Professional Documents
Culture Documents
Revised Battery Sizing
Revised Battery Sizing
Projects
Customer Vertiv
Consultant
Application Back up for UPS
LOAD RATING 50 KVA
BATTERY TYPE 12 V
BACKUP TIME 30 MIN
INVERTER EFFICIENCY 95 %
END CELL VOLTAGE 10.50 V
POWER FACTOR 0.8
NO. OF Battery 32
Battery Cut off Volt 336 V
TEMPERATURE DERATING FACTOR
1
27 Deg C
AGING FACTOR 1
DESIGN MARGIN 1
K factor 1.44
CALCULATION: -
AH Capacity 180