Boiler Purging time is 5 mins, which

ensures proper removal of any unburnt fuel


What is particles/combustible gases to be
Purging? transported outside boiler furnace
PURGE PERMISSIVIE PROPOSED CHANGE /PURPOSE/EFFEC

Purge permissive Current Status Proposed Change

Air flow < 30 % In service In service

All Aux air damper


In service In service
modulating(open condition)
All feeder Off In service In service
All scanner No Flame In service In service

All Mill HAG Close In service Bypass

All HDR/LOTV valve close In service In service


All oil off /LONV In service In service
All pulv off In service In service
Both PA off In service In service

Drum Level Proper In service Bypass

Burner Tilt Horizontal In service In service


D CHANGE /PURPOSE/EFFECT

Purpose Effect

To Ensure adequate air flow inside boiler furnace that is required


Not Applicable
to transfer unburnt fuel to stack

To ensure adequate air flow Not Applicable

NO fuel supply equipment should be running Not Applicable


NO flame sensed by flame scanners Not Applicable

No effect as "Both PA fan


NO fuel supply equipment should be running
OFF" will be in service.

NO fuel supply equipment should be running Not Applicable


NO fuel supply equipment should be running Not Applicable
NO fuel supply equipment should be running Not Applicable
NO fuel supply equipment should be running Not Applicable

No Effect.Boiler drum level


NO boiler trip conditions persisting/Boiler should be RESET LOW/HIGH is kept bypass
already.
To ensure proper air flow profile Not Applicable
Reason

NA

NA
NA
NA

Close limit feedback not coming


sometimes leading to Purge delay
NA
NA
NA
NA

1-2 port mismatch leads t odelay

NA