Professional Documents
Culture Documents
net/publication/277313027
CITATIONS READS
0 542
4 authors:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Osama E. Gouda on 28 May 2015.
Abstract - Adaptive SPAR offers many advantages over Usually, this dead time is a fixed interval [7], and it can
conventional techniques. In the case of transient faults, the reflect the time margin for a phase to separate from the three
arcing extinction time can be accurately determined and in the phase line without losing stability in the system. It's obvious,
case of a permanent fault, breaker reclosure can be avoided. that stability margin can be increased as much as the dead
This paper describes, in some detail, the design of a new
Adaptive SPAR technique that extracts high frequencies
time reduced. The optimum solution to this problem is to
transients, from the CVT. The main case of study in this paper is adapt the dead time according to the information captured
the High Dam / Nagh Hamady, Nagh Hamady /Assuit 500 kV from the voltage and current signals associated with the faulty
double circuit transmission system in the Egyptian network. phase after tripping. Adaptive dead time schemes were
Fault scenario cases representing different fault locations, developed in literature in order to reduce the dead time using
inception angles, actual representation to secondary arc different techniques involving neural network [8, 9], fuzzy
characteristics, and with/without shunt reactor existence were logic [10], zero sequence voltage [11], and power of high
extracted from simulation work, and then verified through real frequency components in current signals [12]. In this paper, a
field records in that system. The outcome of this study indicates new SPAR algorithm is developed, where dead time is
that the proposed technique can be used as an effective means of
achieving an adaptive single pole auto reclosure scheme.
adapted according to the fault extinguishing information. The
proposed SPAR performs several functions, first it can
Index Terms - Transmission lines, Single Pole Auto Reclosure, discriminate between natures of faults, and secondly it can
Adaptive, Dead Time, Transient Fault, Permanent Fault. detect the instant of fault extinguished. Discrimination
between faults nature is important to decide closing or
blocking decisions, while fault extinguishing detection is
I. INTRODUCTION essential to ensure the instant of reclosing decision. Hence,
Operation of transmission networks faces a lot of obstacles the faulty phase will stay out of service for the least essential
regarding the trip/close decision on each line and its time required and then reclosed back-in to service without
consequences on the stability of the network [1, 2]. A unsuccessful AR attempt (i.e. close onto fault ). If permanent
successful Automatic close back-in decision (Auto Reclose) fault is detected, the other healthy phases will be tripped and
to a line can maintain the reliability of the network by the proposed SPAR will be blocked for further later closing
restoring power supply and obtain a secure decision by attempts.
avoiding the attempt to close onto fault. Also, Auto Reclosing Algorithms used in this SPAR depend on the harmonic
(AR) Dead Time affects the stability of the transmission line distortion analysis of the voltage waveform at the faulty line
and therefore the whole network. end terminal in order to perform the first function. The
second function is accomplished using transient waveforms
According to statistics shown in [3] Arcing faults represents based fault detection / location technique. The algorithms are
90 % of the transmission faults. Most of these faults are discussed in details and the Egyptian 500 kV network is used
transient faults that may extinguish by tripping the line. These for testing of the algorithms. Different fault scenarios where
faults may occur due to moisture in the early morning or subjected to the algorithms, in which different fault locations,
polluted insulators, which are common conditions in the inception angles, actual representation to secondary arc
Egyptian environment [4]. Therefore, AR is supposed to be a characteristics and with/without shunt reactor existence were
necessary application in order to improve reliability to extracted from simulation work, and then verified through
important transmission lines. Single pole Auto Reclosing real field records in that system.
(SPAR) algorithms can be programmed either in an
individual device or implemented as a function in a numerical II. TRANSIENT BASED SPAR ALGORITHMS
relay. Traditional SPAR Algorithms perform their main After the fault been detected, classified, and located through
function successfully; which is to reclose the faulty phase protection devices, a single phase tripping order is issued to
after specific predefine dead time, regardless the fault circuit breaker. In this instant, three scenarios can be expected
situation (extinguished or not) [5, 6]. regarding fault existence after breaker tripping action. The
614
first scenario is the extinguishing of the fault instantaneously V (F1 ) : Amplitude of fundamental frequency component of
by the trip decision, and no secondary arc exists but the
oscillation due to shunt reactor starts, if any. The first faulted line sending end voltage.
scenario represents the transient fault type. The second
scenario is the existences of fault after tripping decision, CCVT (Secondary CCVT (Transient
which extinguishing instant appears within specific time Voltage Signal) Voltage Signals)
period (i.e. fixed dead time). The second scenario represents
the long duration transient fault type. The third scenario, is Circuit
Breaker Data Window
the existence of secondary arc for specific time period (i.e.
(Trip)
fixed dead time), without the extinguishing instant
occurrence. The third scenario represents the permanent fault
type and any closing attempt to it will be unsuccessful. Protection 1st Sub Routine 2nd Sub Routine
(Phase Condition # 1 Condition # 2
The new SPAR algorithms have to perform two sub- routines Selection)
in order to reach successful reclose attempt. The first sub-
routine is to distinguish between existence and absence of
secondary arc. The second sub routine is to search for arc No
extinguish in case of secondary arc existence. The flow chart Cond. Cond.
shown in figure (1) describes the proposed SPAR algorithms
1> ε 1 2> ε 2
with details about its inputs, expected functions, and
implemented routines.
Transient Fault Yes
First: The analog inputs to the algorithms will be the
secondary voltage from the instrument transformers installed Action: Close
on the line under study and the transient voltage signals from t < DT
the communication tap of the coupling capacitive voltage
transformer (CCVT) [13]. The transmission protection No
Yes
devices should supply the algorithms with information, which
is phase selection. The digital inputs to the algorithms will be
provided from the circuit breaker regarding trip decision.
Permanent Fault
Second: the inputs will be in processing successive windows
Action: Block AND
of data. The information regarding the protection data, the Gate
secondary voltage from one end terminal will be fed to the
first sub routine in order to differentiate between existence
and non existence of secondary arc. This sub routine will
accomplish "Condition#1" status. In this sub routine, the Long Transient Fault
voltage inputs from both line ends processed using Discreet
Action: Close
Fourier Transform (DFT) in order to compute fundamentals
and odd harmonic components. The computed frequency
Fig. 1 Proposed SPAR algorithms flow chart.
components of voltage from one line end will be used to
calculate a discrimination quantity. The calculated THD % amplitude, from the faulty phase
sending end voltage (Shunt reactor location); can be used to
Since, it's well known that arcing faults voltages has a high determine the secondary arc existence when exceeding
percentage of harmonics, and after studying the voltage signal specific threshold. But due to the existence of different
of several fault scenarios, it was found that the percentage of threshold with the variation of system conditions related to
odd harmonics in ranges of (3, 5, 7, 9) are more obvious. shunt reactors existence/ non existence, another expression
Therefore, a good method of measuring the harmonics of will be derived from the first, which is difference of THD
secondary arc and separate it from the shunt reactor between faulty phase and other two healthy phases.
oscillation will be through using Total Harmonic Distortion
Percentage "THD %" [14]. THD_ diff =| (THD_ p1) − (((THD_ p2) + (THD_ p3)) / 2) |
(2)
2
∑ (V (Fn ) ) Where;
n = 3 ,5 , 7 ,9 THD _ p 1, THD _ p 2 THD _ p 3 : It is the Total Harmonic
THD % = × 100 (1)
V (F1) Distortion percentage for the faulty phase and the other two
healthy phases, respectively.
Where;
V (Fn ) : Amplitude of (n) harmonic component of faulted line THD _ diff : It is absolute difference in Total Harmonic
sending end voltage. Distortion percentage between he faulty phase and the other
two healthy phases.
615
If "THD_diff" didn't exceed specific threshold ( ε 1 ) then
"Condition#1" not specified, and fault is transient, and no
arcing exist. Therefore, Closing Decision can be
accomplished instantaneously. If "THD_diff" increases than
specific threshold ( ε 1 ) then "Condition#1" is satisfied, and
secondary arcing exist. Therefore, another subroutine will
work in parallel with the 1st subroutine to search for the arc
extinguishing instant. The transient input signal will fed to
the 2nd subroutine, in order to search for arc extinguishing
moment. The transient signal can detect any transient
disturbance within the line length and locate its position
Fig. 2 Egyptian 500 kV network.
according to the following equation [15].
Table I
L − (t b − t a)v Fault Scenarios used for testing the SPAR.
x= (3)
2
Ex Instant
Case D Ph Rec In feed Type
(msec)
Where;
x : It is the distance to fault from the sending end of the line. 10
1 A Yes Normal 1 0 – 100
L : It is the line length. %
616
fault). Finally, a validation process is presented in this study, 6000
T ran sien t CC V T S ig n al (V )
0
discussed above, a comprehensive study for voltage and
transient signals corresponding to different fault types and -2000
system conditions is done. Figures (3, 6) shows the sending
end voltage signal for cases 1 and 3 respectively, while -4000
breaker control circuit to produce trip decision, which appears Time (sec)
at the instant 0.2 seconds as the 2nd disturbance. It's obvious Fig. 5 Transient Voltage signal for transient fault on Phase "B", located at
10% apart from line sending end, with reactor absence.
from the transient signals that no transient signals appear
afterwards, and also the shunt reactor oscillation is shown 150
SPAR close decision must not be issued after the trip time
instant instantaneously, in order to leave some delay time 50
Sending End Voltage (V)
60
-150
40 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Sending E nd V oltage (V)
Time (sec)
20
Fig. 6 Sending End secondary Voltage for transient fault on Phase "B",
0
located at 10% apart from line
-20 sending end, with reactor absence.
-40
-60
Case 7 show a long duration transient fault type, where the
-80
transient signal, and the sending end secondary voltage signal
-100
are shown in figures (7, 8), respectively. As shown in figure
0 0.1 0.2 0.3 0.4
Time (sec)
0.5 0.6 0.7 0.8 0.9
(7), the signal starts at 0.25 seconds (i.e. after the breaker trip
Fig. 3 Sending End secondary Voltage for transient fault on Phase "A", action by 50 msec), and a third disturbance appears with high
located at 10% apart from line sending end, with reactor existence. magnitude at 0.67 seconds from the start of the simulation
1.5
x 10
4 time. Hence, long duration transient fault occurs, where
secondary arc exist and extinguished at the 3rd disturbance
1
time.
Figures (9, 10) show the transient signals and sending end
secondary voltage for case 10, which represent permanent
Transient CCVT Signal (V)
0.5
617
100
20
80
15
10 60
5 40
Transient CCVT Signal (V)
-5 0
-10 -20
-15 -40
-20 -60
-25 -80
-30 -100
0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Time (sec) Time (sec)
Fig. 7 Transient Voltage signal for long duration transient fault on Phase "C", Fig. 10 Sending End secondary Voltage for Permanent fault on Phase "C",
located at 90% apart from line sending end, with reactor absence. located at10% apart from line sending end, with reactor existence.
150
50
Case1
45 Case3
100 Case7
40 Case10
35
50
Sending End Voltage (V)
30
0
THD % 25
20
-50
15
10
-100
5
0
-150
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Time (sec)
5 10 15 20 25 30 35 40 45
Data Window ( 0.5*Cycle )
Fig. 8 Sending End sending Voltage for long duration transient fault on Fig. 11 SPAR THD % results.
Phase "C", located at 90% apart from line sending end, with reactor absence.
30 4 - - 1 7
20
5 1 37 36 38
6 5 36 34 36
Transient CCVT Signal (V)
10
7 1 39 36 38
0
8 3 (48) End - -
-10
9 1 (48) End - -
-20
10 8 (48) End - -
-30
Table (II) shows conditions 1 and 2 for all the 10 simulated
-40
0.3 0.4 0.5 0.6 0.7 0.8
cases described in table (I). Each condition is specified by its
Time (sec)
start time and end time of the condition by the moving data
Fig. 9 Transient Voltage signal for Permanent fault on Phase "C", located window number, which is illustrated in figure (11).
at10% apart from line sending end, with reactor existence.
618
Table III conditions (1 and 2) didn't exist. The proposed SPAR
SPAR Functions results for all simulation cases.
decision was a close decision, and the fault type was transient
SPAR Action as shown in figure. As shown in table (IV) detects the time
Adaptive DT
Case
Fault
duration for the close action which is 390 milliseconds after the record
Type start time. The breaker trip at 130 milliseconds after the
Time (msec)
Type
(msec) record start time, and the SPAR algorithms starts after 100
1 1 460 1 260 milliseconds from the trip order, So, if the transient fault
conditions is specified, therefore, the SPAR will give a close
2 1 460 1 260
within 60 milliseconds and the total adaptive dead time as
3 1 460 1 260 shown in table will be 260 milliseconds from the trip order.
4 1 460 1 260
300
5 1 660 2 460
6 1 640 2 440 200
10 2 740 3 540
-100
Table (III) show the results for the fault type, SPAR action,
and SPAR action time, respectively, for all the 10 simulated -200
Fig. 12 Transient Voltage signal (recorded case) for Transient fault on Phase
respectively. As shown in figures the cases are well identified "B", located at 50% apart from line sending end, with reactor existence.
to their fault types and correct SPAR actions and the time
where the action is taken is recognized in milliseconds. 8000
Table (III), shows the SPAR action type and proposed time in 6000
time, and the SPAR algorithms starts after 100 milliseconds 2000
table will be 260 milliseconds from the trip order. Long -4000
duration transient faults, will have a close when it reaches it's
extinguish condition as shown in cases 5, 6, and 7. Permanent -6000
faults will give a block decision after the corresponding fault -8000
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
type conditions satisfied and passed the maximum allowed Time (sec)
dead time of the system, which is this simulation cases is 370 Fig. 13 Sending End Primary Voltage signal (recorded case) for Transient
fault on Phase "B", located at 50% apart from line sending end, with reactor
milliseconds from the start of algorithms work or 470 existence.
milliseconds from the trip order.
25
V. ALGORITHMS TESTING ON REAL FIELD RECORDS THD
Condition 1
Condition 2
Validation through the field record is required in order to 20
THD %, Condition 1, Condition 2
619
Recorded Fault Case SPAR Function "Fault Type", "Action", "Action Time" [3] Y.G. Paithankar, S.R. Bhide, "Fundamentals of Power System
results. Protection ", Prentice-Hall of India Private Limited, New Delhi,
2003.
SPAR Action [4] M. Khalifa, A. El-Morshedy, O. E. Gouda, S. E. D. Habib, "A
Fault Adaptive DT duration new monitor for pollution on power line insulators. II. Simulated
Time Type (msec) field tests", IEE Proceedings C Generation, Transmission and
Type Distribution, Volume 135, Issue 1, Jan 1988 P.24 – 30.
(msec)
[5] "REXA 101, User’s Guide", Link: www.abb.com.
1 390 1 260 [6] "LFAA 101, 102", Link: www.areva-td.com/protectionrelays.
[7] S. P. Ahn, C. H. Kim, R.K. Aggarwal, A. T. Johns, “An
alternative approach to adaptive single pole auto-reclosing in high
voltage transmission systems based on variable dead time
The agreement between the tasks goals and the algorithms control”, IEEE Transaction on Power Delivery, Vol. 16, No. 4,
pp. 676-686, October 2001.
results, prove the feasibility of the proposed SPAR to be used [8] M. Jannati, B. Vahidi, S.H. Hosseinian, H.R. Baghaee, “A new
in any fault case or system condition. Thresholds and dead adaptive single phase auto-reclosure scheme for EHV
time must be provided after a load flow, short circuit and transmission lines” , Proceedings of 12th International Middle-
transient stability studies to the line under study before SPAR East Power System Conference, (MEPCON 2008), Egypt, pp.
203-207, March 2008.
installation. It's preferred to monitor and capture data through [9] M.A. El-Hadidy, D.H. Moustafa, A.S. Attia, “Using neuro-
high resolution and using higher sampling rate devices (i.e. wavelet technique for adaptive single phase autoreclosure of
fault recorders, PMU's) in order to reach the specific goals transmission lines”, Proceedings of the 39th International
accurately. Universities Power Engineering Conference, (UPEC 2004), UK,
Vol. 1, pp. 684-688, September 2004.
VI. CONCLUSIONS [10] X. Lin, P. Liu, “Method of distinguishing between instant and
permanent fault of transmission lines based on fuzzy decision,”
This paper proposes new algorithms for Adaptive SPAR IEEE Catalog No. 98EX137, pp. 455-460, 1998.
technique that extracts high frequencies transients, and [11] S. Jamali, A. Parham, "One Terminal Digital Algorithm for
Adaptive Single Pole Auto-Reclosing Based on Zero Sequence
secondary voltage waveform from the CVT. The new Voltage", Iranian Journal of Electrical & Electronic Engineering,
Adaptive SPAR can differentiate between permanent and Vol. 4, 78 No. 3, July 2008.
transient faults during the dead time period. The system can [12] Z. Q. Bo, R. K. Aggarwal, A. T. Johns, “A novel technique to
then, adapt itself to reduce the dead time and reclose in case distinguish between transient and permanent fault based on
detection of current transients,” Proceeding of 4th International
of transient faults, or trip the other two phases and blocking Conference on Advances in Power System Control and
the circuit breaker in case of permanent faults, respectively. Management, APSCOM-97, Hong Kong, pp. 217-220, November
1997.
The used transient signals from CVT proves the fault [13] F. S. Carvalho, S. Carneiro Jr., “Transient conditions in CCVTs
extinguishing detection process, since its well known by the outputs and their effects on the detection of traveling waves”,
high accuracy and speed in detection and location of transient Electric Power Systems Research, Vol. 76, No. 8, pp. 616-625,
May 2006.
disturbance within the line, without been affected with the [14] H. Khorashadi-Zadeh, Zuyi Li , "A Novel PMU-Based
common instrument transformer problems (i.e. Saturation, Transmission Line Protection Scheme Design", 39th North
and Ferro Resonance). American Power Symposium (NAPS '07), pp. 13 – 19, 2007.
The use of THD as a discriminator between the existence and [15] Z.Q. Bo, M.A. Redfern, G.C. Weller, "Positional protection of
transmission line using fault generated high frequency transient
non existence of the arcing phenomena helps to improve the signals", IEEE Transactions on Power Delivery, Vol. 15, No. 3,
SPAR decision by differentiating between fault arcing pp. 888- 894, Jul 2000.
phenomena and other harmonics oscillation due to shunt [16] L. Dube, MODELS in ATP, Language Manual,
reactor existence within the line under study. 1996.
It's available on:http://www.eeug.org/files/secret/MODELS
While traditional protection relays may easily mal-operate [17] A.T. Johns, R.K. Aggarwal, Y.H. Song, "Improved techniques for
modelling fault arcs on faulted EHV transmission systems," IEE
due to the oscillations resulted from reactor existence, the Proceedings Generation, Transmission and Distribution, Vol. 141,
proposed adaptive SPAR succeeded to overcome this No. 2, pp. 148-154, 1994.
phenomena and successful achieve its main tasks. The new [18] The MathWorks Inc., Using MATLAB, 2007.
SPAR algorithms presented in this paper reduces the dead
time according to each fault case, and differentiate between
fault types in order to reach successful SPAR decisions, in
order to improve transmission system stability during
operation process.
REFERENCES
[1] F. Calero, D. Hou "Practical Considerations for Single-Pole-Trip
Line-Protection Schemes", SEL Technical Paper 6184, Link:
www.selinc.com.
[2] IEEE Guide for Automatic Reclosing of Line Circuit Breakers for
AC Distribution and Transmission Lines, IEEE Standard
C37.104. 2002.
620