You are on page 1of 6

)‫( )استبيان فني للعينات‬Technical Questionnaire for Schools)

‫ أي‬-‫بلد المنشأ‬-- ‫تاريخ الصنع‬-‫السعة‬-‫الكفاءة‬- ‫النوع‬-‫الموديل‬- ‫ (العالمة التجارية‬:‫ تعبئة كال من التالي‬،‫ يتم في خانة مواصفات عرض المتقدم‬: ‫مالحظة‬
)‫مواصفات أخرى يتطلبها البند‬
‫ محافظة عدن‬،‫ مديرية دار سعد‬- ‫ مكتب وزارة التربية والتعليم بمنظومات طاقة الشمسية‬+ ‫ مدارس‬8 ‫مشروع تزويد‬

Is quotation
compliant?
Bidder to Bidder’s Offer
Item Description
No. Confirm. Specifications/Details
‫مواصفات البند‬
‫هل العرض مطابق‬ ‫مواصفات عرض المتقدم‬
‫الرسم؟‬
‫ي‬ ‫للعرض‬
‫يرج من المتقدم إكماله‬
‫ى‬
1 Solar PV Module
-solar panels 550 W
-mono-crystalline or polycrystalline;
- The module type must conform with CE and IEC 61215, IEC
61730, IEC 61701 or equivalent standards;
- Module conversion efficiency should be equal to or greater
than 19.5 % under STC;
- The PV manufacturer should be approved as tier-1;
1.1 - The PV module shall perform satisfactorily in temperature ☐ Yes ☐ No
between – 40 oC to +85 oC;
- The rated output power of any supplied module shall have
tolerance of 0-5 W;
- The module shall be provided with a junction box with IP67;
- The supplied module DC voltage should be not less than 1000
VDC;
- The product warranty should be at least 10 years.
MPPT Inverter (5&8 kW, 50Hz, 220V, 48V, 120A) Built-in
2
MPPT Solar Charger
- Single Phase, Pure Sine wave, 230 V, 50 Hz, 5&8 kW, Built-in
MPPT Solar Charger, including all accessories required for
parallel operation as per technical specifications and drawings:
A. Input (DC):
- Max. PV input voltage = at least 500v. Min PV input voltage =
< 100v. Start-up voltage = < 120v. No. of MPPTs = 2. Max.
number of PV strings per MPPT = at least 2. Max. PV input
current = at least 25A.
B. Output (AC)
- AC output power = > 5&8KW. Max. AC output current = >
2.1 22&36A. AC voltage = 220v. Frequency = 50Hz. Total harmonic ☐ Yes ☐ No
distortion (THD) < 3 % (of nominal power).
C. Battery input:
- Battery Type: OPZV. Battery Voltage= 48v. Maximum
charging/discharging current(A)=> 100A.
D. Protection:
- Protections required: AC overload and load short circuit,
overvoltage, overheating and battery reverse polarity, PV
reverse connection protection, Leakage current protection.
Grid monitoring. PV string current monitoring. DC switch.
E. General Data
)‫( )استبيان فني للعينات‬Technical Questionnaire for Schools)
‫ أي‬-‫بلد المنشأ‬-- ‫تاريخ الصنع‬-‫السعة‬-‫الكفاءة‬- ‫النوع‬-‫الموديل‬- ‫ (العالمة التجارية‬:‫ تعبئة كال من التالي‬،‫ يتم في خانة مواصفات عرض المتقدم‬: ‫مالحظة‬
)‫مواصفات أخرى يتطلبها البند‬
‫ محافظة عدن‬،‫ مديرية دار سعد‬- ‫ مكتب وزارة التربية والتعليم بمنظومات طاقة الشمسية‬+ ‫ مدارس‬8 ‫مشروع تزويد‬

Is quotation
compliant?
Bidder to Bidder’s Offer
Item Description
No. Confirm. Specifications/Details
‫مواصفات البند‬
‫هل العرض مطابق‬ ‫مواصفات عرض المتقدم‬
‫الرسم؟‬
‫ي‬ ‫للعرض‬
‫يرج من المتقدم إكماله‬
‫ى‬
- Efficiency = > 92%. Operating ambient temperature -25 °C to
60 ℃. Allowable relative humidity (non-condensing) = 0 – 100
%. Display: LCD. Communication: Wi-Fi, RS485. To be certified
to meet at least CE and UL marking and complaint with IEC
62109; The inverter should allow the plate matrix voltage of at
least 500 volts. The inverter shall have Parallel capability
connection characteristic with many Cells. The inverter shall
allow internet connection for remote monitoring; Product
warranty shall be 5 years.

3 Solar Battery with Racks


- Battery bank voltage shall be 48 volts with built in battery rack as per
technical specifications.
- Batteries shall be Gel type OPzV 2V cell, the rating shall be calculated @ 10
Hr discharge rate;
-battery Capacity : 450,600,800,1000 & 1500 Ah
- Battery cyclic life shall be at least 3500 cycles at 50% depth of discharge
(DOD), third party test reports shall be provided proofing the battery lifecycle.
- Reliable performance at high operating temperatures of up to 50° C;
- Wires connected to batteries shall utilize appropriately sized and rated lugs
3.3 or terminals and proper hardware; battery shall be installed in a secured, well- ☐ Yes ☐ No
ventilated powerhouse, or in an outdoor rated enclosure.
- One brand of battery shall be used for the entire installation;
- The operating temperature for the battery shall be -20°C to +55 °C;
- Product warranty shall be 2 years; warranty certificates shall be provided by
the manufacturer;
- Battery Rack with built in busbars should be configured for 48 VDC, powder
coated with a corrosion resistant acid proof powder, the battery rack busbars
shall be covered.

4 DC Cabling
-DC Cabling 1KV, Flexible stranded copper per EN 60228, TUV certified.
Insulation: Halogen-free, thermoset polyolefin. Jacket: low smoke non-
halogenated, flame retardant, oil, abrasion, chemical and sunlight resistant
meeting UL 44, UL 854.
- All cables shall be marked properly according to approved design so that
cable can be easily traced and identified;
PV array to battery circuit(s) to be sized for maximum 3% voltage drop at rated
4.3 array power (Imp); ☐ Yes ☐ No
Cable ends connections are to be made through suitable lugs or terminals,
crimped properly & with use of cable glands;
this item is including the cables and cable trays
Cable Tray :- 1mm thickness, Perforated type Galvanized steel cable trays,
cable tray covers, clamping bolts and other cable tray accessories such as
coupler plates, bends, tees, reducers, vertical elbows in manufactured
accordance with ASTM A653 SS, Grade 33, coating designation G90.
)‫( )استبيان فني للعينات‬Technical Questionnaire for Schools)
‫ أي‬-‫بلد المنشأ‬-- ‫تاريخ الصنع‬-‫السعة‬-‫الكفاءة‬- ‫النوع‬-‫الموديل‬- ‫ (العالمة التجارية‬:‫ تعبئة كال من التالي‬،‫ يتم في خانة مواصفات عرض المتقدم‬: ‫مالحظة‬
)‫مواصفات أخرى يتطلبها البند‬
‫ محافظة عدن‬،‫ مديرية دار سعد‬- ‫ مكتب وزارة التربية والتعليم بمنظومات طاقة الشمسية‬+ ‫ مدارس‬8 ‫مشروع تزويد‬

Is quotation
compliant?
Bidder to Bidder’s Offer
Item Description
No. Confirm. Specifications/Details
‫مواصفات البند‬
‫هل العرض مطابق‬ ‫مواصفات عرض المتقدم‬
‫الرسم؟‬
‫ي‬ ‫للعرض‬
‫يرج من المتقدم إكماله‬
‫ى‬

5 AC Cabling
- AC Cabling Stranded type, TUV certified, double insulating material 1kV
XPLE/PVC/CU
- All cables shall be marked properly according to approved design so that
cable can be easily traced and identified;
- All outdoor exposed wiring to be protected from UV radiation and physical
damage, all cabling above ground should be suitably mounted inside cable
5.1 trays with proper covers; ☐ Yes ☐ No
- XLPE insulated and PVC seethed single or multi core flexible copper cables
meeting IEC 60227 and IEC 60502;
- Cable ends connections are to be made through suitable lugs or terminals,
crimped properly & with use of cable glands;

6 Inverter / Battery DC Breakers Box


Supply, install, test, and commissioning DC breakers box including different DC
6.1 breakers and all the required accessories as per drawings ☐ Yes ☐ No

7 AC Coupling
- Metal Enclosure, Indoor, Built in SPD, RCCB, MCCB as shown on schematic
wiring diagram
- Internal connection should be through busbars;
- Ingress protection must be at least IP41;
- Enclosure material should be galvanized steel sheets;
7.1 - Fault level for the main breaker: At least 25 kA; ☐ Yes ☐ No
- advised to use high quality breakers;
- The EMDB should be in accordance with the drawings;
- Warranty: at least 1 year.

8 NEW Main Distribution Board (New-MDB)


- main electrical distribution board for the building model (New-MDB) with a
magnetic main circuit breaker MCCB three phase - 380 V - 50 Hz - payload 250
A (25KA) Bus bar 300A with sub circuit breakers number 8 sub circuit breaker 3
phase installs 6 circuit breakers below and leave the rest space for expansion
In the future:
2 x 100 A 3 phase MCCB TP (25KA).
4 x 63 A 3 phase MCCB TP 16KA).
The plate cover and the outer frame of the sheet shall be thickness of 1.5 mm
8.1 and painted electrostatic. Resistant to moisture, echo and water (Powder ☐ Yes ☐ No
Coated). The price includes a metal base for the plate with a height of 60 cm
and all the necessary accessories for the plate and the control in addition to
the aforementioned voltage and current measuring devices, signal lamps,
current transformers and so on. The price includes all the supplies for fixing,
numbering and preparing for cable entry slots so that they are regular circular
holes with the installation of copper and plastic glides compatible with cable
clips and main and subsidiary extensions with the assignment of the main and
)‫( )استبيان فني للعينات‬Technical Questionnaire for Schools)
‫ أي‬-‫بلد المنشأ‬-- ‫تاريخ الصنع‬-‫السعة‬-‫الكفاءة‬- ‫النوع‬-‫الموديل‬- ‫ (العالمة التجارية‬:‫ تعبئة كال من التالي‬،‫ يتم في خانة مواصفات عرض المتقدم‬: ‫مالحظة‬
)‫مواصفات أخرى يتطلبها البند‬
‫ محافظة عدن‬،‫ مديرية دار سعد‬- ‫ مكتب وزارة التربية والتعليم بمنظومات طاقة الشمسية‬+ ‫ مدارس‬8 ‫مشروع تزويد‬

Is quotation
compliant?
Bidder to Bidder’s Offer
Item Description
No. Confirm. Specifications/Details
‫مواصفات البند‬
‫هل العرض مطابق‬ ‫مواصفات عرض المتقدم‬
‫الرسم؟‬
‫ي‬ ‫للعرض‬
‫يرج من المتقدم إكماله‬
‫ى‬
branch cables ends with special copper wicker with all accessories Installation
and operation. The main and subsidiary partitions of the plates shall be
thermomagnetic in number, capacity and type according to drawings and
specifications and according to the rules of workmanship and the instructions
of the supervising engineer.

9 AC Sub Distribution Board (AC-SDB)


-main electrical distribution board for the building model (AC-SDB) AC Sub-
distribution boards unit complete to segregate non-critical loads as per solar
integration single line diagram. The price includes a magnetic main circuit
breaker MCCB three phase - 380 V - 50 Hz - payload 100 A (25KA) Bus bar 125A
9.1 with sub circuit breakers number 24 sub circuit breaker 1 phase (MCB) ☐ Yes ☐ No
according to drawings and specifications and according to the rules of
workmanship and the instructions of the supervising engineer.

10 Automatic Transfer Switch


- Low Voltage ATS 4P, 100A, 2 ways as per technical specifications including
10.1 metal enclosure ☐ Yes ☐ No

11 Earthing System + Lightning


- Earthing System As per technical specifications and drawings including
cabling, cable lugs, earthing rods and all required accessories
- Each array structure of the PV modules should be grounded properly;
- lighting arrester shall be copper.
-Earthing pit
- Earth resistance should be tested in presence of the UNDP representative by
11.1 calibrated earth tester, the earth resistance should not be more than 5 Ohm. ☐ Yes ☐ No
- Earthing installation in accordance with the IEE Wiring regulations, BS 7671
- All conductive materials shall be copper.
- The size of conductor shall be according to table 54.7 of IEE – BS 7671 – IEC
60365-5-54.

12 Lighting System
-LED light fixture (20 W) 1200 mm length to replace existing florescent
including dismantling the old units as per technical specification
- Mount type: Surface Mount;
- Colour: White;
- Lamp luminous efficacy: not less than 100 lm/W;
12.1 - Housing: Metal; ☐ Yes ☐ No
- Input Voltage and frequency: 220-240V, 50 Hz;
- Working Lifetime (Hour): at least 10,000 h;
- Certification: All related certificates shall be provided such CE, RoHS;
- Warranty at least two years.
- LED light bulb (1X 9 w) as per technical specifications
- Lamp luminous efficacy: not less than 90 lm/W;
12.2 - Cap type & base: bayonet bulbs- B22d-BC/ E27; ☐ Yes ☐ No
- Colour temperatures (CCT): 5000 K to 6500 K;
- Input Voltage and frequency: 220V, 50 Hz;
)‫( )استبيان فني للعينات‬Technical Questionnaire for Schools)
‫ أي‬-‫بلد المنشأ‬-- ‫تاريخ الصنع‬-‫السعة‬-‫الكفاءة‬- ‫النوع‬-‫الموديل‬- ‫ (العالمة التجارية‬:‫ تعبئة كال من التالي‬،‫ يتم في خانة مواصفات عرض المتقدم‬: ‫مالحظة‬
)‫مواصفات أخرى يتطلبها البند‬
‫ محافظة عدن‬،‫ مديرية دار سعد‬- ‫ مكتب وزارة التربية والتعليم بمنظومات طاقة الشمسية‬+ ‫ مدارس‬8 ‫مشروع تزويد‬

Is quotation
compliant?
Bidder to Bidder’s Offer
Item Description
No. Confirm. Specifications/Details
‫مواصفات البند‬
‫هل العرض مطابق‬ ‫مواصفات عرض المتقدم‬
‫الرسم؟‬
‫ي‬ ‫للعرض‬
‫يرج من المتقدم إكماله‬
‫ى‬
- Working Lifetime (Hour): at least 15,000 h;
- Operation temperature rang: up to 50°C;
- Certification: All related certificates shall be provided such CE, RoHS;
- Warranty: at least two years.

13 Fans
- energy efficient ceiling fans 1200 mm length to replace existing ceiling fans
including dismantling the old units as per technical specification
- No. of blades:3
- Air delivery: not less than 200CMM;
-speed controller & Remote control
13.1 - metal components must be rust proof ☐ Yes ☐ No
- Input Voltage and frequency: 220-240V, 50 Hz;
- Certification: All related certificates shall be provided such CE, RoHS;
- Warranty at least two years.

- exhaust fan with a capacity of at least 200 CFM to be installed at the iron grill
sides at the proposed battery room. The work should include all the required
13.2 accessories, Switch, cables(3*2.5mm2), trays, civil works and any component ☐ Yes ☐ No
to ensure a professional installation according to the supervisor engineer.

- wall Mounted fans 30W)


- fan 30 W;
- Voltage rating: 220-240 VAC, 50 Hz ±2%;
- Working life time: not less than 15,000;
- Wall Mounted type;
13.3 - Warranty: at least one years. ☐ Yes ☐ No
The work should include all the required accessories, Switch,
cables(3*2.5mm2), trays, civil works and any component to ensure a
professional installation according to the supervisor engineer.

14 Smoke and Heat Detectors:


Smoke and Heat Detector: Supply, install and testing Smoke and heat detector,
including button for false alert. Battery for three years long life, warning sound
14.1 delivers sounds of >85 Db ☐ Yes ☐ No

15 Extinguishers:
Supply, install, test and commissioning 5kg Carbon Dioxide (CO2) Extinguisher
15.1 - Warranty: at least two years. ☐ Yes ☐ No
Supply, install, test and commissioning 6kg Powder extinguisher
15.2 - Warranty: at least two years. ☐ Yes ☐ No
16 Other Components
16.1 25A wall mount Switch for Air Conditioner with wiring ☐ Yes ☐ No
17 Mounting Structure
)‫( )استبيان فني للعينات‬Technical Questionnaire for Schools)
‫ أي‬-‫بلد المنشأ‬-- ‫تاريخ الصنع‬-‫السعة‬-‫الكفاءة‬- ‫النوع‬-‫الموديل‬- ‫ (العالمة التجارية‬:‫ تعبئة كال من التالي‬،‫ يتم في خانة مواصفات عرض المتقدم‬: ‫مالحظة‬
)‫مواصفات أخرى يتطلبها البند‬
‫ محافظة عدن‬،‫ مديرية دار سعد‬- ‫ مكتب وزارة التربية والتعليم بمنظومات طاقة الشمسية‬+ ‫ مدارس‬8 ‫مشروع تزويد‬

Is quotation
compliant?
Bidder to Bidder’s Offer
Item Description
No. Confirm. Specifications/Details
‫مواصفات البند‬
‫هل العرض مطابق‬ ‫مواصفات عرض المتقدم‬
‫الرسم؟‬
‫ي‬ ‫للعرض‬
‫يرج من المتقدم إكماله‬
‫ى‬
-Fabrication and erection in position columns, rafters, bracing ☐ Yes ☐ No
and others made out of Cold-formed galvanized steel (min --
galvanized 80~120mic) sections with minimum yield strength
of 240Mpa
17.1
-galvanized HSS steel purlins (60x30x1.25) (min galvanized
80~120mic)
- bolts is A325 or A490 high strength bolts (Hardness equal
8.8).
17.2 Cement ☐ Yes ☐ No
17.3 Sand ☐ Yes ☐ No
17.4 aggregate ☐ Yes ☐ No
☐ Yes ☐ No
17.5 Steel reinforcement