Quotation notice no.

- 8/01/2019-20

REQUEST FOR QUOTATION

Vendors are requested to give their best possible rate quotes for Design, Supply, Install,
Interfacing, Integrating & Commissioning of Instrumentation, Automation & SCADA system for
Water Supply system of PCMC for establishing a Central Monitoring System (CMS). The
quoted rates should be exclusive of GST and applicable HSN code as well as the GST rates
should be mentioned separately in the prescribed format as given below. Also the Catalogue No.
should be mentioned wherever available. The rate should be inclusive of loading, unloading,
transportation and installation charges, complete with delivery at the site that will be required
during the execution of the work as and when required as per the site requirements and
instructions of Engineer In Charge. The quote should be submitted in sealed envelope on or
before 07/12/2019 and addressed to :

The Executive Engineer


Water Supply Department,
Pimpri Chinchwad Municipal Corporation
Pimpri, Pune-18.

Item Quoted Total Applica


No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
1 Supply, delivery, installation, testing,
training and commissioning of
Pressure measuring instruments
consisting of pressure transducers,
pressure transmitters with cabinet
for pressure transmitter, digital
pressure indicator, sensors,
converters, cables, structure
required for mounting viz:
platforms, railings, etc and all
required installation hardware
complete and as directed by
Engineer-in -charge
each
a)At ESR outlet 30
set
each
b) At Sump pump delivery 112
set
c) at remote locations (with each
10
protection enclosure) set
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
SUBTOTAL 142

2 Supply, delivery, installation, testing,


training and commissioning of
Temperature Scanner to measure
temperature of motors at pump
house / BPS
each
At Pump House : each motor 112
set

3 Supply, delivery, installation, testing,


training and commissioning of level
measurement systems to measure
UGR / GSR level and water / sump
level at pump house / BPS consisting
of level transducers, level
transmitters, sensors, converters,
cables, digital level indicators with
proper cabinets, structure required
for mounting the level transducer
viz: platforms, railings etc and all
required installation hardware
complete and as directed by
Engineer-in-charge
a) At ESR / GSR / Sump each
44
set
each
SUBTOTAL 44
set
4 Supply, delivery, installation, testing,
training and commissioning of
Residual Chlorine measuring
instruments consisting of
transducers, transmitters, sensors,
converters, cables, proper cabinets,
structure required for mounting viz:
platforms, railings etc and all
required installation hardware
complete and as directed by
Engineer-in-charge
a) At ESR /GSR each
43
set
b) At WTP each
1
set
each
SUBTOTAL 44
set
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
5 Supply, delivery, installation, testing,
training and commissioning of
Electromagnetic flow meter (EMF)
with accuracy 0.5% of measured
value and protection as per given
specifications for size 50mm -
1600mm. Including sensor,
transmitter, surge arrestor, 25meter
sensor/ transmitter cable, GI duct of
suitable size for 25 mtr/ each flow
meter including pipe cutting,
levelling and installation of flow
meter in pipe lines with necessary
tool tackles cranes etc. as may be
required at site and based on
technical specification etc. as per
attached with 10 years battery back-
up with data logger
Dia (mm)
each
50 0
set
each
100 0
set
each
150 0
set
each
200 5
set
each
300 17
set
each
400 11
set
each
450 0
set
each
500 3
set
each
600 2
set
each
700 0
set
each
800 0
set
each
900 0
set
each
1000 1
set
each
1200 0
set
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
each
1500 0
set

SUBTOTAL 39

6
Supply, delivery, installation, testing,
training and commissioning of
Turbidity meter consisting of
transducers, transmitters, sensors,
converters, cables, structure
required for mounting the
transducer viz: chambers, platforms,
railings etc and all required
installation hardware complete and
as directed by Engineer-in -charge

At Raw Water Pumping/ WTPs each


2
set

7 Supply, delivery, installation, testing,


training and commissioning of pH
measuring instruments consisting of
transducers, transmitters, sensors,
converters, cables, structure
required for mounting the
transducer viz: chambers, platforms,
railings etc and all required
installation hardware complete and
as directed by Engineer-in -charge

At WTPs each
2
set

8 Supply, delivery, installation, testing,


training and commissioning of RPM
measuring instruments consisting of
transducers, transmitters, sensors,
converters, cables, structure
required for mounting the
transducer viz: chambers, platforms,
railings etc and all required
installation hardware complete and
as directed by Engineer-in -charge

At Pump Houses each


89
set
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
9 Supply, delivery, installation, testing,
training and commissioning of
Energy measuring (Power analyser)
instruments.
Communicating type energy
monitoring system capable of
monitoring all energy parameters
consisting of transducers,
transmitters, sensors, converters,
cables, cabinets, structure required
for mounting the transducer viz:
platforms, railings etc and all
required installation hardware /
software complete etc. and as
directed by Engineer-in -charge

At Pump Houses each


109
set

10 Supply, delivery, erection,


installation, testing and
commissioning of all required
communication interface, SCADA
interfaces, telemetry interfaces,
RTUs / PLC hardwares, controls,
cables and all required accessories
to communicate with all field
instruments to receive, store,
transfer data /information.
Consisting of PLC / RTUs system with
all peripherals, converters &
cabinets, power points and structure
required for mounting viz:
platforms, railings etc and all
required hardware / softwares
complete and as directed by
Engineer-in -charge
a) At ESR / GSR locations (PLC) each
40
set
b) At ESR / GSR (RTU only) each
3
set
c) At Control Room PLC each
1
set
each
SUBTOTAL 44
set
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
11 Supply, delivery, installation, testing
of valve actuators required for
automatic control of existing Sluice
Valves as per the General
Specifications described in
Technical Specifications for
Instrumentation
Consisting of required transmitters,
cables, hand wheel for emergency
manual operation , wired on
terminal blocks, and including
repairs and reconditioning the
existing Sluice Valves etc., complete
and all required installation
hardware complete and as directed
by Engineer-in -charge
100 mm each
0
set
200 mm each
0
set
250 mm each
0
set
300 mm each
0
set
350 mm each
0
set
400 mm each
50
set
450 mm each
44
set
500 mm each
18
set
600 mm each
13
set
700 mm each
2
set
750 mm each
0
set
each
Subtotal 127
set
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
12 Supply, delivery, installation, testing
for interfacing of valve actuators
required for automatic control of
existing Sluice Valves as per the
General Specifications described in
Technical Specifications for
Instrumentation in Volume 1
Consisting of required transmitters,
cables, hand wheel for emergency
manual operation , wired on
terminal blocks, and including
repairs and reconditioning the
existing Sluice Valves etc., complete
and all required installation
hardware complete and as directed
by Engineer-in -charge

At ESR locations/ pump house each


127
set
13 Supply, delivery, installation, testing,
training and commissioning of
SCADA Controlled Flow Control
Valve (FCV) as per the General
Specifications described Technical
Specifications for Instrumentation
Consisting of Body, Cover & Stem
Cap in Ductile Iron ASTM A 536
65/45/12. Stem, Seat Ring, Spring of
SS: 316. Diaphragm, Seals, O-Rings
EPDM/Buna N. The SS: 316 Seat
Rings shall be guaranteed for life of
the Valves for potable water use
only. The Valve shall have
removable Stem Cap for in line
inspection and easy maintenance.
The painting shall be NSF 61 fusion
bonded epoxy coating safe for
drinking water. All external fasteners
shall be SS: 304. and all other
features / functions as directed by
Engineer-in -charge

a) At Bypass locations or as specified


by PCMC
100 mm each
3
set
150 mm each
11
set
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
200 mm each
6
set
250 mm each
2
set
300 mm each
8
set
400 mm each
1
set
450 mm each
1
set
Sub Total 32
14 Supply, delivery, erection,
installation, testing and
commissioning of Lightning / Surge
protection system with all required
accessories for all field instruments,
controls, towers, antennas etc.
consisting of all protection/lightning
devices with all peripherals, cabinets
and structure required for mounting
viz: chambers, platforms, railings
etc. with all required hardware
complete and as directed by
Engineer-in -charge
a) At ESR each
38
set
b) At Pump House each
1
set
each
c) At Control Room 1
set
each
SUBTOTAL 40
set
15 Supply, delivery, erection,
installation, testing and
commissioning of Instrumentation
Cable with all required accessories
for all field instruments & controls
i.e. for telemetry consisting of all
peripherals and structure required
for mounting viz: furnitures,
platforms, railings etc. with all
required hardware complete and as
directed by Engineer-in -charge

At all Pump Houses & ESR locations


1900 meter
& Central Location.
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
16 Providing and constructing R.C.C.
chambers 2mX2mX2.5m for field
instruments of required size and
depth in M-20 grade concrete
including necessary, excavation,
backfilling, P.C.C. 150 mm thick
below foundation, R.C.C. wall 150
mm thick, R.C.C. precast roof cover
in M.S. angle frame in strip of 30 cm
width with proper hooks for lifting,
necessary number of M.S. steps
embedded in wall etc. complete

a) At ESR Inlet and outlet 37 nos.


b) At Bypass locations or FCV
32 nos.
location
SUBTOTAL 37
17 Supply, delivery, erection,
installation, testing, training and
commissioning of Wireless
Telemetry / GPRS (4G LTE) VPN
network as a communication media
including GPS site survey of all
locations for determining
communication parameters &
towers for Central Monitoring
system with proper Towers/
Antennas /subscriber module /
reflector disk at each location and
central location and all necessary
accessories inclusive of all liscence
fees at all locations of pumping
stations and ESR consisting of all
required equipments, Towers,
Antennas, subscriber module, disk,
pedestal for tower base, lightning
arrestors, cables, structure required
for mounting viz: poles, platforms,
railings, furnitures etc and all
required installation hardwares
complete and as directed by
Engineer-in -charge
a) At ESR/GSR/ Pump House 44 nos.
b) At Control Room 1 nos.
SUBTOTAL 45
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
18 ii) Providing Fabricated self
supported triangular shape MS
Tubular Tower of suitable height
from ground , providing matched
pedestal for tower base, providing
Aluminium earthing wire upto
nearest earth terminal, providing GI
lightening arrestor at WTP / pump
House locations and At Central
Location
a) Tower Height upto 5 meter (For
0 nos.
ESR)
b) Tower Height 10 to 15 meter (For
0 nos.
Pump Houses)
c) Tower Height 25 to 30 meter (At
0 nos.
Control Room)
SUBTOTAL 0
19 Providing supplying, fixing and
commissioning GPRS Data logger
with internal battery having (6 years
battery life) dual channel for flow
and pressure logging with internal
pressure transducer, PC software,
PC connection cable, Infra-red
reading head, pressure hose,
instruction manual etc. complete as
directed by the Engineer-in-charge.

1) FlowMeter remote Locations 6 nos.


SUBTOTAL 6 nos.
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
20 Supply, delivery, erection,
installation, testing, training and
commissioning of local SCADA
Softwares & Monitoring including
all associated softwares like
Operating system, database
software, SCADA software,
application software, pump house
resource planning software etc.& its
all accessories as per the General
Specifications & Technical
Specifications for telemetry / SCADA
of this document. Softwares
Consisting of Windows based MMI
Software inclusive of all liscence to
provide dynamic graphics, process
mimics, real time & historical
trending, group displays, faceplate
displays, alarm management and
reports and all mounting structures
viz, furnitures, cabinets, platforms,
railings, cables etc. as directed by
Engineer-in -charge

At central locations 1 each

21 a) Supply, delivery, erection,


installation, testing, training and
commissioning of Central
Monitoring System for all ESR/GSR
/ Pumping stations including a)
project Plan b) System hardware c)
System Software and all necessary
accessories as per the General
Specifications & Technical
Specifications for telemetry
consisting of all monitoring
equipments, Laser disply screens not
less than 3.3 m x 1.8 m, cables, all
hardwares/softwares to
communicate with telemetry
system, power supplies, structure
required for mounting viz:
furnitures, mounting bracket /
stand, UPS, interior decorations,
cabinets, platforms, railings etc. and
all required installation hardwares
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
and as directed by Engineer-in -
charge

At central location Control Room syste


1
m
22 Supply, delivery, erection,
installation, testing, and
commissioning of Central Server PC
for storing data including all
necessary accessories consisting of
reputed make Server PC with Min
configuration: Intel Core I7, 3 GHz or
above, 16 GB RAM, 1 TB HDD,
10/100 Ethernet, Keyboard, Mouse,
1.44MB FDD, CD / DVD ROM, CD
writer, Windows latest software
inclusive of liscence with
commercial grade monitor(LCD) not
less than 42" along with networking
components and internet
connection for web enabled data
facility, printers and all mounting
structures viz, furnitures, cabinets,
platforms, railings etc. and all
required installation softwares and
hardwares cables and as directed by
Engineer-in -charge
At central location i.e. Control Room Syste
1
m
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
23 Supply, delivery, erection,
installation, testing, training and
commissioning of PCs, Softwares,
Keyboards, Printers etc. including all
associated softwares like Operating
system, database software,
application software, resource
planning, WDM software etc.& its all
accessories Minimum configuration
for PCs are :- Reputed make PC with
Intel Core i7, 3 GHz or above, 16 GB
RAM, 1TB HDD, 10/100 Ethernet,
Keyboard, Mouse, 1.44MB FDD,
Lump
CDROM, Windows latest software
sum
inclusive of liscence with not less
(Min
than 42" commercial grade monitor
3
(LED) along with all networking
user)
components to connect with server
and other PCs.Softwares Consisting
of Windows based MMI Software
inclusive of liscence to provide
dynamic graphics, process mimics,
real time & historical trending,
group displays, faceplate displays,
alarm management and reports and
all mounting structures viz,
furnitures, chambers, platforms,
railings, cables etc. as directed by
Engineer-in -charge.

At central location i.e. Control Room 1


24 Supply, delivery, erection, testing
and commissioning of
Uninterrupted Power Supply system
for 240 V AC 50 Hz. consisting of
inverters and Lead Acid Batteries of
high capacity and all electrical
power supplies & point
arrangement, mounting structures
viz, furnitures, chambers, platforms,
railings, cables etc. and as directed
by the Engineer-in -charge
a) AT ESR locations 17 nos.
b) At Central Location Control Room. 1 nos.
c) 2 kw off grid solar system with 8-
10 Hours Backup (for remote flow 32 nos.
meter / FCV locations)
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
SUBTOTAL 50 nos.
25 Supply, delivery, erection,
installation, testing and
commissioning of Air conditioning
unit for Central control Room with
all accessories consisting of 2 ton
capacity, sized to maintain a
temperature of 24 + 1 degree
Celsius, 50 % relative humidity
inside at all time, energy efficient. It
shall be constructed with the
strength and rigidity adequate for
normal conditions of handling,
transport and usage. All power point
and mounting structures viz,
furnitures, cabinets platforms,
railings, cables etc. complete shall
be provided and as directed by
Engineer-in -charge
At Central Location Control Room . 2 nos.
SUBTOTAL 2

26 Providing and laying in position all


specials

Providing and laying in position


following cast iron flanged spigot
(tail piece) and all associated works
etc. complete
Dia (mm)
50 0 Each
80 0 Each
100 0 Each
125 0 Each
150 0 Each
200 5 Each
250 0 Each
300 16 Each
350 0 Each
400 12 Each
450 0 Each
500 3 Each
600 2 Each
700 0 Each
750 0 Each
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
SUBTOTAL 38

Providing and laying in position


following cast iron double flanged
tapers (all size in mm) body X
Branch
75 X 50 0 Each
80 X 50 0 Each
100 X 80 0 Each
125 X 80 0 Each
125 X 100 0 Each
150 X 80 0 Each
150 X 100 0 Each
150 X 125 0 Each
200 X 100 0 Each
200 X 125 0 Each
200 X 150 0 Each
250 X 150 0 Each
250 X 150 0 Each
250 X 200 0 Each
300 X 150 0 Each
300 X 200 10 Each
300 X 250 0 Each
350 X 200 0 Each
0 Each
350 X 250
350 X 300 0 Each
400 X 250 0 Each
400 X 300 28 Each
400 X 350 0 Each
450 X 300 2 Each
450 X 350 0 Each
450 X 400 0 Each
500 X 350 0 Each
500 X 400 24 Each
500 X 450 0 Each
600 X 400 0 Each
600 X 450 0 Each
600 X 500 8 Each
700 X 500 2 Each
700 X 600 0 Each
750 X 600 0 Each
750 X 700 0 Each
800 X 600 0 Each
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
800 X 700 0 Each
800 X 750 0 Each
900 X 700 0 Each
900 X 750 0 Each
900 X 800 0 Each
1000 X 800 0 Each
1200 X 900 4 Each
SUBTOTAL 78

Providing and Laying in Position


Cast Iron Blank Flanges [Conform
to IS 1538]
mm dia
80 0 Each
100 0 Each
125 0 Each
150 0 Each
200 0 Each
250 0 Each
300 10 Each
350 0 Each
400 30 Each
450 2 Each
500 24 Each
600 8 Each
700 2 Each
750 0 Each
800 0 Each
900 0 Each
1000 4 Each
SUBTOTAL 80

Labour for laying in position


following cast iron blank flanges (all
sizes in mm)
80 mm dia 0 Each
100 mm dia 0 Each
125 mm dia 0 Each
150mm dia 0 Each
200 mm dia 0 Each
250 mm dia 0 Each
300 mm dia 10 Each
350 mm dia 0 Each
Item Quoted Total Applica
No. Description of items Applicable
Qty. Unit Rate Amount ble HSN
GST (%)
(In Rs) (Rs.) Code
400 mm dia 30 Each
450 mm dia 2 Each
500 mm dia 24 Each
600 mm dia 8 Each
700 mm dia 2 Each
750 mm dia 0 Each
800 mm dia 0 Each
900 mm dia 0 Each
SUBTOTAL 76

27 Supply, delivery, erection,


installation, testing and
commissioning of VSAT technology
along with all power point and
mounting structures viz, furnitures,
cabinets platforms, railings, cables
etc. complete shall be provided and
as directed by Engineer-in -charge
Raw Water pumping station or
location specified by PCMC 1 each
28 Supply, delivery, erection,
installation, testing and
commissioning of CC TV Cameras at
ESR/Pumping Stations along with all each
power point and mounting 44 locati
structures viz, furnitures, cabinets on
platforms, railings, cables etc.
complete shall be provided and as
directed by Engineer-in -charge
29 Operation & Maintenance of the
entire central monitoring system
including operation and per
7
maintenance all existing and Year
newaly created assets for the
period of 7 years
Total Cost (in Rs.)
Note:- Annexure -1 (Pg. no. 1 to 53) shall be referred for detailed technical specifications of the
corresponding items as above

Sd/-
Joint City Engineer
Water Supply Department
Pimpri Chinchwad Municipal Corporation
ANNEXURE-1: ITEM WISE DETAILED TECHNICAL SPECIFICATIONS

Note:-The Detailed Technical Specifications provided below shall supplement the Technical
Specifications specified as above. Whenever there is a conflict, the provisions of Detailed
Technical Specifications shall prevail over other.

1. ITEM NO. 1 PRESSURE MEASURING INSTRUMENTS

Pressure gauges shall comply with BS EN 837-1:1998 and BS1780. Pressure gauges
and transmitters shall have over range protection up to 1.5 times the maximum line
pressure and shall be capable of withstanding full line pressure on any side with the
other side vented to atmosphere without damage or effect on the calibration. No
plastic material shall be used in their construction. Internal parts shall be of stainless
steel, bronze or approved corrosion-resistant material. Where necessary, a special
diaphragm shall be used to segregate the gauge tube from corrosive fluid media. In
chlorine applications, the diaphragm shall be in silver or tantalum. The minimum
diameter for any pressure gauge shall be 150 mm unless specified otherwise or
where the gauge forms part of a standard item of equipment.
Where compensation of more than 2% of the instrument span is needed for the
difference in level between the instrument and the tapping point, the reading shall
be suitably adjusted and the amount of compensation shall be marked on the dial.
The zero and span of a pressure transmitter shall not change by more than 0.1% of
the span per degree Celsius change in ambient temperature. After application for 10
minutes of pressure at 130% of maximum pressure, the change in zero and span
shall not exceed 0.1% of the span.
Pressure transmitters shall have accuracy typically better than 0.25% of span,
depending on the application and shall be protected to BS EN 60529:1992, IP 65
standard or higher. For transmitters installed in locations liable to flooding or
underwater applications, they shall be to IP 68 standard and shall operate up to a
maximum submergence of 20 meters of water.
Pressure transmitters shall provide a 4 to 20mA d.c. output proportional to the
pressure range at a maximum load of 750 ohms.
The specifications for pressure transmitter shall be as follows,
a. Type: 2 wire type
b. Housing: IP 68
c. Output: 4-20mA
d. Supply: 24 VDC

Page 1 of 53
e. Local Display: LCD.
f. Accuracy: Better than 0.5 % of range

The specific Technical specification is as below;


Function Transmit & indicate
Mounting In Line
Connection ½ “ NPT
Service Clear water
Damping Adjustable
Turn on time <2.5 sec.
Pressure Range 0-200 meter or As per requirement
Enclosure Class Weather proof ( NEMA 4 and IP 65)
Intrinsically safe Yes
Accuracy + 0.075%
Turn down ratio 25:1
Response time 250 msecs or less
Operating Temp. 0 to 55oC
Humidity 5 to 95 % Rh, Non condensing
Transmitter
Type SMART microprocessor based
Power supply 16 to 48 V DC (Nominal 24 VDC)
Output 4-20 mA
Span and zero adjustment Provided
Indicator LCD display with front facia capability for
programming
Range setting switches Provided
Element
Sensor Piezoresistive/ capacitive
Load resistance Max 600 Ohm.
Zero Elevation/ Suppression Provided
Accessories 2 way manifold- 01 No. per Transmitter
Material 316 SS
Accessories Mounting bracket, chequears plate etc.
Reputed make Siemens/E & H/Krohne Marshall/Emerson/ABB

Installation:- Instrument shall be installed at the locations mentioned in this


document or as directed by the Engineer in charge. Remote locations instrument
with GPRS loggers / modem shall be suitably protected through lockable panels/
cages / cabinets and display arrangements to avoid theft or damage to the
instrument. Instrument shall provide the real time information / data at Central
Monitoring System.

2. ITEM NO. 2 TEMPERATURE TRANSMITTERS WITH SENSORS

Specifications for Temperature Transmitters


General
Type Micro Processor Based, SMART
Input RTD Pt – 100
Output 4 – 20 mA with superimposed digital signal
Accessing Protocol HART

Page 2 of 53
Power Supply 16 – 48 VDC/230 AC
Minimum Load Capability 600 Ohms at 24 VDC
Housing Weather Proof to NEMA4 & IP-65
Design Intrinsically Safe
Accuracy + 0.075 %
Response Time 250 msecs or less
Cable Entry ½ inch NPT / Connecting Type
Mounting as per site
Integral Output Indicator 41/2 digit LCD display with front facia capability for
programming in any engineering units
Lighting Protection to be provided
Operating Temperature 0 to 550C
Humidity 5 to 95% RH, Non-condensing

RTD with Thermowell


Element
No. of elements Duplex
Calibration As per Standards
Element Material Platinum
Resistance at 00C 100 ohms
Leads Standard
Sheath O.D 6 mm
Sheath Material 316 SS
Nipple and Union Material Chrome plated Steel
Union Required

Head
Head Cover Screwed Cap with Cover
Material Cast Aluminum
Conduit Connection ¾ inch ET
Enclosure Weather Proof to NEMA4 & IP-65
Cable Gland Required

Thermowell
Material 316 SS
Construction Drilled Bar Stock

Accessories
Mounting Bracket
SS tag Plate

Installation:- Instrument shall be installed at the locations mentioned in this


document or as directed by the Engineer in charge with suitable protection and
digital display arrangement for the instrument as per site situation. Instrument shall

Page 3 of 53
be interfaced with local PLC to provide the real time information / data at Central
Monitoring System.

3. ITEM NO. 3 LEVEL MEASUREMENT SYSTEMS

Level Monitoring System


Function : Transmit and indicate
Range : 0‐7m for ESR 0-20 m RWPS (as per site
condition)
M.O.C : SS316
Power : 24VDC
Accuracy : 0.20%
Resolution : 0.10%
Display : 3¼ digit
Calibration : Zero and span internal
Output : 4–20 mA 600 ohms. 0.1%resolution
Housing : Weather proof (IP‐68)
Design : suitable for water application
Response time : 250 msecs or less
Remote Indicator : 4½ digit LCD display with front facia capability
For programming in any engineering units
Process connection : 1- 1/2”NPT /BSP or as per Manufacturer
Standard
Lightning protection : to be provided externally at RTU end
Operating Temperature : 0 to 550C
Humidity : 5 to 95% (suitable for outdoor)

Accessories
Mounting bracket
Reputed Make:-Siemens/E& H/Krohne Marshall/Emerson/ABB

Installation:- instrument shall be installed at the locations mentioned in this


document or as directed by the Engineer in charge with suitable protection and
digital display arrangement for the instrument as per site situation. Instrument shall
be interfaced with local PLC to provide the real time information / data at Central
Monitoring System.

4. ITEM NO. 4 RESIDUAL CHLORINE MEASURING INSTRUMENTS

The Analyzer shall operate on Analysis Method like DPD Colorimetric principal. The
application is for Drinking Water Residual Chlorine analysis.
Following specifications as a minimum shall be applicable in the basic Instrument
model offered as chlorine analyser. The analyser shall be provided with all the
necessary accessories required to operate the Instrument once unpacked and
installed at site.
a. Range: 0.1 to 5 mg / Lit free or total residual chlorine, with automatic color /
turbidity compensation

Page 4 of 53
b. Programming: The instrument shall be freely programmable using Menus & Key
pad.
c. Sensor Operating Pressure: 1 Bar
d. Sensor Op Temp. : 45 Deg. C.
e. Response Time: < 120 Sec.
f. Min. Detection Limit : 0.035 mg/L
g. Cycle Time: One complete sample analysis every 2-1/2 minutes. The output shall
be retained at the same value until next sampling is carried out.
h. Accuracy: 0.5 % of range or 0.035 mg/L as Cl2, whichever is greater
i. Supply: 230 VAC +/- 10%, 100 VA Max.
j. Output: 4-20 mA. Output shall be Programmable and shall be isolated from the
ground.
Additionally Potential Free Contact output (230 V, 5 A Rating) for sample
concentration shall be available.
k. Load : <= 500 ohm
l. Display: 4 & ½ Digit LCD
m. Repeatability: Better than 0.2% of range
n. Enclosure: IP62 Min. & Housing shall be in ABS plastic.
o. Accessories: All the required accessories shall be built in to the system offered
and no external accessories shall be required to operate the instrument in the
normal fashion.
p. Certification: The offered instrument shall be at least CE approved and UL listed.
The instrument shall work continuously at remote place without any
requirement of calibration etc. at least for a period of 30 days, from the previous
maintenance date. The instrument shall be Tamperproof or pass word protected
to prevent unauthorized handling of the same.
Reputed Make:-Siemens/E& H/Krohne Marshall/Emerson/ABB/Halma/Teledyne

Installation:- instrument shall be installed at the locations mentioned in this


document or as directed by the Engineer in charge with suitable protection and
digital display arrangement for the instrument as per site situation. Instrument
shall be interfaced with local PLC to provide the real time information / data at
Central Monitoring System.

Page 5 of 53
5. ITEM NO. 5 ELECTROMAGNETIC FLOWMETERS

Providing and fixing Full Bore Electromagnetic Flow Meters.

Item includes:-
1. Excavation for fixing Flow meters in all types of soils & surfaces in all types of
site conditions including drainage, dewatering, etc.

2. Providing installing Electromagnetic Flow Meters with cost of accessories


required. Flowmeters shall be either mains powered or Battery powered
depending on the suitability of site and decision of engineer in-charge.
Battery powered flow meter shall be provided with battery backup of min. 6
years considering data logging / interval of min. one hour. Battery powered
flow meter with too much reduced bore diameter, if any, shall be avoided.

General Technical Specification & Conditions for Electromagnetic (Full


bore):-
PCMC has provided the size of pipe is indicative. The actual size, O.D.I.D.,
thickness shall be measured by Manufacture before supply of meter, any
deviation and delay or damage cost due to non-fitting of meter shall be
borne by Manufacture. The liquidity damage due to delay in fitting for
wrong selection of fittings and accessories lies with Manufacture.

1.1 If there is any problem with ovality of pipes after the pipes are cut, the
contractor as per the relevant standards shall jack up the pipes and the

Page 6 of 53
jointing work shall be carried out.

1.2 The Manufacture will have a full system of local offices in India and full
service capability in the Metro-cities throughout the country. Full contact
details for key personnel, both national and local shall be furnished on
request. The supplier shall provide evidence of at least five years
involvement in the manufacturing of meters worldwide.

1.3 The sensor / transmitter cables shall be capable of withstanding the climatic
condition as applicable at site and should be weatherproof. The cable shall
be installed in a suitable uPVC/ HDPE duct to minimize the risk of damage
during excavations for other works. All the cable laid at a minimum depth of
0.5 m below the ground. Maximum length between the sensor & the
transmitter shall not be more than that recommended by the meter
Manufacture.

1.4 The transmitter shall operate so as to avoid loss of data in the event of
temporary loss of electrical power supply and contractor shall include of
provision of maintenance free battery backup facility (8 hours duration) to
cater for temporary loss of such power supply. The contractor must allow
for normal variations in mains electrical power parameters to be expected
at site.

1.5 All the data loggers should be of the same type & make. I.e. they should be
compatible for all the meters supplied as part of this bid. The logger should
be suitable for local conditions. Each signal transmitter should be provided
with an appropriate dual channel flow & pressure logger of type approved
by the client, with a data storage capacity of 120 days at 5 minutes logging
interval. Logger shall be supplied with compatible communication leads
from transmitters to loggers & loggers to portable download devices (hand
held units / laptops) & GSM / WAP Mobile phone. The main objective that
flow meter logger data shall be transmitted to Central Location via
GSM/GPRS data logger or modem.

1.6 The loggers shall receive a compatible pulse or continuous output as


appropriate from the transmitter. Appropriate software of Windows type or
similar software approved shall be included for downloading the flow on to
a portable download device. The loggers shall have integral maintenance
free batteries with a minimum of 10 years life, on continuous operation and
rated not worse than IP68 protection. Pressure transducer should be of
appropriate type with a pressure range of 5 m to 150 m with an accuracy of
not less than + 1%. The logging interval should have a range of 1 second to
24 hrs as decided and approved by PCMC. The main objective is that for
remote location where electric supply is not available, battery operated flow
meter shall be provided. Replacement of batteries will be in the scope of
Contractor. The data from such remote location shall be transferred to
Central location through GPRS modems. Proper chambers shall be provided
for flow meters with protection housing arrangement for flow meter
transmitter and GPRS data logger/ modem. 4G LTE router with dual sim
arrangement shall be provided for such remote locations. Internal bore
diameter of flow meter due to battery arrangement should not be such that
it would not result in flow head loss and such remote operated flow meter

Page 7 of 53
shall be approved from PCMC first though QAP before procurement at site.

1.7 The portable devices shall be compatible to the logger & flow meters for the
purpose of retrieving data and resetting the data loggers / meter as part of
this contract. The portable download devices should be simple to operate,
robust in construction. The portable download devices should be compatible
for downloading the data to a desktop or laptop computers. Supply of
portable download devices also includes supply of necessary programming
and communication leads for connection with data logger and desktop /
laptop computers. All the necessary software for downloading of data from
logger to portable devices & software for download of data from portable
devices to laptop / desktop computers to be provided by the contractor.

1.8 The flow meter shall be supplied with compatible features for “Gateway for
Remote Monitoring of flow meter via Web Browsers”. The system should
enable remote monitoring, remote diagnosis and remote configuration of
connected HART sensors/actuators, either via telephone lines (analogue and
ISDN), Ethernet TCP/IP and GSM/GPRS communications (4G LTE). The
measured data shall be web-compatible and shall be retrieved at central
station.

1.9 Separate Control Panel Unit to accommodate flow transmitter, GSM/ GPRS
modem and all other accessories including data logger shall be provided by
Contractor and suitable display arrangement. Thickness of control panel
shall not be less than 2 mm.

1.10 All safety precaution with lighting protection shall be provided to all the flow
meters, the failure / damage to flow meter for any reason for the warranty
and period of annual maintenance contract shall be with Manufacture,
hence, cost of insurance against all failure / damage (if any) shall be borne
by Manufacture no additional payment will be made.

1.11 Specification of flowmeters (mains powered):-

Minimum Technical Specification for Electromagnetic Flow Meter


Flow Sensor
Type : Pulse DC Excitation, (Bi-directional )
System : Separate with cable output
End Connection : Flanges of Carbon Steel
Flange Rating : As per Operating Pressure
Electrode SS 316
Electrode Type : Round Head Electrodes
Meter Tube : SS 304
Liner : Hard Rubber, EPDM
Coil Housing : SS 304
Protection category : IP 68
connection/ junction box : SS 304
Earthing : Grounding Rings
Accuracy : 0.5 % of MV inclusive of linearity, repeatability,
Pressure effects and hysteresis

Page 8 of 53
1-3 m/s velocity

Flow Transmitter / Converter


Model : Microprocessor based, Modular design,
Type : remote mounting
Display Language : English
Display : Two line back lit LCD for indication of actual flow rate,
forward , reverse flow direction and sum totalizer with soft
keys, conductivity
Output : 4-20 mA, HART / Modbus RS 485 for flow and pressure
separately. Additional output for pulse and status
Protection category : IP 67
Enclosure : Die cast Aluminum with polyurethane finish with glass
window
Programming : From Front facia through keyboard
Power Supply : 240 V AC, 50 Hz wherever mains power supply is available
Cable Gland : 1/2" NPT, 4 glands double compression type
Mounting : Wall mounted with long cables
Separation : 100 meters max. without boosters
Interface : HART/ Modbus RS 485
Power failure mode Provision
: of RAM/ PROM to store parameter entered and
measured flow data during power failure
Terminal Shock: - Hazard- protected push lock terminal
Error Identification 0/3.6/22
: mA
Diagnosis Empty: Pipe Detection, Electronic Temperature, Coil
Temperature, Application Error
Interchangeability Fully: interchangeable with all the flow sensors
Flow Indicator & Internal,
: 5 mm high, LED display with 6 digit LCD, Totalizer
Totalizer and display in Single Unit
Loggers & data Data: logger shall be the dual channel type, one flow channel
acquisition and one pressure channel.

1.1 Specification of flowmeters (battery powered):-

2 Minimum Technical Specification for Electromagnetic Flow Meter


Flow Sensor
Type : Pulse DC Excitation, (Bi-directional )
System : Separate with cable output
End Connection : Flanges of Carbon Steel
Flange Rating : As per Operating Pressure
Electrode SS 316
Electrode Type : Round Head Electrodes
Meter Tube : SS 304
Liner : Hard Rubber, EPDM
Coil Housing : SS 304
Protection category : IP 67
connection/ junction box : SS 304

Page 9 of 53
Earthing : Grounding Rings
Accuracy : 0.5 % of MV inclusive of linearity, repeatability, Pressure
effects and hysteresis

1-3 m/s velocity

Flow Transmitter / Converter


Model : Microprocessor based, Modular design,
Type : remote mounting
Display Language : English
Display : Two line back lit LCD for indication of actual flow rate,
forward , reverse flow direction and sum totalizer with soft
keys, conductivity
Output : 4-20 mA, HART / Modbus RS 485 for flow and pressure
separately. Additional output for pulse and status
Protection category : IP 67
Enclosure : Die cast Aluminum with polyurethane finish with glass
window
Programming : From Front facia through keyboard / optical pin
programming
Power Supply : 24 VDC at remote location via solar power (suitable battery
life )
Battery Back up : lithium batteries, replaceable, suitable life
Memory retention : 8-10 years, non-volatile
Cable Gland : 1/2" NPT, 4 glands double compression type
Mounting : Wall mounted with long cables
Separation : 100 meters max. without boosters
Interface : HART / MODBUS RS 485
Power failure mode Provision
: of RAM/ PROM to store parameter entered and
measured flow data during power failure
Terminal Shock: - Hazard- protected push lock terminal
Error Identification 0/3.6/22
: mA
Diagnosis Empty: Pipe Detection, Electronic Temperature, Coil
Temperature, Application Error
Interchangeability Fully: interchangeable with all the flow sensors
Flow Indicator & Internal,
: 5 mm high, LED display with 6 digit LCD, Totalizer
Totalizer and display in Single Unit
Loggers & data Data: logger shall be the dual channel type, one flow channel
acquisition and one pressure channel. The loggers shall have a data
storage capacity of 360 days @ 15 min logging intervals. It
should have maintenance free batteries with min 10 years
life @ 15 min interval and IP 68 protection. Data can be
exported to PC / Laptop / Palm tap via GSM/ GPRS (4G LTE
dual sim) and USB.

Page 10 of 53
6. ITEM No. 6 TURBIDITY METER

Following specifications as a minimum shall be applicable in the basic Instrument


model offered as Turbidity Measuring System. The analyser shall be provided with
all the necessary accessories required to operate the Instrument once unpacked and
installed at site.

Type : Microprocessor Based


Measuring Principal : ISO 7027, 90o Scattered light, Infra-red ( Nephelometric)
Measuring Range 0 – 40 NTU (clear water)
Cleaning : Ultrasonic Cleaning System
Temperature rating 1 – 50 deg C
Cleaning : Built – in Self-cleaning type
Flow rate : 0.1 to 1 Lit/min
Protection Class : IP66/ NEMA 4X
Display resolution : 0.0001 NTU ( below 10 NTU)
Display : High contrast LCD provided live measurement readouts in
large digits and shows up to four additional process variables
Diagnostics : Analyzer should continuously monitor itself and the sensor(s)
for problematic conditions. The display flash Fault and/or
Warning when these conditions occur.
Output : 4-20 mA
Power supply : 230 VAC @ 50/60Hz
Response Time : Less than 5 sec
Accuracy : <10 NTU : 0.0001 NTU
<40NTU: +/-2% of reading or +/_ 0.02 NTU whichever is
greater.
Repeatability : +/- 1 % of the reading
Outputs : 1 x 4 -20mA current output, Bidirectional RS485 Modbus, 2 x
relay freely programmable
Material
Enclosure : Polycarbonate
Sample Cuvette : Borosilicate Glass
Flow through Fittings : Polypropylene/ss
Inlet tube : Stainless Steel

Necessary Flow through chamber with ½’’ NPT process connection shall be provided
for real time readings.
Installation:- instrument shall be installed at the locations mentioned in this document
or as directed by the Engineer in charge with suitable protection and digital display
arrangement for the instrument as per site situation. Instrument shall be interfaced
with local PLC to provide the real time information / data at Central Monitoring
System.

Page 11 of 53
7. Item No. 7 pH meter

All pH analyzer instruments shall be provided with integral LCD display and shall be
designed for field mounting. The measuring / transmitting equipment shall be
installed local to the respective sampling point. It should have rugged sensor probe,
Automatic calibration function for easy, one-touch calibration with data output
facility to a computer or printer by optional extension unit. The instrument can
compensate for changes in the ambient temperature.

Type Microprocessor
: based
Mounting Field :Mount
Measuring Range 0 to 14.00
: pH
Power Supply 16-48: V DC
Out put 4 to 20
: mA. DC 1 for pH/ Orp
Display 2 line LCD display
Area classification Safe
Temperature compensation Automatic
:
Enclosure Class IP-65:
Size 247X170X115mm
:
Accuracy +/- 0.02
: pH
Repeatability +/- 0.2
: % of the measuring range
Resolution 0.01 :pH
pH Sensor :
Service Clear: water
Measuring Range 0 -14: pH
Mounting NPT ¾": Threaded
Temperature sensor PT 100/NTC
:
Sensor communication Digital
: with transmitter
Electrode Length 23mm+Electrode
: Guard
Maximum Pressure 10 bar:
O
Operating Temperature 110 :C
Reference Diaphragm PTFE:
Reference System Double: chamber reference system
Membrane / Diaphragm Lead :free Glass / PTFE
Field mounting Housing ABS Polycarbonate
:

Installation:- instrument shall be installed at the locations mentioned in this


document or as directed by the Engineer in charge with suitable protection and
digital display arrangement for the instrument as per site situation. Instrument shall
be interfaced with local PLC to provide the real time information / data at Central
Monitoring System.
8. ITEM NO. 8 RPM MEASURING INSTRUMENTS

Type Microprocessor based

Page 12 of 53
Duty Under + Over Speed
Supply Voltage 230 VAC
Enclosure Cast Aluminum
Protection grade IP-65
Initial time delay 1-20 Sec.
Digital Display 7 Segment, 4 digit, 0.5"LED display
Speed range 1 - 9999 RPM
Output RS-485 / 4-20 mA HART
Accuracy +/- 1 RPM
Sensor
Supply voltage 12 VDC
Enclosure Nickel plated brass tube
Protection grade IP-68
Probe size M30 X 1.5 P X 65 L
Sensing distance 9 mm + 10 % ( effective): 15 mm + 10 % ( Nominal)
Mounting Non flush

Installation:- Instrument shall be installed at the locations mentioned in this document or as


directed by the Engineer in charge with suitable protection and digital display arrangement
for the instrument as per site situation. Instrument shall be interfaced with local PLC to
provide the real time information / data at Central Monitoring System.

9. ITEM NO. 9 ENERGY MEASURING (POWER ANALYSER) INSTRUMENTS

Power Analyzer
Measurement Parameters VLN , V1, V2, V3, VLL, V12, V23, V31,
A, A1, A2, A3
W, W1, W2, W3
VAR, VAR 1, VAR 2, VAR 3
VA, VA 1, VA 2, VA 3
PF, PF 1, PF 2, PF 3
Frequency F
Sensing / Measurement True RMS, 1 sec update time, 4 Quadrant Power &
Energy
Accuracy (Wh) Class 1.0 as per IEC 62052-11, 62053-21
Input Voltage 4 Voltage inputs V1, V2, V3, VN, 110 or 415 VL-L
nominal (Range 80 to 460 VL-L
Aux. Supply (control power) 44 to 00 V ac / dc (3 VA Max)
Input Current Current Inputs A1, A2, A3, 20 mA to 6 A (field
Configurable)
Overload 10A Max Continuous
Frequency 45 to 65 Hz
Resolution RMS 4 Digit
Communication RS-485 Modbus RTU Protocol
Isolation 2000 volts AC for one minute between communication
& other circuits
Demand Integration period multiple of 5 minutes from 5 to 30
minutes 15 sec. update time
Safety Measurement category III, Pollution Degree 2,
Protection against shock by double insulation at user

Page 13 of 53
accessible area
Pumping Hours Measurement Possible
Reputed Make:- Conzerve/HPL Socomec/Schneider/ L & T /Msystem

Installation:- instrument shall be installed at the locations mentioned in this


document or as directed by the Engineer in charge with suitable protection and
digital display arrangement for the instrument as per site situation. Instrument shall
be interfaced with local PLC to provide the real time information / data at Central
Monitoring System.

10. ITEM NO. 10 ALL REQUIRED COMMUNICATION INTERFACE, SCADA INTERFACES,


TELEMETRY INTERFACES, RTUS / PLC HARDWARES, CONTROLS

General Description of Proposed System


The Telemetry / SCADA specified herein shall be designed, manufactured, installed,
tested and shall provide along with the following functions:

To provide central monitoring system and Master Control Centre to collect, store,
control and monitor the Water Distribution Management System (WDMS) PCMC
water supply and monitoring system etc.
 To monitor Real-time water distribution & management process
 To perform calculations based on sensor and manual operator data inputs.
 Store and retrieve all the information of each location.
 Compile and prepare daily, weekly and monthly reports for water & energy
and as directed by engineer in charge.
 Provide mimic / graphic display to indicate water supply and distribution
system through extensive graphics support, which also reduces the learning
curve of an average operator. All the data logged at central server shall be
analysed through representation of this data in various meaningful user
defined graphs, trends and customized analytical requirements of the
system.

All the required field instruments to measure flow, level and pressure, residual
chlorine shall be provided, calibrated, tested and installed. The signals from the
field instruments both existing and newly proposed instrumentation shall be wired
to the PLCs / RTU’s with necessary programming etc. complete for further
communication and data integration with Central SCADA Server software.
The system shall be open system architecture utilizing standard operating and
communication systems like GPRS (4G LTE router with dual SIM). The system
supplier shall provide documentation of successful field performance of the
proposed system, including hardware and software applications. Unproven or
proprietary systems shall not be acceptable.

The SCADA / Monitoring Requirements;

Page 14 of 53
a) Layout drawings for each piece of equipment fabricated or assembled by the
Contractor, showing the position of each component with required clearance
where applicable, and with overall dimensions.
b) Wiring diagrams indicating each component of the system and all wiring and
cabling thereto, showing manufacturers, types, duties, ranges and
nomenclature, referencing the P&I diagram where applicable, with inputs,
output, cable wiring and terminal identifications clearly marked.
c) PLC/ RTU IO instrumentation drawings, cable along with sizings and cable
layout trenches as per site condition.
d) Communication details / protocol details for all communicating instruments viz.
PLC, GPRS telemetry, SCADA, etc. shall be provided.
e) Mimic video displays in the form of hard copies or photographs which are
clearly legible and are notated to indicate dynamic data and control pick points
where applicable.
f) Control video displays in the form of hard copies or photographs which are
clearly legible and are notated to indicate dynamic data and control pick points.
g) Complete input and output list giving type, circuit number, tag name, short
description, outstation, database reference, associated field device, range (if
applicable), critical/non-critical alarm status and the like.
h) Description of quality control methods and approvals.
i) Calibration certificates for all the instruments along with test procedures.
j) Detailed works and acceptance test procedures.
k) Programme for manufacture, delivery, installation, interfacing and
commissioning.

RTUs / PLCs General Specifications


Based and requirements as stated above and system architecture defined in Section
6, Contractor shall be responsible to supply, install, commission the RTU’s / PLC’s as
per the General Requirements as below:-
1. RTUs / PLC enclosures shall be corrosion resistant welded for outdoor locations.
Enclosures shall be fabricated from a minimum of 14 gauge cold rolled steel
with a baked enamel finish in the manufacturer’s standard color. The modular
design allows for efficient system updates, flexible baying options and virtually
endless configurations, all based on a robust 16-fold tubular frame system

2. RTUs / PLC protected from lightning or other transient voltages by a power


arrestor.
3. Condensation protection shall be provided to RTUs / PLC. Enclosure shall have
the arrangements to prevent condensation build-up.
4. All power supplies required for operation shall be provided. Power supplies
shall be sized to have a minimum of 40% spare capacity providing increased
reliability and allowing for the addition of future equipment.
5. All wiring shall be in complete conformance with the standards as specified in
general specifications. All wiring neatly tied and fastened and for ease of
servicing and maintenance, all wiring shall be color coded and uniquely
numbered.
6. Battery Backup system for RTUs / PLCs shall be provided and working in
conjunction with the unit’s power supply, shall be an intelligent battery backup

Page 15 of 53
system including voltage converter, battery health logic module, charger and
sufficiently sized battery. Battery system shall provide a seamless switchover to
battery upon detection of main power supply failure. Once main power is
restored, the unit shall provide seamless switchback to normal power source
and recharge the battery. Battery health logic module shall individually monitor
main power supply, battery and converter voltages for low voltage conditions,
and provide low voltage cutoff to protect battery from an unrecoverable
depletion.
7. Battery system shall be of sufficient capacity to provide a minimum of four (6)
hours of backup in the event of a failure of the main power source. To avoid
battery damage and erroneous data transmissions when operating on battery,
should the battery voltage drop below 10.8 V, the PLC shall be inhibited from
operation. Recovery shall be automatic upon restoration of normal power. The
intelligent battery back-up system shall be able to source 5 Amps allowing
operation of mission critical components including; sensors, local alarm and
communication equipment during a power failure condition.
8. All RTUs / PLCs shall be SMART and shall have real time multitasking soft-ware
and powerful communication Capabilities.
9. It shall be comprising of CPU and signal conditioning ends for analog and digital
signals.
10. It shall have a LCD display for indicating local data. Matrix keyboard shall also
be provided for interface. The LCD display shall be in the form of an HMI
minimum 7” TFT LCD screen.
11. All RTUs / PLCs signals, status signals, alarm and process variable data shall be
transmitted and received between the central location and the remote
locations via the radio telemetry system. The system shall convert commands,
alarms and variable analog data to digital blocks and transmit this information
between the Central and the multiple remote locations.
12. RTUs / PLCs shall be furnished completely configured and tested for providing
the specified communication, monitoring, display, input/output, annunciation,
etc. for the Central Monitoring System. Any additional components required for
operation, whether specifically referenced herein or not, shall be provided.
13. RTUs / PLCs system shall be based on a robust, field proven, current technology
hardware platform allowing utilization of the latest advances in technology and
permitting the most open programming and communication architectures. The
PLC system shall be modular and scalable to be efficiently applied at each of the
specified sites within the system.
14. RTUs / PLCs shall store field /system parameters including, logic configuration,
set points, time delays, alarm and event data, counters and tantalizers, etc. in
field programmable non-volatile memory. Sufficient non-volatile memory must
be provided to store up to 7 days of data. The PLC shall also provide enough
protected memory for time stamped data logging for upto 06 months.

Page 16 of 53
RTUs / PLCs allow telemetry operations over radio frequency communication media
as well as GPRS media affording the most efficient and reliable operation.
Telemetry System communication architecture can be based on any one or a
combination of these communication media.

RTU/ PLC Specifications :-


The Remote Terminal Units (RTUs) shall be micro-processor based units of modern
field proven design. RTUs must be modular in design to allow expansion of any
count communications and I/O interfaces and capable of a variety of data transfer
methods using various communications media as above.
THE RTU’s MUST AS A MINIMUM HAVE THE FOLLOWING FEATURES:-
A) GENERAL
1) The RTU programming language used shall be windows based.

2) Input / output modules shall be furnished to accommodate all process and


data controls plus any additional modules not mentioned but required to carry out
any additional necessary for operation of the facility, shall be supplied and
implemented by the Contractor.

3) RTU/PLC shall be modular or Flexible backplane arrangement that allows


distribution of RTU modules within a single enclosure, or distributed between field
enclosures. Each individual module shall be coded and encased in a protective
housing isolating the internal circuits from handling by human hands. Each module
shall have LED displays for status indication. The complete RTU, including RF stage,
shall be of industrial grade capable of operating in harsh environments especially
temperature. The RTU/PLC must be having UL certification.

4) The RTU shall be auto-configuring at startup whereupon the contents and slot
location is automatically identified to the programming software when it is
initialized. The RTU shall auto-execute a self-diagnostic upon initialization.
Diagnostic results shall be available to the programming software via local
computer and/or remotely via radio interrogation.

5) Processor modules shall be minimum 1Ghz quad core processors with a


minimum of 32MB RAM (for data storage) &flash RAM (for firmware/program
storage) and have a minimum of 2 communications ports each. RTU should have a
retentive mass memory NVRAM ( min 32Mb). The RTU applications programs and
firmware shall be remotely downloadable via the communications network. It shall
also be possible to add communications functionality (e.g. additional protocols) to
the RTUs without visiting site. Applications programs (site database and logic
program/s) shall be able to be uploaded from the RTUs.

Page 17 of 53
A. DATA TRANSFER
The RTUs proposed MUST support a number of data transfer philosophies that
include,
1. Standard polling – where the master station continuously requests some/all
real-time data values.
2. Exception Reporting – where the RTU initiates messages.
3. Time tagged data uploads – where the master station requests data that has
been logged based on its priority/class. All data is logged in an event log buffer
with a time stamp of 1mS resolution (system wide accuracy of 10mS or better).
4. Dynamic message routing –RTUs must be able to ‘learn’ of changes to network
routing and dynamically change message routes.
5. Peer-to- peer communications – allowing RTUs to communicate with each
other rather than simply with a master station.
6. Store and forward communications – allowing RTUs to ‘pass on’ messages for
other RTUs. This is used to extend the coverage of point to multipoint style
networks and also allows linear communications paths (where RTUs are
typically ‘daisy chained’).
7. Transparent port connections – allowing RTUs to ‘connect’ ports between
remote locations for the transfer of non-RTU data/messages. This requires the
RTU to receive and package a non-RTU message within a RTU message packet
for transfer to another RTU location for output (the output message is stripped
of the RTU message headers, CRC etc.).

B. POWER SUPPLIES
The RTU power supply shall accept AC or DC input and provide all necessary
power to support the RTU operation. The power supply outputs shall be fully
isolated from the input power source and include both monitoring and control of
the various outputs to allow advanced power management functionality. The
power supply shall be able to run from its standby battery for a minimum of 6
hours.
Battery Backup shall maintain operation of fully configured RTU, radio, I/O power
for a minimal of 6 hours assuming a radio transmission every 10 minutes. The
battery charging system shall provide maximum battery capacity and life.
C. COMMUNICATIONS EXPANSION MODULES
The RTU shall have minimum 03 ethernet ports & it shall be possible to support
additional 16 ports if so required.
D. BACKPLANES
Backplanes shall allow distribution of RTU modules within a single enclosure, or
distributed between field enclosures.

E. DATA LOGGING
The RTU shall have data logging capability of any I/O or register data value. The
event log entry shall be time tagged with a 1 mS resolution time stamp and each
entry shall include the following parameters:
 year, month, day, hour, minute, second, millisecond,
 RTU ID, data ID, data priority (0-7), data user type (0-31)
 data value, (2 bytes)
The event log capacity shall be configurable in the RTU memory setup, with a
minimum capability of event logs for upto 6 months before any data is

Page 18 of 53
overwritten. The RTU logic shall allow the packing/archiving of ‘old data’ using
the data priority field to mark data older than a specified period as deleted.
The RTU event logs shall be retrievable using any/all arguments of;
 date/time,
 priority,
 user type,
 RTU/data ID
The RTU/PLC stored data must have sufficient security. It shall be possible for internet
connected user to see these reports from remote location.

F. LOCAL COMMUNICATIONS
The RTU shall support a number of device drivers that allow communications with
local devices such as meters, PLCs, and other intelligent electronic devices (IEDs).
These interfaces will typically operate on any of the RTU communications ports
using data transfer protocols such as DNP3, MODBUS,Modbus TCP or Profinet
HART, etc. The drivers for the same should be resident in PLC/RTU.The RTU shall
allow the use of multiple protocols per communications port.

G. NETWORK COMMUNICATIONS
The RTU shall be capable of communications within a network of greater than
1000 RTUs using industry standard SCADA protocols. The RTU shall be
configurable to manage network communications in slave mode, master mode or
as a data concentrator (where a data concentrator operates in both slave and
master modes). The RTUs shall maintain ‘images’ of network data received from
other RTUs to allow reference of such data (and its communications status) to be
included in the RTU logic.

H. RTU DIAGNOSTICS
The RTU shall have in-built diagnostics that allow local and remote interrogation
of diagnostic information. Basic diagnostic information shall be presented to the
user via the module LEDs and advanced diagnostic information via the RTU
programming and configuration interface program.
The advanced diagnostic information for I/O modules should include the
health/presence of each RTU module and the current state/value of each I/O
channel (including power supply I/O data). Diagnostic information specific to the
processor module and RTU in general should include the scan rate of I/O and
logic, the current time and date, the RTU firmware version, firmware options (i.e.
protocols, application extensions etc.), list error status flags. Communications
statistics should be accessible for each RTU in the network that include the
number of message successes; message fails and fails since last success.
The RTU shall have port monitoring capability that allows local and remote
capture of messages to/from any RTU port for display in the programming and
configuration interface.

I. SPARE CAPACITY
Each RTU shall be sized to accommodate all of the I/O listed in the scope of works
and include an additional 20% spare installed I/O capacity. There shall be at least
2 backplane slots spare in the offered solution for RTUs with up to 24 modules
and at least 4 backplane slots spare for RTUs with greater than 24 modules.
J. SECURITY

Page 19 of 53
The RTU shall have two types of security, one for the programming and
configuration interface and the other for the RTU ports.

K. Programming and Configuration Interface - User Security


The programming and configuration interface shall support at least multiple
levels of user access that can be configured by a system administrator. These
should include as a minimum,
1. Unlimited Access Allows unlimited access, can read and write all
RTU parameters including configuration
parameters. RTU parameters include :- Local
Registers, Network Registers, System Registers,
Hardware (I/O) Registers, Event Logs, and Logic
Program/s.
2. Read All, Write All (except config.)Allows reading and writing of all RTU
parameters, except for System Registers and
Ladder Logic. Thus reconfiguring an RTU is not
possible from this access level.
3. Read All, Limited Write Access Allows reading all RTU parameters. Writing is
limited to some Local Registers. No other
parameters can be written at this access level.
4. Read-Only Access Allows reading all RTU parameters. No
parameters can be written at this access level.
5. Limited Read Access only This access level allows reading some Local
Registers. No parameters can be written.
6. No Access No RTU parameters can be read or written. This
access level is useful only for RTU port
configuration.
Whenever the interface program is started, the user should be prompted to enter
a username and password. This is checked against the User Database, to verify
the password, and to provide the authorized access level. Alternatively, the user
can select 'View-Only' mode.

L. RTU Security
Each RTU Communication Port shall have a configurable access level.
The access of data shall be password protected. The levels of security shall also
be configurable.

Minimum Technical Specifications for PLC/RTU:-At ESR/ GSR Level the non-
redundant Processor with suitable redundant power supply and communication
interfaces shall be used while designing the system. The processor should be
capable of handling minimum 2048 hard wired / wireless I/O’s in addition to the
internal process and functions.

Communication between the I/O modules and Processor should be smooth and
without any interruption. The process signals will be “hold previous good” during
hot-swapping of any I/O module.
The power supply module for the processor and I/O should be suitable to provide
smooth power to the all instrumentation in the PLC panel and shall be working on
UPS backed 230 V AC power supply.
I/O Modules:

Page 20 of 53
The proposed I/O modules should be have identical Channel density and shall be
from the same product family as that of processor. The I/O modules should be hot
swappable.
Sr. No. Description Specification
1 PLC Type Standalone PLC
2 IO details 48DI ,24DO , 16AI,8AO
3 Operational Voltage 24V DC
4 Display Local indication using LED
5 CPU Quad core processor up to 1Ghz processing
speed
6 Programming Memory 32 MB ON board memory
& Data Memory
7 Clock Real time clock (RTC)
8 Communication port 3 Nos 10/100 base Ethernet port,
1 Nos USB Port
9 Ethernet Services FTP Server, SNMP, DHCP Client, IEC
VAR Access, Modbus TCP Server/Client
10 Web Services Web Server
11 Operating temperature -10 to 70 deg C.
12 Storage temperature -40 to 70 deg C
13 Humidity 5- 95 % Non-condensing
14 Cybersecurity As per IEC62443
certification
15 Vibration 3 gn (vibration frequency: 8.4...150 Hz) on
panel mounting
16 Shock Resistance 15gn for 11 ms
17 Operating Altitude 0 – 2000m
18 approvals UL

While defining the channel density of the I/O modules, I/O requirement for each
location shall be taken into consideration. In addition to the required I/O at each
location, 10 % spare I/O’s shall be provided in each panel.
Human Machine Interface (HMI): The panels requiring local display and control of
the process shall be provided with the suitable color touch-screen HMI mounted on
the front panel and interfaced with the PLC processor. The HMI software should be
designed in such a way that it will cater to the local monitoring and control
requirements.
All analog input channels shall be provided with the surge protection and signal
conditioning devices as may be required. The Digital Output Channels shall be
provided with the interposing relay to avoid the high voltage surges.
PLC panels should be provided with required space heathers, ventilation and fan
arrangements, Electrical Service socket and earthing arrangements and shall be
wired as per the relevant standards and norms adopted for such panels in the
industry.
Specifications:-

PLCs Specifications (At MCS):-


At Master Control Room located at Central Station. PLC should have redundant
Power supply system for smooth and break free running of the system. CPU at

Page 21 of 53
Master station shall be hot redundant having capacity of handling remote I/O‘s in
addition to the internal process and functions
The program memory of the processor be of NV type shall have internal battery
backup. The processor should continue functioning as defined the process logic
after power restoration and should not require any manual intervention.
All the ESR/GSR RTU shall communicate with the redundant CPU at MCS , The
architecture shall be as below:-

11. ITEM NO. 11 VALVE ACTUATORS

Actuators are proposed for sluice valves at pumping locations wherever in plant
SCADA proposed or any other locations proposed by PCMC like ESR /GSR’s.
Proposed quantity is subject to increase or decrease. The actuators proposed here
shall be smart having features like multi turn 3 phase actuator having appropriate
bracket / mounting arrangement including 2 nos. of limit switches for open and
close condition, torque limit switch and splash proof enclosure. The actuator shall be
selected by the vendor as per site condition & their torque rating shall be as per
valve on the proposed location. The Actuators shall be suitable for the medium,
climatic, environmental and pressure conditions of the system in which they are to
be fitted. Actuators shall be provided with:
(a) AC Electric Motor with minimum class insulation.
(b) Reduction gear unit.
(c) Torque switch mechanism with relay output.
(d) Limit switch mechanism complete with set of limit switches and
additional two spare sets for suitable position.
(e) SS Hand wheel, for manual operation.
(f) Valve position indicator.
(g) Hand-auto lever with suitable locking arrangement.
(h) 10 W single phase space heater in the switch compartment.
(i) Blinking light throughout the valve operation.
(j) Junction box for terminating power and control cables.
(k) with in built serial RS485 MODBUS RTU port

(l) It should have smart features like smart Phone app to upload logged
data from actuator
(m) With additional accessories for integrating with PLC system.

The actuator shall be suitable for operation on 415V, 3 phase, and 50 Hz power
supply. The motor winding insulation shall conform to Class H & duty shall conform
to Class C(: Modulation or modulating duty. The actuator is required to frequently
drive the valve to any position between fully open and fully closed). as per relevant
BS and motor shall be protected by suitable thermal overload relays. The actuator
shall be capable of producing not less than 1 1/2 times the required operator torque
at the required time cycle of valve operation. The transmission shaft connecting the
actuator to the valve shall be provided with 2 bearings one at actuator end and one
at valve end with universal couplings at suitable places. The required numbers of
switch/contacts meet requirements for PLC system. The electric motor shall be of
the squirrel cage type as per IS 325 with insulation to IS 1271 Clash & duty as per
class C( &in compliance with EN 15714-2). The windings shall be impregnated to
render them non-hygroscopic and oil resistant. All internal metal parts shall be

Page 22 of 53
painted. The motor shall be rated for 15 minutes. They shall also be suitable for
operating on the specified electric supply and shall satisfactorily open and close the
valve under variations of electric supply specified.
Motor shall be protected by suitable overload protection device. The reversing
contactor starter and local controls shall be integral with the valve actuator. The
starter shall comprise mechanically and electrically interlocked reversing contactors
of appropriate rating fed from a 110 Volt control transformer. The common
connection of the contactor coils at the transformer shall be grounded. HRC
cartridge type primary and secondary fuses shall be provided.
Local control shall comprise pushbuttons for open, close and stop operations and a
Lockable Local/Remote/off selector switch. The control schematics shall be subject
to approval. Internal wiring shall be of 650/1100 volt grade PVC insulated stranded
copper conductor of minimum 1.5 sq. mm for control circuits and of minimum 4 sqm
copper for the power circuit. Each wire shall be number identified at each end. The
terminals shall be of stud type.
Cable entries shall be suitable for PVC insulated/ sheathed, armored cables. A
separate terminal box shall be provided for the heater. A separate terminal box shall
be provided for cabling to control circuits.
The actuator enclosure shall be fully weatherproof and hose proof to IP 67 and shall
be fitted with an anti-condensation heater, which shall be switched off when the
motor is running. The torque switch mechanism shall function as follows to stop the
motor on closing or opening of the valve, or upon actuation by the torque when the
valve disc is restricted in its attempt to open or close.
The torque switch in the closing direction shall interrupt the control circuit if
mechanical overload occurs during the closing cycle or when the valve is fully closed.
The torque switch in the opening direction shall interrupt the control circuit if
mechanical overload occurs during the opening cycle or when the valve is fully open.
The mechanism shall facilitate adjustment of the torque at which the switches are
required to operate. Non-adjustable limit switches shall stop the motor and give
indication when the disc has attained the fully open or closed position.
The adjustable limit switches shall have control rated 2A, 48 V DC for specified
system interlock, at the desired value position in both the opening and closing
directions.
Motor Operator shall be provided with clearly visible local valve position indicators
mounted on the operator assembly to give an indication whether the valve is fully
open, fully closed or in an intermediate position.
Settings and emergency operation shall be possible with the use of a hand wheel.
The Hand wheel shall be of stainless steel and the drive mechanically independent
of the motor drive and any gearing should limit the operating torque at the hand
wheel to less than 15 kg and be such as to permit emergency manual operation in a
reasonable time. During electric operation the hand wheel shall not rotate.
Actuators shall be adjusted at the manufacturer’s works to ensure that they provide
the correct, fully, open position and fully closed position. Mechanical adjustable
stops shall be provided to prevent over-travel of the valve in the open and closed
positions.
The contractor shall supply the required dia of valves at his cost. The valves shall be
accepted after the third party inspection by SGS, RITES or any other agency
authorized by PCMC, the charges for the same shall be borne by the contractor.

Page 23 of 53
12. ITEM NO. 12 INTERFACING OF VALVE ACTUATORS

At ESR / UGRs / MBRs Inlet and Outlet Water pumping Locations or any other
locations within distribution system, there may be chances of having existing valve
actuators installed already. It will be the responsibility of the Contractor to interface
with the telemetry system and control the valve through telemetry / SCADA system
if suggested by PCMC. It is inclusive all the required accessories like sensors,
transmitters, cables, power points etc. to be provided to interface with the valve
actuators and communicate the data with Central Server Station. Consent from
PCMC is required before taking up such work.
It is the responsibility of Contractor to provide complete interfacing required to
receive the data from such valve actuators.

13. ITEM NO. 13 SCADA Controlled Flow Control Valve

There are too many direct tappings and bypass points within the distribution system
on transmission mains. Such points shall be installed with flow meter and flow control
valve. Such FCV’s shall be operated as per the water requirement or water demand or
as instructed by PCMC. Contractor shall need to understand the water supply network
and agreed upon the operational philosophy for valve management control and also
to regulating the direct dappings points for water distribution management in due
consultation with PCMC officials.
Such FCV’s shall operate remotely on timer or remote switch which will operated
from central control station over GPRS (4G LTE) based network. Also this Remote
Controlled Water Delivery Unit / FCV has arrangement to control flow rate of water,
hence it is possible to have equal distribution of water by simple monitoring and
control. Remote Controlled OHT/MBR/ESR management system has arrangement of
measuring volume of water flow delivered into the system and information to control
the same. The indicative location of flow control valve locations are as following
which is subject to change / modify. PCMC is in the process of removing such direct
tappings points but it is not possible practically then FCV shall be installed at such
locations.

The technical specification of the SCADA Controlled FCV’s are as below;

Function

- The valve will be controlled by an electronic-controller, which enables control of


the requested flow rate or as per demand and it should have facility to be

Page 24 of 53
controlled through existing SCADA system at end user. The controller should
enable receive as an input either pulse/volume contact-input or 4-20mA
analogue signal.
- The start / stop operation of the controller can be made manually or by external
dry-contacts (digital) signals.
- The Flow Control valve should have the opened feature of timetable Vs Flow
rates to enable change of set points during different times (peak, non peak,
night hours) during operation. The set point change should be possible as well as
from existing SCADA system.
- The valve should be able to perform flow control as well as combination of
hydraulic control, if required at site.

Electronic Controller and trim.

- The controller will activate the main control valve by two 2/2 Solenoid valves.
One solenoid closes, the other opens the valve. The controller should activate
the solenoids by electric pulses, when a controlled parameter deviates from its
programmed value.
- The programming of the controller should be made in plain English, no special
programming skill will be required
- The programming will be protected from un-authorized change, by entry codes.
- The controller requires continuing supply of energy to activate the solenoids. It
can be provided by a local 24V, 220 or 110VAC grid, by water-driven turbine or
by a solar panel. All supply sources will charge a rechargeable battery, which
enables sufficient energy to run the valve and sensors for at least seven day of
power cutoff .
- The initial programming of the controller will not be lost, even in the case it is
not supplied by any power source, including the battery.
- The controller will be insulated against direct water spraying and dust to IP65.

Main Valve

- The valve shall be hydraulically operated, direct diaphragm type , single chamber
weir type / globe type
- The valve shall consist of three major components: the body, stem, cover and
the diaphragm assembly. The diaphragm shall form a sealed chamber in the
upper portion of the valve, separating operating pressure from line pressure.
- The standard valve model fits all control operations, using different pilot control
systems.
- The standard valve body is made of ductile iron, withstanding both high
hydraulic and mechanical stresses. While the valve closes, the closure pace
slows down, reducing the risk of water hammer.
- The valve shall contain a resilient, nylon reinforced rubber diaphragm.
- The ratio between valve flow capacity (KV) / Cv and the valve position shall be
linear so to allow stable regulation even under high pressure differentials and
low-flow conditions.
- Disassembly and reassembly of all the valve's components shall be made
possible on site, without having to remove the valve from the line.
- Each valve should be hydrostatically tested at least 60% above the rated
pressure. A test report should be supplied with each valve.

Page 25 of 53
- Control-trim's fittings and devices will be produced of brass or SST and the
control-tubes shall be flexible, reinforced polyethylene or higher grade and shall
be hydrostatically tested with the main valve
Operation
- In case the valve will be used in the future for pressure-reducing function, it
should, in all the specified diameters, regulate in a stable accurate manner even
if the demand flow speed reduces to less than 0.3 m/sec as a standard feature.
This is made possible, without having to adopt additional throttling device, and
without having to install additional smaller low-flow by-pass valve.
- The pressure losses inflicted by the above mentioned fully opened valve should
not exceed 0.3 bar at nominal flow speed of 3 m/sec.
- The pilot system will be such that allows full venting of the control chamber to
minimize pressure losses when the flow is lower than the regulated set-value.
- Complete closure time shall be controllable and shall not be longer than 10
minutes from fully-open position at minimal flow conditions.

Maintenance
- The valve should require low maintenance. No set periodic packing or parts
replacement should be required.
- The valve's pilot control loop should include a low maintenance, inline "self-
cleaning" control-filter.
- Valve manufactures / vendor shall have service center in India and technical
support / repair services shall be available if required in a quick time.

14. ITEM NO. 14 LIGHTING / SURGE PROTECTION SYSTEM

Both lighting and Surge protection shall be provided to protect all electronic
instrumentation system from induced surges propagating along the signal and
power supply lines. The protection systems shall be such that the protective level
shall not interfere with normal operation, but shall be provided. Field instruments
(regardless of location outdoors), shall be protected by isolation transformers and
surge suppressors. Individual field instruments shall be protected by surge
suppressers. Surge suppressors shall be provided for 4-20mA inputs, ethernet ports
& power supply

Technical Specifications:-
LIGHTNING SURGE PROTECTOR FOR ETHERNET Communication protection (PoE / 10
BASE-T / 100 BASE-TX / 1000 BASE-T)
The surge protector must have CE & UL approval marking according EN 50581 or
above for RoHS directive and EN 61000-6-2 form EMC Directive
Also equipped with the Surge protection capability of IEC61643-21(Category C1,C2)

Should be designed specifically for Ethernet network


Conforms with 1000 Base-T, PoE and PoE Plus -circuit bar
DIN rail mounting
Applicable network: -
10 BASE-T: IEEE 802.3i 100 BASE-TX: IEEE 802.3u 1000 BASE-T: IEEE 802.3ab
PoE: IEEE 802.3af PoE plus: IEEE802.3a installation

Page 26 of 53
Operating temperature: -25 to +85°C (-13 to +185°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)

PERFORMANCE
Max continuous operating voltage :±6V Line to Line (Pair), :58V Line to Line(PoE),
±150V Line to Earth or better
Voltage Protection Level: :±15V max @2KV Line to Line (Pair), ±100KV max @2KV Line
to Line(PoE), ±600KV Line to Earth or better
Leakage Current : 25µA Line to Line (Pair), 25µA Line to Line(PoE), 5µA Line to Earth or
better
Max Discharge current: 100A Line to Line (Pair), 100A Line to Line(PoE) , 10kA Line to
Earth or better
Nominal current : 1A Line to Line (Pair), Line to Line(PoE) , Line to Earth or better
Series resistance : 0Ω

SURGE PROTECTOR FOR AC POWER SUPPLY

The surge protector must have


CE & UL approval marking according EN 50581:2012 or above for RoHS directiveCE &
UL approval marking according EN 61000-6-4:2007 or above for EMC directive
CE & UL approval marking according EN 61010-1:2012 or above for low voltage
directive
Performance :
Designed specifically for AC power supplies up to 5 amps
Discharge current capacity 10000 A
The surge protector should have life monitor
LED display and alarm contact output indicate the degradation and life span of the
surge protection circuits
No power supply interruption even when the unit is degraded or at the end of its life.
Construction: Plug-in
Alarm indicators Power: The LED turns on while the circuit is alive and the internal
fuse is not blown; and is off when the power supply is removed or the fuse is blown.
Alarm contact: The N.C. contact is on when the life span of the discharge elements
has ended, when the voltage limiter has degraded, and/or when the power supply is
removed.
Rating: 125 V AC @ 0.5 A (cos ø = 1) 30 V DC @ 1 A (resistive load)
Maximum switching voltage: 125 V AC or 110 V DC
Maximum switching power: 62.5 VA or 30 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Operational voltage range: 180 264 V 50/60 Hz, approx. 2 VA
Discharge voltage (peak voltage) Line to line: 410 V min. Line to ground: 400 V min.
Maximum surge voltage Line to line: 700V max. Line to ground: 800 V max.
Withstand voltage of protected equipment between the circuit and the metal housing
must be
1000 V AC or more.
Response time :<0.01µsec

Page 27 of 53
Leakage current : <14mA at 200V AC Line to ground:<0.1mA at 300 V AC
Discharge Current capacity : 10000 A(8/20 µsec)
Maximum load current : 5Amps , Internal series resistance :0.5Ω
EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2
Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2
Alarm contact to power: Reinforced insulation (300 V) RoHS Directive EN 50581

Surge Protection for for 4 – 20mA DC a


Should be suitable for both 4-wire and 2-wiretransmitters
Absorbs surges only without affecting instrumentation signal
No interruption of signal by unplugging surge protector element
Operating temperature: -5 to +55°C
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Performance Max. continuous operating voltage : Line to line: 30 V
Line to earth: ±140 V
Voltage protection level (Up):
• @ 1 kV (100 A) Line to line: 40 V Line to earth: ±650 V
• @ 2 kV (1 kA) Line to line: 45 V Line to earth: ±800 V
Response time: Line to line: ≤ 4 nsec. Line to earth: ≤ 20 nsec.
Leakage current: Line to line: ≤ 5 μA @ 30 V DC
Line to earth: ≤ 5 μA @ ±140 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
Nominal current (IN): 100 mA
Internal series resistance: 20 Ω ±10 % (including return)
Capacitance @ 1 MHz: Line to line: ≤ 1000 pF
Line to earth: ≤ 100 pF
Surge protection: IEC 61643-21
Categories C1, C2, D1
Standards & approvals
EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2RoHS Directive EN
50581Approval:Protectors for Data

15. ITEM NO. 16 INSTRUMENTATION CABLE WITH ALL REQUIRED ACCESSORIES

All cabling required for connecting all field instrument, sensors, transmitters, PLC
etc. Shall be provided by Contractor. This item shall be executed as per specific
requirement supported with justification with prior consent and approval of the
Engineer.
Specifications for cables: ‐
1. All conduit and cable entering control panel shall be gland sealed to prevent the
intrusion of gas and moisture.
2. All signal cables for carrying 4‐20 Ma , 0‐5 V, low level transducer outputs, etc.
shall be copper PVC insulated twisted pairs, individually screened with tinned
copper drain wire, overall screened, steel wire armored and overall PVC sheath.
The twisted pairs shall be constructed with 24‐30 twists per meter.
3. The rated working voltage shall be 100 V rms and the maximum working voltage
shall be 600 Vrms. The continuous current rating shall be at least 5. Insulation
between conductors and earth shall not be less than 10 Mega Ohms at 500

Page 28 of 53
Volts.
4. Screening shall provide a minimum of 95% coverage of Copper braid or Mylar
backed Aluminum foil. Individual shields in multicore cables shall be insulated
from each other and from the overall shield and armoring.
5. Strict segregation shall be followed with not more than one type of signal run in
any multicore cable. The different types of signals shall be segregated from
each other and shall be contained in separate cables.

Application For connecting sensors and transmitters


Type Copper, PVC insulated, Shielded with aluminum
polyester tape with tinned copper drain wire,
Twisted pair, overall shielded with aluminum
polyester tape with tinned copper drain wire PVC
inners heated GI wire (0.90mm) Armored, PVC
sheathed cable as per IS- 5308

No of pairs 1 pair X 1 X 1 Sqmm / 1 pair X2 X 1 Sqmm / 1 pair X


3 X 1 Sq. mm
Working Voltage 100-600 Vrms

Application For providing power to field equipments


Type PVC insulated PVC sheathed copper conductor
armored cable1.1 KV grade as per IS 1554
No. of core 2/3/2004
Gauge 1.5 Sq.mm
Working Voltage 1100 Vrms

Application For providing power to in house equipments


Type copper flexible, unarmored, PVC insulated
No. of core 3
Gauge 1.5 Sq.mm
Working Voltage 1100 Vrms

16. ITEM NO. 16 RCC CHAMBERS

RCC Chambers of required size (tentative 2m X 2m X 2.5m) at site in M20 grade


concrete shall be constructed on site for electromagnetic flowmeters and flow
control valves. Item includes:-
1) Excavation for construction of instrument chambers in all types of soils and
surfaces in all types of site conditions including drainage, dewatering, etc.
including back filling.
2) The chambers shall have P.C.C of 150 mm thick below foundation, R.C.C. wall
150 mm thick, R.C.C. precast roof cover in MS angle frame in strip of 30 cm
width with proper hooks for lifting, necessary number of M.S. steps embedded
in wall etc. complete.
3) The frame for the cover shall be fixed as per standard drawings. The top level of
frame shall be flush with the road level or footpath level as the case may be.

Page 29 of 53
4) Cover lifting arrangement shall be made so that the cover may be lifted easily
5) The chamber cover and frame shall be able to withstand heavy duty grade of
loading conforming to relevant IS code, square type and shall be galvanized
according to ISO : 1460 R & R 1461 or IS 4736
6) Each chamber cover and frame shall have a permanent marking sunk cast on
them providing following information: Year of manufacture. Figure of PCMC
emblem.
7) Where a road or footpath is to be kept opened up in the course of work, special
care shall be taken to see that proper protection is provided to prevent any
accidents from occurring. Work shall be done in such a manner that it will not
unduly inconvenience pedestrians or occupants of buildings or obstruct road
traffic.
8) Care shall be taken to see that apparatus, tools or other excavating instruments
are not left in a dangerous or insecure position as to fall or be knocked into
trench thereby injuring any workmen who may be working inside the trench.
9) The flags and lamps shall be placed in conspicuous position so as to indicate the
pedestrians and drivers of vehicles the full extent, i.e. both width and length of
the obstruction. The distance between lamps or between flags shall not exceed
1.25 meters along the width and 6 meters along the length of the obstruction in
non-congested areas, but 4 meters along the length in congested areas.
10) No work shall be treated as complete until acceptance testing and quality
control checks are completed and found satisfactory.

17. ITEM NO. 17 COMMISSIONING OF WIRELESS TELEMETRY

Either Radio telemetry or GPRS (4G LTE) with VPN server as a communication media
shall be used to communicate with all locations of ESR’s / ESR / MBR/ GSR/ remote
locations. All pumping locations wherever pumping SCADA proposed if any,
preferably communication media shall be RF including central server station for
monitoring & SCADA purpose.
GPS site surveys at all locations for determining communication parameters and
tower heights at all locations of Bulk Water Pumping Stations remote locations
covered under this project including Central Station and associated cost shall be
borne by Contractor.
Unless otherwise specified following are the minimum & must requirements of the
radio Wireless communication system:-
1. The System shall monitor (both data & CCTV) all the remote locations (24 Hrs.)
2. High speed retrieve, store data from remote sites (24 Hrs.)
3. Analyze, process, print, display etc. all the field variables & data.
4. Alarm & report generation
5. The System shall support remote maintenance of radio units
6. The System shall operate up to 35 to 50 Kms.
7. The System is equipped with surge suppressors to protect it from unavoidable
lightning conditions.
8. The System shall support high level of security mechanisms such as DES for end
to end connectivity to avoid any breaches due to Interference or hacking.
9. Only licensed communication frequency band should be provided for
communication. Contractor shall be responsible to take license for RF spectrum

Page 30 of 53
from WPC (Wireless Planning & Coordination) & SACFA (Standing Advisory
Committee on Radio Frequency Allocation; Wing of the Ministry of
Communications, Delhi and shall do the necessary Liaoning.
10. Necessary Frequency Liaoning and annual Royalty charges for the complete O &
M period shall be borne by the Contractor only.
11. Remote Radio Telemetry System shall use powerful radio transceivers to
seamlessly connect Central monitoring location with remote sites.
12. Radio Telemetry System shall use rugged, high speed intelligent, radio modems
that are designed for seamless communications and capable of wireless
communications of up to 30 Kms.
13. Contractor shall be responsible to provide the proper antennas and self-
supported MS tubular Tower (triangular shape) of suitable height (approx. 30 m
height) depending upon the site location and as approved by PCMC engineer- in
charge for clear communication between all described ESR/ UGR / GSR, Pump
House location and Central Tower at Sector 23 WTP, Nigdi to ensure powerful
telemetry functionality including all other integrals required to achieve this
functionality.
14. Steel structures (towers) required for the work shall be certified by civil
structural engineer or as directed by engineer in charge. Necessary N.O.C.
wherever required while executing the work shall be provided and same shall
be approved by engineer in charge.
15. Remote Radio Telemetry System Software shall have an easy to use, intuitive
interface. The built-in address book should allow to quickly set up radio
telemetry system monitoring sites with a unique identifier and name.

Unless otherwise specified following are the minimum & must Technical
Specifications for the Wireless Communication system:-
For ESR / Pumping Stations / Pure water Pumping System/ remote locations:

RF Modem
1. A single control room should communicate with proposed remote locations
2. System should be capable of communicating faithfully over the distances of 30-
35 Kms in a city area like Pimpri-Chinchwad Municipal Corporation Boundary.
3. Output Wattage of Wireless Data communication System should be 1-25 watt
software programmable with or without RF amplifier.
4. Wireless Data communication System should have Online/ OPC enabled local
as well as remote diagnostics feature. Without disturbing communication (to
provide information about Supply Voltage to the Wireless equipment;
Temperature; Radiated and Reflected RF power, RSSI signal level)
5. Radio modem Modulation Type should have all : 2 FSK , 4 FSK , 8 FSK , 16 FSK
6. Should work with or without RTS/CTS handshaking signals.
7. RF Connector : SMA Female Type
8. Temperature range: -30 to +60 Celsius.
9. Equipment should have: Class 1, Div. 2, FCC, CE approvals.
10. Reputed Make – Calamp / Elpro / Siemens/ Messung
11. Radio communication should support Non line of site communication
12. Radio Modem should have built in Dynamic routing feature
13. Radio Modem should be able to program for Bridge or Router Mode
14. It should have built in store and forward feature.
15. Radio Modem should support: most of the industries Ethernet protocols.

Page 31 of 53
16. Radio modem should be able to operate in Star or Mesh Topology.
17. Same radio modem should work as a Master, Repeater and Remote.
18. Should have min 8 Channels
19. Duty cycle : 100 %

Type : VHF data modem with transreceiver


Data Interface : RS-232 standard / Ethernet
Frequency Range : VHF : 136-174 MHz
Channel Bandwidth : 6.25, 12.50, 25.00 KHz selectable
Operating mode : Simplex or Half duplex
Communication Protocol : Support all protocols (Transperent)
Data Encryption : AES encryption
Operating Temperature : -300C to +600C
Supply Voltage : 10.00 to 30.00 VDC
o : 480 mA (Rx) and 4.6A (Tx) @ 10 V
Current Drain @ 25 C
Cold Start : 15 Sec
Approvals And Certifications : FCC , IC , UL (Pending)
RF Power Output : 1 – 25 Watt Software Adjustable
Frequency Tolerance : +1.0 PPM
FM Hum And Noise : Less Than -45 dB @ 25 KHz
Duty Cycle : 100%
Receiving Sensitivity : -116dBm @ 8kbps at 10-6 BER
Selectivity : > Than 75dB at 25 KHz
Data Rates : 32 kbps @ 25 kHz
Modulation : 4 FSK
Remote Diagnostic features : Yes
Programming : User Programmable with selectable modes
Indication LED : Power, Status, LAN link, LAN Activity, Rx, Tx.

GPRS Modem/ Router:


The device shall act as REMOTE MANAGEMENT DEVICE.
This shall have facility to connect PLC with central SCADA server PC at central
location office through GPRS (4G LTE Dual Sim) with VPN connectivity. Necessary
VPN server shall be established at Central Monitoring Station to connect with all
remote locations.
The PSTN / Broad band with dynamic IP connection or SIM card with GPRS enabled
with Dynamic IP be created. The connection will be provided based on best
available connectivity at each ESR or remote location. The Contractor shall provide
connectivity device which will be able to incorporate any connection. The
specifications for the device shall match following. Remote Maintenance PLC point
to Point RAS or Internet remote access: and any PLC / device / equipment with
TCP/IP
Remote Service: Data acquisition (Tag names) in MODBUS/RTU, MODBUS/TCP ‘Tag
names’ enable alarm management, Basic programming, custom Web pages,
reporting, Data Logging: Internal data base for data logging 21.000 points. Retrieval
of the data base with files transferred by FTP put or email attachment.

Page 32 of 53
 Alarms: ‘Tag name’ database: 128Kb. Alarm Notification by email, SMS, FTP
put and/or SNMP trap.
 Available standard limits to configure: Very Low, Low, High, Very High + Dead
zone and activation delay.
 Alarm summary and historian available in HTTP and via FTP files transfer.
 Alarm cycle management: ALM, RTN, ACQ and END.
 MMI HTTP: System and user defined Web site.
 SNMP: ‘Tag Name’ read/write
 FTP: Whole set of parameters are available in files
 Callback: Call back on user request or on amount of rings
 Direct or Internet call back (supports dynamic DNS)
 Firewall IP filtering
 Script-dedicated application to be programmed with the Basic language.
 Router IP forwarding, NAT, port forwarding and routing tables.
 Internet RAS connection (PPP), PAP/CHAP security. Data compression, ISP
connection
 (Internet Service Provider) primary and secondary, supports DNS.
 Synchronization Embedded real-time clock, manual setup via http or
automatic NTP setup
 File Management FTP client and server for configuration and data transfer.
 Web Site Security: DAA and session control. HTML standard supports the
entire PDA browsers.
 SSI technology (Server Side Include) and BASIC scripted ASP (Active Server
Pages).
 Maintenance SNMP V1 with MIB2 and/or via FTP files
 Material ARM processor @75Mhz, 8Mb SDRAM, 8Mb Flash, Din Rail Mounting
 Power supply 12 - 24VDC +/-20%, SELV; consumption: 3-6 watts
 1x SUBD9 serial port: RS232, RS422 or RS485, 1,5kV isolation
 1x RJ45 Ethernet 10/100 base Tx; 1,5kV isolation
 1x digital input: 0/24VDC; 3,5kV isolation
 1x digital output: open collector 200mA@30VDC; 3,5 kV isolation
 Embedded modem: PSTN or GSM/GPRS
 GPRS 4G/5G LTE Modem (Dual Sim) with VPN Connectivity
 GPRS Modem should have Hardware Watch Dog
 Reputed Makes : Siemens/ Messung / Mitsubishi/ ACTL / Cisco
 GPRS 4G/5G LTE Solution should have Hardware based Network Manager at
control center to handle GPRS connections and should support min 300 VPN
connections and should work without any software at control center
 Operating Temperature range: 0° to 50°C, 80% humidity (no condensation)
The MCS shall also have static IP with bandwidth of suitable requirement along
with a Firewall. The Firewall specifications shall be as follow:-
Firewall provides visibility into top risk users, unknown apps, advanced threats,
suspicious payloads, should protect network from ransomware and advanced
threats including top-rated IPS, Advanced Threat Protection, Cloud Sandboxing, Web
and App Control, Email Protection and a full-featured Web Application Firewall.

Page 33 of 53
Firewall security solution should be able to fully identify the source of an
infection on your network and automatically limit access to other network resources
in response.In addition it should adds VPN technologies for remote access .

Specifications:
Form factor: 1U
Ports/ Slots :8/1
Firewall throughput :16Gbps
VPN Throufhput:1.45Gbps
Maximum Licensed users; unrestricted
Certifications:CB, UL, CE, FCC Class A, ISED, VCCI, RCM, CCC, KC, BIS
Storage (local quarantine/logs): integrated SSD
I/O ports :2 x USB 3.0 (front)1 x Micro USB (front)1 x USB 3.0 (rear)1 x COM (RJ45)
(front)1 x HDMI (rear)
Display :Multi-function LCD module
Power supply :Internal auto-ranging100-240VAC, 50-60 Hz

18. ITEM NO. 18 FABRICATED SELF-SUPPORTED TRIANGULAR SHAPE MS TUBULAR


TOWER

Contractor shall be responsible for Supply, delivery, erection, installation, testing,


training and commissioning of towers for Central Monitoring / SCADA system with
proper Towers/ Antennas /subscriber module / reflector disk at each location and
central location and all necessary accessories inclusive of all license fees at all
locations of ESR/ UGR/WTP. It is inclusive of all required equipments, Towers,
Antennas, subscriber module, disk, pedestal for tower base, lightning arrestors,
cables, structure required for mounting viz: poles, platforms, railings, furniture etc.
and all required installation hardwares complete and as directed by Engineer-in –
charge
Providing Fabricated self-supported triangular shape MS tubular Tower of suitable
height from ground, providing matched pedestal for tower base, providing
aluminum earthing wire up to nearest earth terminal, providing GI lightening
arrestor at Central Location (PCMC Head office)

19. ITEM NO. 19 GPRS BASED DATA LOGGER

Providing supplying, fixing and commissioning GPRS Data logger with internal
battery having (6 years battery life) dual channel for flow and pressure logging with
internal pressure transducer, PC software, PC connection cable, Infra-red reading
head, pressure hose, instruction manual etc. complete as directed by the Engineer-
in-charge.
The Contractor shall supply the required GPRS enabled Data logger to be installed at
remote locations only (where RTU/PLC’s not available) or as directed by Engineer in
Charge. The GPRS Data LOGGER shall be accepted after the third party inspection by
SGS, RITES or any other agency authorized by PCMC, the charges for the same shall
be borne by the Contractor. Equipments / Instrumentation Shall be provided as per
Approved Make of PCMC.
The minimum technical specifications of the instruments shall be as given below.

Page 34 of 53
20. ITEM NO. 20 SCADA SOFTWARES & Monitoring

SCADA Server & Softwares


The Contractor shall supply all programming (PLCs) and SCADA software’s necessary
to provide a fully debugged Pumping / valve Operation and control for water
distribution management system (WDMS) along with control operation of valves
actuators remote SCADA. SCADA System shall communicate with field PLC through
RF/ GPRS for data, information & Control. The software required shall consist of
those programs necessary for the system to efficiently perform the functions
specified herein, plus enable convenient and efficient preparation of new programs.
The system shall be capable of operating in a foreground/background mode. The
Contractor shall assume complete responsibility for the successful operation of all
software and application programs provided as part of the system. All programs can
be completely debugged and operable prior to delivery of the system. The PCMC
shall not be required to expend any programming effort in order to achieve a fully
operational system.

Page 35 of 53
The central processor shall be provided with self-test diagnostic routines, which are
automatically executed every time the processor is powered up or the bootstrap
routine is initiated. The Contractor shall supply and install all necessary cables and
connectors etc.
Operating system, database software, monitoring & display software, pump house
resource planning software etc. and all other required peripherals shall be provided
under this project for achieving required functionality of the Local SCADA system at
each location. SCADA softwares shall be of reputed and accepted make.

End User Interface


There shall be three levels of End user Interface:
Central Monitoring Station
The Central Monitoring Station shall have the following main components
1. Screens to display the layout schematic of the system as per actual
configuration on the field
2. Online and historical trends plotted with respect to benchmark graphs. The
benchmarks are to be arrived at using practical data over a reasonable period
of time
3. Settings screen for important parameters like timing, pressure and flow,
residual chlorine etc.
4. User login and authentication screens
5. Dashboards of important KPIs as specified by the Engineer in Charge
6. Bar graphs as per Engineer-in-charge to be plotted against Benchmark levels
Cloud based web Pages
1. Important Data to be uploaded to the cloud using state of the art protocols like
IOT drivers etc. and viewed using Http protocol. Any software/hardware/drivers
required for the same shall be provided by Contractor
2. This shall be only in view mode and no changes shall be possible in this method
3. It should be possible to add a link to these Web Pages on the PCMC website.
The link to be added by the customer using the services of the service
provider/agency maintaining the website of PCMC.
Apps
1) Apps for IOS and android devices to be developed by the Contractor
2) Apps to be downloadable by users/citizens if required
3) Screens of the apps to be developed as per Engineer in Charge
4) No Changes to be possible using the apps.

Page 36 of 53
21. ITEM NO. 21 CENTRAL MONITORING SYSTEM

Space for Central Monitoring / SCADA System Control Room will be provided by
PCMC as decided and all the required furniture and other accessories shall be in
Contractor scope. All the equipment, cables, electrical boards / points,
instrumentation and all required hardwares and softwares to be provided for the
system shall be from a standard line of equipment manufactured and supported by
a manufacturer approved by the PCMC Engineer. Contractor should supply install &
commission the system with specific project plan for effective and successful
monitoring system including all necessary hardwares and softwares (not covered in
price bid under specific item).

Control Room Furniture


All necessary furniture, Chairs, conference table of high grade quality material and
all aesthetics designs approved by PCMC shall be provided. In addition to the
control system equipment, the Contractor shall provide furniture to complement or
match both the colour and styling of the equipment. Control room furniture shall
comply with relevant IEC standards for ergonomic design. Details of the control
room furniture shall be submitted to the Engineer for approval.
Fabric-covered upholstered swivel-type adjustable arm chairs with casters shall be
provided along with a rigid and lockable steel cupboard for the storage of operating
and maintenance manuals, drawings, logger paper, charts, disks and the like.
The visual display unit consoles or VDU desk shall incorporate suitable nos. drawer
unit with drawers for operators use and for standard files.

Large Video Display System


The LVS shall be designed for continuous operation, i.e. 24 hours per day. Viewing
distance for the display screen & viewer shall be small.
The LVS system should have following technical specification General Specification
of Video wall.
1. The product should be from reputed make manufacturer which has installations
worldwide and should be of international repute. It should have their own
manufacturing unit in India. The Indian Manufacturing unit should be certified
for the following quality management System ISO 9001: 2008, ISO 14001: 2004
2. The cubes, controllers and the associated software should be preferably from
the same manufacturer to ensure seamless integration.
3. The system shall be complete with display wall with 50” each Diagonal Laser
based Rear projection system preferably 3.3 meter x1.8 meter with multiple
unit or as system desired.
Screen to screen gap should be ≤ 0.2 mm.
Each cube should have minimum specification as below:

Cube
1. Resolution: 1920 x 1080 DMD resolution of chip.
2. Light Source type: Laser light source,

Page 37 of 53
3. Brightness of each projection engine : Minimum 2000 lumens
4. Brightness Uniformity: ≥ 97% and control should be IP based and IR remote
control should also be provided for quick access.
5. Input terminals – 1X-Digital DVI, 1X-HDMI, 1X-Analog Dsub-15, 1X-Analog
RGBHV
6. Cooling: Inside cube should be by means of a heat pipe only. Pump based
cooling involving hazardous liquids is not acceptable.
7. Cube Size: 50” with Rear Maintenance.

Video Wall Controller


1. Controller: Controller to control Video wall in a matrix (3.5 x2 m) outputs,
inputs along with software’s.
2. Processor: Single Quad Core Intel (R) CoreTM i7 Quad Core 3.4 GHz Processor) or
better and supports 64-bit Operating System Windows 8 / 10 with RAM
capacity of 16 GB or more with HDD 1000 GB or more.
3. Net Working: Dual Port Gigabit Theme.
4. Power Supply: 1+1 (Redundant Hot Swappable).
5. Inputs: Minimum 6 DVI
6. Outputs: 6 DVI outputs

Video Wall Management


1. Display and Scaling: Display multiple sources anywhere on display up to any
size.
2. Input Management: All input sources can be displayed on the video wall in
freely resizable and movable windows and should have and load desktop
layouts from Local or remote machines.
3. It should be able to provide an error message in three sections a) Problem area
b) Error Module location c) Error Module image.
4. Provide video wall status including Source, light source, temperature, fan and
power information.
5. Should provide a virtual remote on the screen to control the video wall.
6. Input sources can be scheduled in “daily”, “periodically” or “sequentially” mode
per user convenience.
7. System should have a quick monitor area to access critical functions of the
video wall.
8. UPS with 1 to 2 hrs batteries backup on full load (single phase 10 kVA or more
as per site requirement) shall be provided.

Monitoring system instruments earthing


Monitoring system instruments and all related equipment earths shall be
electrically bonded to the instrumentation earthing system or be provided with a
separate independent isolated earth terminal bonded directly to the main station
earth terminal in accordance with BS 6739.

Tentative CMS Layout & interior designing

Page 38 of 53
The indicative layout for the proposed system arrangement is tentatively as per
below. The layout as mentioned below in indicative and subject to change as per
PCMC approval.

CMS room interior designing and allied works shall include;


a) Supply of Acoustic Metal Paneling :-
Paneling with factory made removable type self inter lockable metal panels of
Preformed textured RIGID PVC coated GI sheet panels. The metal panels fixed on
structure made of 1.6 mm thick MS channels bent over automatic punching to fix
metal panel and bending CNC. and their properties shall be as follows :-
1) Resistance to extremes of weather exposure and temperature.
2) Very low coefficient of expansion.
3) Can be cleaned using detergents.
4) The Tiles shall be Class A fire rated as per ASTM E-84 (from UL/Intertek) for the
surface burning characteristics of wall Panelling tiles to be submitted along with the
technical Bid. This is mandatory requirement from Fire safety point of view.
5) The wall panelling system must be RoHS certified (from UL/Intertek) to ensure
restriction of hazardous substance in any of the materials.
6) Minimum 40% of the tiles shall have at least 10,000 micro-perforations per
square meter to achieve NRC of 0.6 Sound Absorption Coefficient by diffuse field
method; IS: 8225-1987 “Measurement of Sound Absorption Coefficient in
Reverberation Room” (Equivalent to ISO: 354- 1985 and ASTM 423-90).
7) UL Certificate on Load bearing capacity of paneling - Paneling structure shall have
load carrying capacity of 300 Kg to hold any display unit on clamp having minimum
length of 750mm
8)Metal rafter made out of 75 X 50mm MS C sections covered by factory made
metal panels of Preformed textured PVC coated GI sheet panels.

Page 39 of 53
b) Supply of 12mm thick frameless tempered clear glass Double door Size :-
1500mm X 2400mm
With door spring and locking arrangements and both way handle and patch fittings.
Specifications : Tempered glass is formed by heating glass to the softening point in
a horizontal tempering stove, and then quickly cooling it.
Properties:
1) Safety (tempered): when broken, it spits into tiny harmless pieces
2) Strong intensity: heat-strengthened glass is approximately twice as strong as
annealed glass of the same thickness, and tempered glass is about 4 times
3) Outstanding performance in resisting thermal stress and wind-load
4) Tempered glass cannot be cut, drill hole and other further processed.

c) Supply of Designer Acoustic Metal False ceiling with linear planks :-


100% Modular factory made Powder coated Dual layer hook ceiling with
combination of acrylic panels for installation of linear lights, designed to enhance
visual feel and provision for easy installation and maintenance of integrated
lighting. The perforated (140-150 mm Wide) and non-perforated (275-300mm
Wide) ceiling panels of various lengths (as per the site requirement) shall be
alternatively connected to form designer ceiling. Machine profiled section 125-
175mm wide and 60-80mm deep having provision for fixing acrylic sheet shall run
across the length at the room. Tiles shall be processed on high precision CNC &
laser Machines to achieve perfect accuracy. Structure shall be made from heavy
duty modular steel frame (minimum sheet thickness 0.8mm) with combination of
Master section and series of main runners spaced at 1200 mm (center to center)
securely fixed to the slab by the means of anchor fastener & 8 mm GI rod (max
length 1200mm) fully threaded with Hex nut for precise level adjustment. Light
fitting can be defined as per the LUX requirement. It shall have Laser cut circular
hole for light fixing as per defined lux requirement and approved layout. Non-
perforated tile slots to be punched to accommodate AC grills.

d) Supply of Calcium Silicate Board Ceiling Material:-


Plain Calcium Silicate acoustic Boards for false ceiling with 8mm Approx. thick,
Structure for underside of suspended grid formed of GI perimeter channels. Wood
screws and metal expansion raw plugs for fixing with wall. Plastic emulsion paint of
approved make and shade for finishing surface of Calcium Silicate Boards.

e) Supply of Round LED Ceiling light :-


High performance LED downlighter with high system efficacy for good quality and
uniform lighting. Conforms to general lighting norms for office and other indoor
applications.
a) Temperature- 3000 K to 6500K
b) CRI >70
c) Power Consumption 12W to 24W
d) Aesthetically designed enclosures
e) Highly efficient constant current LED drivers
f) Ideal replacement for traditional PAR/CFL lamp
g) Up to 80% energy saving.
h) LED’s life >25,000 hrs @ L70

Page 40 of 53
f) Supply of Cove Light for designer Ceiling :-
It will be a continuous rail of LED light, high brightness , neutral, or warm white with
wall washing applications. Its slim profile and simple daisy-chain system allows high
design flexibility to form long.
Light source: LED
Lumen output: 840 lm/Mtr.
Light color: 3000K/6000K
Power consumption: 9.8 W/Mtr.
Voltage: 12V AC 50Hz
Optics: Sand-blasted matt finish reflector
Color: White
Lifetime: 40000 burning hrs. (At L70)
g) Supply of Cove Light for designer Ceiling :-
It will be a continuous rail of LED light, high brightness , neutral, or warm white with
wall washing applications. Its slim profile and simple daisy-chain system allows high
design flexibility to form long.
Light source: LED
Lumen output: 840 lm/Mtr.
Light color: 3000K/6000K
Power consumption: 9.8 W/Mtr.
Voltage: 12V AC 50Hz
Optics: Sand-blasted matt finish reflector
Color: White
Lifetime: 40000 burning hrs. (At L70)

h) Supply of Wires, Switches & Conduits for ceiling lights :-


Wires for ceiling lights inter looping and switches will be provided, consisting of PVC
insulated copper conductor stranded flexible FRLS wires of 1100 volts grade of
insulation, in metallic conduits, PVC/ metallic conduits. Minimum size of copper
conductor shall be 1.5 sq. mm for lighting and 2.5 sqmm for power. color of wires
shall be Red/Yellow/Blue (or as per Local Standards) for the all single phases, Black
for neutral and Green for earthing.
i) Supply of Acoustic flooring :- The decorative flooring shall reduce impact sound by
14dB (ISO 717-2)). It shall be twin-layer linoleum built up from 2 mm acoustic
laminate and 2 mm Corkment backing. Top Surface Shall be Green Guard certified to
avoid VOC free / low emitting surface and finish shall be similar to the Acoustic Laminate
flooring
j) Supply of New Modular Control Desk made in "XLAT OE" system.
1. Desktop made of 25mm Laminated MDF Board.
2. Structure: - Made of heavy duty Extruded Vertical and Horizontal Aluminium
profiles of HE9WP grade. The Extrusions shall be duly powder coated with 40+ micron
over all surfaces. All sheet metal parts must be finished with a durable, black,
electrostatic powder coating. The structure shall be rigid enough to withstand BIFMA
X5.5: 2014 (Latest Addition).
3. Back Sheet: CRCA Sheet with Powder Coated Finish.
4. Front Edge: - UL Certified design of High-density Poly Urethane Foam moulded on
industrial grade aluminium core to form 50mm deep tapered edge to be installed on
worktop. The Edge shall be mechanically replaceable within 30 minutes in case of
damage or wear without opening or removing the worktop.

Page 41 of 53
5. Monitor Arm Assembly shall have auto-lock, push & add/remove die-cast
aluminium extendible arms of 150mm each with tool less addition/deletion feature
to cater future requirements. Tool less addition / deletion in less than a minute.
Approx Dimensions: 750 mm (H) x 1000 mm (W) x 700 mm (D)

22. ITEM NO. 22 CENTRAL SERVER PC

General:-
The central processor(s) shall be of industrial quality and of proven high reliability
suitable for continuous operation (24hrs.).
The processor shall be furnished with a real-time calendar clock with battery back-
up which provides the current time and date during system boot-up with no
operator action required.
The processor shall contain sufficient memory for all requirements described
herein, including future requirements, and 30% spare capacity when all application
programmes are loaded and operating,. The central processor shall be equipped
with storage facilities consisting of:
 Random access memory (RAM) for the storage of all current data (real-time
database);

 Large capacity, fast access, mass storage magnetic (hard) disks for on-line data
storage;

 High density cartridge or streaming tape drive or optical disk system, with
removable media, for offline archiving of data;

 CD DVD Read/Writer, for off-line archiving of data;

Additional high capacity fixed and removable storage media, shall be provided for
data back-up.
At least 50% of the hard disk shall remain unused and available for other uses after
all database, program, historical and working files required by the system are
resident.
The operating system and application software shall reside on the hard disk. Upon
power-up, power restoration after power failure or warm start, the system shall
automatically load and become fully operational without the need for operator
action.
Minimum Server configurations:

: System x 3650 Server or latest version


Type : 2U Rack Mount
Processor : Xeon 8 Core E5-2630V3 90W 2.4 GHZ /1866MHZ/20MB
INTEL
Chipset : Intel
RAM : 2x16 GB RAM ECC DDR
Cache L2 8 M B or higher
Raid support : Support Raid 0,1 & 10
Optical drive : DVD Writer ( Sony or any OEM )

Page 42 of 53
HDD : 5x1TB 2.5" inch 7.2k RPM6Gbps SATA Hot plug Hard Drive
Ports : 4 USB, 1 KBD,1 MOUSE, 1 Parallel & 2 Serial
Ethernet : Four integrated RJ-45 Gigabit Ethernet 1000 BASE-T ports
Power supply : 550 watt redundant power supply
Cooling fan : Yes
Keyboard : standard Keyboard
Mouse : Optical Mouse
Monitor : 55” LCD / LED (make standard)
OS : WINDOWS SERVER 2012 or latest

It is under the scope of this project that the Contractor shall provide the web
enabled facility/ cloud server facility for server data of whole Central monitoring
System including internet facility and necessary communications. PCMC users can
be able to access this data with user name and password facility.

23. ITEM NO. 23 PCS, SOFTWARES, KEYBOARDS, PRINTERS ETC

Minimum configuration for PCs are as under:-

Processor Intel Core i7


Make Industrial Grade Reputed Make
Chipset Intel
RAM 16 GB DDR
Cache 8MB Total Cache
Optical drive Combo drive
HDD 2TB SATA
Ports Display Port – 1 VGA /HDMI
USB 4.0 – 6 Nos.
Serial port - 1 Rear
Parallel port – 1 Rear
Ethernet network - 1 Rear
Stereo Line –In 1 Rear
Stereo Line – Out - 1 rear
Ethernet Gigabit LAN
Power supply power Supply – 280 W
Keyboard wireless Keyboard
Mouse wireless Mouse
Monitor 55” LCD/LED
Operating Software Windows -10 or latest

Page 43 of 53
System Softwares
All programming necessary to provide a fully debugged operating system shall be
provided. The software required shall consist of those programs necessary for the
system to efficiently perform the functions specified herein, plus enable convenient
and efficient preparation of new programs. The system shall be capable of
operating in a foreground/background mode. All programs can be completely
debugged and operable prior to delivery of the system. The PCMC shall not be
required to expend any programming effort in order to achieve a fully operational
system.
The overall operating software package shall be modular, primarily comprised of an
integrated group of proven, standard software modules. Individual standard
modules shall be designed such that adoption to this system’s specific needs shall
be accomplished through entry of definitive data in stored parameter tables. The
system software shall be of standard product. No programming shall be required
beyond configuration and minor customization. The system software shall be
designed to provide a disturbed database.
All of the programs are to be generalized in nature such that the PCMC may later
add new functions. The scheduling and initiation of future application programs and
the servicing of their input and output requirements, including construction of new
printing formats and other system interfaces, shall be accomplished without
recompiling of application software.
Specifics for the system are given as a guide, however manufacturer’s standard
offerings that can accomplish all of the specified functions will be considered. The
system shall be capable of accepting process control operational directives in a
conversational mode. Data validation shall be performed on operator inputs and
reject illegal entries.
System parameters such as data, time, set points, alarm limits, loop tuning
constants, etc., shall be entered or modified via the operator’s terminal. Any input,
which modifies the system, shall be logged on the logging printer with data and
previous value.
Software Licensing- The computer system supplier shall include all necessary
licensing for operation of all software on all computer systems provided. All
packaged and system software licenses shall be registered by the Contractor in
the name of the Pimpri-Chinchwad Municipal Corporation.

d) Operating System
The Operating System software shall be the latest version of Microsoft Windows to
provide system resource allocation and management in a Real-Time, multi user
environment.
The Operating System shall provide an orderly shutdown on loss of power or low
voltage and automatically restart the system, including processor and peripherals,
upon restoration of power without operator intervention. The power failure
protection shall protect against loss of program and/or work in progress at the time
of occurrence.

d) OIS User Interface


The operator shall be capable of to access displays via a printing device and/ or soft
key menus with a choice of function keys, cursor, control keys, or any key on the
key PCMC. Supported pointing devices shall include a mouse, touch screen, light
pen or trackball.
The system shall support operator access to multiple displays at one time, including
split screens where the operator may view more than one process area at a time. In

Page 44 of 53
addition, the system shall support unlimited use of pop-up displays for additional
help or diagnostic information.
Access to all displays and to all command functions shall be based on the operator’s
security level to protect against unauthorized use. The security level shall be
established during the operator sign-on procedure.
Visibility and operation of command buttons, symbols etc. shall be controllable
based up on the operator’s security level.
The operator shall be able to have access to context sensitive help at any time
during operation of the system.
The operator shall be able to access multiple data sources/ items with a single tag
name.

d) Programmer’s console
For systems, which require it for modifications or additions to be made to the
operating system or application programmes, a programmer’s terminal shall be
provided of the type recommended by the system software and hardware
manufacturers.
d) Diagnostic capability
The system shall be provided with the capability to diagnose hardware
malfunctions in the central station and related peripheral equipment. Diagnostic
programmes shall be password-protected to prevent unauthorized use. The
diagnostic procedures shall be able to be performed by operations personnel with a
minimum of training. Software routines shall be provided which can isolate a single
problem to the circuit board level. The routines shall be menu-driven to allow for
ease of use. Complete documentation of diagnostic procedures shall be provided as
part of the system documentation.

Keyboard
Unless otherwise specified, keyboards shall be equipped with upper and lower case
alphanumeric keys as well as a minimum of 10 function keys. Each key shall be
clearly and permanently labeled to show its purpose.
Standard editing keys such as tab, insert, delete and backspace shall be provided.
Cursor control shall be available for the keyboard giving right, left, up, and down
movements.
Keyboards located in the process area shall be protected from dust and splashed
water.
Certain keys shall be programmable. A minimum of 8 keystroke-sequences, apart
from the standard functions, shall be available after project completion for
assignment of programmable functions.
Key boards for use in program modifications shall be of the standard QWERTY
configuration with separate 10-key pad for numeric input.

Cursor-positioning device
Cursor-positioning devices shall be of the mouse or track-ball type or otherwise
approved by the engineer. Two select buttons shall be provided as a minimum.

Printer Requirements
Two types of printers shall be supplied for reports, alarms and events as detailed
below. It shall be possible to configure any text based output from the master
station to either of these printers.

Page 45 of 53
It shall be possible to add additional printers if required. Additional printers shall be
capable of being assigned the functions of alarm/event logging, or report printing/
scanning of documents.
a) Printer Connections
Alarm / Event printers, shall offer at a minimum of 100 characters per second,
upper and lower case ASCII character set with true descenders, a minimum of 132
characters per line, and a self-test facility capable of printing automatically the
entire character set.
The minimum size of printer buffers shall be 4k characters.
Each printer type shall connect to the system using the standard interfaces such as
RS232 / Ethernet with both RTS/CTS control signal and XON/XOFF data transfer
control methods supported.
All printer types shall be of a low noise type or shall be provided with acoustic
hoods to ensure the ambient noise level never exceeds 30Dba.
Printer types shall be provided with all necessary cables and connectors. Should a
printer be off-line when an output is ready, the control system shall send a message
to the operator.
b) Alarm/Event printers
The alarm/event printer shall be a dot matrix/ laser printer with a minimum of four
colors available. Alarms shall be highlighted by colored printing (i.e. plant alarms
red/system alarms orange/return to normal green) while events and alarm
acceptance shall be printed in black. This printer shall be located in the Control
Room in a self-contained printer stand.
c) Report colour printers
The report colour printer shall be an A4 printer capable of producing high quality
text and graphical reports for plant and management purposes and full colour high
quality prints of screen display mimics, trends etc. In text mode the printer shall be
capable of up to 7 pages per minute for text and 1 minute per page for graphics.
The resolution shall be 600 by 600 dpi for colour and 600 by 600 dpi for black as a
minimum. The printer shall be capable of receiving and printing data formatted for
a Hewlett Packard printer. It shall be located in the control room of each location.
24. ITEM NO. 24 UNINTERRUPTED POWER SUPPLY

The monitoring system processor(s), VDUs, logging printer and communications


equipment shall be powered through an uninterruptible power supply (UPS) via a
dedicated distribution system. The UPS shall provide for full functioning of this
equipment for minimum of one hour in the event of a power failure. UPS capacity
shall be over-sized in terms of rating and power duration by 50% to provide for
future additional equipment. The Uninterruptible Power Supply system shall
consists of a regulated rectifier to operate from commercial AC power, a battery to

Page 46 of 53
store emergency power, and an all – static inverter to convert DC power from the
rectifier or battery to high quality AC. The power supply system shall normally
operate from the existing commercial power. When commercial power failure
occurs, the battery shall immediately and without switching, take over as the
source of power to the inverter which shall continue to provide high quality AC
power to the equipment.
The UPS shall be a of minimum following Specifications:-
Make Transtech /Emerson/ Schneider / APC
Type On Line
:
Input 230 VAC
: +/- 15 %
Output 230 VAC
: +/- 1 %
Power factor 0.8 Lag
:
Power capacity Min 5: KVA or As per requirement of site and system
with approval of PCMC
Frequency 50 Hz: +/- 0.5 Hz.
Wave form Pure sine
: wave
Total Harmonic Distortion < 4 %:on linear load
Inverter IGBT based
: high freq PWM
Inverter efficiency > 85 %:
Duty Continuous
:
Transfer time Zero secs.
:
Battery Voltage 48 – 360
: VDC as per requirement
Battery Type Sealed: Maintenance Free
o
Operating Temp 0-45 :C
Humidity Up to: 95 % RH
Protection Output
: high / Output Low/ Output Short Ckt/Batt.
Low Trip
Alarm Battery
: Low
Indicators Mains: ON, Inverter ON, Battery Low, Fault
Metering Output: voltage
Exact sizing shall be the responsibility of the system suppliers based on total load
requirements of equipments proposed.

The system batteries shall be sized to sustain operation for a minimum of 360
minutes. The system batteries shall be of the gelsel or NiCad type and shall reside in
the same enclosure as the UPS.

Whichever sites do not have access to power, will have to be determined by the
contractor. The Solar UPS in such site shall have following specifications:-

2 kw off grid solar system for with 8-10 Hours Backup


2 kw solar system should be designed to give power supply for 24 to areas where power
supply is not available.
Inverter - 3600 VA (1 nos.)
Battery - 150 Ah (4 nos.)
Solar Panels - 2100 Watt (350 watt * 6 nos.)

Page 47 of 53
Running load

Up to 2400 watts of power


inverter capacity 3600 VA
efficiency Inverter - 97%, Module >16%
module type mono-crystalline
battery included yes

25. ITEM NO. 25 AIR CONDITIONING UNIT

Window type room air conditioner of 2 ton capacity (or as per the site requirement)
shall be provided at the Central Control Room for monitoring system and any other
location decided by PCMC. The air conditioner shall be sized to maintain a
temperature of 24 + 1 degree Celsius, 50 % relative humidity inside at all time. Air
conditioner and its part shall be constructed with the strength and rigidity adequate
for normal conditions of handling, transport and usage. AC shall be of reputed
brand.

26. ITEM NO. 26 CAST IRON PIPE SPECIALS

1. The horizontal Cast C.I. double flanged pipes shall conform to IS 7181-1986
(reaffirmed 205) duly inspected and tested and having BIS certification mark
2. The C.I. fittings shall conform to IS – 1538 – 1993 duly inspected and tested and
having BIS certification mark
3. Method of sampling of cast iron pipes and fittings shall conform to IS 11606 –
1986
4. Specification for rubber and insertions shall conform to IS 1638
5. Code of structural steel in general building construction (for nuts and bolts) shall
conform to IS 800
6. Flanged pipes centrifugally cast with screwed/welded flanges shall conform to IS
1536-2001
7. Tolerance
7.1 Tolerance on Thickness-
The tolerance on the wall thickness of pipes and flange thickness of pipes shall be
as follows:-

Dimension Tolerance mm
Wall Thickness - (1 + 0.05e)
Flange Thickness + (2 + 0.05b)
Where e = Thickness of pipe in mm, and
b = Thickness of flange in mm

Page 48 of 53
8.2 Tolerance on Mass Fittings
The mass of fittings are given I the specifications prepared by UADD. Tolerance on
mass of fittings shall be as follows:-
(i) The permissible tolerances on standard mass of fittings shall be + 8 percent
except for bends, fittings with more than one branch and non-standard
fittings, in which case the tolerance shall be + 12 percent. Fittings of a
heavier mass than the maximum may be accepted provided they comply in
every other respect with the requirement of this standard.
8.3 Permissible Deviation I double flanged cast iron pipe (Horizontal) from a
straight line. The pipes shall be straight. When rolled along two gantries
separated by approximately two thirds the lengths of the pipes to be choked,
the maximum deviation fm, shall be thus fm < 1.25L.
9. Laying of pipes and fittings/specials includes all precautions to guard against
possible damaged to the existing structure/pipelines, cables, etc., taking
precautions to prevent dirt from entering the pipe ends, lowering and laying
pipes and specials in the trenches with specials arrangement such as cranes,
tripods with chain pulley block, use of slings of canvas etc. to fit the ends of
pipes and fittings/ specials to lift an lower the same. Inspection of pipes and
fittings for defects by striking with a light hammer while suspended. Laying of
pipes perfectly true in alignment and to gradient etc.
10. Fixing means laying in specified position to ensure interconnection between all
flanged pipes, fittings and valves. It is also to ensure that the bolt holes of two
flanges of pipe fittings are correctly aligned.
11. As per prevailing excise duty norms there is excise duty exemption on certain
diameter of water supply pipes of different material class. All though in
computation of item rates for pipes, the rates are inclusive of excise duty but
excise duty exemption shall be obtained as per prevailing rules for such pipes.
This benefit shall be availed by local bodies. All the concerned officers shall be
responsible to get all the exemptions of such taxes and duties.
12. Measurement
The net length of pipes as laid or fixed should be measured in running meters
correct to a cm. Specials should be excluded and enumerated and paid for
separately. The portion of the pipe within the collar at the joints should not be
included in the length of pipe work.
13. Rates
(i) The rates include the charge for all tools and plant such as chain pulley
blocks and other appliances etc. required for lifting and laying the pipes and
specials in position.
(ii) The rates include provision and use of all coverings etc. to protect the works
from inclement weather etc. and from damages from fall of materials and
other causes

Page 49 of 53
(iii) The rates include provision of handling, storing under cover as required
and returning of empty cases or containers to the store without any extra
cost, for such materials as may be supplied by the Department.
(For Detail refer to Specifications prepared by the Urban Administration and
Development Department, IS Code and CPHEEO Manual)

27. ITEM NO. 27 VSAT TRANS-RECEIVER

This item shall be executed only when any remote location where either RF or GPRS
communication is not possible. The minimum specifications for VSAT technology is as
following;

Indoor Unit
Operating Voltage 100-240 VAC
RF Input / Output Two F Connectors, 75 Ohm Female
Data Interface 100 Base T / RS-232 ( Optional)
Type VSAT Terminal
Make Gilat / Hughes
Out Band Carrier
Standard DVB-S
Carrier Bit Rate 340 Kbps – 66 Mbps
Modulation QPSK
Coding Viterbi & Reed Somolon or Turbo
FEC rate ½, 2/3, ¾, 5/6, 7/8
Inbound Carrier
Access Scheme Combined TDMA, FDMA
Bit Rate 60 Kbps – 2 Mbps ( as per requirement)
Modulation GMSK
Coding Turbo coding FEC 3/4, 7/8
Out Door Unit
Antenna Size Ku Band 0.55 m to 1.2 m, C band 1.8 m
Operating Temp -40 to + 60 C
Humidity Up to 100 %
Transmitter ODU 1W, 2W Ku Band
LNB Standard TVRO type

28. Item No. 28 CCTV camera

It is proposed to install the CCTV cameras at ESR locations and monitor the activities at
respective location. Realtime data monitoring shall be at Central Monitoring Station. The
minimum specifications shall be as per following;

Page 50 of 53
Make Bosch, Axis, Tyco, vivotek, honeywell
2 Image Sensor 1/2.8" Progressive CMOS or better
3 Max. Resolution 1920x1080
4 Lens Type Fixed-focus
5 Focal Length f = 2.8 mm or better
6 Aperture F1.6
7 Auto-iris Fixed-iris
8 Field of View 109° (Horizontal)
61° (Vertical)
126° (Diagonal)
9 Shutter Time 1/5 sec. to 1/25,000 sec. or better
10 Day/Night Removable IR-cut filter for day & night function
11 Minimum Illumination 0.4 Lux @ F1.6 (Color)
0.01 Lux @ F1.6 (B/W)
0 Lux with IR illumination on
12 Pan/Tilt/Zoom
ePTZ: 48x digital zoom
Functionalities
(4x on IE plug-in, 12x built in)
13 Built-in IR illuminators, effective up to 30 meters
IR Illuminators
with Smart IR, IR LED*2
14 On-board Storage Slot type: MicroSD/SDHC/SDXC card slot
Seamless Recording
15 Video
16 Compression H.265, H.264, MJPEG
17 Maximum Frame Rate 30 fps @ 1920x1080
18 Maximum Streams 3 simultaneous streams or better
19 S/N Ratio 50 dB or better
20 Dynamic Range 110 dB or better
Adjustable resolution, quality and constant bit rate
21 Video Streaming
control
Time stamp, text overlay, flip & mirror; Configurable
brightness, contrast, saturation, sharpness, white
22 Image Settings balance, exposure control, gain, backlight
compensation, privacy masks; Scheduled profile
settings, video rotation, 3DNR, DIS, HLC
23 Audio
24 Audio Capability Two-way audio
25 Compression G.711, G.726
26 Interface Built-in Mic
External Mic input
External line output
27 Network
28 Users Live viewing for up to 10 clients
IPv4, IPv6, TCP/IP, HTTP, HTTPS, UPnP,
RTSP/RTP/RTCP, IGMP, CIFS/SMB, SMTP, FTP, DHCP,
29 Protocols
NTP, DNS, DDNS, PPPoE, QoS, SNMP, 802.1X, UDP,
ICMP, ARP
30 Interface 10 Base-T/100 Base-TX Ethernet (RJ-45)

Page 51 of 53
31 ONVIF Supported
32 Intelligent Video
33 Video Motion Detection Five-window video motion detection
34 Alarm and Event
Motion detection, manual trigger, digital input,
periodical trigger, system boot, recording
35 Alarm Triggers
notification, camera tampering detection, audio
detection, MicroSD card life expectancy
Event notification using digital output, HTTP, SMTP,
36 Alarm Events
FTP, NAS server and MicroSD card
File upload via HTTP, SMTP, FTP, NAS server and
37
MicroSD card
38 General
RJ-45 cable connector for Network 10/100 Mbps PoE
39 Connectors
connection
Audio Mic in
Audio line out
DC 12V
Digital input *1
Digital output *1
40 LED Indicator System power and status indicator
41 Power Input DC 12V
IEEE 802.3af PoE Class 0
42 Power Consumption Max. 7 W or better
Safety Certifications CE, LVD, FCC Class B, VCCI, C-Tick, UL
43 Operating Temperature Starting Temperature: 0°C ~ 50°C
44 Working Temperature: -10°C ~ 50°C
45 Humidity 90%
46 CyberSecuirty Embedded

The feed from camera shall be monitored on MCS through a Network Video recorder (NVR).
The NVR shall have following minimum specifications:-

1 Approved Makes Axis/Bosch/Dell/Fujitsu/HP/Milestone/Delta-


Vivitek /Honeywell/Pelco/Sony
2 Type 45 Channel Rack-mountable NVR or Recording Server
3 Storage Should have Minimum 4Hard Disk slots.
Capacity
4 Operating Embedded OS suitable for the whole integration
System
5 Memory 8GB or better
6 Video Compression H.264/MJPEG
7 Recording support simultaneous recording of 45 IP cameras at
Support 1080p resolution
8 Synchronous Playback Minimum 16 Channel
910 Network Protocol HTTP/HTTPS, TCP/IP, RTSP, UDP, NTP, DHCP, IPC
Support Search
11 Input 100~240 V AC, 50/60 Hz. Any power converter that
Voltage is required to power the NVR has to be supplied by
Bidder.
12 Compatibility The supplied NVR must be compatible in all respects

Page 52 of 53
to the cameras being supplied at the locations
13 Operating 10°C ~ 40°C or better
temperature
14 Approval CE, FCC
The system shall be complete in all respect . The cameras shall be mounted at
suitable point so that the view is available at ESR/GSR & wired through PoE
switch through Cat6 cable & will relay the data to MCS through VPN.

29. ITEM NO. 29 OPERATION AND MAINTENANCE

Detailed scope of works explained in section 6 of this document. However, Following


are the minimum obligations covered under the scope of Operation and Maintenance
of Contractor.
1. Maintaining the minimum personnel as specified in contract during the entire O
& M period
2. Compliance with the obligations under this Contract.
3. Maintaining the minimum performance levels required during the contract
period
The Contractor must meet following Performance Targets on monthly basis:
a. Downtime of instruments / data logger / communication system
b. Control Valve operations through SCADA as per given schedule of
PCMC
c. Reporting / communication obligations
d. Periodic calibration of instrumentation and routine check up for
hassle free performance
e. Replacement / Restoration of equipment / Communication system
4. O & M of all monitoring and control instrumentation assets implemented during
constructions period
5. Monitoring of important parameters like Flow, Pressure, Energy and Turbidity.
6. O & M of SCADA Web Data Server and monitoring System of project area with
web enabled facility
7. O & M of telemetry system including Integrated GIS system and WDMS system
8. O & M of PLCs, Flow Meters, Chlorine Analysers, level, pressure, pH, turbidity etc.
9. Information management and reporting
10. Paying all licencing, royalty fees, development fees, internet fees, leased line,
dual sim charges etc.
11. O & M of existing and new instrumentation added into the CMS system or as
instructed by PCMC.
12. All the cost of operation of GPRS (4G LTE router)/GSM/VSAT modems/Broadband
internet modems, data transmission charges payable to service providers are
included in this item.

Sd/-
Joint City Engineer
Water Supply Department