Feature rich J+J multi-voltage actuator with Quick guide to the J3’s
standard features :
LED status light and plug & play accessories.
Multi-voltage with auto-voltage
sensing.
New in 2008, the J3 range of mounting to ISO:5211 valves. The effect of condensation is
eliminated by an internal ther- 110 ~ 240V AC or DC .
electric actuators takes its There is no need to remove the
highly successful predecessor, mostatic anti-condensation
cover to connect the J3 elec- heater that does not require a
the J2 range, to the next level. LED Status light to indicate
trically, saving installation time. separate independent power operational status of actuator
supply.
With an all new, rugged weath-
Using the external DIN plugs
erproof and anti-corrosive Electronic over-torque protec-
and external wiring diagrams
Polyamide housing, the J3 supplied with the actuator,
Standard function for the tion against valve jams
offers more user-friendly fea- J3-H20 is power open, power
installations can be pre-wired.
tures than the J2, and intro-
close, stays put on power Thermostatic anti-condensation
duces a highly visible LED status
failure. heater
light.
This visual indicator shows New to the J3 are plug and
whether the actuator is operat- play accessories –the function Manual override for emergency
ing correctly, or has tripped out can be changed to either failsafe hand operation
either by its electronic torque or modulating by fitting the new
limiter, or has been left in plug and play conversion kits.
‘manual’ mode. The modulating kit has the new 2 Volt free end of travel confir-
digital positioner that offers mation switches
auto-calibrating and self reset-
Site operators are no longer
left with the ‘valve or actuator?’ ting functionality.
IP65 weatherproof anti-
question when an actuator
corrosive and UV protected
doesn’t respond to a signal. These conversion kits are avail- Polyamide housing
Protection against valve jams is
able as optional extras.
provided by an electronic
The J3 is quick and easy to torque limiter, which auto-
install, with IS0:5211 multi- relaxes the gearbox when acti- Local visual position indicator
The J3 is a very smart red
flange mounting and a double vated, allowing the manual
override to be selected to assist box!
square drive, allowing fast
in clearing the jam. ISO5211 multi-flange mounting
with double square drive
Constantly lit LED The LED flashes with 2 blinks The LED flashes on/ off
CE marked
If the actuator is operating If the actuator has been left in When the actuator senses an
correctly with no faults, the ‘manual’ mode, the actuator’s impending valve jam, the elec- IS0 9000 manufacturer
LED shows a constantly lit motor runs but doesn’t drive tronic torque limiter is acti-
the output shaft. After a pre-set vated and on activation,
light. time, the actuator knows that
repeatedly flashes the LED on
as the torque limiter has not Failsafe and digital
activated and that the motor is and off.
positioner plug & play kits
running, it must be in manual.
available.
J3 Model J3 -H20
Specifications: J3 -H20
Voltage range - automatically sensed by actuator 85-250V AC (1ph) or DC
Heater 4W
Consumption
Visual indication of the 220V/1ph Maximum torque, heater on/ off 0.12 A / 0.10A
actuator’s operating
220V DC Maximum torque, heater on / off 0.06A / 0.05A
status is constantly
shown by a highly 110V/ 1ph Maximum torque, heater on/ off 0.19A / 0.18A
visible LED light.
110V DC Maximum torque, heater on/ off 0.11A / 0.08A
Weight 1.5 kg
Materials of construction:
Housing Anti-corrosive Polyamide
Fasteners Stainless steel
Gears Polyamide (speed reducing) & steel
Shaft Stainless steel
Output drive Zammac
Position indicator Glass filled Polyamide
Method of operation:
On receipt of a continuous power signal within the voltage range shown above, the motor runs and, via
a flat gear system, rotates the output shaft. The motor is stopped by internal cams striking micro
switches. On receipt of a reversing continuous signal, the motor turns in the opposite direction revers-
ing the output drive.
Note:
The power signal needs to remain on at all times to activate the thermostatic anti-condensation heater.
The volt free end of travel confirmation switches must NOT be used to cut the power.
Model J3 - H20 J3
Dimensions: J3 - H20
Modulating Option