You are on page 1of 1

BATTERY CALCULATION SHEET

Projects
Customer Vertiv
Consultant
Application Back up for UPS
LOAD RATING 50 KVA
BATTERY TYPE 12 V
BACKUP TIME 30 MIN
INVERTER EFFICIENCY 95 %
END CELL VOLTAGE 10.50 V
POWER FACTOR 0.8
NO. OF Battery 32
Battery Cut off Volt 336 V
TEMPERATURE DERATING FACTOR
1
27 Deg C
AGING FACTOR 1
DESIGN MARGIN 1
K factor 1.44
CALCULATION: -

IDC = UPS KVA X 1000 X PF


Inv Efficiency X Nos of battery x ECV

IDC = 50 X 1000.00 X 0.80


0.95 X 32 x 10.50

IDC = 125.313283208 Amp

IDC with factor= 125 x 1 = 125 Amp

AH Capacity 180

Battery AH selected : - 180AH Nos of battery = 32


Battery type selected : - 6EL180
Make :- EXIDE