You are on page 1of 1

IMPORTANT:

1 1.1 1.2 2 3 4 4.6


This drawing is the copyright © of chapmanbdsp and shall
not be copied or reproduced without permission.

This drawing shall not be scaled.

Unless stated otherwise, all dimensions are in millimetres.

Where applicable, all dimensions shall be checked by the


contractor onsite, prior to commencement of any works.

This drawing shall be read in conjunction with all other


drawings and the services specification document(s).

All materials and workmanship shall conform with the


relevant British & European Standards, Specifications and
Codes of Practice.

KEY PLAN: Q
LIFT
N

STAFF REST
AREA SUB ENT. LOBBY
0B01 -

Power for LIFT


Coffee Machine
Kettle
Blender, Etc.

PANTRY COUNTER BUFFET COUNTER

Cleaners
MW REF.
B EMP

IT ROOM

FEMALE MALE
B.1 STAFF TOILET
Bench
STAFF TOILET
Changing

Shower

LINEN ROOM

Bench
Laundry
trolley

Changing
FOH OFFICE
(4 Desks)

Shower
B.2 Laundry
trolley

BOH CORRIDORS
0B02 --

BOH OFFICE CHEF OFFICE 00 12-12-2022 Schematic Design Issue DC


(3 Desks) (2 DESKS) EXIT Rev Date Description Appr
C
910X460 910X460
1070X460

Client
910X460

CR01
910X460

CHILLER
+2°c
910X460

910X460 1070X460 1070X460


1070X460 1070X460
910X460

C.1

ICE
1070X460 CR02 FLAKE

BEVERAGE
CHILLER
910X460 +2°c
SUSHI
910X460

PROJECT MANAGERS:
910X460

FREEZER
(LIG FREEZER)

FISH
FLAKE PREP
TFIL

ICE MACHINE
910X460 910X460
910X460 910X460 P
R
E
P
C.2 CUBE
TFIL

ICE MACHINE
910X460 910X460 910X460 910X460

MEAT
PREP

1070X460

1070X460

POULTRY
PREP
VACUUM
PACKING

1070X460 1070X460 1070X460


DESIGN ARCHITECT:
D
1070X460 1070X460 1070X460 910X460

2/1GN 2/1GN
910X460

CR04
FREEZER
-18°c

1070X460 1070X460 SORTING


TABLE

1070X460 1070X460 BOH (KITCHEN)


0B02 BY OTHERS

CR03 VEGETABLE
CHILLER WASH
2/1GN 2/1GN
+2°c

1070X460 1070X460 1070X460

E MEP CONSULTANT:

GENERATOR
ROOM
www.chapmanbdsp.com info@chapmanbdsp.com
CHARCOAL
STORE

NOTES:- LEGEND:
SYMBOL DESCRIPTION
1. NEW EMERGENCY LIGHT FITTINGS AND SIGNAGES SHALL BE 2W, LED EMERGENCY LUMINAIRE, SELF-CONTAINED,
SELF-CONTAINED AUTOMATICALLY MONITORED AND TESTED NON-MAINTAINED, RECESSED, WITH INDICATOR LED,
BY DEDICATED CONTROL SYSTEM WHICH SHALL BE INTERFACED 90MIN BATTERY BACK-UP, IP20 WITH DALI CONTROL
FOR MONITORING
WITH MAIN EMERGENCY LIGHTING CONTROL PANEL FOR BRAND : ABB (Seranga 2: CTSR2-DEA-M3) Status
FAULTS/STATUS AND BATTERY LOW CONDITION.
2W, LED EMERGENCY LUMINAIRE, SELF-CONTAINED,
SCHEMATIC DESIGN
NON-MAINTAINED, SURFACED/ RECESSED, WITH
2. ALL NEW EMERGENCY LUMINARIES SHALL BE PROVIDED WITH INDICATOR LED, 90MIN BATTERY BACK-UP, IP40, WHITE, Project
INTEGRAL 3 HOUR PACKS THAT SHALL INCLUDE BATTERIES, BRAND : ABB (Seranga 2: CTSR2-SEM3-BC1)
F CHARGERS, CHANGEOVER CONTACTS AND GREEN COLOURED ZUMA
INDICATING LED(S). LED(S) SHALL BE CLEARLY VISIBLE FROM 2W, LED EXIT SIGN, SELF-CONTAINED, MAINTAINED, Basement 1, Ground & First Floor, Plot 2.09
BELOW THE FITTING WHILE FITTING IS ILLUMINATED. EXIT
WALL MOUNTED WITH 90MIN BATTERY BACK UP WITH KFAD, KSA
STANDARD ARROW LEGEND, IP20, WITH DALI CONTROL
FOR MONITORING
3. NEW EMERGENCY LIGHTS SHALL BE CONNECTED TO BRAND : ABB (Movion for FOH and Weatherforce for BOH) Drawing Title
MONITORING LOOP WHICH SHALL BE TERMINATED TO THE
NEW PROPOSED EMERGENCY LIGHTING MONITORING PANEL. 2W, LED EXIT SIGN, SELF-CONTAINED, MAINTAINED, Electrical Services
MONITORING LOOP SHALL BE 2 CORED DALI. CEILING MOUNTED WITH 90MIN BATTERY BACK UP WITH
STANDARD ARROW LEGEND, IP20, WITH DALI CONTROL
FOR MONITORING Basement 1 -
4. ZUMA NEW EMERGENCY LIGHTING SYSTEM WILL BE BRAND : ABB (Movion for FOH and Weatherforce for BOH)
INTERFACED WITH THE TENANT FIRE ALARM SYSTEM TO Proposed Emergency Lighting Layout
ACTIVATE THE EMERGENCY LIGHTING UNDER FIRE ALARM EMP EMERGENCY MONITORING PANEL.
CONDITION. BRAND : ABB (Naveo Pro gateway)

EMERGENCY MONITORING LOOP


5. EXISTING BASE BUILD EMERGENCY LIGHTING FIXTURE WITHIN Drawn Engineer Checked Date origin
THE ZUMA DEMISE SHALL BE REMOVED AND HANDED OVER TO LOCAL NETWORK ELECTRICAL CIRCUIT MS MF DC OCT 2022
LANDLORD. Scale @A1 File/BIM ref
OUT OF SCOPE 1:100 CAD FILE
Sheet number Revision

00

You might also like