Module
Module Options
Description
1
2
3
4
LED Indicators
Miscellaneous Options
Breaker Control
Displayed Pages
Event Log
Display Options
Logging Options
Data Logging
Configuration
Data Logging
Options
Data Log Options
Enable
Inputs
Analogue Input Configuration
ECU (ECM) Options
Input Configuration
Analogue Inputs
Analogue Inputs
Analogue
Inputs
Flexible Sensor A
The Analogue Input is currently configured as a Oil Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor B
The Analogue Input is currently configured as a Temperature Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor C
The Analogue Input is currently configured as a Fuel Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor D
Sensor Description
Input Type
Not used
Sensor Alarms
Digital Inputs
Digital Inputs
Digital
Inputs
Digital Inputs A - C
Digital Input A
Digital Input B
Digital Input C
Digital Input E
Digital Input F
Digital Input H
Digital Input I
Digital Input K
Digital Input L
Analogue Inputs A - C
Analogue Input A (Digital)
Analogue Input D
Analogue Input D (Digital)
Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise
Source Polarity
Output C (N/C) Not Used De-Energise
Output D Close Gen Output Energise
Source Polarity
Output E Preheat During Preheat Timer Energise
Output F Common Alarm Energise
Output G Audible Alarm Energise
Output H System In Auto Mode Energise
Output I Fuel Pump Control Energise
Output J Fuel Level Low Alarm Energise
Output K Not Used Energise
Output L Not Used Energise
Virtual LEDs
LED Configuration
Source Polarity
LED 1 Not Used Lit
LED 2 Not Used Lit
LED 3 Not Used Lit
LED 4 Not Used Lit
LED 5 Not Used Lit
LED 6 Not Used Lit
LED 7 Not Used Lit
LED 8 Not Used Lit
LED 9 Not Used Lit
LED 10 Not Used Lit
LED 11 Not Used Lit
LED 12 Not Used Lit
LED 13 Not Used Lit
LED 14 Not Used Lit
LED 15 Not Used Lit
LED 16 Not Used Lit
LED 17 Not Used Lit
LED 18 Not Used Lit
LED 19 Not Used Lit
LED 20 Not Used Lit
Timers
Start Timers
Start Delay
Start Timers
Load/Stopping Timers
Load Timers
Stopping Timers
Module Timers
Interface Timers
Page 5m
Scroll 2s
Sleep Timer 5m
Generator
Generator Options
Generator Options
Enable Yes
Phase Rotation L1-L2-L3
Breaker Control
Generator Rating
Generator Rating
Generator De-Rate
Generator De-Rate
Generator Voltage
Under Voltage Alarms
Alarm Yes
Action Shutdown
Trip 184V PhN 80.0%
Pre-Alarm Yes
Trip 196V PhN 85.2%
Loading Voltage
Nominal Voltage
230V PhN
Alarm Yes
Action Shutdown
Trip 40.0 Hz 80.0%
Pre-Alarm Yes
Trip 42.0 Hz 84.0%
Loading Frequency
Nominal Frequency
50.0 Hz 100.0 %
Pre-Alarm Yes
Return 54.0 Hz 108.0%
Trip 55.0 Hz 110.0%
Alarm Yes
Trip 57.0 Hz 114.0%
Generator Current
Generator Current
Generator
Current
Enable No
Action Shutdown
Trip Level 20 %
Delay 0s
Short Circuit
Enabled Yes
Action Electrical Trip
Trip 200 % 1000.0 A
Time Multiplier 0.01
Earth Fault
Enable Yes
Action Shutdown
Trip Level 10 % 50.0 A
Time Multiplier 0.5
Generator Power
Overload Protection
Overload Protection
Pre-Alarm Yes
Trip 90 % 252 kW
Return 80 % 224 kW
Delay 5s
Alarm Yes
Action Shutdown
Trip 100 % 280 kW
Delay 5s
Load Control
Dummy Load Control
Enable No
Outputs in Scheme 1
Trip 20 % 56 kW
Trip Delay 5s
Return 50 % 140 kW
Return Delay 5s
Enable No
Outputs in Scheme 1
Outputs at Start 1
Trip 80 % 224 kW
Trip Delay 5s
Return 70 % 196 kW
Return Delay 5s
Transfer Time / Load Delay 0.7s
Reverse Power
Reverse Power Alarm
Enabled Yes
Action Electrical Trip
Trip 35 kW
Delay 2.0s
Low Load
Low Load Alarm
Enabled No
Description Low Load
Trip 30 %
Delay 1m
Mains Decoupling
Loss Of Mains
R.O.C.O.F. Alarm
Enable No
Trip 0.13 Hz/s
Enable No
Trip 6.0 °
Voltage
Limits
Stage 2 Enable No
Trip 50V PhN 21.7% 50V PhN Delay 0.0s s
Stage 1 Enable No
Trip 184V PhN 80.0% 184V PhN Delay 2.5s s
Nominal Voltage
Stage 1 Enable No
Trip 262V PhN 113.9% 262V PhN Delay 1.0s s
Stage 2 Enable No
Trip 274V PhN 119.1% 274V PhN Delay 0.5s s
Frequency
Limits
Stage 2 Enable No
Trip 47.0 Hz 94.0% Delay 0.5s s
Stage 1 Enable No
Trip 47.5 Hz 95.0% Delay 20.0s s
Nominal Frequency
50.0 Hz 100.0%
Stage 1 Enable No
Trip 52.0 Hz 104.0% Delay 0.5s s
Stage 2 Enable No
Trip 52.5 Hz 105.0% Delay 0.0s s
Synchronising
Synchronising
Sync
Sync Options
Options
Governor
AVR
Check Sync
Dead Bus
Check Sync
MSC Link
MSC Link
MSC Failure Action Warning
MSC Alarms Disabled Action None
Too few modules action None
Minimum modules on MSC link 1
Enable Redundant MSC Link
Disable Auto ID Allocation
MSC ID 1
Load Control
Load Options
P123
Action None
Delay 1s
AVR
Loss Of Excitation
Action None
Delay 0s
Power Control
Constant Power Mode (Default)
Frequency-Power Mode
Voltage-Power Mode
Bus
Bus Settings
Enable Yes
Phase Rotation L1-L2-L3
Tclear 0.14 s
Trec1 0.14 s
Trec2 0.45 s
Trec3 1.50 s
Trec4 1.50 s
Engine
Engine Protection
Water In Fuel
Action Warning
Arming Always
Activation Delay 0s
Action Warning
Oil Pressure
Input Type
VDO 10 Bar
Enable Alarm
Shutdown
Trip 1.03 Bar 103 kPa, 14.94 PSI
Pre-Alarm
Trip 1.24 Bar 124 kPa, 17.98 PSI
Return 1.38 Bar 138 kPa, 20.02 PSI
Coolant Temperature
Coolant Temperature
Coolant
Temperature
VDO 120 °C
Enable Alarm
Pre-Alarm
Trip 70 °C 158 °F
Return 75 °C 167 °F
Pre-Alarm
Return 88 °C 190 °F
Trip 90 °C 194 °F
Electrical Trip
Trip 92 °C 198 °F
Shutdown
Trip 95 °C 203 °F
Enable No
On 50 °C, 122 °F
Off 55 °C, 131 °F
Enable No
Off 70 °C, 158 °F
On 75 °C, 167 °F
Fan Control
Fuel Level
Fuel Level
Not used
Enable No
On 25 %
Off 75 %
Fuel Monitoring
Fuel Alarms
Low Fuel Level Alarms
Alarm
Action None
Trip 0
Delay 0s
Pre-Alarm
Trip 0
Return 0
Delay 0s
Pre-Alarm
Return 0
Trip 0
Delay 0s
Alarm
Action None
Trip 0
Delay 0s
Enable No
Mode Standard Mode
Action Warning Always Latched
Running Rate 10 % / Hr 10 % / Hr
Stopped Rate 10 % / Hr 10 % / Hr
Instrumentation Sources
DEF Level
Level Alarms
Engine Options
ECU (ECM) Options
Miscellaneous Options
Startup Options
Start Attempts 3
Pre-heat
Enabled Yes
On 50 °C 122 °F
On 50 °C 122 °F
Duration 0s
Post-heat
Enabled Yes
On 50 °C 122 °F
On 50 °C 50 °C
Duration 0s
Speed Switch
Enable 0: Default Dataset ECU
ECU Wakeup
Enable No
Periodic Wakeup Time 1h
Coolant Measurement Persistence No
Droop
Enable No
4.0 %
DTC
1
2
3
4
5
DTC
6
7
8
9
10
Miscellaneous
Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s
DM1 Signals
ECU Amber
Action Warning
Arming Always
Activation Delay 0s
ECU Red
Action Shutdown
Arming From Safety On
Activation Delay 0s
ECU Malfunction
Action Warning
Arming Always
Activation Delay 0s
ECU Protect
Action Warning
Arming From Safety On
Activation Delay 0s
Advanced
DPTC Filter
Enabled Yes
Action Warning
Arming From Safety On
HEST Active
Enabled Yes
Action Warning
Arming From Safety On
DEF Level
Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s
SCR Inducement
Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s
Message Failure
ECU CAN Message Timeouts
Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s
Cranking
Options
Crank Disconnect
Manual Crank
Idle Setting
Options
Idle Running 0s
Idle Running Off 0s
Fast Loading From Idle No
Speed Sensing
Options
Speed Settings
Under Speed
Alarm No
Action Shutdown
Trip 1200 RPM
Pre-Alarm No
Trip 1260 RPM
Return 1350 RPM
Over Speed
Pre-Alarm No
Return 1620 RPM
Trip 1650 RPM
Alarm
Trip 1710 RPM
Overspeed Options
Overspeed Overshoot 0 %
Overshoot Delay 0s
Plant Battery
Voltage Alarms
Alarm No
Action Shutdown
Trip 95 °C, 203 °F
Pre-Alarm No
Trip 85 °C, 185 °F
Return 80 °C, 176 °F
Enabled False
Instrumentation DEF Tank Level (numeric)
Icon 1
Position X 92
Position Y 18
DTC DTC DTC
952079
Icon 2
Position X 87
Position Y 40
Instrumentation ECU (ECM) Warning
On Slow Flash Fast Flash
When Active
Icon 3
Position X 30
Position Y 38
Page=5, Register=196,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Between 3 to 6
Icon 4
Position X 6
Position Y 38
Page=5, Register=185,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1
Icon 5
Position X 58
Position Y 17
Page=5, Register=122,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 6
Position X 32
Position Y 18
Page=5, Register=193,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 7
Position X 4
Position Y 18
Page=5, Register=123,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 2
Icon 8
Position X 87
Position Y 40
Instrumentation ECU (ECM) Shutdown
On Slow Flash Fast Flash
When Active
Icon 9
Position X 92
Position Y 18
DTC DTC DTC
952064
DPF Regeneration
Enabled False
Instrumentation <Not Used>
Icon 1
Position X 96
Position Y 41
Instrumentation ECU (ECM) Warning
Position X 17
Position Y 39
Page=5, Register=185,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1
Icon 3
Position X 64
Position Y 20
Page=5, Register=122,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 4
Position X 19
Position Y 19
Page=5, Register=123,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 2
Icon 5
Position X 100
Position Y 20
DTC DTC DTC
952079
Icon 6
Position X 100
Position Y 20
DTC DTC DTC
952064
Icon 7
Position X 96
Position Y 41
Instrumentation ECU (ECM) Shutdown
On Slow Flash Fast Flash
When Active
SCR-DEF Lamps
Enabled False
Instrumentation <Not Used>
Icon 1
Position X 4
Position Y 22
Page=5, Register=193,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 2
Position X 86
Position Y 23
Page=5, Register=196,
Instrumentation
Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Between 3 to 6
Communications
Communications Options
Module Identification
Site Identity
Genset Identity
RS232 Port
Basic
Serial Port Configuration
Server ID 10
Baud Rate 115200
Port Usage Modbus Server
Modem Settings
Alarm numbers
GSM Modem No
SMS Message centre number
SMS Recipient numbers
Advanced
Initialisation Strings
Connection Settings
SMS Control
SMS Module Control
Require PIN No
PIN prefix : 0 0 0 0
Enabled commands
RS485 Ports
RS485 Port 1
Server ID 10
Baud Rate 115200
Port Usage Modbus Server
Client inactivity timeout 5s
Inter-frame delay 0 ms
Ethernet Port
Dynamic Host Configuration Protocol
Names
Domain Name
Host Name
Vendor Name
IP Addresses
IP address
0 . 0 . 0 . 0
Subnet Mask
255 . 255 . 255 . 0
Gateway Address
0 . 0 . 0 . 0
DNS Address
0 . 0 . 0 . 0
Modbus
Remote Display
Display Enable
Enable
Link Lost Alarm Action Shutdown
Connection Port
Port Ethernet
Notifications
Notifications
Notifications
SNMP
SNMP Settings
Enable No
Device Name
Manager 1 Address
Manager 2 Address
Manager Port 161
Notification Port 162
Read Community String public
Write Community String private
SMTP
SMTP Server
Enable SMTP No
Server Address
Server Port 25
Require Authentication No
Domain
User Name
Password
Sender
Name
Email
Recipient A
Name
Email
Recipient B
Name
Email
Notifications
Notifications
SNMP Trap
Named Alarms No
Unnamed Alarms No
Mode Change No
Power Up No
Engine Starts No
Engine Stops No
Mains Fail No
Mains Return No
ECU Lamps No
Fuel Level Monitoring No
Bus Off Load No
Bus On Load No
Incorrect Password Entered No
Application Switched Multi Set No
Application Switched Single Set No
Application Switched Mains No
Application Switched Group No
Generator Breaker Opened No
Generator Breaker Closed No
Mains Breaker Opened No
Mains Breaker Closed No
Group Starts No
Group Stops No
Scheduler
Scheduler
Scheduler
Scheduler Options
Scheduler Options
Bank 1
Bank 1
Bank 2
Bank 2
Maintenance Alarm
Maintenance Alarm 1
Enable No
Description Maintenance Alarm 1
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 2
Enable No
Description Maintenance Alarm 2
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 3
Enable No
Description Maintenance Alarm 3
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Enabled On Module
Description
1 Configurable CAN 1
2 Configurable CAN 2
3 Configurable CAN 3
4 Configurable CAN 4
5 Configurable CAN 5
6 Configurable CAN 6
7 Configurable CAN 7
8 Configurable CAN 8
9 Configurable CAN 9
10 Configurable CAN 10
Enabled On Module
Description
11 Configurable CAN 11
12 Configurable CAN 12
13 Configurable CAN 13
14 Configurable CAN 14
15 Configurable CAN 15
16 Configurable CAN 16
17 Configurable CAN 17
18 Configurable CAN 18
19 Configurable CAN 19
20 Configurable CAN 20
21 Configurable CAN 21
22 Configurable CAN 22
23 Configurable CAN 23
24 Configurable CAN 24
25 Configurable CAN 25
26 Configurable CAN 26
27 Configurable CAN 27
28 Configurable CAN 28
29 Configurable CAN 29
30 Configurable CAN 30
Transmitted Instrumentation
Instrumentation Configuration
Enabled Source
1 -1
2 -1
3 -1
4 -1
5 -1
6 -1
7 -1
8 -1
9 -1
10 -1
Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options
Advanced
Advanced
Advanced
Advanced Options
Protections
Disable No
Protections Are Disabled Never
Protections Disabled Alarm Action Indication
Coolant Level Protection Override Disabled
Out Of Sync
Other Timers
Synchronisation Delay 3s
Mains Decoupling Supervision 1.0s
Enable No
Sync mode Disabled
Excitation speed 1200 RPM
Start Delay 5s
Excitation delay 5.0s
Excitation ramp time 1.5s
Delay phase rotation 5.0s
AVR
AVR Options
Action None
Arming From Safety On
Activation Delay 0s
AVR Fault
Action None
Arming From Safety On
Activation Delay 0s
AVR
Enable
Enable by Input
Enable by Front Panel
Number of Resets 1
Time Period 5m
Inhibit Engine Stop
Configurable Gencomm
Pages
Page 166