

Configurable Gencomm
Pages

Page 166

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1

about:blank 15/01/2024
8620 MKII Configuration Page 44 of 47

4-5 -1 68-69 -1 132-133 -1 196-197 -1


6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 167

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1

about:blank 15/01/2024
8620 MKII Configuration Page 45 of 47

18-19 -1 82-83 -1 146-147 -1 210-211 -1


20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 168

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1

about:blank 15/01/2024
8620 MKII Configuration Page 46 of 47

32-33 -1 96-97 -1 160-161 -1 224-225 -1


34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 169

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1

about:blank 15/01/2024
8620 MKII Configuration Page 47 of 47

46-47 -1 110-111 -1 174-175 -1 238-239 -1


48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Configurable Editor Screens
User Editable Module Parameters

Editable Item 1 Not Used


Editable Item 2 Not Used
Editable Item 3 Not Used
Editable Item 4 Not Used
Editable Item 5 Not Used
Editable Item 6 Not Used