You are on page 1of 5

Date Submitted:

Prepared by:
Reviewed by:
Approve by:

Item No. Date Found Time Found

1 October 15, 2016 1000H

2 March 16, 2017 1500H

3 June 21, 2017 1000H

4 July 11, 2017 1500H

5 July 31, 2017 1040H

6 July 31, 2017 1140H

7 July 31, 2017 1140H

8 July 31, 2017 1140H


September 4, 2017
PH, RJAY & PV
PV

Cable Issue Cable Size Wire Colour

Grounded and damaged cable 240 mm² Black

Loose wiring/termination 240 mm² Black

Grounded and damaged cable 240 mm² Red

Grounded and damaged cable 240 mm² Red

Grounded and damaged cable 240 mm² Black

Grounded and damaged cable 240 mm² Black

Grounded and damaged cable 240 mm² Black

Grounded and damaged cable 240 mm² Black


Damaged Cable Summar

Affected Equipment Effect on Generation Location (Array)

Offline CB5
Inverter 1B Array 2
(Insulation Resistance Fault)

Low Voltage Side Cable of


I2A was offline from 1500 - 1600 Array 1
the 2.5 MVA Rransformer at MV 2

Inverter 2A Offline CB4


Array 3
Combiner Box 4 (Insulation Resistance Fault)

Inverter 3B Offline CB3


Array 1
Combiner Box 3 (Insulation Resistance Fault)

Inverter 3A Offline CB4


Array 2
Combiner Box 3 (Insulation Resistance Fault)

Inverter 3B Offline CB1


Array 2
Combiner Box 1 (Insulation Resistance Fault)

Inverter 3B Offline CB2


Array 2
Combiner Box 2 (Insulation Resistance Fault)

Inverter 3B Offline CB6


Array 2
Combiner Box 6 (Insulation Resistance Fault)
Damaged Cable Summary Report

Material Loss
Date Repaired/
Action/s Taken
Replaced
Cable Length (M) Others

2 Terminal Lugs
120 Meters October 16, 2016 Replaced Cable
(for 240 mm2 Cable)

12 Terminal Lugs
80 Meters March 17, 2017 Replaced Cable
(for 240 mm2 Cable)

2 Terminal Lugs
170 Meters June 22, 2017 Replaced Cable
(for 240 mm2 Cable)

2 Terminal Lugs Repaired Cable,


290 Meters (for 240 mm2 Cable) July 12, 2017 Wrapped with Rubber
Rubber Wire & 2 Ft. Sleeve Tape & Sleeve
2 Terminal Lugs
290 Meters (for 240 mm2 Cable) August 25,2017 Replaced Cable
Rubber Wire & 2 Ft. Sleeve

2 Terminal Lugs
290 Meters August 28, 2017 Replaced Cable
(for 240 mm2 Cable)

2 Terminal Lugs
270 Meters August 28, 2017 Replaced Cable
(for 240 mm2 Cable)

2 Terminal Lugs
250 Meters August 28, 2017 Replaced Cable
(for 240 mm2 Cable)
Remarks