You are on page 1of 3

Time delayed overcurrent TOC

protection
1MRK 580 020-BEN
Page 1
Issued: December 2000
Status: New
Data subject to change without notice

Features • Definite time characteristic • Very low overreach of the measuring ele-
ments
• Phase segregated output starting signals
• Wide current setting range
• Special functional input for blocking the trip
signal only • Optional time delayed residual current
function

Application The time delayed overcurrent protection, activated under fuse failure conditions which
TOC, operates at different system conditions has disabled the operation of the line distance
for currents exceeding the preset value and protection.
which remains high for longer than the delay
time set on the corresponding timer. The The time delayed residual overcurrent protec-
function can also be used for supervision and tion is intended to be used in solidly earthed
fault detector for some other protection func- systems. The time delayed residual overcur-
tions, to increase the security of a complete rent protection is suitable as back-up protec-
protection system. It can serve as a reserve tion for phase to earth faults, normally tripped
function for the line distance protection, if by operation of the distance protection. The
protection function can also serve as protec-
tion for resistive phase to earth faults.

Functionality The current measuring element continously The input signal BLOCK blocks all func-
measures the current in all three phases and tions.The input signal BLKTR blocks both
compares it to the set operate value IP>. A fil- trip signals TRP and TRIP.
ter ensures immunity to disturbances and dc
components and minimizes the transient As the time delayed residual overcurrent
overreach. If the current in any of the three function is integrated together with the time
phases is above the set value IP>, a common delayed phase overcurrent function some sig-
start signal STP and a start signal for the nals are common: TOC--BLOCK which
actual phase(s) are activated. The timer tP is blocks both functions and TOC--TRIP which
activated and the phase overcurrent trip sig- is a common trip from both functions. There
nal TRP is activated after set time. is also a separate trip signal TOC--TRN
which is a separate trip from the time delayed
The TOC current function block can also con- residual overcurrent function.
tain a time delayed residual current function.
Both the phase overcurrent and the residual If the residual current is detected to be larger
current function (if included) can activate the than the setting value TOC--STIN and the set
trip signal TRIP. time has elapsed, a trip is activated at the out-
signals TOC--TRIP and TOC--TRN
Time delayed overcurrent protection TOC
1MRK 580 020-BEN
Page 2

Function block
TOC-- TOC--
TOC TOC
BLOCK TRIP BLOCK TRIP
BLKTR TRP BLKTR TRP
TRN STP
STP STL1
STL1 STL2
STL2 STL3
STL3
STN xx00000681.vsd

xx00000197.vsd Figure 2: TOC function block phase overcurrent ele-


ment, ordering number
Figure 1: TOC function block including all options, 1MRK 001 457-BA
ordering numbers 1MRK 001 457-BA,
1MRK 001 456-XA

TOC--
TOC
BLOCK TRIP
BLKTR TRN
STN
xx00000709.vsd

Figure 3: TOC function block residual overcurrent


element, ordering number
1MRK 001 456-XA

Input and output Table 1: Input signals for the OCP (OCP--) function block
signals Signal Description
BLOCK Block of the phase overcurrent function. It also blocks the
residual overcurrent function if it is included in the TOC cur-
rent protection.
BLKTR Block of trip from the overcurrent function. It also blocks the
trip from the residual overcurrent function if it is included in
the TOC current protection.

Table 2: Output signals for the TOC (TOC--) function block


Signal Description
TRIP Trip by time delayed phase overcurrent function. Trip also by
time delayed residual current function if it is included in the
TOC protection function.
TRP Trip by time delayed phase overcurrent function
TRN Trip by the time delayed residual overcurrent protection
STP Start phase overcurrent
STL1 Start phase overcurrent, phase L1
STL2 Start phase overcurrent, phase L2
STL3 Start phase overcurrent, phase L3
STN Start of the time delayed residual overcurrent protection
Time delayed overcurrent protection TOC
1MRK 580 020-BEN
Page 3

Technical data Table 3: TOC - Time delayed overcurrent protection


Function Setting range Accuracy
Operate current I> Phase measuring ele- (10-400) % of Ir in +/- 2.5 % of Ir at I ≤ Ir
ments steps of 1 % +/- 2.5 % of I at I >Ir
Residual measuring (10-150) % of Ir in +/- 2.5 % of Ir at I ≤ Ir
elements steps of 1 % +/- 2.5 % of I at I >Ir
Time delay Phase measuring ele- (0.000-60.000) s in +/- 0.5 % of t +/- 10
ments steps of 1 ms ms
Residual measuring (0.000-60.000) s in +/- 0.5 % of t +/- 10
elements steps of 1 ms ms
Dynamic overreach at τ< 100 ms - <5%

Manufacturer
ABB Automation Products AB
Substation Automation Division
SE-721 59 Västerås
Sweden
Tel: +46 (0) 21 34 20 00
Fax: +46 (0) 21 14 69 18

You might also like