PITTAS-DRAGNIS
LABORATORY TEST SERVICES
FOR LIGHTNING PROTECTION
AND EARTHING SYSTEMS
Page 1 of 15
Subject of Report: Copper Taper Air Rod – CT10C
Total pages of
15
report:
Report date of
25/03/2019
issue:
Responsible Name: Vasilios Antonados – El. Engineer
engineer for
conducting the Signature:
tests:
Name: Vasilios Pittas – Technical Director
Checked and
authorized by: Signature:
Page 2 of 15
VALIDITY CONDITIONS OF THE PRESENT DOCUMENT:
This type test report may not be reproduced other than in full, except with the prior written approval of
the issuing laboratory. This type test report only covers the samples submitted for test and does not
produce evidence of the quality for series production.
Table of Contents
1 Sample Description ........................................................................................... 4
2 Standards and References................................................................................ 5
3 Test Procedure.................................................................................................. 6
3.1 Environmental Tests ................................................................................. 6
3.1.1 Test Procedure .................................................................................... 6
3.1.2 Testing Equipment – Measuring Instruments Description .................... 7
3.2 Electrical Resistivity .................................................................................. 7
3.2.1 Test Procedure .................................................................................... 7
3.2.2 Testing Equipment – Measuring Instruments Description .................... 8
3.3 Tensile Strength ....................................................................................... 8
3.3.1 Test Procedure .................................................................................... 8
3.3.2 Testing Equipment – Measuring Instruments Description .................... 8
4 Results and Parameters Recorded ................................................................... 9
5 Conclusions..................................................................................................... 10
6 APPENDIX A: Test Report Approval ............................................................... 10
7 APPENDIX B: Tables – Photographs............................................................. 11
Dimensions:
Diameter (D): 16 mm
Sample length (L)* : 1000 mm
Cross sectional area: 201.06 mm²
Weight per piece: ≈ 1.70 kg/pc
The rod was marked by pressing with the manufacturing trademark and identifying
symbol.
Photograph of Component
Six new specimens of copper air rod, with protocol numbers 177a, 177b, 177c,
177d, 177e, 177f were cleaned with a suitable degreasing agent followed by cleaning
in demineralizing water and drying under air.
HENG – Copper Taper Air Rod – CT10C
Protocol number: 177 Pittas - Dragnis Page 4 of 15
2 STANDARDS AND REFERENCES
Document
Description
Name and Version
International Lightning Protection System Components(LPSC)
Standard Part 1: Requirements for connection components.
IEC 62561-1:2017
International Lightning Protection System Components(LPSC)
Standard Part 2: Requirements for conductors and earth electrodes.
IEC 62561-2:2018
European Standard Protection against lightning – Part 1: General principles
EN 62305-1
European Standard Protection against lightning – Part 3: Physical damage to
structures and life hazard
EN 62305-3
TEST
The electrical resistance of all 3 specimens was measured over a length of
100 mm, prior to the environmental tests.
The specimens are placed in the salt mist chamber and sprayed for a period of
2 hours at a temperature of 25 oC. At the end of the spraying period, the specimens
transferred to the humidity chamber and stored at a temperature of 40 oC and a relative
humidity of 95 oC for 22 hours.
After that, the specimens complying with salt mist treatment were subjected to
humid sulphurous atmosphere treatment. The cabinet is filled with demineralized water.
The specimens are placed in position and the cabinet is closed. The sulfur dioxide
entrains into the cabinet through the inlet pipe. The test machine is programmed to
raise the temperature in the cabinet at 40 oC gradually in a period of one hour and a
half.
The test duration is 7 cycles. Each cycle lasted 24 hours and consisted by 8
hours in the cabinet and 16 hours in the ambient atmosphere at a temperature of
24 oC and relative humidity 58%.
The electrical resistance of all 3 specimens was measured again, over a length
of 100 mm, after the environmental tests.
Severity of the
test (2): • Three salt mist spray periods duration two (2) hours
• Three Storage periods in humid chamber for 22 hours
The methodology used for the tensile strength [Rm] tests is complying with ISO
6892-1. Specimens 177d, 177e, 177f were tested un-machined as per D.1 of ISO 6892-
1:2009.
(IEC 62561-2:2018 paragraph 5.2.6/ page 17)
3.3.2 TESTING EQUIPMENT – MEASURING INSTRUMENTS DESCRIPTION
EasyDur , AURA 30
MetroCal / M3-1202-014
REG. NBR 28727
PASS
for termination rods, earth lead-in rods
dimensions – and down conductors) or -
Cross Table. Diameter: 16 mm ≥ 15 mm.
sectional area
Tables are presented at
APPENDIX B, page11 of the
report.
PASS
a good visual appearance. No
Salt mist
After the test, the specimens shall
satisfy the following criteria: 177b corrosion of parent metal,
test deformation or change of dimensions
• Electrical resistance over a 100 177c
of the specimens was observed.
mm length shall not exceed the
value measured before the tests by Following to the test and after
more than 50%. removal of superficial corrosion
• The specimens shall be of products the specimens had a good
good visual appearance and have appearance, no change of mass or
no rough edges or burrs alterations or change in the
mechanical properties appeared.
throughout their length
The number of corrosion distribution
Ηumid • The base metal of specimens
177a
PASS
that is, pits, cracks, blisters,
sulphurous shall not exhibit any visual according to ISO 10289:1999 was
177b
atmospher corrosive deterioration when within the rating 9 (0,1%).
e treatment inspected with normal or corrected 177c
vision without magnification. 100
Recorded Electrical resistance
mm from both ends of the values, over a distance of 100 mm,
specimens are excluded from Before and after the completion of
inspection. environmental tests, were not
different than 50%.
Rafter≤1.5×Rbefore.
The specimens are deemed to
177d The maximum electrical resistivity
Electrical
resistivity
have passed the test if they comply
177e
corrected at 20oC was lower than the PASS
with the requirements of table 4 maximum value stated in table 4 of
test (Appendix B) 177f the standard (0.018 μΩm).
Electro-
N/A
magnetic Products covered by this standard are, in normal use, passive in respect of
capability electromagnetic influences (emission and immunity)
(EMC)
The tests were successful and the results are in the range of limits set by the standard.
NOTE: The following products are made from the same raw materials, have the same
properties and follow the same manufacture process, as tested CT10C:
• Copper Taper Air Rod, L=500 mm – CT50C.
• Copper Taper Air Rod, L=300 mm – CT30C.
The undersigned acknowledge they have reviewed the Test report 177 - Copper
Taper Air Rod – CT10C Test Report and agree with the approach it presents. Changes
to this Test Report will be coordinated with and approved by the undersigned or their
designated representatives.
(mΩ) (mΩ)
R177a 0.0090 0.0092
R177b 0.0091 0.0095
R177c 0.0088 0.0089
Testing equipment used: MEGGER, Type DLRO 10Χ, S/N 080308/3961 Τ0 = 15.3 oC, T1 =12.6 oC.
Resistance (μΩ)
Resistance RT2 𝑹×𝒂
Specimen Corrected at 𝝆 = (μΩm)
(μΩ) 𝒍
20 oC
Specimen 177d
Specimen 177e
Specimen 177f