PITTAS-DRAGNIS
LABORATORY TEST SERVICES
FOR LIGHTNING PROTECTION
AND EARTHING SYSTEMS
Page 1 of 18
REPORT IDENTIFICATION
Subject of Report: Aluminium Square Tape Clamp – STC50A
Total pages of
18
report:
Applied standard: IEC 62561-1:2017
Page 2 of 18
VALIDITY CONDITIONS OF THE PRESENT DOCUMENT:
This type test report may not be reproduced other than in full, except with the prior written approval of
the issuing laboratory. This type test report only covers the samples submitted for test and does not
produce evidence of the quality for series production.
Table of Contents
Table of Contents....................................................................................................... 3
1. Sample Description – Test Assembly ................................................................ 4
2. Standards and References................................................................................ 6
3. Tests ................................................................................................................. 7
3.1 Conditioning/Ageing tests ......................................................................... 7
3.1.1 Test procedure..................................................................................... 7
3.1.2 Testing Equipment – Measuring Instruments Description .................... 8
3.2 Electrical Test ........................................................................................... 9
3.2.1 Test Procedure .................................................................................... 9
3.2.2 Testing Equipment – Measuring Instruments Description .................. 10
3.3 Static Mechanical Test............................................................................ 10
3.3.1 Test Procedure .................................................................................. 10
4. Results and Parameters Recorded ................................................................. 11
5. Conclusions..................................................................................................... 12
6. APPENDIX A: Test Report Approval ............................................................... 12
7. APPENDIX B: Tables – Photographs............................................................. 13
The material of the connector was compatible with the conductor used.
HENG aluminium 25mm(W) x 3mm(T) Tape – AT253A was used.
Manufacturer’s symbol and Product’s identification number were moulded on the
connector. Component classification were given on the smallest packing unit.
Component Classification: Class H (Heavy Duty)
Installation: General use.
Intended to withstand a static mechanical load.
Non-permanent connection component.
The connection component was designed so that it connects the conductors,
without damaging them or the item, itself.
Samples received: 23th September 2019.
TEST
The specimens are placed in the salt mist chamber and sprayed for a period of
2 hours at a temperature of 25 oC. At the end of the spraying period, the specimens
transferred to the humidity chamber and stored at a temperature of 40 oC and a relative
humidity of 95 oC for 22 hours.
After that, the specimens complying with salt mist treatment were subjected to
humid sulphurous atmosphere treatment. The cabinet is filled with demineralized water.
The specimens are placed in position and the cabinet is closed. The sulfur dioxide
entrains into the cabinet through the inlet pipe. The test machine is programmed to
raise the temperature in the cabinet at 40 oC gradually in a period of one hour and a
half.
The test duration is 7 cycles. Each cycle lasted 24 hours and consisted by 8
hours in the cabinet and 16 hours in the ambient atmosphere at a temperature of
24 oC and relative humidity 58%.
Severity of the
test (2): Three salt mist spray periods duration two (2) hours
Three Storage periods in humid
chamber for 22 hours
Chamber volume: 358 dm3
Demineralized water: 2.00 dm3
Demineralized water conductivity: ≤500 μS/m
Humid
Sulfur dioxide: 0.20 dm3
sulphurous
Chamber temp. During test: 40oC
atmosphere
Angle of inclination of specimens during the test: 15o
Exposed surface of the specimens: <0.6 m2
Generator Circuit
HENG – Aluminium Square Tape Clamp – STC50A
Test Report Id. Number: 257 Pittas - Dragnis Page 9 of 18
3.2.2 TESTING EQUIPMENT – MEASURING INSTRUMENTS DESCRIPTION
PASS/
Specim
Test Required passing criteria Results of tests FAIL
en
Status
Following to the test, the specimens
PASS
had a good visual appearance. No
Salt mist
corrosion of parent metal,
test deformation or change of dimensions
of the specimens was observed.
PASS
sulphurous alterations or change in the
atmosphere mechanical properties appeared.
treatment The number of corrosion distribution
that is, pits, cracks, blisters,
according to ISO 10289:1999 was
within the rating 9 (0,1%).
The component is deemed to have
passed the test if:
The contact resistance measured
with a source of 10A, as close as
possible to the joint is equal or less
The contact resistance measured as
than 1mΩ.
close to the component as possible
It does not exhibit any crack to was less than 1mΩ.
normal or corrected vision without
After examining the surface of the
magnification nor does it have any
257a connectors, with normal and
PASS
loose parts or deformation impairing
Electrical corrected vision no cracks, loose
its normal use.
test
257b parts or deformation of the connector
This torque should be greater than were found. There was no movement
0.25 and less than 1.5 times of 257c
of the conductors from the connector.
tightening torque. In case of
connectors with more than one The observed results are further
screw, only the loosening torque of presented in table A - Appendix B
the first screw is relevant to this test; page 14.
The 20 mm length of conductor
from the connector, prior to the test is
not less than 3mm after completion of
the test.
The specimens are deemed to
have passed the test if there is 257d No movement of the conductors
PASS
Static less than 1mm movement of the greater than 1mm was recorded. No
mechanical conductor during the test and no 257e damage to the component or
test damage to the component or 257f conductor.
conductor.
PASS
Electro-
N/A
magnetic Products covered by this standard are, in normal use, passive in respect of
capability electromagnetic influences (emission and immunity)
(EMC)
257a-1
257a-2
257a-3
257b-2
257b-3
257c-2
257c-3