Professional Documents
Culture Documents
2CV_MX3
Centrifugal
Compressor System
Topics
Inlet (ICFM)
Actual Head Plot
Accounts for Energy
LOSSES in a real
compressor.
PSIA
Inlet (ICFM)
Useful operating range
The actual
operating range is
limited.
Surge Choke
Too low of a flow
in a compressor
PSIA
IV = TL
BV modulating
Flow
Surge Terminology in CENTAC
Diffuser Vanes
INGERSOLL-RAND
Condensate System
•Removes condensate from the
compressed air
•Inlet air contains water vapour which
condenses to form liquid water when air
is cooled after compression
•Minimized condensate carrying over
into the next stage
PNLD PNEUMATIC NO LOSS DRAIN
NO LOSS DRAIN TRAPS USED IN FIELD
Damage Parts when auto drain traps failed and completely choke:
Note: This pictures was taken in SOVIGAZ Vietnam when operators did not service
the auto drain traps for one year of running and warranty don’t cover parts failed
due to poor maintenance by customer
Air Filter Assembly
Filter dust, dirt, carbon and
any foreign object before
clean atmospheric air is
compressed
IGV
1st Stg 2nd Stg 3rd Stg
CV
To System
BV
Silencer CENTAC
To atmosphere
CENTAC
Instrument Air
system
INSTRUMENT AIR SYSTEM
IA to IV & BV with
Isolation Valve pressure range 65
– 120 Psig
Instrument Air
Supply
Pressure
Regulator
Instrument Air System
Comp#2
Comp#3
Comp#4
Comp#5
Comp#6
CUSTOMER
Comp#7
INSTRUMENT AIR SYSTEM
IA START UP COMPRESSOR SYSTEM WITHOUT
AD
comp INSTRUMENT AIR
Comp#8 Comp#1
Comp#3
IA pressure
Comp#4 regulator &
STEP 1; Close IV/BV
instrument air isolation
valve IV/BV and valve
pressure Comp#5
regulator of seal
air on comp 1 to
7 while keeping
the comp 8
Comp#6
instrument air CUSTOMER
valves open.
Also close the Comp#7
INSTRUMENT AIR SYSTEM
valve at main
header
IA START UP COMPRESSOR SYSTEM WITHOUT
AD
comp INSTRUMENT AIR
Comp#8 Comp#1
Comp#3
IA pressure
Comp#4 regulator &
STEP 2; Test IV/BV
run the IA isolation
compressor and valve
Refrigerated air Comp#5
dryer and
monitor the IA
pressure must
have minimum
Comp#6
of 65 Psig to CUSTOMER
IV/BV pressure
gauge of Comp Comp#7
INSTRUMENT AIR SYSTEM
8
IA START UP COMPRESSOR SYSTEM WITHOUT
AD
comp INSTRUMENT AIR
Comp#8 Comp#1
Comp#3
IA pressure
Comp#4 regulator &
STEP 3; Test run IV/BV
the Comp 8 and isolation
load test then valve
monitor the system Comp#5
pressure in CMC
display until
pressure reached
Comp#6
to minimum of 65
Psig CUSTOMER
Comp#7
INSTRUMENT AIR SYSTEM
IA START UP COMPRESSOR SYSTEM WITHOUT
AD
comp INSTRUMENT AIR
Comp#8 Comp#1
Instrument air
Comp#2 supply of Main
header valve
Comp#3
IA pressure
Comp#4 regulator &
STEP 4; Open IV/BV
the IA valve of isolation
main header valve
Comp#5
Comp#6
CUSTOMER
Comp#7
INSTRUMENT AIR SYSTEM
IA START UP COMPRESSOR SYSTEM WITHOUT
AD
comp INSTRUMENT AIR
Comp#8 Comp#1
Comp#3
IA pressure
Comp#4 regulator &
STEP 5; Open IV/BV
the IA pressure isolation
regulator and valve
isolation valve Comp#5
of Comp 2 to 8
then test run &
load test one
compressor at
Comp#6
the time until all CUSTOMER
compressors
are running Comp#7
INSTRUMENT AIR SYSTEM
loaded
IA START UP COMPRESSOR SYSTEM WITHOUT
AD
comp INSTRUMENT AIR
Comp#8 Comp#1
Comp#3
IA pressure
Comp#4 regulator &
STEP 6; Enable IV/BV
remote Switch on isolation
all compressors valve
and Reset the Comp#5
CEM to monitor
the compressor
system from CEM
Comp#6
CUSTOMER
Comp#7
INSTRUMENT AIR SYSTEM
Inlet Valve - Butterfly
A non-contacting
vibration probe is
mounted in each plain
bearing
The vibration probe
Vibration Transmitters
measures the radial
vibration of each rotor
assembly
The probe is connected
to a vibration transmitter
for protection and
readout
Lubrication
System
Pre-Lube Pump Running in
Lubrication system
Oil Filter PRV
Oil Mixing
Valve
Oil Cooler X 2
1st/2nd
Stage Driver
Main Oil pump Demister
Assembly
Prelube
pump &
Oil level
motor
Gauge
PRV Heater x1
Oil Reservoir
Lubrication system
Oil Filter PRV
Oil Mixing
Valve
Oil Cooler X 2
1st/2nd
Stage Driver
Main Oil pump Demister
Assembly
Prelube
pump &
Oil level
motor
Gauge
PRV Heater x1
Oil Reservoir
Demister Assembly
Demister are
design to trap
vaporize oil fumes
and mist and
condense it back to
liquid oil
Oil Reservoir Heater
Oil reservoir heater are
provided to heat the oil in
the reservoir to preset
temperatures
If oil temperature is too
low, condensation occurs
and water formed in the oil
1 heater is installed in the
reservoir
Work in conjunction with
built in thermostat
Oil Pressure Relieve valve
Pressure relief
valve to control oil
pressure going into
the bullgears
Typically adjusted
to 25 to 35 psig
Adjustment
From pump
To reservoir To bullgear
Thermostatic Expansion Valve
To provide proper
injection temperature
to the compressor
bullgear assemblies
105-115degF 95degF
140degF
Thermostatic Element
Oil Filter Assembly
Oil filtration consist of a dual
oil filter assembly with manual
valve to select which filter to
use or standby.
Oil filter are used to trap
unwanted particles in the oil
system
10 micron filter element
Prelube Pump and Motor
Allow oil circulation
when control power
is “on” and machine
is not running
Is driven by an
electric motor
Main Oil Pump
Circulate oil when the machine is
running
Driven by the bullgear
Main Oil Pump
Water in
CENTAC®
MicroController
Topics
• Provides control
functions of the
compressor and also
monitors critical
instrumentations
• Located inside the
Control panel
Base Control Module (BCM)
• Analog Inputs
• Analog Outputs
• Digital Inputs
• Digital Outputs
• OUI (RS232)
• Network (RS485)
• Current Input
• Fuses
• Battery
BCM – Fuses & Battery
• Fuses (5X20MM, 1.5 Amp GMA Fast Blow)
• F100 - For BCM CPU card. (If blows call for service)
• F101 - For OUI
• F102 - For Analog Inputs/Outputs
• F103 - For Digital Inputs
• Battery (Tadiran TL-5101 3.6V 1/2AA Lithium)
– 10 Year Life expectancy
• Event Log
• Hours
• Starts
• Date - Time
• Non-Essential Parameters
BCM – Fuses & Battery
Operator User Interface (OUI)
• An interface between
user and the controller.
Display to provide
readout of all information
from the BCM and
keypad to allow scrolling
through the different
menu available and
changing setpoint and
control the machine
• Located on front panel
door
• Black Bezel Cover for
NEMA 4 Rating
Operator User Interface (OUI)
• 240 X 128
Graphical LCD
Screen
• Touch Pad
Overlay
– Acknowledge
– Reset
– Start
– Stop
– Load
– Unload
– Edit/Enter
– Navigational
– Contrast
Universal Communication Module
(UCM)
• Used for external
communications with
system such as PLC,
SCADA or BAS, PC &
Software
• Support
communication protocol
such as RS422/RS485
Modbus, and Allen
Bradley DF1
• Located inside the
control panel
Topic 2
Control Mode of
Operation
Control Modes
–Modulate
–Auto-Dual
Manual Mode
Manual Mode is operate by user
or operator manually by switching
to load then adjust the bypass
valve gradually to close until the
system pressure reach the set point
X
pressure
Inlet valve will start to throttle
from 100% until it reach the surge
line depending on operator’s
setting on bypass valve
Manual Mode basically using
for testing the CENTAC minimum
and maximum performance
Modulate Control
Modulate Control
Characteristics
–Constant Pressure
Discharge
–Unused (wasted)
Bypass Air
–Compressor Never
Unloads
Auto-Dual Control
Auto-Dual Control
Characteristics
–Provides Useful Inlet Valve
Throttle Range
–Reduced Cycling of
Machine
–Allows Compressor to
Unload for Energy Savings
–Best of Both Worlds -
Modulation and
Load/Unload or two steps
–Adjustable Unload Point
and Timer
Topic 3
Compressor
Operating States
Compressor Operating States
• The different operating states dictates the control
of the inlet and bypass valves
• Waiting • Loaded
• Not Ready• Full load
• Ready • Max load
• Starting • Unloading
• Loading • Unloaded
• Minload • Coasting
Waiting
• When power is re-
applied to
compressor
• To prevent machine
from restarting after
re-application of
power immediately
after power loss
• Allows proper oil
circulation before
the machine can be
re-started
Inlet Valve : 0% , Bypass Valve :
100% • Default is 120 secs
Not ready
• When there is an
trip or stop
command has been
issued
• Press reset to clear
the trip if the
problem had been
rectified
• E-stop is pressed
• Acknowledge button
–Silence the horn (if
available) or
acknowledge an
alarm
How to use the OUI - Reset
• Reset button -
clears all trip
latches. Required to
be pressed after a
trip condition to
restart the
compressor.
• If fault exist, cannot
reset till it is rectified
How to use the OUI - Start
• Unload button –
command to unload
the compressor.
• Upon pressed, the
“unload selected”
will be displayed at
bottom right
How to use the OUI – Enter/Edit
• Enter/Edit Key –
toggles the display
between
Navigational mode
or the edit mode
• Pressing it will
highlight the
setpoint that can be
altered and
pressing again will
confirmed and
saved the new
values
How to use the OUI -
• Navigational Keys –Navigational
arrow key for Up,
Right, Left and
down perform
differently
depending upon
current display
mode.
• During navigation
mode – keys used
to scroll through
different pages and
folders
How to use the OUI -
• During edit mode – Navigational
up and down key
used to change
setpoint values. Up
for + and down for –
• During edit mode –
Left and Right key
is use to scroll
between different
parameters that can
be altered in that
page
How to use the OUI - Contrast
• Contrast key –
changes the
contrast of the
backlight for graphic
LCD display
• Pressing this key
steps among the 16
contrast level and
when stepped to the
16th level, pressing
this key again will
returns to the 1st
level
Graphic Display
• 4 folders – System,
Info and Settings
• Status bar – shows
compressor
operating state and
status, control
location and folder’s
page number
• Page display
information such as
motor current,
pressure, date&
time and etc
Graphic Display – Status bar
• Compressor
operating states
• Control location :
– Remote
– Local
– Network
• Compressor status :
– Start Disable
– RMT – Stop
– Alarm/Trip
– E-stop
– Load selected
– Unload selected
Graphic Display – System folder
• 1st page always
display system
pressure, pressure
setpoint, motor
current, inlet &
bypass valve
position and date &
time
• This is the page
where the pressure
setpoint can be
changed
Graphic Display – System folder
• Analog input page
provides the actual
value for each stage
pressure, temperatures
& vibration and oil
pressure and
temperature
• Number of page
needed for such
display depends on the
total number of
information being
monitored
Graphic Display – System folder
• Digital inputs page shows
the current state of the
digital input to the
controller and the inputs
will vary depending on the
optional inputs installed:
– Starter feedback
– E-Stop, Start Disable
– Low water flow, low seal air
– Starter Aux voltage
– Motor protection trip
– Remote comm/function
enabled
– Remote Start/Stop
• Anti-surge settings
page allows the setting
of Maxload setting
(HLL), Minload setting
(TL), enable surge
3/11
indexing and setting of
surge increment and
also enabling of surge
absorber function
Graphic Display – Settings
folder • Surge happens 4 times
within 10 mins, the
compressor will unload
till reset by operator
• To enable the Surge
Absorber, check the
box
3/11
Graphic Display – Settings
folder • Surge Sensitivity
controls the sensitivity
levels of how surge is
detected.
• High value means high
sensitivity
3/11
Graphic Display – Settings
folder • Control parameters
page is used for
matching control
system to local
application
• PB, IT and D are
provided for both inlet
and bypass valves to
give controller precise
control over the valve
response to changes in
the air system
Graphic Display – Settings
folder • Control Mode Selection
page allows user to
select between two
standard control
modes, Modulate and
Autodual and also
manually controlling the
valves during
5/11 compressor setup
(commissioning or
troubleshooting)
Graphic Display – Settings folder
• Miscellaneous Settings
page allows user to set
the starting time, CT
ratio, inlet valve unload
position and setpoint
ramp rate
6/11
Graphic Display – Settings
folder • Alarm and Trip Settings
page provides a means
for changing the analog
health monitoring
values
• The number of
variables depends
upon the number of
compression stages
and optional input
Graphic Display – Settings folder
9/11
Graphic Display – Settings folder
Shows the Analog
Signal range and
actual values
Graphic Display – Service folder
17. Drain the drip legs on any other horizontal run of air piping.
18. Check for oil leaks. Correct as necessary.
19. Inspect for gasket / o-ring leakage.
20. Check for water leaks. Correct as necessary.
21. Open the control air line drip leg valve to remove any
moisture that may have collected.
22. Check the instrument air line filter. Drain any moisture,
which may have collected.
23. Check and record the oil filter differential pressure, if
available. Replace the filter element as necessary.
MAINTENANCE
Quarterly Maintenance
Quarterly Maintenance
Semiannual Maintenance
Annual Maintenance