= 250 MPa (TABLE 5)
410 MPa

Concrete
(1400 × 1400 × 600)
footing

= geometrical similar
= 1400 ×
area

1400 ×
= = 819635 mm2
585

= 25 MPa (concrete)

= 600 × 280 =
Grout
168,000 mm2

= 60 MPa

= =
Anchor bolts 4 × M24 bolts, Grade 4.6, 30 dia. holes in plate
113 kN 64.3 kN

6 mm fillets, E48/W50X
Welds = 0.978 kN/mm
electrodes

CASE 1 AXIAL COMPRESSION AND SHEAR

DESIGN CHECK NO. 1 Design capacity for bearing on concrete support

Concrete ≤ = 4345 kN

≤ = 3415 kN

Hence, = 3415 kN > = 90 kN COMPLIES

Grout ≤ = 4720 kN

> = 90 kN COMPLIES

DESIGN CHECK NO. 2 Design capacity of steel base plate

= 0.5 (550 – 0.95 × 533) = 21.8 mm

= 0.5 (230 – 0.80 × 209) = 31.4 mm

=
= 0.25
83.4 mm

= 533 + 209 = 742 mm

TABLE 7 =2 = 2.13

1 of 2 26/02/2021, 12:57 pm
Design Guide 7 - Pinned Based Plate Connections - 11 DESIGN EX... https://asi.tekreader.com/files/design-guide-7-pinned-based-plate-conne...

= minimum of
Concrete (CHECK NO. 1)

= minimum of [34.4; 27.0] = 27.0 MPa

= = 0.0322

= minimum of = min [0.193; 1.0]

= 16.1 mm

=
= max(21.8; 31.4; 16.1)
31.4 mm

=
=
5775 kN

> = 90 kN COMPLIES

DESIGN CHECK NO. 3 Design capacity of weld at column base

Column base cold sawn cut so prepared for full contact—no transfer of compression through weld

= 30 kN

assume only web welds resist , welds full length along both sides of web excluding fillets

= 2 × (530 – 2 × (15.6 + 14.0))

= 942 mm

2 of 2 26/02/2021, 12:57 pm