You are on page 1of 1

1

7.
6.
5.

8.
4.
L= 51 m; ∆V= 5,78 V; ∆V%=0,87 %

NOTAS:
SIN ESCALA

INVERSOR 3 - MPPT 1 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


STRING 22 - 16 MODULOS FV 535 Wp EMT50 mm

1
JA SOLAR JAM72S30 535/MR L= 34 m; ∆V= 3,85 V; ∆V%=0,58 %
INVERSOR 3 - MPPT 1 - ENTRADA 2 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
STRING 23 - 16 MODULOS FV 535 Wp EMT50 mm MPPT 1
JA SOLAR JAM72S30 535/MR L= 52 m; ∆V= 5,89 V; ∆V%=0,89 % 2
INVERSOR 3 - MPPT 2 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
EMT50 mm
INVERSOR 3 (MAESTRO)

STRING 24 - 16 MODULOS FV 535 Wp


3

JA SOLAR JAM72S30 535/MR L= 35 m; ∆V= 3,97 V; ∆V%=0,59 %


INVERSOR 3 - MPPT 2 - ENTRADA 2 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
MPPT 2

STRING 25 - 16 MODULOS FV 535 Wp EMT50 mm

D
D

2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K JA SOLAR JAM72S30 535/MR L= 24 m; ∆V= 2,72 V; ∆V%=0,41 %
EMT50 mm 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
DIAGRAMA UNILINEAL DE CORRIENTE CONTINUA

INVERSOR 1 - MPPT 1 - ENTRADA 1 INVERSOR 3 - MPPT 3 - ENTRADA 1


STRING 1 - 14 MODULOS FV 535 Wp L= 133 m; ∆V= 6,73 V; ∆V%=1,16 % STRING 26 - 16 MODULOS FV 535 Wp EMT50 mm

1
5

INSTALACIÓN A CONECTAR EN BAJA TENSIÓN.


JA SOLAR JAM72S30 535/MR JA SOLAR JAM72S30 535/MR L= 47 m; ∆V= 5,27 V; ∆V%=0,79 %
INVERSOR 3 - MPPT 3 - ENTRADA 2 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
MPPT 3

STRING 27 - 16 MODULOS FV 535 Wp EMT50 mm


6

2
2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K JA SOLAR JAM72S30 535/MR L= 49 m; ∆V= 5,5 V; ∆V%=0,83 %

MPPT 1

ANTES DE INTALAR CONSULTAR MANUAL DE LOS EQUIPOS.


INVERSOR 1 - MPPT 1 - ENTRADA 3 EMT50 mm INVERSOR 3 - MPPT 4 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K

INVERSOR 1 (ESCLAVO)
STRING 2 - 14 MODULOS FV 535 Wp L= 132 m; ∆V= 6,69 V; ∆V%=1,15 % STRING 28 - 16 MODULOS FV 535 Wp EMT50 mm
7

3
JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K JA SOLAR JAM72S30 535/MR
INVERSOR 1 - MPPT 2 - ENTRADA 1 EMT50 mm
MPPT 4

STRING 3 - 14 MODULOS FV 535 Wp L= 131 m; ∆V= 6,64 V; ∆V%=1,14 %


8

4
JA SOLAR JAM72S30 535/MR L= 37 m; ∆V= 4,14 V; ∆V%=0,62 %
INVERSOR 3 - MPPT 5 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
STRING 29 - 16 MODULOS FV 535 Wp EMT50 mm

5
9

2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K JA SOLAR JAM72S30 535/MR

MPPT 2
INVERSOR 1 - MPPT 2 - ENTRADA 3 EMT50 mm
MPPT 5

STRING 4 - 14 MODULOS FV 535 Wp L= 130 m; ∆V= 6,6 V; ∆V%=1,13 %

6
10

JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K L= 61 m; ∆V= 6,86 V; ∆V%=1,03 %
INVERSOR 1 - MPPT 3 - ENTRADA 1 EMT50 mm INVERSOR 3 - MPPT 6 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
STRING 5 - 14 MODULOS FV 535 Wp L= 125 m; ∆V= 6,39 V; ∆V%=1,1 % STRING 30 - 16 MODULOS FV 535 Wp EMT50 mm

7
11
CANADIAN SOLAR CSI-110K-T400

JA SOLAR JAM72S30 535/MR JA SOLAR JAM72S30 535/MR L= 50 m; ∆V= 5,61 V; ∆V%=0,84 %


INVERSOR 3 - MPPT 6 - ENTRADA 2 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K

1.- LOS MATERIALES QUE REQUIEREN CERTIFICACIÓN PARA SU USO CUMPLEN CON LO ESTABLECIDO POR LA SEC.
MPPT 6

CANADIAN SOLAR CSI-50KTL-GI-HFL


STRING 31 - 16 MODULOS FV 535 Wp EMT50 mm

8
12

3F + 1N + 1T
3F + 1N + 1T

2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K L= 59 m; ∆V= 6,63 V; ∆V%=1 %

MPPT 3
JA SOLAR JAM72S30 535/MR
INVERSOR 1 - MPPT 3 - ENTRADA 3 EMT50 mm INVERSOR 3 - MPPT 7 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K

2.- LOS VALORES DE CAPACIDAD DE CORRIENTE DE CADA CONDUCTOR FUERON EXTRAÍDOS DEL PLIEGO TÉCNICO RIC N°04.
B.P.C. 150x100 mm
L= 126 m; ∆V= 6,44 V; ∆V%=1,11 %
B.P.C. 150x100 mm

STRING 6 - 14 MODULOS FV 535 Wp STRING 32 - 16 MODULOS FV 535 Wp EMT50 mm

9
13

JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K JA SOLAR JAM72S30 535/MR
EMT50 mm

EL INVERSOR MAESTRO LLEVARA DISPOSITIVO WIFI LOGGER STICK PARA RESPECTIVO CONTROL Y MONITOREO DE INVERSORES.
INVERSOR 1 - MPPT 4 - ENTRADA 1

INVERSOR UNIDIRECCIONAL CUENTA CON PERFIL DE RED DE CHILE, PUEDE VISUALIZARSE A TRAVÉS DE LA APP "CSI CLOUD PRO".
MPPT 7

STRING 7 - 14 MODULOS FV 535 Wp L= 128 m; ∆V= 6,51 V; ∆V%=1,12 %

10
14

L=8 m; ΔV= 0,53 V; ΔV%= 0,14%


JA SOLAR JAM72S30 535/MR L= 72 m; ∆V= 8,11 V; ∆V%=1,22 %
L=10 m; ΔV= 0,43 V; ΔV%= 0,11%

INVERSOR 3 - MPPT 8 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


STRING 33 - 16 MODULOS FV 535 Wp EMT50 mm
4C# 35 mm2 RZ1-K +1#C 35 mm2 RZ1-K

11
15
4C# 120mm2 RZ1-K +1#C 70 mm2 RZ1-K

2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K JA SOLAR JAM72S30 535/MR

MPPT 4
INVERSOR 1 - MPPT 4 - ENTRADA 3 EMT50 mm
MPPT 8

STRING 8 - 14 MODULOS FV 535 Wp L= 129 m; ∆V= 6,55 V; ∆V%=1,13 %


16

12
JA SOLAR JAM72S30 535/MR L= 60 m; ∆V= 6,75 V; ∆V%=1,01 %
INVERSOR 3 - MPPT 9 - ENTRADA 1 2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
STRING 34 - 18 MODULOS FV 535 Wp EMT50 mm
17

JA SOLAR JAM72S30 535/MR


MPPT 9

C
C

18

TODOS LOS TABLEROS DE CAPACIDAD IGUAL O SUPERIOR A 100 A, DEBERAN CONTAR CON CELOSÍAS EN DISPOSICIÓN DIAGONAL, INSTALADAS EN SUS CARAS LATERALES.
L= 60 m; ∆V= 6,75 V; ∆V%=0,9 %
INVERSOR 3 - MPPT 10 - ENTRADA 1 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
STRING 35 - 14 MODULOS FV 535 Wp EMT50 mm
19

JA SOLAR JAM72S30 535/MR L= 129 m; ∆V= 6,53 V; ∆V%=1,12 %


MPPT 10

3.- EL CONDUCTOR DE TIERRA, DEBE TENER UNA SECCIÓN COMO NIMIMO IGUAL A LA MITAD DE LA SECCIÓN QUE POSEEN LOS CONDUCTORES DE FASE, ESTO SEGÚN EL PLIEGO TECNICO N°6.
20

L= 3 m

8
7
4
2

9
5
3
EMT. 32 mm

10

13
12
11
CABLE DE COMUNIACIÓN RS485

CÓDIGO
22-06-VCS-DE-LAY-01-2

22-06-VCS-DE-STR-08-2
22-06-VCS-DE-STR-07-2

22-06-VCS-DE-CTR-12-2
22-06-VCS-DE-PAT-11-2
22-06-VCS-DE-SEG-10-2
22-06-VCS-DE-CAN-06-2
22-06-VCS-DE-CAN-05-2

22-06-VCS-DE-DEQ-13-2
22-06-VCS-DE-CDG-04-2
22-06-VCS-DE-DUC-03-2
22-06-VCS-DE-DUA-02-2

22-06-VCS-DE-EDM-09-2
L= 5 m
A WIFI LOGGER STICK

EMT. 32 mm

L= 3 m

LISTADO DE LÁMINAS

SEGURIDAD
PUESTA A TIERRA
LAYOUT GENERAL
CABLE DE COMUNICACIÓN RS485

CONTROL Y MONITOREO
DISPOSICIÓN DE EQUIPOS
DIAGRAMA DE STRINGS -2
DIAGRAMA DE STRINGS -1

ESTRUCTURA DE MONTAJE
CUADROS DE GENERACIÓN
CABLE DE COMUNIACIÓN RS485

2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K

CANALIZACIÓN Y CABLEADO - 2
CANALIZACIÓN Y CABLEADO - 1
DESCRIPCIÓN
INVERSOR 2 - MPPT 1 - ENTRADA 1 EMT50 mm
STRING 9 - 15 MODULOS FV 535 Wp L= 138 m; ∆V= 7,03 V; ∆V%=1,13 %
1

JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


INVERSOR 2 - MPPT 1 - ENTRADA 2 EMT50 mm

DIAGRAMA UNILINEAL CORRIENTE ALTERNA


MPPT 1

STRING 10 - 15 MODULOS FV 535 Wp L= 137 m; ∆V= 6,98 V; ∆V%=1,12 %


2

DIAGRAMA UNILINEAL CORRIENTE CONTINUA


JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
INVERSOR 2 - MPPT 2 - ENTRADA 1 EMT50 mm
INVERSOR 2 (ESCLAVO)

STRING 11 - 15 MODULOS FV 535 Wp L= 136 m; ∆V= 6,94 V; ∆V%=1,11 %


3

N
JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
INVERSOR 2 - MPPT 2 - ENTRADA 2 EMT50 mm

B
B

MPPT 2

L= 135 m; ∆V= 6,87 V; ∆V%=1,1 %


4

STRING 12 - 15 MODULOS FV 535 Wp


JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
INVERSOR 2 - MPPT 3 - ENTRADA 1 EMT50 mm
L= 130 m; ∆V= 6,64 V; ∆V%=1,06 %
5

STRING 13 - 15 MODULOS FV 535 Wp


2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
CROQUIS DE UBICACIÓN:

JA SOLAR JAM72S30 535/MR


INVERSOR 2 - MPPT 3 - ENTRADA 2 EMT50 mm
MPPT 3

L= 131 m; ∆V= 6,69 V; ∆V%=1,07 %


6

STRING 14 - 15 MODULOS FV 535 Wp

H19 319587 mE; 6176213.4mS


JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
EMT50 mm
INVERSOR 2 - MPPT 4 - ENTRADA 1
L= 132 m; ∆V= 6,73 V; ∆V%=1,08 %
7

STRING 15 - 15 MODULOS FV 535 Wp


COORDENADAS UTM: DATUM (WGS84): JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
INVERSOR 2 - MPPT 4 - ENTRADA 2 EMT50 mm
MPPT 4

L= 133 m; ∆V= 6,78 V; ∆V%=1,09 %


8

STRING 16 - 15 MODULOS FV 535 Wp


JA SOLAR JAM72S30 535/MR 2x1C# 10 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K
INVERSOR 2 - MPPT 5 - ENTRADA 1 EMT50 mm
FECHA:

STRING 17 - 15 MODULOS FV 535 Wp L= 133 m; ∆V= 6,78 V; ∆V%=1,09 %


9

NOMBRE:

JA SOLAR JAM72S30 535/MR


MPPT 5
10

2x1C# 6 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


TIMBRE DE INSCRIPCIÓN:

INVERSOR 2 - MPPT 6 - ENTRADA 1 EMT50 mm


STRING 18 - 15 MODULOS FV 535 Wp L= 86 m; ∆V= 6,54 V; ∆V%=1,05 %
11
CANADIAN SOLAR CSI-100K-T400

JA SOLAR JAM72S30 535/MR 2x1C# 6 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


INVERSOR 2 - MPPT 6 - ENTRADA 2 EMT50 mm
MPPT 6

STRING 19 - 15 MODULOS FV 535 Wp L= 83 m; ∆V= 6,31 V; ∆V%=1,01 %


12

JA SOLAR JAM72S30 535/MR 2x1C# 6 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


3F + 1N + 1T

INVERSOR 2 - MPPT 7 - ENTRADA 1 EMT50 mm


STRING 20 - 15 MODULOS FV 535 Wp L= 87 m; ∆V= 6,46 V; ∆V%=1,04 %
13
B.P.C. 150x100 mm

JA SOLAR JAM72S30 535/MR


MPPT 7
14

2x1C# 6 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


L=9 m; ΔV= 0,35 V; ΔV%= 0,09%

INVERSOR 2 - MPPT 8 - ENTRADA 1 EMT50 mm


L= 87 m; ∆V= 6,46 V; ∆V%=0,97 %
PROY.
EXIST.

STRING 36 - 16 MODULOS FV 535 Wp


15

JA SOLAR JAM72S30 535/MR


4C# 120 mm2 RZ1-K +1#C 70 mm2 RZ1-K

MPPT 8

UBICACIÓN:
16

PROYECTO:

2x1C# 4 mm² H1Z2Z2-K + 1C# 4mm² H07Z1-K


EXISTENTE

INVERSOR 2 - MPPT 9 - ENTRADA 1 EMT50 mm


PROYECTADO

STRING 21 - 16 MODULOS FV 535 Wp L= 51 m; ∆V= 5,78 V; ∆V%=0,87 %


17

FUSIBLE 20 A gPV

JA SOLAR JAM72S30 535/MR


ACEPTACIÓN DEL PROPIETARIO:
STRING FOTOVOLTAICO

10.748.040-4

A
MPPT 9
A

SEXTA REGIÓN
18

MARIO PABLO SILVA SILVA


19

HIJUELA S/N, COMUNA SAN FERNANDO,


SIMBOLOGÍA
MPPT 10
20

REVISÓ:
LÁMINA:
CHILE
INVERSOR SOLAR FRONIUS TAURO ECO 100 - 3 -D

Rising Sun

M. PAREDES
INSTALADOR:
DESCRIPCIÓN:

03 DE 13
VIÑA CASA SILVA
COMERCIAL FOTOVOLTAICO

ABROBÓ:
CÓD. LAM:

L. SANTIAGO

19.191.699-9 / LICENCIA CLASE A


FECHA:

MATÍAS PAREDES / ING. ELÉCTRICO


06/2022
DIAGRAMA UNILINEAL CORRIENTE CONTINUA

22-06-VCS-DE-DUC-03-0