You are on page 1of 1

IMPORTANT:

1 1.1 1.2 2 3 4 4.6


This drawing is the copyright © of chapmanbdsp and shall
not be copied or reproduced without permission.

This drawing shall not be scaled.

Unless stated otherwise, all dimensions are in millimetres.

Where applicable, all dimensions shall be checked by the


contractor onsite, prior to commencement of any works.

This drawing shall be read in conjunction with all other


drawings and the services specification document(s).

All materials and workmanship shall conform with the


relevant British & European Standards, Specifications and
Codes of Practice.

KEY PLAN: Q
LIFT
N

STAFF REST
AREA SUB ENT. LOBBY
0B01 -

Power for LIFT


Coffee Machine
Kettle
Blender, Etc.

PANTRY COUNTER BUFFET COUNTER

Cleaners
MW REF.
B
DB.ZUMA.B1.01

SMDB.ZUMA.B1.01

IT ROOM

FEMALE MALE
B.1 STAFF TOILET
Bench
STAFF TOILET
Changing

Shower

LINEN ROOM

Bench
Laundry
trolley

Changing
FOH OFFICE
(4 Desks)

Shower
B.2 Laundry
trolley

BOH CORRIDORS
0B02 --

BOH OFFICE CHEF OFFICE 00 12-12-2022 Schematic Design Issue DC


(3 Desks) (2 DESKS)
C Rev Date Description Appr
DB.ZUMA.B1.02 910X460 910X460
1070X460

Client
910X460

CR01
910X460

CHILLER
+2°c
910X460

910X460 1070X460 1070X460


1070X460 1070X460
910X460

C.1

ICE
1070X460 CR02 FLAKE

BEVERAGE
CHILLER
910X460 +2°c
SUSHI
910X460

PROJECT MANAGERS:
910X460

FREEZER
(LIG FREEZER)

FISH
FLAKE PREP
TFIL

ICE MACHINE
910X460 910X460
910X460 910X460 P
R
E
P
C.2 CUBE
TFIL

ICE MACHINE
910X460 910X460 910X460 910X460

MEAT
PREP

1070X460 100A 3-PH ISOLATOR FOR


1070X460
POWER SUPPLY (BY
POULTRY
PREP
LANDLORD) TO SERVE
SMDB.ZUMA.B1.01
VACUUM
PACKING

1070X460 1070X460 1070X460


3 DESIGN ARCHITECT:
D 200A 3-PH ISOLATOR FOR
3
1070X460 1070X460 1070X460 910X460
POWER SUPPLY (BY
2/1GN 2/1GN
LANDLORD) TO SERVE
910X460

CR04
FREEZER
-18°c ESMDB.ZUMA.B1.01
1070X460 1070X460 SORTING
500x150mm
TABLE
ELEC RISER
BOH (KITCHEN)
1070X460 1070X460
DB.ZUMA.B1.03
0B02 BY OTHERS

CR03 VEGETABLE
RISE UP TO
CHILLER
2/1GN 2/1GN
+2°c
WASH
GROUND
AND FIRST
1070X460 1070X460 1070X460
FLOOR

E MEP CONSULTANT:

GENERATOR
ROOM
www.chapmanbdsp.com info@chapmanbdsp.com
CHARCOAL
STORE

ATS.ZUMA.B1.01

ESMDB.ZUMA.B1.01 LEGENDS:-
SYMBOL DESCRIPTION

1 NEW SINGLE PHASE ISOLATOR

3 NEW THREE PHASE ISOLATOR


Status
NEW G.I CABLE TRUNKING FOR POWER SERVING SCHEMATIC DESIGN
KITCHEN EQUIPMENT AT HIGH LEVEL
NOTES:-
Project
NEW G.I CABLE TRUNKING FOR POWER SERVING
1. ALL ELECTRICAL CONTAINMENT AND OTHER EXTRANEOUS METAL WORKS TO
KITCHEN EQUIPMENT AT HIGH LEVEL
F BE ELECTRICALLY CONTINOUS BONDED IN ACCORDANCE WITH BS7671. ZUMA
NEW G.I CABLE TRUNKING FOR POWER AT HIGH Basement 1, Ground & First Floor, Plot 2.09
2. ELECTRICAL CONTRACTOR SHALL ALLOW FOR THE INSTALLATION OF LEVEL KFAD, KSA
PRE-MANUFACTURED BENDS, SETS, TEES, OPEN JUNCTIONS AND ALL OTHER
ASSOCIATED JOINTS, SUPPORTS AND ACCESSORIES TO FORM THE CABLE
NEW G.I CABLE TRUNKING FOR LIGHTING AT HIGH
CONTAINMENT . Drawing Title
LEVEL
3. BASE BUILD ISOLATORS PROVIDED BY THE LANDLORD WILL SERVE THE ZUMA
DEMISE NEW SMDBs - REFER TO PRELIMINARY ELECTRICAL LOAD SCHEDULE NEW G.I CABLE TRAY FOR POWER SERVING
FOR PANEL REFERENCES. KITCHEN EQUIPMENT AT HIGH LEVEL
Electrical Services
4. BASE BUILD ISOLATORS SHALL BE SHIFTED ABOVE THE ZUMA CEILING VOID
AND SHALL REMAIN CONNECTED TO EXISTING AND DEDICATED SMDB / MDB.
NEW G.I CABLE TRAY FOR POWER AT HIGH LEVEL
Basement 1
EXISTING CABLE MUST NOT BE CUT.
NEW G.I CABLE BASKET FOR DATA AT HIGH LEVEL Proposed Containment Layout
5. FIRE ALARM CABLING, LIGHTING CONTROL AND EMERGENCY LIGHTING
CABLING SHALL BE ROUTED IN NEW 25mm (MINIMUM) DIAMETER G.I. CONDUIT.
NEW G.I CABLE TRUNKING FOR POWER SERVING Drawn Engineer Checked Date origin
6. CONTRACTOR TO LIAISE WITH AV IT SPECIALIST FOR THE EXACT ELV KITCHEN EQUIPMENT (ESSENTIAL) AT HIGH LEVEL
CONTAINMENT REQUIREMENT I.E. SIZE, TYPE OF CONTAINMENT AND ROUTING.
MS MF DC OCT 2022
NEW SUB MAIN DISTRIBUTION BOARD Scale @A1 File/BIM ref
7. CONTRACTOR SHALL ALLOW FLEXIBLE CONDUIT IF THE FINAL CIRCUIT WIRING
TERMINATION POINT IS MORE THAN 3 METERS AWAY FROM THE DEDICATED
1:100 CAD FILE
NEW MOTOR CONTROL CENTRE BOARD
CABLE TRUNKING/TRAY/BASKET. SIZE OF THE FLEXIBLE CONDUIT SHALL BE Sheet number Revision
DISCUSSED AND AGREED WITH THE CONSULTANT
NEW FINAL DISTRIBUTION BOARD
00

You might also like