EST-OLYMPIAN 2010B v1.0


ECM Replacement

02/03/2012 16:45

X - Configuration
X Engine Start Fault Protection Activation Delay Time 30 Sec
X Crank Duration 300 Sec
X Crank Cycle Rest Interval 1 Sec
X Purge Cycle Duration 70 Sec
X Maximum Number of Crank Cycles 0
X Cooldown Duration 3 min
X Start Aid Activation Time 0 Sec
X Crank Alert Activation Time 0 Sec
X Crank Terminate RPM 0 RPM
Engine Fuel Type Configuration Unavailable
X Fuel Shutoff Solenoid Type Configuration Diesel
X Engine Type Configuration Energized to Run
Engine Controller J1939 Data Link Support Configuration Unavailable
X Engine Cooldown Speed Configuration No J1939 Support
X Engine Operating State Input Configuration Rated Speed
X Fuel Priming Feature Enable Status Hardwired Input
X Engine Forced Idle Feature Enable Status Enabled
X Maximum Generator Voltage Output Bias Percentage 33 %
X Generator Nominal Output Voltage 500 Volts
X High Battery Voltage Warning Event Threshold 0,4 Volts
High Battery Voltage Warning Event Notification Delay
X 1500 Sec
Time
X High Battery Voltage Shutdown Event Threshold 0,3 Volts
High Battery Voltage Shutdown Event Notification Delay
X 30 Sec
Time
X Low Battery Voltage Warning Event Threshold 11,3 Volts
Low Battery Voltage Warning Event Notification Delay
X 30 Sec
Time
Low Battery Charging System Voltage Warning Event
X 12,5 Volts
Threshold
Low Battery Charging System Voltage Warning Event

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 2 of 65

X Notification Delay Time 30 Sec


X Low Cranking Voltage Warning Event Threshold 0,0 Volts
Low Cranking Voltage Warning Event Notification Delay
X 2 Sec
Time
Customer Password Security Level to Reset Crank/Start
X 3-Factory, Single Use
Counters
X SCADA Data Link Baud Rate 9600 baud
X SCADA Data Link Parity None
X SCADA Data Link Slave Address 1
X SCADA Data Link Access Password 00000000
X SCADA Data Link Connection Timeout Interval 30,0 Sec
X RS-485 Bias Resistor Enable Status Disabled
X Digital Input #1 Active State Configuration Low
X Digital Input #2 Active State Configuration Low
X Digital Input #3 Active State Configuration Low
X Digital Input #4 Active State Configuration Low
X Digital Input #5 Active State Configuration Low
X Digital Input #6 Active State Configuration Low
X Digital Input #7 Active State Configuration Low
X Digital Input #8 Active State Configuration Low
X Digital Output #1 Active State Configuration Low
X Digital Selector #1 Source Configuration Input #2
X Digital Selector #2 Source Configuration Disabled
X Digital Selector #3 Source Configuration Disabled
X Digital Selector #4 Source Configuration Disabled
X Digital Selector #5 Source Configuration Input #5
X Digital Selector #6 Source Configuration Input #5
X Digital Selector #7 Source Configuration Input #1
X Digital Selector #8 Source Configuration Disabled or Not Installed
X Digital Selector #9 Source Configuration Disabled or Not Installed
X Digital Selector #10 Source Configuration Disabled or Not Installed
X Engine Coolant Temperature Sensor Configuration Sensor
High Engine Coolant Temperature Warning Event
X 95 Deg C
Threshold
High Engine Coolant Temperature Warning Event
X 15 Sec
Notification Delay Time
High Engine Coolant Temperature Shutdown Event
X 107 Deg C
Threshold
X High Engine Coolant Temperature Shutdown Event 5 Sec

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 3 of 65

Notification Delay Time


Low Engine Coolant Temperature Warning Event
X 1 Deg C
Threshold
Low Engine Coolant Temperature Warning Event
X 10 Sec
Notification Delay Time
X Engine Coolant Temperature Sensor Configuration Code Map #1
X Engine Oil Pressure Sensor Configuration Sensor
X Low Engine Oil Pressure Warning Event Threshold 200 kPa
Low Idle Low Engine Oil Pressure Warning Event
X 160 kPa
Threshold
Low Engine Oil Pressure Warning Event Notification Delay
X 10 Sec
Time
X Low Engine Oil Pressure Shutdown Event Threshold 100 kPa
Low Idle Low Engine Oil Pressure Shutdown Event
X 100 kPa
Threshold
Low Engine Oil Pressure Shutdown Event Notification
X 10 Sec
Delay Time
X Low Engine Oil Pressure Step Speed 1350 RPM
X Engine Oil Pressure Sensor Configuration Code Map #1
X Flywheel Teeth 126
X Engine Overspeed Setpoint 1700 RPM
X Engine Underspeed Warning Event Threshold 1350 RPM
X Engine Underspeed Warning Event Notification Delay Time 2,0 Sec
X Engine Underspeed Shutdown Event Threshold 1250 RPM
Engine Underspeed Shutdown Event Notification Delay
X 2,0 Sec
Time
X Engine Speed Sensor Configuration Sensor
X Event Input Function #1 Suspect Parameter Number Engine Coolant Temperature
X Event Input Function #1 Failure Mode Identifier High Shutdown
X Event Input Function #1 Event Notification Delay Time 0 Sec
X Event Input Function #1 Active State Configuration High
X Event Input Function #2 Suspect Parameter Number Engine Oil Pressure
X Event Input Function #2 Failure Mode Identifier Low Shutdown
X Event Input Function #2 Event Notification Delay Time 0 Sec
X Event Input Function #2 Active State Configuration High
X Event Input Function #3 Suspect Parameter Number Custom Event
X Event Input Function #3 Failure Mode Identifier High Warning
X Event Input Function #3 Event Notification Delay Time 0 Sec
X Event Input Function #3 Active State Configuration High
X Event Input Function #4 Suspect Parameter Number Custom Event

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 4 of 65

X Event Input Function #4 Failure Mode Identifier High Warning


X Event Input Function #4 Event Notification Delay Time 0 Sec
X Event Input Function #4 Active State Configuration High
X Event Input Function #5 Suspect Parameter Number Air Filter Differential Pressure
X Event Input Function #5 Failure Mode Identifier High Warning
X Event Input Function #5 Event Notification Delay Time 0 Sec
X Event Input Function #5 Active State Configuration High
X Event Input Function #6 Suspect Parameter Number Air Filter Differential Pressure
X Event Input Function #6 Failure Mode Identifier High Warning
X Event Input Function #6 Event Notification Delay Time 0 Sec
X Event Input Function #6 Active State Configuration High
X Event Input Function #7 Suspect Parameter Number Disabled or Not Installed
X Event Input Function #7 Failure Mode Identifier Disabled or Not Installed
X Event Input Function #7 Event Notification Delay Time Disabled or Not Installed
X Event Input Function #7 Active State Configuration Disabled or Not Installed
X Event Input Function #8 Suspect Parameter Number Disabled or Not Installed
X Event Input Function #8 Failure Mode Identifier Disabled or Not Installed
X Event Input Function #8 Event Notification Delay Time Disabled or Not Installed
X Event Input Function #8 Active State Configuration Disabled or Not Installed
X Event Output Function #1 Suspect Parameter Number Engine Oil Pressure
X Event Output Function #1 Trigger Condition **Disabled
X Event Output Function #2 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #2 Trigger Condition Disabled or Not Installed
X Event Output Function #3 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #3 Trigger Condition Disabled or Not Installed
X Event Output Function #4 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #4 Trigger Condition Disabled or Not Installed
X Event Output Function #5 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #5 Trigger Condition Disabled or Not Installed
X Event Output Function #6 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #6 Trigger Condition Disabled or Not Installed
X Event Output Function #7 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #7 Trigger Condition Disabled or Not Installed
X Event Output Function #8 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #8 Trigger Condition Disabled or Not Installed
X Accessory Data Link Diagnostic Response Configuration Activate Warning Condition
X Accessory Data Link Diagnostic Audible Alert Yes
X Accessory Data Link Diagnostic Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 5 of 65

X Accessory Data Link Diagnostic Breaker #2 Trip No


Air Filter Differential Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
Air Filter Differential Pressure Sensor Diagnostic Audible
X No
Alert
Air Filter Differential Pressure Sensor Diagnostic Breaker
X No
#1 Trip
Air Filter Differential Pressure Sensor Diagnostic Breaker
X No
#2 Trip
Ambient Air Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Ambient Air Temperature Sensor Diagnostic Audible Alert No
Ambient Air Temperature Sensor Diagnostic Breaker #1
X No
Trip
Ambient Air Temperature Sensor Diagnostic Breaker #2
X No
Trip
X Digital Output #1 Diagnostic Response Configuration Activate Warning Condition
X Digital Output #1 Diagnostic Audible Alert No
X Digital Output #1 Diagnostic Breaker #1 Trip No
X Digital Output #1 Diagnostic Breaker #2 Trip No
Engine Coolant Level Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Engine Coolant Level Sensor Diagnostic Audible Alert No
X Engine Coolant Level Sensor Diagnostic Breaker #1 Trip No
X Engine Coolant Level Sensor Diagnostic Breaker #2 Trip No
Engine Coolant Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
Engine Coolant Temperature Sensor Diagnostic Audible
X No
Alert
Engine Coolant Temperature Sensor Diagnostic Breaker
X No
#1 Trip
Engine Coolant Temperature Sensor Diagnostic Breaker
X No
#2 Trip
X Engine Oil Level Sensor Diagnostic Response Configuration Activate Warning Condition
X Engine Oil Level Sensor Diagnostic Audible Alert No
X Engine Oil Level Sensor Diagnostic Breaker #1 Trip No
X Engine Oil Level Sensor Diagnostic Breaker #2 Trip No
Engine Oil Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Engine Oil Pressure Sensor Diagnostic Audible Alert No
X Engine Oil Pressure Sensor Diagnostic Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 6 of 65

X Engine Oil Pressure Sensor Diagnostic Breaker #2 Trip No


Engine Oil Temperature Sensor Diagnostic Response
X Disable Condition
Configuration
X Engine Oil Temperature Sensor Diagnostic Audible Alert No
X Engine Oil Temperature Sensor Diagnostic Breaker #1 Trip No
X Engine Oil Temperature Sensor Diagnostic Breaker #2 Trip No
Activate Hard Shutdown
X Engine Speed Sensor Diagnostic Response Configuration
Condition
X Engine Speed Sensor Diagnostic Audible Alert Yes
X Engine Speed Sensor Diagnostic Breaker #1 Trip No
X Engine Speed Sensor Diagnostic Breaker #2 Trip No
Exhaust Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Exhaust Temperature Sensor Diagnostic Audible Alert No
X Exhaust Temperature Sensor Diagnostic Breaker #1 Trip No
X Exhaust Temperature Sensor Diagnostic Breaker #2 Trip No
Right Exhaust Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
Right Exhaust Temperature Sensor Diagnostic Audible
X No
Alert
Right Exhaust Temperature Sensor Diagnostic Breaker #1
X No
Trip
Right Exhaust Temperature Sensor Diagnostic Breaker #2
X No
Trip
Left Exhaust Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Left Exhaust Temperature Sensor Diagnostic Audible Alert No
Left Exhaust Temperature Sensor Diagnostic Breaker #1
X No
Trip
Left Exhaust Temperature Sensor Diagnostic Breaker #2
X No
Trip
Fire Extinguisher Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Fire Extinguisher Pressure Sensor Audible Alert No
X Fire Extinguisher Pressure Sensor Breaker #1 Trip No
X Fire Extinguisher Pressure Sensor Breaker #2 Trip No
Fuel Filter Differential Pressure Sensor Diagnostic
X Activate Warning Condition
Response Configuration
Fuel Filter Differential Pressure Sensor Diagnostic Audible
X No
Alert

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 7 of 65

Fuel Filter Differential Pressure Sensor Diagnostic Breaker


X No
#1 Trip
Fuel Filter Differential Pressure Sensor Diagnostic Breaker
X No
#2 Trip
X Fuel Level Sensor Diagnostic Response Configuration Activate Warning Condition
X Fuel Level Sensor Diagnostic Audible Alert No
X Fuel Level Sensor Diagnostic Breaker #1 Trip No
X Fuel Level Sensor Diagnostic Breaker #2 Trip No
External Tank Fuel Level Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X External Tank Fuel Level Sensor Diagnostic Audible Alert No
External Tank Fuel Level Sensor Diagnostic Breaker #1
X No
Trip
External Tank Fuel Level Sensor Diagnostic Breaker #2
X No
Trip
Generator Bearing #1 Temperature Sensor Diagnostic
X Activate Warning Condition
Response Configuration
Generator Bearing #1 Temperature Sensor Diagnostic
X No
Audible Alert
Generator Bearing #1 Temperature Sensor Diagnostic
X No
Breaker #1 Trip
Generator Bearing #1 Temperature Sensor Diagnostic
X No
Breaker #2 Trip
Generator Output Sensing System Diagnostic Response
X Activate Warning Condition
Configuration
X Generator Output Sensing System Diagnostic Audible Alert Yes
Generator Output Sensing System Diagnostic Breaker #1
X No
Trip
Generator Output Sensing System Diagnostic Breaker #2
X No
Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
X Activate Warning Condition
Response Config
Engine Oil Filter Differential Pressure Sensor Diagnostic
X No
Audible Alert
Engine Oil Filter Differential Pressure Sensor Diagnostic
X No
Breaker #1 Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
X No
Breaker #2 Trip
X Primary Data Link Diagnostic Response Configuration Activate Warning Condition
X Primary Data Link Diagnostic Audible Alert No
X Primary Data Link Diagnostic Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 8 of 65

X Primary Data Link Diagnostic Breaker #2 Trip No


X SCADA Data Link Diagnostic Response Configuration Activate Warning Condition
X SCADA Data Link Diagnostic Audible Alert No
X SCADA Data Link Diagnostic Breaker #1 Trip No
X SCADA Data Link Diagnostic Breaker #2 Trip No
X SCADA Data Link Diagnostic Fault Protection Timer No
Starting Air Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Starting Air Pressure Sensor Diagnostic Audible Alert No
X Starting Air Pressure Sensor Diagnostic Breaker #1 Trip No
X Starting Air Pressure Sensor Diagnostic Breaker #2 Trip No
X Battery Charger Failure Diagnostic Response Configuration Activate Warning Condition
X Battery Charger Failure Diagnostic Audible Alert Yes
Engine Controller Not Responding Diagnostic Response
X Activate Warning Condition
Configuration
X Engine Controller Not Responding Diagnostic Audible Alert No
Engine Controller Not Responding Diagnostic Breaker #1
X No
Trip
Engine Controller Not Responding Diagnostic Breaker #2
X No
Trip
Hard Shutdown & Active Only
X Air Damper Closed Event Response Configuration
Condition
X Air Damper Closed Event Audible Alert Yes
High Air Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Configuration
High Air Filter Differential Pressure Warning Event Audible
X Yes
Alert
High Air Filter Differential Pressure Warning Event Breaker
X No
#1 Trip
High Air Filter Differential Pressure Warning Event Breaker
X No
#2 Trip
High Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Air Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
High Air Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
High Air Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Air Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 9 of 65

Low Air Filter Differential Pressure Warning Event Audible


X Yes
Alert
Low Air Filter Differential Pressure Warning Event Breaker
X No
#1 Trip
Low Air Filter Differential Pressure Warning Event Breaker
X No
#2 Trip
Low Air Filter Differential Pressure Warning Event Fault
X Yes
Protection Timer
Low Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Low Air Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
Low Air Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
Low Air Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Air Filter Differential Pressure Shutdown Event Fault
X Yes
Protection Timer
Activate Hard Shutdown
X Emergency Stop Activated Event Response Configuration
Condition
X Emergency Stop Activated Event Audible Alert Yes
X Emergency Stop Activated Event Breaker #1 Trip No
X Emergency Stop Activated Event Breaker #2 Trip No
High Engine Coolant Level Warning Event Response
X Activate Warning Condition
Configuration
X High Engine Coolant Level Warning Event Audible Alert Yes
X High Engine Coolant Level Warning Event Breaker #1 Trip No
X High Engine Coolant Level Warning Event Breaker #2 Trip No
High Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Engine Coolant Level Shutdown Event Audible Alert Yes
High Engine Coolant Level Shutdown Event Breaker #1
X No
Trip
High Engine Coolant Level Shutdown Event Breaker #2
X No
Trip
Low Engine Coolant Level Warning Event Response
X Activate Warning Condition
Configuration
X Low Engine Coolant Level Warning Event Audible Alert Yes
X Low Engine Coolant Level Warning Event Breaker #1 Trip No
X Low Engine Coolant Level Warning Event Breaker #2 Trip No

Low Engine Coolant Level Shutdown Event Response Activate Hard Shutdown

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 10 of 65

X Configuration Condition
X Low Engine Coolant Level Shutdown Event Audible Alert Yes
Low Engine Coolant Level Shutdown Event Breaker #1
X No
Trip
Low Engine Coolant Level Shutdown Event Breaker #2
X No
Trip
High Engine Coolant Temperature Warning Event
X Activate Warning Condition
Response Configuration
High Engine Coolant Temperature Warning Event Audible
X Yes
Alert
High Engine Coolant Temperature Warning Event Breaker
X No
#1 Trip
High Engine Coolant Temperature Warning Event Breaker
X No
#2 Trip
High Engine Coolant Temperature Warning Event Fault
X Yes
Protection Timer
High Engine Coolant Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Engine Coolant Temperature Shutdown Event Audible
X Yes
Alert
High Engine Coolant Temperature Shutdown Event
X No
Breaker #1 Trip
High Engine Coolant Temperature Shutdown Event
X No
Breaker #2 Trip
High Engine Coolant Temperature Shutdown Event Fault
X Yes
Protection Timer
Low Engine Coolant Temperature Warning Event Response
X Disable Condition
Configuration
Low Engine Coolant Temperature Warning Event Audible
X No
Alert
Low Engine Coolant Temperature Warning Event Breaker
X No
#1 Trip
Low Engine Coolant Temperature Warning Event Breaker
X No
#2 Trip
Low Engine Coolant Temperature Warning Event Fault
X No
Protection Timer
Engine Failure To Start Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Engine Failure To Start Shutdown Event Audible Alert Yes
X Engine Failure To Start Shutdown Event Breaker #1 Trip No
X Engine Failure To Start Shutdown Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 11 of 65

High Engine Oil Level Warning Event Response


X Activate Warning Condition
Configuration
X High Engine Oil Level Warning Event Audible Alert Yes
X High Engine Oil Level Warning Event Breaker #1 Trip No
X High Engine Oil Level Warning Event Breaker #2 Trip No
High Engine Oil Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Engine Oil Level Shutdown Event Audible Alert Yes
X High Engine Oil Level Shutdown Event Breaker #1 Trip No
X High Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Level Warning Event Response
X Activate Warning Condition
Configuration
X Low Engine Oil Level Warning Event Audible Alert Yes
X Low Engine Oil Level Warning Event Breaker #1 Trip No
X Low Engine Oil Level Warning Event Breaker #2 Trip No
Low Engine Oil Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Engine Oil Level Shutdown Event Audible Alert Yes
X Low Engine Oil Level Shutdown Event Breaker #1 Trip No
X Low Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Response
X Activate Warning Condition
Configuration
X Low Engine Oil Pressure Warning Event Audible Alert Yes
X Low Engine Oil Pressure Warning Event Breaker #1 Trip No
X Low Engine Oil Pressure Warning Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Fault Protection
X Yes
Timer
Low Engine Oil Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Engine Oil Pressure Shutdown Event Audible Alert Yes
X Low Engine Oil Pressure Shutdown Event Breaker #1 Trip No
X Low Engine Oil Pressure Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Shutdown Event Fault Protection
X Yes
Timer
High Engine Oil Temperature Warning Event Response
X Disable Condition
Configuration
X High Engine Oil Temperature Warning Event Audible Alert No
High Engine Oil Temperature Warning Event Breaker #1
X No
Trip
X High Engine Oil Temperature Warning Event Breaker #2 No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 12 of 65

Trip
High Engine Oil Temperature Warning Event Fault
X No
Protection Timer
High Engine Oil Temperature Shutdown Event Response
X Disable Condition
Configuration
High Engine Oil Temperature Shutdown Event Audible
X No
Alert
High Engine Oil Temperature Shutdown Event Breaker #1
X No
Trip
High Engine Oil Temperature Shutdown Event Breaker #2
X No
Trip
High Engine Oil Temperature Shutdown Event Fault
X No
Protection Timer
Low Engine Oil Temperature Warning Event Response
X Disable Condition
Configuration
X Low Engine Oil Temperature Warning Event Audible Alert No
Low Engine Oil Temperature Warning Event Breaker #1
X No
Trip
Low Engine Oil Temperature Warning Event Breaker #2
X No
Trip
Low Engine Oil Temperature Warning Event Fault
X Yes
Protection Timer
Low Engine Oil Temperature Shutdown Event Response
X Disable Condition
Configuration
X Low Engine Oil Temperature Shutdown Event Audible Alert No
Low Engine Oil Temperature Shutdown Event Breaker #1
X No
Trip
Low Engine Oil Temperature Shutdown Event Breaker #2
X No
Trip
Low Engine Oil Temperature Shutdown Event Fault
X No
Protection Timer
Unexpected Engine Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Unexpected Engine Shutdown Event Audible Alert Yes
X Unexpected Engine Shutdown Event Breaker #1 Trip No
X Unexpected Engine Shutdown Event Breaker #2 Trip No
Engine Overspeed Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Engine Overspeed Shutdown Event Audible Alert Yes
X Engine Overspeed Shutdown Event Breaker #1 Trip No
X Engine Overspeed Shutdown Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 13 of 65

Engine Underspeed Warning Event Response


X Activate Warning Condition
Configuration
X Engine Underspeed Warning Event Audible Alert Yes
X Engine Underspeed Warning Event Breaker #1 Trip No
X Engine Underspeed Warning Event Breaker #2 Trip No
X Engine Underspeed Warning Event Fault Protection Timer Yes
Engine Underspeed Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Engine Underspeed Shutdown Event Audible Alert Yes
X Engine Underspeed Shutdown Event Breaker #1 Trip No
X Engine Underspeed Shutdown Event Breaker #2 Trip No
Engine Underspeed Shutdown Event Fault Protection
X Yes
Timer
High Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
X High Exhaust Temperature Warning Event Audible Alert Yes
X High Exhaust Temperature Warning Event Breaker #1 Trip No
X High Exhaust Temperature Warning Event Breaker #2 Trip No
High Exhaust Temperature Warning Event Fault Protection
X No
Timer
High Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Exhaust Temperature Shutdown Event Audible Alert Yes
High Exhaust Temperature Shutdown Event Breaker #1
X No
Trip
High Exhaust Temperature Shutdown Event Breaker #2
X No
Trip
High Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
Low Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
X Low Exhaust Temperature Warning Event Audible Alert Yes
X Low Exhaust Temperature Warning Event Breaker #1 Trip No
X Low Exhaust Temperature Warning Event Breaker #2 Trip No
Low Exhaust Temperature Warning Event Fault Protection
X Yes
Timer
Low Exhaust Temperature Shutdown Event Response
X Disable Condition
Configuration
X Low Exhaust Temperature Shutdown Event Audible Alert No
Low Exhaust Temperature Shutdown Event Breaker #1
X No
Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 14 of 65

Low Exhaust Temperature Shutdown Event Breaker #2


X No
Trip
Low Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
High Right Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
High Right Exhaust Temperature Warning Event Audible
X Yes
Alert
High Right Exhaust Temperature Warning Event Breaker
X No
#1 Trip
High Right Exhaust Temperature Warning Event Breaker
X No
#2 Trip
High Right Exhaust Temperature Warning Event Fault
X No
Protection Timer
High Right Exhaust Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Right Exhaust Temperature Shutdown Event Audible
X Yes
Alert
High Right Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
High Right Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip
High Right Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
Low Right Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
Low Right Exhaust Temperature Warning Event Audible
X Yes
Alert
Low Right Exhaust Temperature Warning Event Breaker
X No
#1 Trip
Low Right Exhaust Temperature Warning Event Breaker
X No
#2 Trip
Low Right Exhaust Temperature Warning Event Fault
X Yes
Protection Timer
Low Right Exhaust Temperature Shutdown Event
X Disable Condition
Response Configuration
Low Right Exhaust Temperature Shutdown Event Audible
X No
Alert
Low Right Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
Low Right Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 15 of 65

Low Right Exhaust Temperature Shutdown Event Fault


X No
Protection Timer
High Left Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
High Left Exhaust Temperature Warning Event Audible
X Yes
Alert
High Left Exhaust Temperature Warning Event Breaker #1
X No
Trip
High Left Exhaust Temperature Warning Event Breaker #2
X No
Trip
High Left Exhaust Temperature Warning Event Fault
X No
Protection Timer
High Left Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
High Left Exhaust Temperature Shutdown Event Audible
X Yes
Alert
High Left Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
High Left Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip
High Left Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
Low Left Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
Low Left Exhaust Temperature Warning Event Audible
X Yes
Alert
Low Left Exhaust Temperature Warning Event Breaker #1
X No
Trip
Low Left Exhaust Temperature Warning Event Breaker #2
X No
Trip
Low Left Exhaust Temperature Warning Event Fault
X Yes
Protection Timer
Low Left Exhaust Temperature Shutdown Event Response
X Disable Condition
Configuration
Low Left Exhaust Temperature Shutdown Event Audible
X No
Alert
Low Left Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
Low Left Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip
Low Left Exhaust Temperature Shutdown Event Fault
X No
Protection Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 16 of 65

High Fuel Filter Differential Pressure Warning Event


X Activate Warning Condition
Response Configuration
High Fuel Filter Differential Pressure Warning Event
X Yes
Audible Alert
High Fuel Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
High Fuel Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
High Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Config Condition
High Fuel Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
High Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
High Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Configuration
Low Fuel Filter Differential Pressure Warning Event Audible
X Yes
Alert
Low Fuel Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
Low Fuel Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Warning Event Fault
X Yes
Protection Timer
Low Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Low Fuel Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
Low Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
Low Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Shutdown Event Fault
X Yes
Protection Timer
X High Fuel Level Warning Event Response Configuration Activate Warning Condition
X High Fuel Level Warning Event Audible Alert Yes
X High Fuel Level Warning Event Breaker #1 Trip No
X High Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
X High Fuel Level Shutdown Event Response Configuration
Condition

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 17 of 65

X High Fuel Level Shutdown Event Audible Alert Yes


X High Fuel Level Shutdown Event Breaker #1 Trip No
X High Fuel Level Shutdown Event Breaker #2 Trip No
X Low Fuel Level Warning Event Response Configuration Activate Warning Condition
X Low Fuel Level Warning Event Audible Alert Yes
X Low Fuel Level Warning Event Breaker #1 Trip No
X Low Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
X Low Fuel Level Shutdown Event Response Configuration
Condition
X Low Fuel Level Shutdown Event Audible Alert Yes
X Low Fuel Level Shutdown Event Breaker #1 Trip No
X Low Fuel Level Shutdown Event Breaker #2 Trip No
External Tank High Fuel Level Warning Event Response
X Activate Warning Condition
Configuration
X External Tank High Fuel Level Warning Event Audible Alert Yes
External Tank High Fuel Level Warning Event Breaker #1
X No
Trip
External Tank High Fuel Level Warning Event Breaker #2
X No
Trip
External Tank High Fuel Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
External Tank High Fuel Level Shutdown Event Audible
X Yes
Alert
External Tank High Fuel Level Shutdown Event Breaker #1
X No
Trip
External Tank High Fuel Level Shutdown Event Breaker #2
X No
Trip
External Tank Low Fuel Level Warning Event Response
X Activate Warning Condition
Configuration
X External Tank Low Fuel Level Warning Event Audible Alert Yes
External Tank Low Fuel Level Warning Event Breaker #1
X No
Trip
External Tank Low Fuel Level Warning Event Breaker #2
X No
Trip
External Tank Low Fuel Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
External Tank Low Fuel Level Shutdown Event Audible
X Yes
Alert
External Tank Low Fuel Level Shutdown Event Breaker #1
X No
Trip
External Tank Low Fuel Level Shutdown Event Breaker #2

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 18 of 65

X Trip No
X Fuel Leak Event Response Configuration Activate Warning Condition
X Fuel Leak Event Audible Alert Yes
X Fuel Leak Event Breaker #1 Trip No
X Fuel Leak Event Breaker #2 Trip No
High Engine Oil Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Config
High Engine Oil Filter Differential Pressure Warning Event
X Yes
Audible Alert
High Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
High Engine Oil Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Config Condition
High Engine Oil Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
High Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Config
Low Engine Oil Filter Differential Pressure Warning Event
X Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Fault
X Yes
Protection Timer
Low Engine Oil Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Config Condition
Low Engine Oil Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Shutdown Fault
X Yes
Protection Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 19 of 65

Service Maintenance Interval Warning Event Response


X Activate Warning Condition
Configuration
X Service Maintenance Interval Warning Event Audible Alert No
High Starting Air Pressure Warning Event Response
X Activate Warning Condition
Configuration
X High Starting Air Pressure Warning Event Audible Alert Yes
X High Starting Air Pressure Warning Event Breaker #1 Trip No
X High Starting Air Pressure Warning Event Breaker #2 Trip No
High Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Starting Air Pressure Shutdown Event Audible Alert Yes
High Starting Air Pressure Shutdown Event Breaker #1
X No
Trip
High Starting Air Pressure Shutdown Event Breaker #2
X No
Trip
Low Starting Air Pressure Warning Event Response
X Activate Warning Condition
Configuration
X Low Starting Air Pressure Warning Event Audible Alert Yes
X Low Starting Air Pressure Warning Event Breaker #1 Trip No
X Low Starting Air Pressure Warning Event Breaker #2 Trip No
Low Starting Air Pressure Warning Event Fault Protection
X Yes
Timer
Low Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Starting Air Pressure Shutdown Event Audible Alert Yes
X Low Starting Air Pressure Shutdown Event Breaker #1 Trip No
X Low Starting Air Pressure Shutdown Event Breaker #2 Trip No
Low Starting Air Pressure Shutdown Event Fault Protection
X Yes
Timer
X High Gas Pressure Warning Event Response Configuration Activate Warning Condition
X High Gas Pressure Warning Event Audible Alert Yes
X High Gas Pressure Warning Event Breaker #1 Trip No
X High Gas Pressure Warning Event Breaker #2 Trip No
High Gas Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Gas Pressure Shutdown Event Audible Alert Yes
X High Gas Pressure Shutdown Event Breaker #1 Trip No
X High Gas Pressure Shutdown Event Breaker #2 Trip No
X Low Gas Pressure Warning Event Response Configuration Activate Warning Condition
X Low Gas Pressure Warning Event Audible Alert Yes

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 20 of 65

X Low Gas Pressure Warning Event Breaker #1 Trip No


X Low Gas Pressure Warning Event Breaker #2 Trip No
Low Gas Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Gas Pressure Shutdown Event Audible Alert Yes
X Low Gas Pressure Shutdown Event Breaker #1 Trip No
X Low Gas Pressure Shutdown Event Breaker #2 Trip No
Engine Intake Manifold Charge Combustion Event Activate Hard Shutdown
X
Response Configuration Condition
Engine Intake Manifold Charge Combustion Event Audible
X Yes
Alert
Engine Intake Manifold Charge Combustion Event Loss of
X No
Utility
Engine Intake Manifold Charge Combustion Event Breaker
X No
#1 Trip
Engine Intake Manifold Charge Combustion Event Breaker
X No
#2 Trip
Engine Intake Manifold Charge Combustion Event Fault
X No
Protection Timer
High Generator Bearing #1 Temperature Warning Event
X Activate Warning Condition
Response Configuration
High Generator Bearing #1 Temperature Warning Event
X Yes
Audible Alert
High Generator Bearing #1 Temperature Warning Event
X No
Breaker #1 Trip
High Generator Bearing #1 Temperature Warning Event
X No
Breaker #2 Trip
High Generator Bearing #1 Temperature Warning Event
X No
Fault Protection Timer
High Generator Bearing #1 Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Generator Bearing #1 Temperature Shutdown Event
X Yes
Audible Alert
High Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #1 Trip
High Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #2 Trip
High Generator Bearing #1 Temperature Shutdown Event
X No
Fault Protection Timer
Low Generator Bearing #1 Temperature Warning Event
X Activate Warning Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 21 of 65

Low Generator Bearing #1 Temperature Warning Event


X Yes
Audible Alert
Low Generator Bearing #1 Temperature Warning Event
X No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Warning Event
X No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Warning Event
X Yes
Fault Protection Timer
Low Generator Bearing #1 Temperature Shutdown Event
X Disable Condition
Response Configuration
Low Generator Bearing #1 Temperature Shutdown Event
X No
Audible Alert
Low Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Shutdown Event
X No
Fault Protection Timer
Generator Overcurrent Warning Event Response
X Activate Warning Condition
Configuration
X Generator Overcurrent Warning Event Audible Alert Yes
X Generator Overcurrent Warning Event Breaker #1 Trip No
X Generator Overcurrent Warning Event Breaker #2 Trip No
Generator Overcurrent Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Overcurrent Shutdown Event Audible Alert Yes
X Generator Overcurrent Shutdown Event Breaker #1 Trip No
X Generator Overcurrent Shutdown Event Breaker #2 Trip No
Generator Over Frequency Warning Event Response
X Activate Warning Condition
Configuration
X Generator Over Frequency Warning Event Audible Alert Yes
X Generator Over Frequency Warning Event Breaker #1 Trip No
X Generator Over Frequency Warning Event Breaker #2 Trip No
Generator Over Frequency Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Over Frequency Shutdown Event Audible Alert Yes
Generator Over Frequency Shutdown Event Breaker #1
X No
Trip
Generator Over Frequency Shutdown Event Breaker #2
X No
Trip
Generator Under Frequency Warning Event Response

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 22 of 65

X Configuration Activate Warning Condition


X Generator Under Frequency Warning Event Audible Alert Yes
Generator Under Frequency Warning Event Breaker #1
X No
Trip
Generator Under Frequency Warning Event Breaker #2
X No
Trip
Generator Under Frequency Warning Event Fault
X Yes
Protection Timer
Generator Under Frequency Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Under Frequency Shutdown Event Audible Alert Yes
Generator Under Frequency Shutdown Event Breaker #1
X No
Trip
Generator Under Frequency Shutdown Event Breaker #2
X No
Trip
Generator Under Frequency Shutdown Event Fault
X Yes
Protection Timer
Generator Reverse Power Warning Event Response
X Activate Warning Condition
Configuration
X Generator Reverse Power Warning Event Audible Alert Yes
X Generator Reverse Power Warning Event Breaker #1 Trip No
X Generator Reverse Power Warning Event Breaker #2 Trip No
Generator Reverse Power Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Reverse Power Shutdown Event Audible Alert Yes
Generator Reverse Power Shutdown Event Breaker #1
X No
Trip
Generator Reverse Power Shutdown Event Breaker #2
X No
Trip
Generator Over Voltage Warning Event Response
X Activate Warning Condition
Configuration
X Generator Over Voltage Warning Event Audible Alert Yes
X Generator Over Voltage Warning Event Breaker #1 Trip No
X Generator Over Voltage Warning Event Breaker #2 Trip No
Generator Over Voltage Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Over Voltage Shutdown Event Audible Alert Yes
X Generator Over Voltage Shutdown Event Breaker #1 Trip No
X Generator Over Voltage Shutdown Event Breaker #2 Trip No
Generator Under Voltage Warning Event Response
X Activate Warning Condition
Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 23 of 65

X Generator Under Voltage Warning Event Audible Alert Yes


X Generator Under Voltage Warning Event Breaker #1 Trip No
X Generator Under Voltage Warning Event Breaker #2 Trip No
Generator Under Voltage Warning Event Fault Protection
X Yes
Timer
Generator Under Voltage Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Under Voltage Shutdown Event Audible Alert Yes
X Generator Under Voltage Shutdown Event Breaker #1 Trip No
X Generator Under Voltage Shutdown Event Breaker #2 Trip No
Generator Under Voltage Shutdown Event Fault Protection
X Yes
Timer
Activate Hard Shutdown
X Earth Fault Event Response Configuration
Condition
X Earth Fault Event Audible Alert Yes
X Earth Fault Event Breaker #1 Trip No
X Earth Fault Event Breaker #2 Trip No
Generator Winding #1 High Temperature Warning Event
X Activate Warning Condition
Response Configuration
Generator Winding #1 High Temperature Warning Event
X Yes
Audible Alert
Generator Winding #1 High Temperature Warning Event
X No
Breaker #1 Trip
Generator Winding #1 High Temperature Warning Event
X No
Breaker #2 Trip
Generator Winding #1 High Temperature Warning Event
X No
Fault Protection Timer
Generator Winding #2 High Temperature Warning Event
X Activate Warning Condition
Response Configuration
Generator Winding #2 High Temperature Warning Event
X Yes
Audible Alert
Generator Winding #2 High Temperature Warning Event
X No
Breaker #1 Trip
Generator Winding #2 High Temperature Warning Event
X No
Breaker #2 Trip
Generator Winding #2 High Temperature Warning Event
X No
Fault Protection Timer
Generator Winding #3 High Temperature Warning Event
X Activate Warning Condition
Response Configuration
Generator Winding #3 High Temperature Warning Event
X Yes
Audible Alert

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 24 of 65

Generator Winding #3 High Temperature Warning Event


X No
Breaker #1 Trip
Generator Winding #3 High Temperature Warning Event
X No
Breaker #2 Trip
Generator Winding #3 High Temperature Warning Event
X No
Fault Protection Timer
Generator Winding #1 High Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Generator Winding #1 High Temperature Shutdown Event
X Yes
Audible Alert
Generator Winding #1 High Temperature Shutdown Event
X No
Breaker #1 Trip
Generator Winding #1 High Temperature Shutdown Event
X No
Breaker #2 Trip
Generator Winding #1 High Temperature Shutdown Event
X No
Fault Protection Timer
Generator Winding #2 High Temperature Shutdown Event
Unavailable
Response Configuration
Generator Winding #2 High Temperature Shutdown Event
X Yes
Audible Alert
Generator Winding #2 High Temperature Shutdown Event
X No
Breaker #1 Trip
Generator Winding #2 High Temperature Shutdown Event
X No
Breaker #2 Trip
Generator Winding #2 High Temperature Shutdown Event
X No
Fault Protection Timer
Generator Winding #3 High Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Generator Winding #3 High Temperature Shutdown Event
X Yes
Audible Alert
Generator Winding #3 High Temperature Shutdown Event
X No
Breaker #1 Trip
Generator Winding #3 High Temperature Shutdown Event
X No
Breaker #2 Trip
Generator Winding #3 High Temperature Shutdown Event
X No
Fault Protection Timer
Generator High Power Warning Event Response
X Activate Warning Condition
Configuration
X Generator High Power Warning Event Audible Alert Yes
X Generator High Power Warning Event Breaker #1 Trip No
X Generator High Power Warning Event Breaker #2 Trip No
High Ambient Air Temperature Warning Event Response

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 25 of 65

X Configuration Activate Warning Condition


High Ambient Air Temperature Warning Event Audible
X Yes
Alert
High Ambient Air Temperature Warning Event Breaker #1
X No
Trip
High Ambient Air Temperature Warning Event Breaker #2
X No
Trip
High Ambient Air Temperature Warning Event Fault
X No
Protection Timer
High Ambient Air Temperature Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
High Ambient Air Temperature Shutdown Event Audible
X Yes
Alert
High Ambient Air Temperature Shutdown Event Breaker
X No
#1 Trip
High Ambient Air Temperature Shutdown Event Breaker
X No
#2 Trip
High Ambient Air Temperature Shutdown Event Fault
X No
Protection Timer
Low Ambient Air Temperature Warning Event Response
X Activate Warning Condition
Configuration
X Low Ambient Air Temperature Warning Event Audible Alert Yes
Low Ambient Air Temperature Warning Event Breaker #1
X No
Trip
Low Ambient Air Temperature Warning Event Breaker #2
X No
Trip
Low Ambient Air Temperature Shutdown Event Response
X Disable Condition
Configuration
Low Ambient Air Temperature Shutdown Event Audible
X No
Alert
Low Ambient Air Temperature Shutdown Event Breaker #1
X No
Trip
Low Ambient Air Temperature Shutdown Event Breaker #2
X No
Trip
Automatic Transfer Switch In Normal Position Event
X Active Only Condition
Response Configuration
Automatic Transfer Switch In Normal Position Event
X No
Audible Alert
Automatic Transfer Switch In Emergency Position Event
X Active Only Condition
Response Config
Automatic Transfer Switch In Emergency Position Event
X No
Audible Alert

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 26 of 65

High Battery Voltage Warning Event Response


X Activate Warning Condition
Configuration
X High Battery Voltage Warning Event Audible Alert Yes
X High Battery Voltage Warning Event Breaker #1 Trip No
X High Battery Voltage Warning Event Breaker #2 Trip No
High Battery Voltage Shutdown Event Response Activate Soft Shutdown
X
Configuration Condition
X High Battery Voltage Shutdown Event Audible Alert Yes
X High Battery Voltage Shutdown Event Breaker #1 Trip No
X High Battery Voltage Shutdown Event Breaker #2 Trip No
Low Battery Voltage Warning Event Response
X Disable Condition
Configuration
X Low Battery Voltage Warning Event Audible Alert No
X Low Battery Voltage Warning Event Breaker #1 Trip No
X Low Battery Voltage Warning Event Breaker #2 Trip No
X Low Battery Voltage Warning Event Fault Protection Timer No
Low Battery Charging System Voltage Warning Event
X Activate Warning Condition
Response Configuration
Low Battery Charging System Voltage Warning Event
X Yes
Audible Alert
Low Battery Charging System Voltage Warning Event
X No
Breaker #1 Trip
Low Battery Charging System Voltage Warning Event
X No
Breaker #2 Trip
Low Battery Charging System Voltage Warning Event Fault
X No
Protection Timer
Generator Breaker Failure To Open Event Response
X Activate Warning Condition
Configuration
X Generator Breaker Failure To Open Event Audible Alert Yes
X Generator Breaker Failure To Open Event Breaker #1 Trip No
X Generator Breaker Failure To Open Event Breaker #2 Trip No
Generator Breaker Failure To Close Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Breaker Failure To Close Event Audible Alert Yes
X Generator Breaker Failure To Close Event Breaker #1 Trip No
X Generator Breaker Failure To Close Event Breaker #2 Trip No
X Generator Breaker Open Event Response Configuration Active Only Condition
X Generator Breaker Open Event Audible Alert No
X Generator Breaker Closed Event Response Configuration Active Only Condition
X Generator Breaker Closed Event Audible Alert No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 27 of 65

Utility Breaker Failure To Open Event Response Activate Hard Shutdown


X
Configuration Condition
X Utility Breaker Failure To Open Event Audible Alert Yes
X Utility Breaker Failure To Open Event Breaker #1 Trip No
X Utility Breaker Failure To Open Event Breaker #2 Trip No
Utility Breaker Failure To Close Event Response
X Activate Warning Condition
Configuration
X Utility Breaker Failure To Close Event Audible Alert Yes
X Utility Breaker Failure To Close Event Breaker #1 Trip No
X Utility Breaker Failure To Close Event Breaker #2 Trip No
X Utility Breaker Open Event Response Configuration Active Only Condition
X Utility Breaker Open Event Audible Alert No
X Utility Breaker Closed Event Response Configuration Active Only Condition
X Utility Breaker Closed Event Audible Alert No
Emergency Shutdown Override Mode Active Warning
X Activate Warning Condition
Event Response Config
Emergency Shutdown Override Mode Active Warning
X No
Event Audible Alert
X Engine In Cooldown Event Response Configuration Active Only Condition
X Engine In Cooldown Event Audible Alert No
Engine Speed-Generator Output Freq Mismatch Warning
X Activate Warning Condition
Event Response Config
Engine Speed-Generator Output Freq Mismatch Warning
X Yes
Event Audible Alert
Engine Speed-Generator Output Freq Mismatch Warning
X No
Event Breaker #1 Trip
Engine Speed-Generator Output Freq Mismatch Warning
X No
Event Breaker #2 Trip
High Fire Extinguisher Pressure Warning Event Response
X Activate Warning Condition
Configuration
High Fire Extinguisher Pressure Warning Event Audible
X Yes
Alert
High Fire Extinguisher Pressure Warning Event Breaker #1
X No
Trip
High Fire Extinguisher Pressure Warning Event Breaker #2
X No
Trip
High Fire Extinguisher Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
High Fire Extinguisher Pressure Shutdown Event Audible
X Yes
Alert
High Fire Extinguisher Pressure Shutdown Event Breaker

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 28 of 65

X #1 Trip No
High Fire Extinguisher Pressure Shutdown Event Breaker
X No
#2 Trip
Low Fire Extinguisher Pressure Warning Event Response
X Activate Warning Condition
Configuration
Low Fire Extinguisher Pressure Warning Event Audible
X Yes
Alert
Low Fire Extinguisher Pressure Warning Event Breaker #1
X No
Trip
Low Fire Extinguisher Pressure Warning Event Breaker #2
X No
Trip
Low Fire Extinguisher Pressure Warning Event Fault
X No
Protection Timer
Low Fire Extinguisher Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
Low Fire Extinguisher Pressure Shutdown Event Audible
X Yes
Alert
Low Fire Extinguisher Pressure Shutdown Event Breaker
X No
#1 Trip
Low Fire Extinguisher Pressure Shutdown Event Breaker
X No
#2 Trip
Low Fire Extinguisher Pressure Shutdown Event Fault
X No
Protection Timer
Generator Control Not in Automatic Warning Event Warning & Active Only
X
Response Configuration Condition
Generator Control Not in Automatic Warning Event Audible
X Yes
Alert
Generator Breaker Locked Out Warning Event Response Warning & Active Only
X
Configuration Condition
Generator Breaker Locked Out Warning Event Audible
X Yes
Alert
Generator Breaker Locked Out Warning Event Breaker #1
X No
Trip
Generator Breaker Locked Out Warning Event Breaker #2
X No
Trip
Utility Breaker Locked Out Warning Event Response Warning & Active Only
X
Configuration Condition
X Utility Breaker Locked Out Warning Event Audible Alert Yes
X Utility Breaker Locked Out Warning Event Loss of Utility Yes
X Utility Breaker Locked Out Warning Event Breaker #1 Trip No
X Utility Breaker Locked Out Warning Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 29 of 65

Warning & Active Only


X Loss of Utility Event Response Configuration
Condition
X Loss of Utility Event Audible Alert Yes
Utility to Generator Transfer Failure Warning Event
X Activate Warning Condition
Response Configuration
Utility to Generator Transfer Failure Warning Event Audible
X Yes
Alert
Utility to Generator Transfer Failure Warning Event
X No
Breaker #1 Trip
Utility to Generator Transfer Failure Warning Event
X No
Breaker #2 Trip
Utility to Generator Transfer Failure Shutdown Event
Unavailable
Response Configuration
Utility to Generator Transfer Failure Shutdown Event
X Yes
Audible Alert
Utility to Generator Transfer Failure Shutdown Event
X Yes
Breaker #1 Trip
Utility to Generator Transfer Failure Shutdown Event
X No
Breaker #2 Trip
Generator to Utility Transfer Failure Warning Event
X Activate Warning Condition
Response Configuration
Generator to Utility Transfer Failure Warning Event Audible
X Yes
Alert
Generator to Utility Transfer Failure Warning Event
X No
Breaker #1 Trip
Generator to Utility Transfer Failure Warning Event
X No
Breaker #2 Trip
Activate Hard Shutdown
X Earth Leakage Event Response Configuration
Condition
X Earth Leakage Event Audible Alert Yes
X Earth Leakage Event Breaker #1 Trip No
X Earth Leakage Event Breaker #2 Trip No
X Utility Breaker System Fault Event Response Configuration Activate Warning Condition
X Utility Breaker System Fault Event Audible Alert Yes
X Utility Breaker System Fault Event Breaker #1 Trip No
X Utility Breaker System Fault Event Breaker #2 Trip No
Emergency Power System Supplying Load Event Response Warning & Active Only
X
Configuration Condition
Emergency Power System Supplying Load Event Audible
X No
Alert
X Low Cranking Voltage Warning Event Response Disable Condition

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 30 of 65

Configuration
X Low Cranking Voltage Warning Event Audible Alert No
X Low Cranking Voltage Warning Event Breaker #1 Trip No
X Low Cranking Voltage Warning Event Breaker #2 Trip No
Custom Event #1 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #1 High Warning Event Audible Alert Yes
X Custom Event #1 High Warning Event Breaker #1 Trip No
X Custom Event #1 High Warning Event Breaker #2 Trip No
Custom Event #1 High Warning Event Fault Protection
X No
Timer
Custom Event #1 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #1 High Shutdown Event Audible Alert Yes
X Custom Event #1 High Shutdown Event Breaker #1 Trip No
X Custom Event #1 High Shutdown Event Breaker #2 Trip No
Custom Event #1 High Shutdown Event Fault Protection
X No
Timer
Custom Event #1 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #1 Low Warning Event Audible Alert Yes
X Custom Event #1 Low Warning Event Breaker #1 Trip No
X Custom Event #1 Low Warning Event Breaker #2 Trip No
Custom Event #1 Low Warning Event Fault Protection
X No
Timer
Custom Event #1 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #1 Low Shutdown Event Audible Alert Yes
X Custom Event #1 Low Shutdown Event Breaker #1 Trip No
X Custom Event #1 Low Shutdown Event Breaker #2 Trip No
Custom Event #1 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #1 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #1 Condition Exists Event Audible Alert No
X Custom Event #1 Condition Exists Event Loss of Utility No
X Custom Event #1 Condition Exists Event Breaker #1 Trip No
X Custom Event #1 Condition Exists Event Breaker #2 Trip No
Custom Event #1 Condition Exists Event Fault Protection
X No
Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 31 of 65

Custom Event #2 High Warning Event Response


X Activate Warning Condition
Configuration
X Custom Event #2 High Warning Event Audible Alert Yes
X Custom Event #2 High Warning Event Breaker #1 Trip No
X Custom Event #2 High Warning Event Breaker #2 Trip No
Custom Event #2 High Warning Event Fault Protection
X No
Timer
Custom Event #2 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #2 High Shutdown Audible Alert Yes
X Custom Event #2 High Shutdown Breaker #1 Trip No
X Custom Event #2 High Shutdown Breaker #2 Trip No
X Custom Event #2 High Shutdown Fault Protection Timer No
Custom Event #2 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #2 Low Warning Audible Alert Yes
X Custom Event #2 Low Warning Breaker #1 Trip No
X Custom Event #2 Low Warning Breaker #2 Trip No
X Custom Event #2 Low Warning Fault Protection Timer No
Custom Event #2 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #2 Low Shutdown Event Audible Alert Yes
X Custom Event #2 Low Shutdown Event Breaker #1 Trip No
X Custom Event #2 Low Shutdown Event Breaker #2 Trip No
Custom Event #2 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #2 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #2 Condition Exists Event Audible Alert No
X Custom Event #2 Condition Exists Event Loss of Utility No
X Custom Event #2 Condition Exists Event Breaker #1 Trip No
X Custom Event #2 Condition Exists Event Breaker #2 Trip No
Custom Event #2 Condition Exists Event Fault Protection
X No
Timer
Custom Event #3 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #3 High Warning Event Audible Alert Yes
X Custom Event #3 High Warning Event Breaker #1 Trip No
X Custom Event #3 High Warning Event Breaker #2 Trip No
Custom Event #3 High Warning Event Fault Protection

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 32 of 65

X Timer No
Custom Event #3 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #3 High Shutdown Event Audible Alert Yes
X Custom Event #3 High Shutdown Event Breaker #1 Trip No
X Custom Event #3 High Shutdown Event Breaker #2 Trip No
Custom Event #3 High Shutdown Event Fault Protection
X No
Timer
Custom Event #3 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #3 Low Warning Event Audible Alert Yes
X Custom Event #3 Low Warning Event Breaker #1 Trip No
X Custom Event #3 Low Warning Event Breaker #2 Trip No
Custom Event #3 Low Warning Event Fault Protection
X No
Timer
Custom Event #3 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #3 Low Shutdown Event Audible Alert Yes
X Custom Event #3 Low Shutdown Event Breaker #1 Trip No
X Custom Event #3 Low Shutdown Event Breaker #2 Trip No
Custom Event #3 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #3 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #3 Condition Exists Event Audible Alert No
X Custom Event #3 Condition Exists Event Loss of Utility No
X Custom Event #3 Condition Exists Event Breaker #1 Trip No
X Custom Event #3 Condition Exists Event Breaker #2 Trip No
Custom Event #3 Condition Exists Event Fault Protection
X No
Timer
Custom Event #4 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #4 High Warning Event Audible Alert Yes
X Custom Event #4 High Warning Event Breaker #1 Trip No
X Custom Event #4 High Warning Event Breaker #2 Trip No
Custom Event #4 High Warning Event Fault Protection
X No
Timer
Custom Event #4 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #4 High Shutdown Event Audible Alert Yes

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 33 of 65

X Custom Event #4 High Shutdown Event Breaker #1 Trip No


X Custom Event #4 High Shutdown Event Breaker #2 Trip No
Custom Event #4 High Shutdown Event Fault Protection
X No
Timer
Custom Event #4 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #4 Low Warning Event Audible Alert Yes
X Custom Event #4 Low Warning Event Breaker #1 Trip No
X Custom Event #4 Low Warning Event Breaker #2 Trip No
Custom Event #4 Low Warning Event Fault Protection
X No
Timer
Custom Event #4 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #4 Low Shutdown Event Audible Alert Yes
X Custom Event #4 Low Shutdown Event Breaker #1 Trip No
X Custom Event #4 Low Shutdown Event Breaker #2 Trip No
Custom Event #4 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #4 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #4 Condition Exists Event Audible Alert No
X Custom Event #4 Condition Exists Event Loss of Utility No
X Custom Event #4 Condition Exists Event Breaker #1 Trip No
X Custom Event #4 Condition Exists Event Breaker #2 Trip No
Custom Event #4 Condition Exists Event Fault Protection
X No
Timer
Custom Event #5 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #5 High Warning Event Audible Alert Yes
X Custom Event #5 High Warning Event Breaker #1 Trip No
X Custom Event #5 High Warning Event Breaker #2 Trip No
Custom Event #5 High Warning Event Fault Protection
X No
Timer
Custom Event #5 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #5 High Shutdown Event Audible Alert Yes
X Custom Event #5 High Shutdown Event Breaker #1 Trip No
X Custom Event #5 High Shutdown Event Breaker #2 Trip No
Custom Event #5 High Shutdown Event Fault Protection
X No
Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 34 of 65

Custom Event #5 Low Warning Event Response


X Activate Warning Condition
Configuration
X Custom Event #5 Low Warning Event Audible Alert Yes
X Custom Event #5 Low Warning Event Breaker #1 Trip No
X Custom Event #5 Low Warning Event Breaker #2 Trip No
Custom Event #5 Low Warning Event Fault Protection
X No
Timer
Custom Event #5 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #5 Low Shutdown Event Audible Alert Yes
X Custom Event #5 Low Shutdown Event Breaker #1 Trip No
X Custom Event #5 Low Shutdown Event Breaker #2 Trip No
Custom Event #5 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #5 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #5 Condition Exists Event Audible Alert No
X Custom Event #5 Condition Exists Event Loss of Utility No
X Custom Event #5 Condition Exists Event Breaker #1 Trip No
X Custom Event #5 Condition Exists Event Breaker #2 Trip No
Custom Event #5 Condition Exists Event Fault Protection
X No
Timer
Custom Event #6 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #6 High Warning Event Audible Alert Yes
X Custom Event #6 High Warning Event Breaker #1 Trip No
X Custom Event #6 High Warning Event Breaker #2 Trip No
Custom Event #6 High Warning Event Fault Protection
X No
Timer
Custom Event #6 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #6 High Shutdown Event Audible Alert Yes
X Custom Event #6 High Shutdown Event Breaker #1 Trip No
X Custom Event #6 High Shutdown Event Breaker #2 Trip No
Custom Event #6 High Shutdown Event Fault Protection
X No
Timer
Custom Event #6 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #6 Low Warning Event Audible Alert Yes
X Custom Event #6 Low Warning Event Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 35 of 65

X Custom Event #6 Low Warning Event Breaker #2 Trip No


Custom Event #6 Low Warning Event Fault Protection
X No
Timer
Custom Event #6 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #6 Low Shutdown Event Audible Alert Yes
X Custom Event #6 Low Shutdown Event Breaker #1 Trip No
X Custom Event #6 Low Shutdown Event Breaker #2 Trip No
Custom Event #6 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #6 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #6 Condition Exists Event Audible Alert No
X Custom Event #6 Condition Exists Event Loss of Utility No
X Custom Event #6 Condition Exists Event Breaker #1 Trip No
X Custom Event #6 Condition Exists Event Breaker #2 Trip No
Custom Event #6 Condition Exists Event Fault Protection
X No
Timer
Custom Event #7 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #7 High Warning Event Audible Alert Yes
X Custom Event #7 High Warning Event Breaker #1 Trip No
X Custom Event #7 High Warning Event Breaker #2 Trip No
Custom Event #7 High Warning Event Fault Protection
X No
Timer
Custom Event #7 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #7 High Shutdown Event Audible Alert Yes
X Custom Event #7 High Shutdown Event Breaker #1 Trip No
X Custom Event #7 High Shutdown Event Breaker #2 Trip No
Custom Event #7 High Shutdown Event Fault Protection
X No
Timer
Custom Event #7 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #7 Low Warning Event Audible Alert Yes
X Custom Event #7 Low Warning Event Breaker #1 Trip No
X Custom Event #7 Low Warning Event Breaker #2 Trip No
Custom Event #7 Low Warning Event Fault Protection
X No
Timer
X Custom Event #7 Low Shutdown Event Response Activate Hard Shutdown

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 36 of 65

Configuration Condition
X Custom Event #7 Low Shutdown Event Audible Alert Yes
X Custom Event #7 Low Shutdown Event Breaker #1 Trip No
X Custom Event #7 Low Shutdown Event Breaker #2 Trip No
Custom Event #7 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #7 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #7 Condition Exists Event Audible Alert No
X Custom Event #7 Condition Exists Event Loss of Utility No
X Custom Event #7 Condition Exists Event Breaker #1 Trip No
X Custom Event #7 Condition Exists Event Breaker #2 Trip No
Custom Event #7 Condition Exists Event Fault Protection
X No
Timer
Custom Event #8 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #8 High Warning Event Audible Alert Yes
X Custom Event #8 High Warning Event Breaker #1 Trip No
X Custom Event #8 High Warning Event Breaker #2 Trip No
Custom Event #8 High Warning Event Fault Protection
X No
Timer
Custom Event #8 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #8 High Shutdown Event Audible Alert Yes
X Custom Event #8 High Shutdown Event Breaker #1 Trip No
X Custom Event #8 High Shutdown Event Breaker #2 Trip No
Custom Event #8 High Shutdown Event Fault Protection
X No
Timer
Custom Event #8 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #8 Low Warning Event Audible Alert Yes
X Custom Event #8 Low Warning Event Breaker #1 Trip No
X Custom Event #8 Low Warning Event Breaker #2 Trip No
Custom Event #8 Low Warning Event Fault Protection
X No
Timer
Custom Event #8 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #8 Low Shutdown Event Audible Alert Yes
X Custom Event #8 Low Shutdown Event Breaker #1 Trip No
X Custom Event #8 Low Shutdown Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 37 of 65

Custom Event #8 Low Shutdown Event Fault Protection


X No
Timer
Custom Event #8 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #8 Condition Exists Event Audible Alert No
X Custom Event #8 Condition Exists Event Loss of Utility No
X Custom Event #8 Condition Exists Event Breaker #1 Trip No
X Custom Event #8 Condition Exists Event Breaker #2 Trip No
Custom Event #8 Condition Exists Event Fault Protection
X No
Timer
DIO #1 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 2 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 2 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 38 of 65

DIO #1 Custom Event # 3 Condition Exists Event Breaker


X No
#2 Trip
DIO #1 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 4 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 5 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 6 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 39 of 65

DIO #1 Custom Event # 7 Condition Exists Event Audible


X No
Alert
DIO #1 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 7 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 9 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 9 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 40 of 65

DIO #1 Custom Event #10 Condition Exists Event Breaker


X No
#2 Trip
DIO #1 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event #11 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event #12 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 41 of 65

DIO #2 Custom Event # 2 Condition Exists Event Audible


X No
Alert
DIO #2 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 2 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 3 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 4 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 42 of 65

DIO #2 Custom Event # 5 Condition Exists Event Breaker


X No
#2 Trip
DIO #2 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 6 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 7 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 7 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 43 of 65

DIO #2 Custom Event # 9 Condition Exists Event Audible


X No
Alert
DIO #2 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 9 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event #10 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event #11 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 44 of 65

DIO #2 Custom Event #12 Condition Exists Event Breaker


X No
#2 Trip
DIO #2 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 2 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 2 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 3 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 45 of 65

DIO #3 Custom Event # 4 Condition Exists Event Audible


X No
Alert
DIO #3 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 5 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 6 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 7 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 46 of 65

DIO #3 Custom Event # 7 Condition Exists Event Breaker


X No
#2 Trip
DIO #3 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 9 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 9 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event #10 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 47 of 65

DIO #3 Custom Event #11 Condition Exists Event Audible


X No
Alert
DIO #3 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event #12 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 2 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 48 of 65

DIO #4 Custom Event # 2 Condition Exists Event Breaker


X No
#2 Trip
DIO #4 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 3 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 4 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 5 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 49 of 65

DIO #4 Custom Event # 6 Condition Exists Event Audible


X No
Alert
DIO #4 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 7 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 7 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 9 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 50 of 65

DIO #4 Custom Event # 9 Condition Exists Event Breaker


X No
#2 Trip
DIO #4 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event #10 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event #11 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event #12 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
Event Warning Condition Response Auto Reset Enable
X Enabled
Status

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 51 of 65

X Event Audible Alert Response Auto Reset Enable Status Enabled


X Event Loss Of Utility Response Auto Reset Enable Status Enabled
X Event Breaker #1 Trip Response Auto Reset Enable Status Enabled
X Event Breaker #2 Trip Response Auto Reset Enable Status Enabled
X Generator Connection Configuration Wye (or Star) Connection
X Generator Potential Transformer Primary Winding Rating 1 Volts
Generator Potential Transformer Secondary Winding
X 1 Volts
Rating
X Generator Current Transformer Primary Winding Rating 150 Amps
X Generator Current Transformer Secondary Winding Rating 5 Amps
X Number of Generator Poles 4 Poles
X Generator Rated Frequency 50 Hz
X Generator Rated Voltage 400 Volts
X Generator Rated Power 70 kW
X Generator Rated Apparent Power 88 kVA
Customer Password Security Level to Reset Generator
X 3-Factory, Single Use
Energy Meters
X Generator Breaker Closing Pulse Active Time Disabled or Not Installed
X Generator Breaker Closing Pulse Rest Interval Disabled or Not Installed
X Generator Breaker Maximum Closing Time Disabled or Not Installed
X Generator Breaker Maximum Opening Time Disabled or Not Installed
X Generator Breaker Lockout Configuration Disabled or Not Installed
X Generator Breaker Type Configuration Disabled or Not Installed
X Automatic Generator Breaker Control Source Configuration Disabled or Not Installed
Generator Definite Time Overcurrent Warning Event
X 100 %
Percentage Threshold
Generator Inverse Time Overcurrent Shutdown Event
X 0,27 Sec
Time Multiplier
Generator Definite Time Overcurrent Shutdown Event
X 125 %
Percentage Threshold
Generator Definite Time Overcurrent Shutdown Event
X 10,0 Sec
Notification Delay Time
Generator Over Frequency Warning Event Percentage
X 105,0 %
Threshold
Generator Over Frequency Warning Event Notification
X 10 Sec
Delay Time
Generator Over Frequency Shutdown Event Percentage
X 110,0 %
Threshold
Generator Over Frequency Shutdown Event Notification
X 2 Sec
Delay Time

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 52 of 65

Generator Under Frequency Warning Event Percentage


X 95,0 %
Threshold
Generator Under Frequency Warning Event Notification
X 10 Sec
Delay Time
Generator Under Frequency Shutdown Event Percentage
X 90,0 %
Threshold
Generator Under Frequency Shutdown Event Notification
X 4 Sec
Delay Time
Generator Over Voltage Warning Event Percentage
X 105 %
Threshold
Generator Over Voltage Warning Event Notification Delay
X 10 Sec
Time
Generator Over Voltage Shutdown Event Percentage
X 110 %
Threshold
Generator Over Voltage Shutdown Event Notification Delay
X 2 Sec
Time
Generator Under Voltage Warning Event Percentage
X 95 %
Threshold
Generator Under Voltage Warning Event Notification Delay
X 10 Sec
Time
Generator Under Voltage Shutdown Event Percentage
X 90 %
Threshold
Generator Under Voltage Shutdown Event Notification
X 4 Sec
Delay Time
X Maximum Engine Speed Bias 400 RPM
X Generator Nominal Output Frequency 50,0 Hz
X Programmable Cycle Timer #1 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #1 Activation Day - Monday Deactivate
X Programmable Cycle Timer #1 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #1 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #1 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #1 Activation Day - Friday Deactivate
X Programmable Cycle Timer #1 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #1 Activation Start Time 0 min
X Programmable Cycle Timer #1 Active Time 1 min
Programmable Cycle Timer #1 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #1 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #2 Activation Day - Sunday Deactivate

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 53 of 65

X Programmable Cycle Timer #2 Activation Day - Monday Deactivate


X Programmable Cycle Timer #2 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #2 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #2 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #2 Activation Day - Friday Deactivate
X Programmable Cycle Timer #2 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #2 Activation Start Time 0 min
X Programmable Cycle Timer #2 Active Time 1 min
Programmable Cycle Timer #2 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #2 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #3 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #3 Activation Day - Monday Deactivate
X Programmable Cycle Timer #3 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #3 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #3 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #3 Activation Day - Friday Deactivate
X Programmable Cycle Timer #3 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #3 Activation Start Time 0 min
X Programmable Cycle Timer #3 Active Time 1 min
Programmable Cycle Timer #3 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #3 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #4 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #4 Activation Day - Monday Deactivate
X Programmable Cycle Timer #4 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #4 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #4 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #4 Activation Day - Friday Deactivate
X Programmable Cycle Timer #4 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #4 Activation Start Time 0 min
X Programmable Cycle Timer #4 Active Time 1 min
Programmable Cycle Timer #4 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #4 Output #2 Activation

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 54 of 65

X Configuration Inactive
X Programmable Cycle Timer #5 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #5 Activation Day - Monday Deactivate
X Programmable Cycle Timer #5 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #5 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #5 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #5 Activation Day - Friday Deactivate
X Programmable Cycle Timer #5 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #5 Activation Start Time 0 min
X Programmable Cycle Timer #5 Active Time 1 min
Programmable Cycle Timer #5 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #5 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #6 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #6 Activation Day - Monday Deactivate
X Programmable Cycle Timer #6 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #6 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #6 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #6 Activation Day - Friday Deactivate
X Programmable Cycle Timer #6 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #6 Activation Start Time 0 min
X Programmable Cycle Timer #6 Active Time 1 min
Programmable Cycle Timer #6 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #6 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #7 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #7 Activation Day - Monday Deactivate
X Programmable Cycle Timer #7 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #7 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #7 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #7 Activation Day - Friday Deactivate
X Programmable Cycle Timer #7 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #7 Activation Start Time 0 min
X Programmable Cycle Timer #7 Active Time 1 min
Programmable Cycle Timer #7 Output #1 Activation

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 55 of 65

X Configuration Inactive
Programmable Cycle Timer #7 Output #2 Activation
X Inactive
Configuration
Electronic Control Module Reduced Power Mode Enable
X Enabled
Status
Electronic Control Module Reduced Power Mode Delay
X 20 min
Time
X Relay Output #1 Active State Configuration High
X Relay Output #2 Active State Configuration High
X Relay Output #3 Active State Configuration High
X Relay Output #4 Active State Configuration High
X Relay Output #5 Active State Configuration High
X Relay Output #6 Active State Configuration High
X Relay Output #7 Active State Configuration High
X Relay Output #8 Active State Configuration High
X Maintenance Level 1 Cycle Interval Hours 500 hours
X Maintenance Level 1 Cycle Interval Days 180
Customer Password Security Level to Reset Service
X 3-Factory, Single Use
Maintenance Interval
X Spare Analog Input Enable Status Enabled
X Spare Analog Input Type Configuration Temperature
X Spare Analog Input Suspect Parameter Number Engine Oil Temperature
Spare Analog Input High Warning Event Percentage
X 99 %
Threshold
Spare Analog Input High Temperature Warning Event
X 190 Deg C
Threshold
Spare Analog Input High Pressure Warning Event
X 900 kPa
Threshold
Spare Analog Input High Warning Event Notification Delay
X 10 Sec
Time
Spare Analog Input High Shutdown Event Percentage
X 100 %
Threshold
Spare Analog Input High Temperature Shutdown Event
X 195 Deg C
Threshold
Spare Analog Input High Pressure Shutdown Event
X 1000 kPa
Threshold
Spare Analog Input High Shutdown Event Notification
X 10 Sec
Delay Time
Spare Analog Input Low Warning Event Percentage
X 10 %
Threshold
Spare Analog Input Low Temperature Warning Event

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 56 of 65

X Threshold 15 Deg C
Spare Analog Input Low Pressure Warning Event
X 100 kPa
Threshold
Spare Analog Input Low Warning Event Notification Delay
X 10 Sec
Time
Spare Analog Input Low Shutdown Event Percentage
X 5%
Threshold
Spare Analog Input Low Temperature Shutdown Event
X 10 Deg C
Threshold
Spare Analog Input Low Pressure Shutdown Event
X 75 kPa
Threshold
Spare Analog Input Low Shutdown Event Notification
X 10 Sec
Delay Time
X Spare Analog Input Sensor Configuration Code Map #1
X Programmable Trip Point Function #1 Trigger Condition Trip Above Threshold
Programmable Trip Point Function #1 Percentage
X 90 %
Threshold
Programmable Trip Point Function #1 Hysteresis
X 5%
Percentage
Programmable Trip Point Function #1 Trip Activation
X 10 Sec
Delay Time
Programmable Trip Point Function #1 Trip Deactivation
X 1 Sec
Delay Time
X Programmable Trip Point Function #2 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #2 Percentage
X Disabled or Not Installed
Threshold
Programmable Trip Point Function #2 Hysteresis
X Disabled or Not Installed
Percentage
Programmable Trip Point Function #2 Trip Activation
X Disabled or Not Installed
Delay Time
Programmable Trip Point Function #2 Trip Deactivation
X Disabled or Not Installed
Delay Time
X Programmable Trip Point Function #3 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #3 Percentage
X Disabled or Not Installed
Threshold
Programmable Trip Point Function #3 Hysteresis
X Disabled or Not Installed
Percentage
Programmable Trip Point Function #3 Trip Activation
X Disabled or Not Installed
Delay Time
Programmable Trip Point Function #3 Trip Deactivation
X Disabled or Not Installed
Delay Time

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 57 of 65

X Programmable Trip Point Function #4 Trigger Condition Disabled or Not Installed


Programmable Trip Point Function #4 Percentage
X Disabled or Not Installed
Threshold
Programmable Trip Point Function #4 Hysteresis
X Disabled or Not Installed
Percentage
Programmable Trip Point Function #4 Trip Activation
X Disabled or Not Installed
Delay Time
Programmable Trip Point Function #4 Trip Deactivation
X Disabled or Not Installed
Delay Time
X DIO #1 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
X DIO #1 Event Input Function # 8 Suspect Parameter Disabled or Not Installed

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 58 of 65

Number
X DIO #1 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function #12 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 6 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 59 of 65

X Number Disabled or Not Installed


X DIO #2 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function #12 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 4 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 60 of 65

X Number Disabled or Not Installed


X DIO #3 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function #12 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 2 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 61 of 65

X Number Disabled or Not Installed


X DIO #4 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function #12 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 62 of 65

X Number Disabled or Not Installed


DIO #1 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 3 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 8 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 3 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 6 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 63 of 65

X Number Disabled or Not Installed


X DIO #2 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 8 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 3 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 8 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 3 Trigger Condition Disabled or Not Installed

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 64 of 65

DIO #4 Event Output Function # 4 Suspect Parameter


X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 8 Trigger Condition Disabled or Not Installed
X DIO #1 Digital Output #1 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #8 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #1 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #8 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #1 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #8 Source Configuration Disabled or Not Installed

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 65 of 65

X DIO #4 Digital Output #1 Source Configuration Disabled or Not Installed


X DIO #4 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #8 Source Configuration Disabled or Not Installed
X Generator/Utility Automatic Transfer Enable Status Disabled or Not Installed
X Loss of Utility Event Notification Delay Time Disabled or Not Installed
X Utility to Generator Transfer Delay Time Disabled or Not Installed
X Generator to Utility Transfer Delay Time Disabled or Not Installed
X Generator to Utility Fast Transfer Delay Time Disabled or Not Installed
Utility to Generator Transfer Failure Warning Event
X Disabled or Not Installed
Threshold
Utility to Generator Transfer Failure Shutdown Event
X Disabled or Not Installed
Threshold
Generator to Utility Transfer Failure Warning Event
X Disabled or Not Installed
Threshold
Generator/Utility Automatic Transfer Unpowered Load
X Disabled or Not Installed
Time
X Generator Ready to Load Threshold Percentage Disabled or Not Installed
X Generator Ready to Load Delay Time Disabled or Not Installed
X Generator to Utility Transfer Mode Disabled or Not Installed
X Utility Breaker Closing Pulse Active Time Disabled or Not Installed
X Utility Breaker Closing Pulse Rest Interval Disabled or Not Installed
X Utility Breaker Maximum Closing Time Disabled or Not Installed
X Utility Breaker Maximum Opening Time Disabled or Not Installed
X Utility Breaker Lockout Configuration Disabled or Not Installed
X Utility Breaker Type Configuration Disabled or Not Installed
X Automatic Utility Breaker Control Source Configuration Disabled or Not Installed
Engine Serial Number Not Programmed
X Display Pressure Units Configuration bar
X Display Temperature Units Configuration Degrees Centigrade (Celsius)
X Display Volume Units Configuration liters

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012