Translation of the Lindenstraße 20 3. Mounting 3.5 Mounting Steps for Female Threads M20x1.

5
Original Operating Manual 74363 Güglingen
1.2 Staff Qualification and 9/16 UNF (for Extreme-Pressure Devices)
Fon: +49 7135 102-0 Qualified persons are persons that are familiar with 3.1 Mounting and Safety Instructions
Service: +49 7135 102-211
info@afriso.com the mounting, installation, putting into service,
- airborne parts, leaking fluid,
www.afriso.com operation, maintenance, removal from service, and - Due to wrong installation
Pressure Transmitters / screw-in probes disposal of the product and have the appropriate electric shock
- Do not use any seal!
qualification for their activity. - Always mount the device in a WARNING
DMU 01, DMU 01 K, DMU 03, DMU 03 HD, depressurized and de-
This includes persons that meet at least one of the DANGER
DMU 04, DMU 05P, DMU 07, DMU 07 FG energized condition! NOTE – The high-pressure tube will seal metallically
following three requirements:
in the chamfer on the pressure port. (sealing cone
- They know the safety concepts of metrology NOTE – If there is increased risk of damage to the
60°)
and automation technology and are familiar device by lightning strike or overvoltage, increased
therewith as project staff. lightning protection must additionally be provided! 1 Screw the high-pressure fitting into the female
- They are operating staff of the measuring and NOTE – Treat any unprotected diaphragm with thread on the pressure transducer.
automation systems and have been instructed utmost care; this can be damaged very easily.
in the handling of the systems. They are 2 Then tighten it using an open-end wrench:
© 2021 AFRISO-EURO-INDEX GmbH – NOTES – for mounting outdoors or in a moist approx. 120 Nm.
familiar with the operation of the devices and environment:
technologies described in this documentation. 3.6 Mounting Steps for Milk Pipe Connections
- Connect the device electrically straightaway after
- They are commissioning specialists or are mounting or prevent moisture penetration, e.g. by
employed in the service department, and have  The O-ring is undamaged and seated in the
a suitable protective cap. (The protection rating designated groove.
completed training that qualifies them for the specified on the data sheet applies to the
repair of the system. In addition, they are connected device.) 1 Center the milk pipe connection in the
All rights reserved.

READ THOROUGHLY BEFORE USING THE authorized to put into operation, to ground,
- Select the mounting position such that splashed corresponding mating fitting.
DEVICE and to mark circuits and devices according to
and condensed water can drain off. Stationary 2 Screw the sleeve nut onto the mating fitting.
KEEP FOR FUTURE REFERENCE the safety engineering standards.
liquid on sealing surfaces must be excluded! 3 Then tighten it using a hook wrench.
ID: 900.100.0831 Version: 10.2021.0 All work with this product must be carried out by
- If the device has a cable outlet, the outgoing cable 3.7 Mounting Steps for Clamp and Varivent®
qualified persons!
must be routed downwards. If the cable needs to Connections
1.3 Intended Use be routed upwards, this must be done in an
 A suitable seal for the measured fluid and the
initially downward curve.
The devices are used to convert the physical pressure to be measured is available.
parameter of pressure into an electric signal. - Mount the device such that it is protected from
1 Place the seal onto the corresponding mating
direct solar radiation. In the most unfavorable
The pressure transmitters are exclusively suited fitting
case, direct solar radiation leads to the exceeding
for measuring positive, negative and absolute of the permissible operating temperature. This 2 Center the clamp connection or Varivent
pressures. must be excluded if the device is used in any connection above the corresponding mating
The screw-in probes are exclusively suited to explosion-hazardous area! fitting
filling-level and process measuring technology. - A device with gauge reference in the housing 3 Then fasten the device using a suitable fastener
The user must check whether the device is suited (small hole next to the electrical connection) must (e.g. half-ring or retractable ring clamp
for the selected use. In case of doubt, please be mounted such that the gauge reference is connection) according to the instructions
contact our sales department (info@afriso.com). protected against dirt and humidity. If the specified by the manufacturer
AFRISO assumes no liability for any wrong selection transducer is exposed to liquid admission, the 3.8 Mounting Steps for Flange Connections
and the consequences thereof! gauge reference will be blocked, and the
The fluids that can be measured are gases and equalization of air pressure will be prevented. In  A suitable seal for the measured fluid and the
liquids that are compatible with the materials in this condition, a precise measurement is pressure to be measured is available. (e.g. a
contact with the fluids, described in the data sheet. impossible and damage to the transducer may fiber seal)
For application, it must additionally be ensured that occur. 1 Position the seal between the connecting flange
the fluid is compatible with the parts in contact with - Provide for a cooling section if the device is used and the mating flange
the fluid. in a steam line. 2 Then attach the device to the mating flange
NOTE – When installing the device, avoid high using 4 or 8 bolts/nuts (depending on flange
1.4 Limitation of Liability and Warranty design)
mechanical stresses on the pressure port! This will
Failure to observe the instructions or technical result in a shift of the characteristic curve or to
regulations, improper use and use not as intended, damage, in particular in case of very small pressure 4. Electrical Connection
1. General and Safety-Related Information on and alteration of or damage to the device will result ranges and devices with a pressure connection/port
this Operating Manual in the forfeiture of warranty and liability claims. 4.1 Connection and Safety Instructions
made of plastic.
This operating manual enables safe and proper 1.5 Safe Handling NOTE – In hydraulic systems, arrange the device - Improper installation may result
handling of the product, and forms part of the such that the pressure port points upwards. in electric shock
NOTE – Treat the device with care both in the
device. It should be kept in close proximity to the (venting)
packed and unpacked condition! - Always mount the device in a
place of use, accessible for staff members at any NOTE – If the device is installed with the pressure
NOTE – The device must not be altered or modified WARNING depressurized and de-
time. port pointing upwards, ensure that no liquid drains
in any way. energized condition!
All persons entrusted with the mounting, installation, off on the device. This could result in humidity and
putting into service, operation, maintenance, NOTE – Do not throw or drop the device! dirt blocking the gauge reference in the housing, NOTE – If the device is equipped with a cable
removal from service, and disposal of the device NOTE – Excessive dust accumulation (over 5 mm) and could lead to malfunctions. If necessary, dust fitting and/or cable box, it must be ensured that the
must have read and understood the operating and complete coverage with dust must be and dirt must be removed from the edge of the outer diameter of the line used is within the
manual and in particular the safety-related prevented! screwed joint of the electrical connection. permissible clamping range. Additionally it must be
information. The device is state-of-the-art and is operationally NOTE – Do not remove the packaging or protective ensured that this is seated firmly and gaplessly in
reliable. Residual hazards may originate from the caps of the device until shortly before the mounting the cable fitting!
The following documents are an important part device if it is used or operated improperly. NOTE – Use a shielded and twisted multicore cable
procedure, in order to exclude any damage to the
of the operating manual: for the electrical connection.
diaphragm and the threads!
- Data sheet 1.6 Scope of Delivery
Protective caps must be kept! Dispose of the NOTE – for devices with cable outlet
For specific data on the individual sensors, please Check that all parts listed in the scope of delivery packaging properly!
are included free of damage, and have been - When routing the cable, the following minimum
refer to the respective data sheet. bend radii must be observed:
delivered according to your purchase order: NOTE – The specified tightening torques must not
Download these by accessing www.bdsensors.de or be exceeded! Cable without air hose:
request them by e-mail or phone: info@afriso.com | fixed installation: 5-fold cable diameter
Fon: +49 7135 102-211 - Pressure transducer or screw-in probe 3.2 Mounting Steps for Connections According
flexible use: 10-fold cable diameter
In addition, the applicable accident prevention - for mech. connections to DIN 3852: O-ring to DIN 3852
(premounted) Cable with air hose:
regulations, safety requirements, and country- NOTE – Do not use any additional sealing material fixed installation: 10-fold cable diameter
specific installation standards as well as the - this operating manual such as tow, hemp or Teflon tape! flexible use: 20-fold cable diameter
accepted engineering standards must be observed.
2. Product Identification  The O-ring is undamaged and seated in the - In case of devices with cable outlet and
1.1 Symbols Used designated groove. integrated ventilation hose, the PTFE filter
The device can be identified by means of the type located at the cable end on the relative pressure
plate with order code. The most important data can  The sealing face of the mating component has hose must neither be damaged nor removed!
- Type and source of danger be gathered therefrom. a flawless surface. (RZ 6.3)
- Measures to avoid the NOTE – When devices with ISO 4400 are used, the
danger 1 2 3 4 5 6 1 Screw the device into the mating thread by cable box must be properly mounted so that the
Warning word hand. protection rating specified on the data sheet is
2 Devices with a wrench flat must be tightened ensured! Ensure that the seal supplied is installed
using a suitable open-end wrench. between the connector and the cable box. After
Warning word Meaning
Wrench flat made of steel: connecting the cable, attach the cable box to the
- Imminent danger! G1/4: approx. 5 Nm; G1/2: approx. 10 Nm; device by means of the screw.
- Non-compliance will G3/4: approx. 15 Nm; G1: approx. 20 Nm NOTE – On a device equipped with field housing,
result in death or serious Wrench flat made of plastic: the connection terminals are located underneath the
DANGER injury. max. 3 Nm) housing cover. The cover must be screwed off in
3 Devices equipped with a knurled ring: order to connect the device electrically. Before the
- Possible danger! only tighten by hand cover is screwed on again, the O-ring and sealing
- Non-compliance may 1 Type designation 4 Order code surface on the housing must be checked for damage
result in death or serious 3.3 Mounting Steps for Connections According and, if necessary, replaced! Then screw on the
2 Input 5 Terminal assignment to EN 837 cover by hand and make sure that the field housing
WARNING injury.
3 Output 6 Serial number is tightly closed again.
 A suitable seal for the measured fluid and the
- Hazardous situation!
Fig. 1: Type plate pressure to be measured is available. (e.g. a
- Non-compliance may result
copper seal)
in minor or moderate injury. NOTE – The type plate must not be removed!
CAUTION
 The sealing face of the mating component has
NOTE – draws attention to a possibly hazardous a flawless surface. (RZ 6.3)
situation that may result in property damage in case 1 Screw the device into the mating thread by
of non-compliance. hand.
 Precondition of an action 2 Then tighten it using an open-end wrench: G1/4:
approx. 20 Nm; G1/2: approx. 50 Nm
3.4 Mounting Steps for NPT Connections
 Suitable fluid-compatible sealing material, e.g.
PTFE tape, is available.
1 Screw the device into the mating thread by hand
2 Then tighten it using an open-end wrench: 1/4
NPT: approx. 30 Nm; 1/2 NPT: approx. 70 Nm
4.3 Electrical Installation 7. Troubleshooting 10. Decommissioning, diposal
Connect the device electrically according to the - Airborne parts, leaking fluids,
Dispose of the product in compliance with
information specified on the type plate, the following electric shock all applicable directives, standards and
table, and the connection circuit diagram. safety regulations.
- If malfunctions cannot be
Electronic components must not be
Terminal assignment table: CAUTION resolved, put the device out of
disposed of together with the normal
Electrical Binder M12x1 service and proceed according
household waste.
connections ISO 4400 723 (5- (4-pin) In case of malfunction, it must be checked whether
pin) the device has been correctly installed mechanically 1. Disconnect the product from
Supply + 1 3 1 and electrically. Use the following table to analyze mains.
Supply − 2 4 2 the cause and resolve the malfunction, if possible. 2. Dismount the product (see
ground Fault: no output signal chapter "Mounting the control
Shield 5 4 unit", reverse sequence of
pin Possible cause Fault detection / remedy
steps).
connected incorrectly Checking of connections
Electrical Bayonet MIL-C-26482 (10-6) Checking of all line
connections Conductor/wire breakage 11. Warranty
connections.
Supply + A Checking of ammeter See our terms and conditions at www.afriso.com or
Supply − B Defective measuring (miniature fuse) or of your purchase contract for information on warranty.
Shield Pressure port device (signal input) analog input of your
12. EU Declaration of Conformity
signal processing unit
Electrical Cable colors
Field housing
connections (IEC 60757) Fault: analog output signal too low/small
Supply + IN + wh (white) Possible cause Fault detection / remedy
Supply − IN - bn (brown) Checking of load
gnye (green- Load resistance too high
Shield resistance (value)
yellow) Checking of power pack
Supply voltage too low
output voltage
Checking of the power
p Supply + / in +
A pack and the supply
Defective energy supply
voltage being applied to
the device
UB
Fault: slight shift of the output signal
I Possible cause Fault detection / remedy
Supply – / in -
Cleaning using a non-
Diaphragm of measuring
aggressive cleaning
cell is severely
Fig. 4: Connection circuit diagram solution and soft
contaminated
paintbrush or sponge
NOTE – For unambiguous identification, the Recommendation: Have
intrinsically safe cable is marked with a light blue Diaphragm of measuring the decalcification or
shrinkable tube (around the cable insulation). If a cell is calcified or crusted cleaning performed by
modification (e.g. a shortening) of the cable is AFRISO
inevitable whereby the marking at the end of the
cable is lost, the marking must be restored! Fault: large shift of the output signal
(Renewed marking by a light blue shrinkable tube or Possible cause Fault detection / remedy
by an appropriate marking label) Diaphragm of measuring Checking of diaphragm;
NOTE – In the case of relative pressure gauges, the cell is damaged (caused when damaged, send the
cable contains a ventilation hose for pressure by overpressure or device to AFRISO for
equalization. Route the end of the cable into an area mechanically) repair
or suitable connection box which is as dry as
possible and free from aggressive gases, in order to Fault: wrong or no output signal
prevent any damage. Possible cause Fault detection / remedy
Checking of cable; pitting
5. Commissioning corrosion on the stainless-
Cable damaged
steel housing as a result
 The device has been installed properly mechanically, thermally or
of damage on cable; when
chemically
 The device does not have any visible defect damaged, send the device
to AFRISOfor repair
In case of highly precise devices with an
accuracy of 0.1 % FSO, a microcontroller-controlled 8. Removal from Service
electronic system is used for signal processing. This
electronic system is used for signal improvement. - Airborne parts, leaking fluids,
Due to the principle, the processing of measured electric shock
values requires a longer time than with purely - Always dismount the device in
analog sensors, which only comprise amplification DANGER a depressurized and de-
circuitry. Due to the longer processing time, the energized condition!
output signal follows the measured value not - due to aggressive fluids.
continuously but in jumps. In case of relatively - Wear suitable protective
stable and slowly changing measured values, this clothing, e.g. gloves, safety
property plays a minor role. Compare this with the Attention goggles.
information on the adjusting time in the data sheet.
NOTE – After dismounting, mechanical connections
In the case of i-devices with communications must be fitted with protective caps.
interface, the offset, range, and damping can be
adjusted within the limits specified in the data sheet, 9. Service/Repair
due to the electronic system. The CIS 510
programming kit is required for the configuration. Information on service / repair:
The kit consists of: Adapt 1, Windows®-compatible
- www.afriso.com
P-Scale 510 programming software, power pack
and connection cable. This can be ordered from - info@afriso.com
AFRISO as an accessory. - service@afriso.de

6. Maintenance 9.1 Recalibration


The offset value or range value may shift during the
- Airborne parts, leaking fluids, life of the device. In this case, a deviating signal
electric shock value in relation to the set lower or upper measuring
- Always service the device in a range value is output. If one of these two
DANGER depressurized and de- phenomena occurs after extended use, a
energized condition! recalibration in the factory is recommended. Please
note the chapter “Service/Repair” with regard to this.
- due to aggressive fluids
- Wear suitable protective
9.2 Returning the device
clothing, Get in touch with us before returning your product
Attention e.g. gloves, safety goggles. (service@afriso.de).

In principle, the device requires no maintenance.


If necessary, clean the housing of the device using a
moist cloth and a non-aggressive cleaning solution.
Cleaning of the diaphragm:
Deposits or contamination may occur on the
diaphragm in case of certain fluids. It is
recommended to establish appropriate maintenance
intervals for checking in connection with a function
control purposes.
Clean the diaphragm cautiously using a non-
aggressive cleaning solution and a soft paintbrush
or sponge.
If the diaphragm is calcified, it is recommended to
have the decalcification performed by AFRISO.
Please note the chapter “Service/Repair” with regard
to this.
NOTE – Wrong cleaning may damage the
measuring cell beyond repair. Do not use any sharp
or pointed item to clean the diaphragm.