You are on page 1of 40

INSTALLATION MANUAL

Indoor unit for air to water heat pump system

For installation WITH restricted power supply condition

=6 kW

EKHBHE008BA3V3
EKHBXE008BA3V3
2

1 2 3 4 5 300
1x 1x 2x 1x 2x

500
≥350


1 2

3 260

T T
895

922

830

B B

469

1-1/2" FBSP
4

1" MBSP 30°

90
°
361
96
48

39

35
48
2 4
3 142 101 5
502

3
EKHBHE008BA***
EKHBXE008BA***
Indoor unit for air to water heat pump system Installation manual

CONTENTS Page
READ THESE INSTRUCTIONS CAREFULLY BEFORE
Introduction........................................................................................ 1 INSTALLATION. KEEP THIS MANUAL IN A HANDY
General information ................................................................................... 1 PLACE FOR FUTURE REFERENCE.
Scope of this manual ................................................................................. 3
IMPROPER INSTALLATION OR ATTACHMENT OF
Model identification .................................................................................... 3
EQUIPMENT OR ACCESSORIES COULD RESULT IN
Accessories ....................................................................................... 3 ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
Accessories supplied with the indoor unit .................................................. 3 OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
Safety considerations ........................................................................ 3 TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
Typical application examples ............................................................. 4 SPECIFICALLY DESIGNED FOR USE WITH THE
Application 1 .............................................................................................. 4 EQUIPMENT AND HAVE THEM INSTALLED BY A
Application 2 .............................................................................................. 5 PROFESSIONAL.
Application 3 .............................................................................................. 5
ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL
Application 4 .............................................................................................. 6
Application 5 .............................................................................................. 7
BE CARRIED OUT BY A LICENSED TECHNICIAN.
Application 6 .............................................................................................. 8 BE SURE TO WEAR ADEQUATE PERSONEL PROTEC-
Overview of the indoor unit................................................................ 9 TION EQUIPMENT (PROTECTION GLOVES, SAFETY
Opening the indoor unit.............................................................................. 9 GLASSES, ...) WHEN PERFORMING INSTALLATION,
Main components..................................................................................... 10 MAINTENANCE OR SERVICE TO THE UNIT.
Switch box main components .................................................................. 11
Functional diagram .................................................................................. 12
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
Installation of the indoor unit............................................................ 12
ADVICE AND INFORMATION.
Selecting an installation location.............................................................. 12
Dimensions and service space ................................................................ 13 THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED
Inspecting, handling and unpacking the unit............................................ 13 FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT
Mounting the indoor unit .......................................................................... 13 TEMPERATURES RANGING 4°C~35°C.
Installation of the EKHBDP drain pan kit (only for EKHBX models)......... 14
Refrigerant pipework................................................................................ 14 The English text is the original instruction. Other languages are
Water pipework ........................................................................................ 14 translations of the original instructions.
Charging water......................................................................................... 16
Piping insulation....................................................................................... 17
Field wiring............................................................................................... 17
Relocation of the digital controller............................................................ 20 INTRODUCTION
Start-up and configuration ............................................................... 20
DIP switch settings overview.................................................................... 20
Room thermostat installation configuration.............................................. 21 General information
Pump operation configuration .................................................................. 21
Domestic hot water tank installation configuration ................................... 22 Thank you for purchasing this indoor unit.
Initial start-up at low outdoor ambient temperatures................................ 22
Re-start at low outdoor ambient temperatures......................................... 22 The unit is the indoor part of the air to water ERHQ or ERLQ heat
Pre-operation checks ............................................................................... 22 pumps. These units are designed for wall mounted indoor installation.
Powering up the indoor unit ..................................................................... 22 See "Selecting an installation location" on page 12. The units can be
Setting the pump speed ........................................................................... 23 combined with Daikin fan coil units, floor heating applications, low
Field settings............................................................................................ 23 temperature radiators, Daikin domestic water heating applications
Field settings table ................................................................................... 30 and Daikin solar kit for domestic hot water applications.
Test run and final check................................................................... 32
Final check............................................................................................... 32
Heating/cooling units and heating only units
Test run operation (manual) ..................................................................... 32 The unit range consists of two main versions: a heating/cooling
Maintenance and service ................................................................ 32 (EKHBX) version and a heating only (EKHBH) version.
Maintenance activities.............................................................................. 32
Both versions are delivered with an integrated backup heater. The
Troubleshooting ............................................................................... 33 backup heater only serves as a backup in case of malfunctioning of
General guidelines ................................................................................... 33 the outdoor unit.
General symptoms................................................................................... 34
Error codes .............................................................................................. 35 Backup heater
Technical specifications ................................................................... 37 Indoor unit model Backup heater capacity nominal voltage

General .................................................................................................... 37 EKHB*E008BA3V3 3 kW 1x 230 V


Electrical specifications............................................................................ 37

NOTE ■ An ERLQ0*BA outdoor unit can only be


connected to an EKHBH/XE008BA indoor unit
(bottom plate heater at outdoor unit has to be
controlled by indoor unit).
■ An ERHQ0*BA outdoor unit can be connected to
an EKHBH/XE008BA indoor unit or to an
EKHBH/XE008AA indoor unit (if a bottom plate
heater kit is required, see "Possible options" on
page 2).

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 1
PH Balance between space heating/cooling demand and
domestic hot water demand
■ Only if the unit is correctly sized then at some point
1
during space cooling/heating operation the unit will
reach the requested setpoint. When this occurs,
2
domestic water heating by compressor becomes
possible.
To ensure domestic hot water production, the
schedule timers must be used to disable space
heating/cooling. Refer to the operation manual on how
TD TA to program the schedule timers.
1 Heat pump capacity ■ Booster heater operation is only possible when the
2 Required heating capacity (site dependent) compressor of the heatpump is not operating. The
compressor operates because of space
TD Design temperature
cooling/heating demand or because of domestic
TA Ambient (outdoor) temperature water heating.
PH Heating capacity To ensure domestic hot water production, the
schedule timers must be used to disable space
heating/cooling. Refer to the operation manual on how
■ At selection of the heat pump, the heat pump capacity to program the schedule timers.
must match:
■ If using a room thermostat, domestic water heating by
- the required space heating capacity of the lowest
compressor or by booster heater is NOT possible as
expected outdoor ambient temperature.
long as the room thermostat demands cooling or
AND heating.
- the domestic hot water demand when installing the In this case de-activate the room thermostat demand
optional domestic hot water tank. by its schedule timer.
■ The backup heater capacity and the optional booster Refer to the manual of the room thermostat for a
heater capacity are not supplementary to the heat detailed explanation how to de-activate space
pump capacity. The total capacity of the system cooling/heating by schedule timer, or refer to the
equals the capacity of the heat pump and not the sum separate addendum for an example of the Daikin
of heat pump and backup heater capacity and the room thermostat schedule timer programming.
optional booster heater capacity.
Drain pan kit (option)
Emergency backup heater operation always has
For heating/cooling versions (EKHBX), it is necessary to install the
priority over compressor or booster heater operation.
EKHBDP drain pan kit.
Emergency backup heater operation occurs because of: For more information concerning the drain pan kit, refer to
■ User request to heat up water to the space heating "Installation of the EKHBDP drain pan kit (only for EKHBX models)"
loops. The temperature of this water is too low and is on page 14.
out of the operation range (during initial start-up for Solar kit for domestic hot water tank (option)
example). Refer to "Initial start-up at low outdoor
ambient temperatures" on page 22 and "Re-start at For information concerning the EKSOLHW solar kit, refer to the
low outdoor ambient temperatures" on page 22. installation manual of that kit.
■ During heating operation the water temperature Digital I/O PCB kit (option)
becomes too low and drops out of the operation
An optional EKRP1HB digital I/O PCB can be connected to the
range. Refer to "Checking the water volume and
indoor unit and allows:
expansion vessel pre-pressure" on page 15 to
minimize the backup heater operation. ■ remote alarm output
■ Malfunction of the heat pump unit. ■ heating/cooling ON/OFF output
If during backup heater operation the heating load is higher ■ bivalent operation (permission signal for the auxiliary boiler)
than the heater capacity, the water temperature can not Refer to the operation manual of the indoor unit and to the installation
increase. In this case refer to "Re-start at low outdoor manual of the digital I/O PCB for more information.
ambient temperatures" on page 22.
Refer to the wiring diagram or connection diagram for connecting this
Domestic hot water tank (option) PCB to the unit.

An optional EKHW* domestic hot water tank with integrated 3 kW Remote thermostat kit (option)
electrical booster heater can be connected to the indoor unit. The An optional room thermostat EKRTW, EKRTWA, or EKRTR can be
domestic hot water tank is available in three sizes: 150, 200 and connected to the indoor unit. Refer to the installation manual of the
300 litre. Refer to the domestic hot water tank installation manual for room thermostat for more information.
further details.
Possible options
Simultaneous operation of compressor, backup heater and
EKBPHT08 EKBPHT08BA
booster heater is NOT possible. Read attentively following
warnings to understand the unit operation. EKHBH/XE008AA Possible Not allowed
EKHBH/XE008BA Possible Possible

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
2 4PW56301-1A
Scope of this manual SAFETY CONSIDERATIONS

This installation manual describes the procedures for handling, The precautions listed here are divided into the following two types.
installing and connecting all EKHBH/X indoor unit models. Both cover very important topics, so be sure to follow them carefully.

NOTE Installation of the ERHQ or ERLQ heat pump outdoor Meanings of DANGER, WARNING, CAUTION and NOTE symbols.
unit is described in the outdoor unit installation DANGER
manual.
Indicates an imminently hazardous situation which, if not
Operation of the indoor unit is described in the indoor avoided, will result in death or serious injury.
unit operation manual.
WARNING

Model identification Indicates a potentially hazardous situation which, if not


avoided, could result in death or serious injury.
Indoor unit CAUTION
EK HB XE 008 AA 3 V3 Indicates a potentially hazardous situation which, if not
Backup heater nominal avoided, may result in minor or moderate injury. It may also
voltage: be used to alert against unsafe practices.
V3 = 1P, 230 V
NOTE
Backup heater capacity (kW)
Indicates situations that may result in equipment or
Series
property-damage accidents only.
(a)
Indication of heating/cooling capacity (kW)
XE = heating and cooling, Danger
HE = heating only
Hydro box ■ Before touching electric terminal parts, turn off power switch.
European kit ■ When service panels are removed, live parts can be easily
(a) For exact values, refer to "Technical specifications" on page 37. touched by accident.
Never leave the unit unattended during installation or servicing
Drain pan kit (optional)
when the service panel is removed.
EK HB DP 150 ■ Do not touch water pipes during and immediately after operation
Drain pan as the pipes may be hot. Your hand may suffer burns. To avoid
Hydro box injury, give the piping time to return to normal temperature or be
European kit
sure to wear proper gloves.
■ Do not touch any switch with wet fingers. Touching a switch with
wet fingers can cause electrical shock.
ACCESSORIES ■ Before touching electrical parts, turn off all applicable power
supply.

Accessories supplied with the indoor unit Warning


■ Tear apart and throw away plastic packaging bags so that
See figure 1 children will not play with them.
1 Installation manual Children playing with plastic bags face danger of death by
2 Operation manual
suffocation.

3 Shut-off valve ■ Safely dispose of packing materials. Packing materials, such as


nails and other metal or wooden parts, may cause stabs or other
4 Wiring diagram sticker (inside indoor unit cover)
injuries.
5 Indoor unit cover fixing screw
■ Never directly touch any accidental leaking refrigerant. This
could result in severe wounds caused by frostbite.
■ Do not touch the refrigerant pipes during and immediately after
operation as the refrigerant pipes may be hot or cold, depending
on the condition of the refrigerant flowing through the refrigerant
piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant
pipes. To avoid injury, give the pipes time to return to normal
temperature or, if you must touch them, be sure to wear proper
gloves.
■ Do not touch the internal parts (pump, backup heater, etc.)
during and immediately after operation.
Your hands may suffer burns if you touch the internal parts. To
avoid injury, give the internal parts time to return to normal
temperature or, if you must touch them, be sure to wear proper
gloves.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 3
Caution TYPICAL APPLICATION EXAMPLES
■ Earth the unit.
The application examples given below are for illustration purposes
Earthing resistance should be according to local and national
only.
regulations.
Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire. Application 1
Incomplete earthing may cause electric shocks.
Space heating only application with the room thermostat connected
■ Gas pipe.
to the indoor unit.
Ignition or explosion may occur if the gas leaks.
■ Water pipe.
Hard vinyl tubes are not effective earths.
■ Lightning conductor or telephone earth wire.
Electric potential may rise abnormally if struck by a lightning T
bolt.
1 2 3 4 5 6
■ Install the power wire at least 1 meter away from televisions or
radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not
be sufficient to eliminate the noise.)
■ Do not rinse the unit. This may cause electric shocks or fire.
■ Do not install the unit in places such as the following:
■ Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or FHL1
7
water to leak. FHL2
FHL3
■ Where corrosive gas, such as sulphurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may cause the 1 Outdoor unit 6 Collector (field supply)
refrigerant to leak. 2 Indoor unit 7 Shut-off valve
■ Where there is machinery which emits electromagnetic 3 Heat exchanger FHL1..3 Floor heating loop
waves. 4 Pump T Room thermostat
Electromagnetic waves may disturb the control system, and (optional)
5 Shut-off valve
cause malfunction of the equipment.
■ Where flammable gases may leak, where carbon fibre or Pump operation and space heating
ignitable dust is suspended in the air or where volatile When the room thermostat (T) is connected to the indoor unit, the
flammables, such as thinner or gasoline, are handled. pump (4) will operate when there is a heating request from the room
Such gases may cause a fire. thermostat, and the outdoor unit will start operating to achieve the
■ Where the air contains high levels of salt. target leaving water temperature as set on the user interface.
■ Where voltage fluctuates a lot, such as that in factories. When the room temperature is above the thermostat set point, the
■ In vehicles or vessels. outdoor unit and pump will stop operating.

■ Where acidic or alkaline vapour is present. Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 19) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 21).

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
4 4PW56301-1A
Domestic water heating
Application 2
When domestic water heating mode is enabled (either manually by
Space heating only application without room thermostat connected to the user, or automatically through a schedule timer) the target
the indoor unit. The temperature in each room is controlled by a valve domestic hot water temperature will be achieved by the heat
on each water circuit. Domestic hot water is provided through the exchanger coil or the electrical booster heater.
domestic hot water tank which is connected to the indoor unit.
When the domestic hot water temperature is below the user
configured set point, the 3-way valve will be activated to heat the
domestic hot water by means of the heat pump. In case of a high
domestic hot water temperature setting, the booster heater (11)
provides heating.
1 2 3 4 5 8 6 9
T1 T2 T3 NOTE The indoor unit can be configured so that at low
M outdoor temperatures the domestic hot water is
exclusively heated by the booster heater. This assures
M1 M2 M3 that the full capacity of the heat pump is available for
space heating.
Details on domestic hot water tank configuration for
low outdoor temperatures can be found under "Field
11 12 settings" on page 23, field settings [5-02] to [5-04].
7 FHL1
FHL2
FHL3
Application 3
10
Space cooling and heating application with the room thermostat set
for heating/cooling connected to the indoor unit. Heating is provided
through floor heating loops and fan coil units. Cooling is provided
through the fan coil units only.
1 Outdoor unit 10 Domestic hot water tank Domestic hot water is provided through the domestic hot water tank
(optional) which is connected to the indoor unit.
2 Indoor unit
3 Heat exchanger 11 Booster heater 6
4 Pump 12 Heat exchanger coil
5 Shut-off valve FHL1..3 Floor heating loop
6 Collector (field supply) T1..3 Individual room
thermostat (optional)
7 Shut-off valve
8 Motorised 3-way valve M1..3 Individual motorised T
(delivered with valve to control loop
domestic hot water FHL1 (field supply)
tank) FCU1
9 By-pass valve 1 2 3 4 5 8 13 FCU2
(field supply) FCU3

M M
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.

NOTE Details on pump configuration can be found under 11 12


7 FHL1
"Pump operation configuration" on page 21.
FHL2
FHL3
Space heating
10
The outdoor unit (1) will operate to achieve the target leaving water
temperature as set on the user interface.

NOTE When circulation in each space heating loop (FHL1..3)


is controlled by remotely controlled valves (M1..3), it is
1 Outdoor unit 10 Domestic hot water tank
important to provide a by-pass valve (9) to avoid the
(optional)
flow switch safety device from being activated. 2 Indoor unit
3 Heat exchanger 11 Booster heater
The by-pass valve should be selected as such that at
all time the minimum water flow as mentioned under 4 Pump 12 Heat exchanger coil
"Water pipework" on page 14 is guaranteed. 5 Shut-off valve 13 Motorised 2-way valve
(field supply)
6 Collector (field supply)
It is recommended to select a pressure difference
controlled by-pass valve. 7 Shut-off valve FCU1..3 Fan coil unit (optional)
8 Motorised 3-way valve FHL1..3 Floor heating loop
(delivered with
T Room thermostat with
domestic hot water
heating/cooling switch
tank)
(optional

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 5
Pump operation and space heating and cooling
1 Outdoor unit 14 Motorised 2-way
According to the season, the customer will select cooling or heating 2 Indoor unit
valve for activation of
on the room thermostat (T). This selection is not possible by the room thermostat
3 Heat exchanger (field supply)
operating the user interface.
4 Pump FCU1..3 Fan coil unit with
When space heating/cooling is requested by the room thermostat thermostat (optional)
(T), the pump will start operating and the indoor unit (2) will switch to 5 Shut-off valve
"heating mode"/"cooling mode". The outdoor unit (1) will start 6 Collector (field supply) FHL1..3 Floor heating loop
operating to achieve the target leaving hot/cold water temperature. 7 Shut-off valve T Heating only room
In case of cooling mode, the 2-way valve (13) will close as to prevent thermostat (optional)
9 By-pass valve (field supply)
cold water running through the floor heating loops (FHL).
13 Motorised 2-way valve to T4..6 Individual room
shut off the floor heating thermostat for fan coil
NOTE Make sure to connect the thermostat wires to the loops during cooling heated/cooled room
correct terminals (see "Connection of the thermostat operation (field supply) (optional)
cable" on page 19) and to configure the DIP switch
toggle switches correctly (see "Room thermostat Pump operation
installation configuration" on page 21). With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
NOTE Wiring of the 2-way valve (13) is different for a NC
(normal closed) valve and a NO (normal open) valve! NOTE Details on pump configuration can be found under
Make sure to connect to the correct terminal numbers
"Pump operation configuration" on page 21.
as detailed on the wiring diagram.

The ON/OFF setting of the heating/cooling operation is done by the Space heating and cooling
room thermostat and cannot be done by the user interface on the
According to the season, the customer will select heating or cooling
indoor unit.
through the user interface on the indoor unit.
Domestic water heating
The outdoor unit (1) will operate in heating mode or cooling mode to
Domestic water heating is as described under "Application 2" on achieve the target leaving water temperature.
page 5. With the unit in heating mode, the 2-way valve (13) is open. Hot water
is provided to both the fan coil units and the floor heating loops.
Application 4 With the unit in cooling mode, the 2-way valve (13) is closed to
prevent cold water running through the floor heating loops (FHL).
Space cooling and heating application without the room thermostat
connected to the indoor unit, but with the heating only room When closing several loops in the system by remotely
thermostat (set heating only) controlling the floor heating and the controlled valves, it might be required to install a by-pass
heating/cooling thermostat (set heating/cooling) controlling the fan valve (9) to avoid the flow switch safety device from being
coil units. Heating is provided through floor heating loops and fan coil activated. See also "Application 2" on page 5.
units. Cooling is provided through the fan coil units only.
Wiring of the 2-way valve (13) is different for a NC (normal
6 9
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.

The ON/OFF setting of the heating/cooling operation is done by the


user interface on the indoor unit.
T4
T5
T6
FCU1
FCU2
T FCU3
1 2 3 4 5 13 14 6

M M

7 FHL1
FHL2
FHL3

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
6 4PW56301-1A
Field wiring configuration A
Application 5
L
Space heating with an auxiliary boiler (alternating operation) H Com

Space heating application by either the Daikin indoor unit or by an EKHB* Boiler
auxiliary boiler connected in the system. The decision whether either EKHB*/auto / Boiler X2M thermostat input
the EKHB* indoor unit or the boiler will operate can be achieved by 1 2 3 4 X Y
A
an auxiliary contact or an EKHB* indoor controlled contact.
K1A K2A
The auxiliary contact can e.g. be an outdoor temperature thermostat, K1A K2A
an electricity tariff contact, a manually operated contact, etc. See N
"Field wiring configuration A" on page 7.
Boiler Boiler thermostat input
The EKHB* indoor unit controlled contact (also called ’permission thermostat input
signal for the auxiliary boiler") is determined by the outdoor A Auxiliary contact (normal closed)
temperature (thermistor located at the outdoor unit). See "Field wiring H Heating demand room thermostat (optional)
configuration B" on page 7.
K1A Auxiliary relay for activation of EKHB* unit (field
Bivalent operation is only possible for space heating operation, not supply)
for the domestic water heating operation. Domestic hot water in such K2A Auxiliary relay for activation of boiler (field supply)
an application is always provided by the domestic hot water tank
which is connected to the Daikin indoor unit. Field wiring configuration B
The auxiliary boiler must be integrated in the piping work and in the EKHB* EKHB* EKRP1HB
field wiring according to the illustrations below. X2M X2M
1 2 3 4 1 2 3 4 KCR

CAUTION X1 X2
K1A K1A
■ Be sure that the boiler and the integration of the boiler
K1A
in the system is in accordance with relevant European
H C Com C Com H X Y
and national regulations.
EKRTR* EKRTW* Boiler
■ Daikin can not be put responsible for incorrect or thermostat input

unsafe situations in the boiler system. Boiler Boiler thermostat input


thermostat input
C Cooling demand room thermostat (optional)
H Heating demand room thermostat (optional)
1 2 3 4 5 8 18 17 6 Com Common room thermostat (optional)
K1A Auxiliary relay for activation of bolier unit
M (field supply)
KCR Permission signal for the auxiliary boiler

Operation
■ Configuration A
When the room thermostat requests heating, either the EKHB*
unit or the boiler starts operating, depending on the position of
the auxiliary contact (A).
7 16 15 17 ■ Configuration B
When the room thermostat requests heating, either the EKHB*
unit or the boiler starts operating, depending on the outdoor
temperature (status of "permission signal for the auxiliary
10 11 boiler").
When the permission is given towards the boiler, the space
FHL1 heating operation by the EKHB* unit will be automatically
FHL2 switched off.
FHL3
12 For more details see field setting [C-02~C-04].

1 Outdoor unit 11 Heat exchanger coil


2 Indoor unit 12 Domestic hot water tank
(optional)
3 Heat exchanger
4 Pump 15 Boiler (field supply)
5 Shut-off valve 16 Aquastat valve
(field supply)
6 Collector (field supply)
7 Shut-off valve 17 Shut-off valve
(field supply)
8 Motorised 3-way valve
(delivered with the 18 Non-return valve
domestic hot water (field supply)
tank)
FHL1...3 Floor heating loop
10 Booster heater (field supply)

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 7
NOTE ■ Configuration A Application 6
Make sure that auxiliary contact (A) has sufficient
Space heating with room thermostat application through floor heating
differential or time delay so as to avoid frequent
loops and fan coil units. The floor heating loops and fan coil units
changeover between the EKHB* unit and the
require different operating water temperatures.
boiler. If the auxiliary contact (A) is an outdoor
temperature thermostat, make sure to install the The floor heating loops require a lower water temperature in heating
thermostat in the shade, so that it is not mode compared to fan coil units. To achive these two set points, a
influenced or turned ON/OFF by the sun. mixing station is used to adapt the water temperature according to
Configuration B requirements of the floor heating loops. The fan coil units are directly
Make sure that the bivalent hysteresis [C-04] has connected to the indoor unit water circuit and the floor heating loops
sufficient differential to avoid frequent changeover after the mixing station. The control of this mixing station is not done
between the EKHB* unit and the boiler. As the by the indoor unit.
outdoor temperature is measured via the outdoor The operation and configuration of the field water circuit is the
unit, air thermistor make sure to install the responsibility of the installer.
outdoor unit in the shade, so that it is not
influenced by the sun. Daikin only offers a dual set point control function. By this function
two set points can be generated. Depending on the required water
Frequent switching may cause corrosion of the
temperature (floor heating loops and/or fan coil units are required)
boiler in an early stage. Contact the manufacturer
first set point or second set point can be activated.
of the boiler.
■ During heating operation of the EKHB* unit, the B
7
unit will operate so as to achieve the target
leaving water temperature as set on the user
interface. When weather dependent operation is
active, the water temperature is determined T1
automatically depending on the outdoor
temperature. T2 FCU1
FCU2
During heating operation of the boiler, the boiler 1 2 3 4 5 FCU3
will operate so as to achieve the target leaving
A
water temperature as set on the boiler controller. 6
Never set the target leaving water temperature set
point on the boiler controller above 55°C.
■ Make sure to only have 1 expansion vessel in the
water circuit. An expansion vessel is already
premounted in the Daikin indoor unit.
FHL1
8 9 FHL2
NOTE Make sure to configure the DIP switch SS2-3 on the
FHL3
PCB of the EKHB* switchbox correctly. Refer to "Room
thermostat installation configuration" on page 21.
1 Outdoor unit 8 Shut-off valve
For configuration B: Make sure to configure the field
2 Indoor unit 9 Mixing station (field supply)
settings [C-02, C-03 and C-04] correctly. Refer to
"Bivalent operation" on page 28. 3 Heat exchanger T1 Room thermostat for zone
A (optional)
4 Pump
5 Shut-off valve T2 Room thermostat for zone
CAUTION B (optional)
6 Collector zone A
Make sure that return water to the EKHB* heat exchanger (field supply) FCU1..3 Fan coil unit (optional)
never exceeds 55°C. 7 Collector zone B FHL1...3 Floor heating loop
For this reason, never put the target leaving water (field supply) (field supply)
temperature set point on the boiler controller above 55°C
and install an aquastat(a) valve in the return water flow of The advantage of the dual set point control is that the heat
the EKHB* unit. pump will/can operate at the lowest required leaving water
temperature when only floor heating is required. Higher
Make sure that the non-return valves (field supply) are leaving water temperatures are only required in case fan
correctly installed in the system. coil units are operating.
Make sure that the room thermostat (th) is not frequently This results in a better performance of the heat pump.
turned ON/OFF.
Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 55°C and must operate to close the return
water flow to the unit when the measured temperature exceeds 55°C. When the
temperature drops to a lower level, the aquastat valve must operate to open the
return water flow to the EKHB* unit again.

Manual permission towards the EKHB* unit on the boiler.


In case only the EKHB* unit should operate in space
heating mode, disable the bivalent operation via setting
[C-02].
In case only the boiler should operate in space heating
mode, increase the bivalent ON temperature [C-03] to
25°C.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
8 4PW56301-1A
Pump operation and space heating OVERVIEW OF THE INDOOR UNIT
When the room thermostat for the floor heating loop (T1) and the fan
coil units (T2) are connected to the indoor unit, the pump (4) will
operate when there is a request for heating from T1 and/or T2. The Opening the indoor unit
outdoor unit will start operating to achieve the target leaving water
temperature. The target leaving water temperature depends on which ■ The front flap on the indoor unit cover gives access to the
room thermostat is requesting heating. manometer and user interface.
■ The indoor unit cover can be removed by removing the 2 bottom
Set point Field setting Thermo status
screws and unhitching the cover.
Zone A First UI ON OFF ON OFF
Zone B Second [7-03] OFF ON ON OFF
Resulting water temperature UI [7-03] [7-03] —
Result pump operation ON ON ON OFF

When the room temperature of both zones is above the thermostat


set point, the outdoor unit and pump will stop operating.

NOTE ■ Make sure to connect the thermostat wires to the


correct terminals (see "Overview of the indoor
unit" on page 9).
■ Make sure to configure the field settings [7-02],
[7-03] and [7-04] correctly. Refer to "Dual set point
control" on page 26.
■ Make sure to configure the DIP switch SS2-3 on
the PCB of the EKHBH switch box correctly. Refer
to "Room thermostat installation configuration" on
page 21.

NOTE ■ The request signals for space heating can be


implemented in two different ways (installer
choice).
- Thermo ON/OFF signal from room thermostat
- Status signal (active/not active) from the
mixing station
■ It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high
water temperatures towards floor heating loops,
etc.)
Make sure to fix the cover with the screws when installing
■ Daikin does not offer any type of mixing station. the cover (screws are delivered as accessory).
Dual set point control only provides the possibility
to use two set points.
Parts inside the unit can be hot.
■ When only zone A request heating, zone B will be
fed with water at a temperature equal to the first ■ To gain access to the switch box components – e.g. to connect
set point. the field wiring – the switch box service panel can be removed.
This can lead to unwanted heating of zone B. Thereto, loosen the front screws and unhitch the switch box
■ When only zone B request heating, the mixing service panel.
station will be fed with water at a temperature
equal to the second set point. WARNING
Depending on the control of the mixing station, ■ Switch off all power supply – i.e. outdoor unit power
the floor heating loop can still receive water at a supply and backup heater and domestic hot water
temperature equal to set point of the mixing tank power supply (if applicable) – before removing
station. the switch box service panel.
■ Do not touch the refrigerant pipes during and
Be aware that the actual water temperature through the immediately after operation as the refrigerant pipes
floor heating loops depends on the control and setting of may be hot or cold, depending on the condition of the
the mixing station. refrigerant flowing through the refrigerant piping,
compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the
refrigerant pipes. To avoid injury, give the pipes time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
■ Do not touch the internal parts (pump, backup heater,
etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal
parts. To avoid injury, give the internal parts time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 9
DANGER Main components
■ Do not touch water pipes during and immediately after
operation as the pipes may be hot. Your hand may 20
suffer burns. To avoid injury, give the piping time to
return to normal temperature or be sure to wear 1
proper gloves.
19
■ When service panels are removed, live parts can be
18
easily touched by accident.
Never leave the unit unattended during installation or
servicing when the service panel is removed.
2

17 4

5
6

3
1
3

3
16
7
15
3 14

21

13
2
10 8
9
1 13
10
12 11
1. Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
2. Emergency backup heater
The backup heater consists of an electrical heating element in
the backup heater vessel that will provide heating capacity to the
water circuit in case of malfunction of the outdoor unit.
3. Temperature sensors
Four temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
4. Switch box
The switch box contains the main electronic and electrical parts
of the indoor unit.
5. Heat exchanger
6. Expansion vessel (10 l)
7. User interface
The user interface allows the installer and user to set up, use
and maintain the unit.
8. Refrigerant liquid connection
9. Refrigerant gas connection
10. Shut-off valves (accessory)
The shut-off valves on the water inlet connection and water
outlet connection allow isolation of the indoor unit water circuit
side from the residential water circuit side. This facilitates
draining and filter replacement of the indoor unit.
11. Water inlet connection
12. Water outlet connection
13. Drain and fill valves

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
10 4PW56301-1A
14. Water filter
Switch box main components
The water filter removes dirt from the water to prevent damage
to the pump or blockage of the evaporator. The water filter must
be cleaned on a regular base. See "Maintenance and service"
on page 32.
15. Manometer 14 TR1
1
The manometer allows readout of the water pressure in the
water circuit. K1M K5M

16. Flow switch


The flow switch checks the flow in the water circuit and protects
the heat exchanger against freezing and the pump against X9A
12
damage. 2
17. Pump 3
The pump circulates the water in the water circuit.
K3M 1
18. Backup heater thermal protector X13A A1P
11
The backup heater is equipped with a thermal protector. The
thermal protector is activated when the temperature becomes SS2 4
10
too high. 5
19. Backup heater thermal fuse
F2B F3B F1B
The backup heater is equipped with a thermal fuse. The thermal 5
fuse is blown when the temperature becomes too high (higher FU1
9
than the backup heater thermal protector temperature).
20. Pressure relief valve
FU2
The pressure relief valve prevents excessive water pressure in 13
the water circuit by opening at 3 bar and discharging some
15 A4P
water.
21. Pressure relief valve hose
The actual outlet of the pressure relief valve. Make sure to
provide a proper drain. 6 X2M X4M
8

6
8

X1M X3M

1. Backup heater contactors K1M and K5M.


2. Main PCB
The main PCB (Printed Circuit Board) controls the functioning of
the unit.
3. Booster heater contactor K3M (only for installations with
domestic hot water tank)
4. Booster heater circuit breaker F2B (only for installations with
domestic hot water tank)
The circuit breaker protects the booster heater in the domestic
hot water tank against overload or short circuit.
5. Backup heater circuit breaker F1B, F3B
The circuit breaker protects the backup heater electrical circuit
against overload or short circuit.
6. Terminal blocks
The terminal blocks allow easy connection of field wiring.
7. Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable
ties to the switch box to ensure strain relief.
8. Terminal blocks X3M, X4M (only for installations with domestic
hot water tank)
9. PCB fuse FU1
10. DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure
certain installation parameters. See "DIP switch settings
overview" on page 20.
11. X13A socket
The X13A socket receives the K3M connector (only for
installations with domestic hot water tank).

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 11
12. X9A socket INSTALLATION OF THE INDOOR UNIT
The X9A socket receives the thermistor connector (only for
installations with domestic hot water tank).
13. Fuse FU2 (in line fuse) Selecting an installation location
14. Transformer TR1 The unit is to be wall mounted in an indoor location that meets the
15. A4P following requirements:
Digital I/O PCB (only for installations with solar kit or digital I/O ■ The installation location is frost-free.
PCB kit).
■ The space around the unit is adequate for servicing. (See
NOTE The electrical wiring diagram can be found on the figure 2).
inside of the switch box cover. ■ The space around the unit allows for sufficient air circulation.
■ There is a provision for condensate drain (only for EKHBX
models with drain pan kit EKHBDP) and pressure relief valve
Functional diagram blow-off.
■ The installation surface is a flat and vertical non-combustible
2 3 4 5 67 8 wall, capable of supporting the operation weight of the unit (see
"Technical specifications" on page 37).
■ There is no danger of fire due to leakage of inflammable gas.
■ All piping lengths and distances have been taken into
consideration.
Requirement Value
Maximum allowable refrigerant piping length between
R1T R2T 9 30 m
outdoor unit and indoor unit
t> t>
Minimum required refrigerant piping length between
3m
outdoor unit and indoor unit
Maximum allowable height difference between
20 m
outdoor unit and indoor unit
10 Maximum allowable distance between the 3-way
valve and the indoor unit (only for installations with 3m
domestic hot water tank).
Maximum allowable distance between the domestic
H2O hot water tank and the indoor unit (only for
R4T
installations with domestic hot water tank). The 10 m
t> thermistor cable supplied with the domestic hot water
tank is 12 m in length.

■ During normal operation the hydrobox unit will produce sound


which could be observed as noise. The sound origin can be
R3T
11 water pump operation and/or contactor activation. Therefore it is
t>
advisable to install the hydrobox unit on a firm wall and not in nor
close to a sound sensitive environment (e.g. bedroom).
■ Do not install the unit in places with high humidity (e.g.
bathroom).
1 13 12
■ Select piping diameter in relation to required water flow and
available ESP of pump.
1 Outdoor unit 10 Shut-off valve water outlet
2 Indoor unit
with drain valve (field ■ The equipment is not intended for use in a potentially explosive
installation) atmosphere.
3 Expansion vessel 11 Shut-off valve water inlet with ■ Do not install the unit in places often used as work place.
drain valve (field installation)
4 Manometer In case of construction works (e.g. grinding works) where a lot of
5 Air purge valve 12 Filter dust is created, the unit must be covered.
6 Pressure relief valve 13 Heat exchanger ■ Take care that in the event of a water leak, water can not cause
7 Backup heater R1T any damage to the installation space and surroundings.
R2T ■ Do not place any objects or equipment on top of the unit.
8 Pump Temperature sensors
R3T
9 Flow switch R4T ■ Be sure that sufficient precautions are taken, in accordance with
relevant local and national regulations, in case of refrigerant
leakage.

CAUTION
If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water tank
installation manual.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
12 4PW56301-1A
Dimensions and service space Mounting the indoor unit

Unit of measurement: mm
CAUTION
Dimensions of the unit, see figure 3
The weight of the indoor unit is approximately 46 kg. Two
1 Flexible drain hose 5 Refrigerant gas persons are required to mount the unit.
connection
2 Water outlet connection
1 Put the installation pattern (see packing) on the wall and mark
3 Water inlet connection FBSP Female British Standard the fixation positions (2 on top (● T) and 2 at the bottom (● B)).
Pipe
4 Refrigerant liquid Make sure that the marks (2 by 2) are completely level and the
connection
MBSP Male British Standard dimensions of the marks are corresponding according to
Pipe figure 4.
When the unit is not installed level, air might get trapped in the
Required service space, see figure 2 water circuit resulting in malfunctioning of the unit.
Pay special attention to this when installing an EKHBX model to
prevent overflow of the drain pan.
Inspecting, handling and unpacking the unit
2 Drill 4 holes and install 4 plugs (suitable for M10).
■ The indoor unit is packed in a cardboard box, fixed by straps on
a wooden pallet. 3 Put the screws in top plugs and hang the indoor unit on the top
screws.
■ At delivery, the unit must be checked and any damage must be
reported immediately to the carrier claims agent. 4 Put the screws in bottom plugs and fix the screws firmly.
■ Check if all indoor unit accessories (see "Accessories" on
page 3) are enclosed.
■ Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during 1 2 3
transport.
■ The indoor unit weighs approximately 46 kg and should be lifted
by two persons using the two lifting bars provided.

CAUTION
Do not grasp the switch box or piping to lift the unit! Two
lifting bars are provided to lift the unit.

1 4

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 13
Installation of the EKHBDP drain pan kit (only for Water pipework
EKHBX models)
Checking the water circuit
For heating/cooling models, it is necessary to install the drain pan kit
(see "Accessories" on page 3). The units are equipped with a water inlet and water outlet for
connection to a water circuit. This circuit must be provided by a
During cooling operation, water vapour (humidity) in the air might licensed technician and must comply with all relevant European and
condense to liquid and collect on the cold refrigerant and water pipes. national regulations.
This water is collected in the drain pan, which must be connected to a
drain. NOTE The unit is only to be used in a closed water system.
For installation instructions, refer to the instruction sheet delivered Application in an open water circuit can lead to
with the drain pan kit. excessive corrosion of the water piping.

CAUTION
NOTE Before continuing the installation of the unit, check the
Make sure to position the pressure relief valve hose end in following points:
the drain pan. Failure to do so might lead to water coming
into contact with electrical parts, resulting in electrical ■ The maximum water pressure = 3 bar + static
shocks or short-circuit of the electrical system. pressure of pump.
■ The maximum water temperature is 65°C (safety
device setting).
Refrigerant pipework
■ Two shut-off valves are delivered with the unit. To
facilitate service and maintenance, install one at
For all guidelines, instructions and specifications regarding
the water inlet and one at the water outlet of the
refrigerant pipework between the indoor unit and the outdoor unit,
indoor unit. Mind position of the shut-off valves.
please refer to the outdoor unit installation manual.
Orientation of the integrated drain and fill valves is
The location of the gas pipe and liquid pipe on the indoor unit is important for servicing. See figure 3.
shown under "Main components" on page 10. ■ Drain taps must be provided at all low points of
Refrigerant piping the system to permit complete drainage of the
specifications Indoor unit Outdoor unit circuit during maintenance.
Gas pipe connection 15.9 mm (5/8 inch) 15.9 mm (5/8 inch) Two drain valves integrated in the shut-off valves
are provided to drain the water from the indoor
Liquid pipe connection 6.4 mm (1/4 inch) 6.4 mm (1/4 inch)
unit water system.
■ Make sure to provide a proper drain for the
When connecting the refrigerant pipes, always use two
pressure relief valve to avoid any water coming
wrenches/spanners for tightening or loosening nuts!
into contact with electrical parts.
Failure to do so can result in damaged piping connections
and leaks. ■ Air vents must be provided at all high points of the
system. The vents should be located at points
which are easily accessible for servicing. An
automatic air purge is provided inside the indoor
unit. Check that this air purge valve is not tightened
too much so that automatic release of air in the wa-
ter circuit remains possible.
■ Take care that the components installed in the
field piping can withstand the water pressure and
water temperature.
■ Always use materials which are compatible with
water used in the system and with the materials
used on the indoor unit.
■ Select piping diameter in relation to required
water flow and available ESP of the pump.
■ The minimum required water flow for the indoor
unit operation is 12 l/min. When the water flow is
lower than this minimum value, flow error 7H will
be displayed and the operation of the indoor unit
will be stopped.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
14 4PW56301-1A
Checking the water volume and expansion vessel pre-
pressure NOTE When circulation in each space heating loop is
controlled by remotely controlled valves, it is important
The unit is equipped with an expansion vessel of 10 litre which has a that this minimum water volume is kept even if all the
default pre-pressure of 1 bar. valves are closed.
To assure proper operation of the unit, the pre-pressure of the Example
expansion vessel might need to be adjusted and the minimum and
maximum water volume must be checked.
1 A minimum water volume is required to prevent that the water
temperature drops too much during defrost (low ambient 1 2 3 4 5 6 8
temperature). T1 T2 T3
If the water volume is too low, two problems can occur:
1 The water temperature drops too much during defrost and
defrost stops to protect the plate heat exchanger against M1 M2 M3

freezing.
2 The compressor does not start up after the defrost cycle
because the water temperature is too low.
In both cases the backup heater will operate instead of the 7 FHL1
FHL2
compressor to increase the water temperature.
FHL3
When the water temperature is high enough, the backup heater
stops and the compressor restarts. 1 Outdoor unit 8 By-pass valve (field
supply)
2 Indoor unit
If the heating load is higher than the backup heater
capacity, the water temperature can not increase. In 3 Heat exchanger FHL1..3 Floor heating loop
(field supply)
this case refer to "Re-start at low outdoor ambient 4 Pump
temperatures" on page 22 5 Shut-off valve T1..3 Individual room
thermostat
6 Collector (field (optional)
Repeated forced defrost stops can in some cases supply)
cause severe ice build-up on the outdoor unit. This will M1..3 Individual
7 Shut-off valve motorised valve to
lead to reduced unit performance. control loop FHL1
(field supply)
The minimum required water volume in the system is 20 l.
However, to minimize emergency backup heater operation it is
highly recommended to have a water volume of 40 l. 2 Using the table below, determine if the expansion vessel pre-
pressure requires adjustment.
In most applications this minimum water volume will have a
3 Using the table and instructions below, determine if the total
satisfying result.
water volume in the installation is below the maximum allowed
In critical processes or in rooms with a high heat load water volume.
though, extra water volume might be required.
Installation Water volume
height
difference(a) ≤280 l >280 l
Actions required:
• pre-pressure must be
decreased, calculate according
to "Calculating the pre-
No pre-pressure adjustment pressure of the expansion
≤7 m required. vessel"
• check if the water volume is
lower than maximum allowed
water volume (use graph
below)
Actions required:
• pre-pressure must be
increased, calculate according
to "Calculating the pre-
pressure of the expansion Expansion vessel of the unit
>7 m
vessel" too small for the installation.
• check if the water volume is
lower than maximum allowed
water volume (use graph
below)
(a) Installation height difference: height difference (m) between the highest point of
the water circuit and the indoor unit. If the indoor unit is located at the highest
point of the installation, the installation height is considered 0 m.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 15
Calculating the pre-pressure of the expansion vessel Connecting the water circuit
The pre-pressure (Pg) to be set depends on the maximum Water connections must be made in accordance with local
installation height difference (H) and is calculated as below: regulations and the outlook diagram delivered with the unit,
respecting the water in- and outlet.
Pg=(H/10+0.3) bar
Checking the maximum allowed water volume NOTE Be careful not to deform the unit piping by using
excessive force when connecting the piping.
To determine the maximum allowed water volume in the entire circuit,
Deformation of the piping can cause the unit to
proceed as follows:
malfunction.
1 Determine for the calculated pre-pressure (Pg) the
corresponding maximum water volume using the graph below. If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
2 Check that the total water volume in the entire water circuit is the water circuit:
lower than this value.
■ Use clean pipes only.
If this is not the case, the expansion vessel inside the indoor unit is
■ Hold the pipe end downwards when removing burrs.
too small for the installation.
■ Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
2.5
■ Use a good thread sealant for the sealing of the connections.
The sealing must be able to withstand the pressures and
2 temperatures of the system.
pre-pressure [bar]

■ When using non-brass metallic piping, make sure to insulate


1.5 both materials from each other to prevent galvanic corrosion.
■ Because brass is a soft material, use appropriate tooling for
connecting the water circuit. Inappropriate tooling will cause
1
damage to the pipes.

0.5 NOTE ■ The unit is only to be used in a closed water


0.3 system. Application in an open water circuit can
0 10 50 100 150 200 250 300 350 400 450 lead to excessive corrosion of the water piping.
maximum water volume [l]
■ Never use Zn-coated parts in the water circuit.
= pre-pressure Excessive corrosion of these parts may occur as
= maximum water volume copper piping is used in the unit's internal water
circuit.
Example 1
■ When using a 3-way valve in the water circuit.
The indoor unit is installed 5 m below the highest point in the water It is very important to guarantee full separation
circuit. The total water volume in the water circuit is 100 l. between domestic hot water and floor heating
In this example, no action or adjustment is required. water circuit.
■ When using a 3-way valve or a 2-way valve in the
Example 2
water circuit, the maximum change over time of
The indoor unit is installed at the highest point in the water circuit. the valve shall be less than 60 seconds.
The total water volume in the water circuit is 350 l.
Result: Charging water
■ Since 350 l is higher than 280 l, the pre-pressure must be
decreased (see table above). 1 Connect the water supply to a drain and fill valve (see "Main
components" on page 10).
■ The required pre-pressure is:
Pg = (H/10 + 0.3) bar = (0/10 + 0.3) bar = 0.3 bar 2 Make sure the automatic air purge valve is open (at least 2
■ The corresponding maximum water volume can be read from turns).
the graph: approximately 410 l.
3 Fill with water until the manometer indicates a pressure of
■ Since the total water volume (350 l) is below the maximum water approximately 2.0 bar. Remove air in the circuit as much as
volume (410 l), the expansion vessel suffices for the installation. possible using the air purge valves. Air present in the water
circuit might cause malfunctioning of the backup heater.
Setting the pre-pressure of the expansion vessel
4 Check that the backup heater vessel is filled with water by
When it is required to change the default pre-pressure of the opening the pressure relief valve. Water must flow out of the
expansion vessel (1 bar), keep in mind the following guidelines: valve.
■ Use only dry nitrogen to set the expansion vessel pre-pressure.
■ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure
should only be adjusted by a licensed installer.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
16 4PW56301-1A
Overview
NOTE ■ During filling, it might not be possible to remove all
air in the system. Remaining air will be removed The illustration below gives an overview of the required field wiring
through the automatic air purge valves during first between several parts of the installation. Refer also to "Typical
operating hours of the system. Additional filling application examples" on page 4.
with water afterwards might be required. 5
■ The water pressure indicated on the manometer
will vary depending on the water temperature T F
(higher pressure at higher water temperature). I K
However, at all times water pressure should
B D E 11
remain above 0.3 bar to avoid air entering the 6
circuit. G
M
■ The unit might dispose some excessive water 2 7
through the pressure relief valve.
M H
■ Water quality must be according to EU directive
98/83 EC.
C
8 I
3 J
Piping insulation 1 4

The complete water circuit, inclusive all piping, must be insulated to


9
prevent condensation during cooling operation and reduction of the
A 10
cooling and heating capacity.
If the temperature is higher than 30°C and the humidity is higher than A Single power supply for G 3-way valve for domestic
RH 80%, then the thickness of the sealing materials should be at outdoor unit, backup hot water tank (optional)
least 20 mm in order to avoid condensation on the surface of the heater and booster
H 2-way valve for cooling
sealing. heater
mode (field supply)
B Outdoor unit
C Bottom plate heater I Domestic hot water tank
Field wiring EKBPHT(a) (optional)

D Backup heater J Booster heater


(optional)
WARNING E Indoor unit
■ A main switch or other means for disconnection, F Room thermostat K User interface (digital
having a contact separation in all poles, must be (optional) controller)
incorporated in the fixed wiring in accordance with (a) Bottom plate heater is only applicable in combination with ERLQ or in case of
optional EKBPHT kit.
relevant local and national legislation.
■ Switch off the power supply before making any
Required
connections.
number of Maximum
■ Use only copper wires. Item Description conductors running current
(a)
■ Never squeeze bundled cables and make sure that it 1 Power supply cable for outdoor 2+GND
unit
does not come in contact with the piping and sharp
(b)
edges. 2 Indoor unit power supply and 3+GND
communication cable
Make sure no external pressure is applied to the (c)
3 Power cable for bottom plate 2
terminal connections. heater
■ All field wiring and components must be installed by a 4 Power supply cable for backup 2+GND or (d)
licensed electrician and must comply with relevant heater 3+GND
European and national regulations. 5 Room thermostat cable 3 or 4 100 mA(e)
■ The field wiring must be carried out in accordance 6 3-way valve control cable 2+GND 100 mA(e)
with the wiring diagram supplied with the unit and the
7 2-way valve control cable 2+GND 100 mA(e)
instructions given below.
(b)
8 Booster heater power supply 4+GND
■ Be sure to use a dedicated power supply. Never use a and thermal protection cable
power supply shared by another appliance. (f)
9 Thermistor cable 2
■ Be sure to establish an earth. Do not earth the unit to
10 Booster heater power supply 2+GND 13 A
a utility pipe, surge absorber, or telephone earth. cable
Incomplete earth may cause electrical shock.
11 User interface cable 2 (g)
■ Be sure to install an earth leakage circuit breaker in
(a) Refer to nameplate on outdoor unit.
accordance with relevant local and national (b) Cable section 2.5 mm2
regulations. Failure to do so may cause electrical (c) Minimum cable section 1.5 mm2
shock or fire. (d) See table under "Connection of the backup heater power supply" on page 18.
(e) Minimum cable section 0.75 mm2
■ Be sure to install the required fuses. (f) The thermistor and connection wire (12 m) are delivered with the domestic hot
water tank.
(g) Cable section 0.75 mm2 till 1.25 mm2, maximum length: 500 m.

CAUTION
Select all cables and wire sizes in accordance with
relevant local and national regulations.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 17
Field wiring guidelines
WARNING
■ Most field wiring on the indoor unit side is to be made on the
After finishing the electric work, confirm that each electric terminal block inside the switch box. To gain access to the
part and terminal inside the electric parts box is connected terminal block, remove the indoor unit cover and switch box
securely. service panel, see "Opening the indoor unit" on page 9.

Internal wiring - Parts table WARNING


Refer to the internal wiring diagram supplied with the unit (on the Switch off all power supply – i.e. outdoor unit power
inside of the indoor unit switch box cover). The abbreviations used supply and backup heater and domestic hot water
are listed below. tank power supply (if applicable) – before removing
A1P ................. Main PCB the switch box service panel.
A2P ................. Digital controller PCB (user interface)
■ Cable tie mountings are provided at the bottom of the switch
A3P ......... * ..... Thermostat (EKRTW/R) (PC= internal Power Cicuit) box. Fix all cables using cable ties (field supply).
(optional)
■ A dedicated power circuit is required for the backup heater.
A3P ......... * ..... Solar pump station PCB (EKSR3PA) (optional)
■ Installations equipped with a domestic hot water tank (optional),
A4P ......... * ..... Digital I/O PCB (EKRP1HB) (optional)
require a dedicated power circuit for the booster heater.
A4P ......... * ..... Receiver PCB (EKRTR) (optional)
Please refer to the domestic hot water tank installation manual.
BSK ......... * ..... Solar pump station relay (EKSR3PA) (optional)
E1H ................. Backup heater element 1 Connection of the indoor unit power supply and
E2H ................. Backup heater element 2 communication cable
E3H ................. Backup heater element 3 Power circuit and cable requirements
E4H ......... # ..... Booster heater (3 kW)
Power supply for the indoor unit is to be provided through the outdoor
F1B,F3B .......... Fuse backup heater unit. Data communication with the outdoor unit is provided through
F2B.......... # ..... Fuse booster heater the same cable.
F1T.................. Thermal fuse backup heater (250 V, 94°C)
For all guidelines and specifications regarding field wiring between
FU1 ................. Fuse 3.15 A T 250 V for PCB the indoor unit and the outdoor unit, please refer to the outdoor unit
FU2 ................. Fuse 5 A T 250 V installation manual.
FuR,FuS.......... Fuse 5 A 250 V for digital I/O PCB Procedure
K1M................. Contactor backup heater step 1
1 Using the appropriate cable, connect the power circuit to the
K2M................. Contactor backup heater step 2 appropriate terminals as shown on the wiring diagram and the
K3M......... # ..... Contactor booster heater illustration below.
K4M................. Pump relay
2 Connect the earth conductor (yellow/green) to the earthing
K5M,K6M ........ Contactor for backup heater all pole disconnection screw on the switch box mounting plate.
M1P................. Pump
3 Fix the cable with cable ties to the cable tie mountings to ensure
M2S....... ## ..... 2-way valve for cooling mode (field supply)
strain relief.
M3S......... # ..... 3-way valve: floor heating/domestic hot water
PHC1............... Optocoupler input circuit 4 When routing out cables, make sure that these do not obstruct
mounting of the indoor unit cover, see figure 3.
Q1DI................ Earth leakage circuit breaker (field supply)
Q1L ................. Thermal protector backup heater Note: only relevant field wiring is shown.
Q2L,Q3L.. # ..... Thermal protector booster heater
X1M X3M
R1H ......... * ..... Humidity sensor (EKRTR) (optional)
1 2 3

R1T ......... * ..... Ambient sensor (EKRTW) (optional)


R1T ................. Outlet water heat exchanger thermistor
R2T ......... * ..... External sensor (floor or ambient) (EKRTETS)
(optional)
R2T ................. Outlet water backup heater thermistor
R3T ................. Refrigerant liquid side thermistor
R4T ................. Inlet water thermistor
1 2 3
R5T ......... # ..... Domestic hot water thermistor
1 2 3
S1L.................. Flow switch
S2S ................. Benefit kWh rate power supply contact Connection of the backup heater power supply
S3S ................. Dual set point 2 contact Power circuit and cable requirements
S4S ................. Dual set point 1 contact
SS1 ................. DIP switch Use a dedicated power circuit for the backup heater and
booster heater. Never use a power circuit shared by
TR1 ................. Transformer 24 V for PCB
another appliance.
V1S ................. Spark suppression 1
V2S ................. Spark suppression 2 This power circuit must be protected with the required safety devices
according to local and national regulations.
X1M~X9M ....... Terminal blocks
Select the power cable in accordance with relevant local and national
* Optional regulations. For the maximum running current of the backup heater,
# Applications with domestic hot water tank only refer to the table below.
## Heating/cooling applications only Backup Backup heater Maximum
heater nominal running
Indoor unit model capacity voltage current Zmax (Ω)
EKHB*E008BA3V3 3 kW 1x 230 V 13 A —

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
18 4PW56301-1A
Procedure Wiring the 2-way valve
1 Using the appropriate cable, connect the power circuit to the 1 Using the appropriate cable, connect the valve control cable to
main circuit breaker as shown on the wiring diagram and the the X2M terminal as shown on the wiring diagram.
illustration below.
2 Connect the earth conductor (yellow/green) to the earthing NOTE Wiring is different for a NC (normal closed) valve
screw on the X1M terminal. and a NO (normal open) valve. Make sure to
connect to the correct terminal numbers as detailed
3 Fix the cable with cable ties to the cable tie mountings to ensure
on the wiring diagram and illustrations below.
strain relief.
Note: only relevant field wiring is shown. Normal closed (NC) 2-way valve Normal open (NO) 2-way valve

X2M 5 6 7 X2M 5 6 7
1x 230 V
X1M X3M
L1 N M M
NC NO

2 Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Wiring the 3-way valve
1 Using the appropriate cable, connect the valve control cable to
the appropriate terminals as shown on the wiring diagram.
L1 N

Connection of the thermostat cable NOTE Two types of 3-way valves can be connected.
Wiring is different for each type:
Connection of the thermostat cable depends on the application.
■ "Spring return 2-wire" type 3-way valve
See also "Typical application examples" on page 4 and "Room The 3-way valve should be fitted as such that
thermostat installation configuration" on page 21 for more information when the 3-way valve is idle (not activated),
and configuration options on pump operation in combination with a the space heating circuit is selected.
room thermostat.
■ "SPST 3-wire" type 3-way valve
Thermostat requirements The 3-way valve should be fitted as such that
■ Power supply: 230 V AC or battery operated when terminal ports 9 and 10 are electrified,
■ Contact voltage: 230 V. the domestic hot water circuit is selected.

Procedure "Spring return 2-wire" valve "SPST 3-wire" valve


1 Connect the thermostat cable to the appropriate terminals as X2M 8 9 10 X2M 8 9 10
shown on the wiring diagram and installation manual of the room
thermostat kit.
2 Fix the cable with cable ties to the cable tie mountings to ensure M M
strain relief.
3 Set DIP switch SS2-3 on the PCB to ON. See "Room thermostat 2 Fix the cable(s) with cable ties to the cable tie mountings to
installation configuration" on page 21 for more information. ensure strain relief.
Connection of the first set point and second set point contacts Wiring the bottom plate heater
The connection of the set point contact is only relevant in case dual
set point contact is enabled. 1 Using the appropriate cable, connect the power supply cable to
See also "Typical application examples" on page 4 and "Dual set the appropriate terminals as shown on the wiring diagram below.
point control" on page 26.
Contact requirements X2M 15a 15

The contact shall be a voltage free contact that ensure 230 V


1 2
(100 mA).
X1Y
Procedure
bottom plate heater
1 Connect the contact of first set point and second set point to the
appropriate terminals as shown in the figure below 2 Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
X2M SP1 First set point contact 3 When routing out cables, make sure that these do not obstruct
1 2 3 4 SP2 Second set point contact mounting of the indoor unit cover.
SP2 SP1 4 Select the appropriate field setting values for the bottom plate
heater. See "[F-02]", "[F-03]", and "[F-04]" on page 29.
2 Fix the cables with cable ties to the cable tie mountings to
ensure strain relief.
3 Depending on the required pump operation set DIP switch
SS2-3 and field setting [F-00]. See "Pump operation
configuration" on page 21 and field setting [F-00] in "[F] Option
setup" on page 29.

Connection of the valve control cables


Valve requirements
■ Power supply: 230 V AC
■ Maximum running current: 100 mA

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 19
Relocation of the digital controller NOTE ■ When wiring, run the wiring away from the
power supply wiring in order to avoid
The digital controller is from factory located on the indoor unit. (See receiving electric noise (external noise).
"Main components" on page 10 for actual position). If required, the
digital controller can be repositioned. ■ Peel the shield for the part
that has to pass through the
Be aware that only 1 digital controller can be connected to the indoor inside of the digital controller
unit. case ( l ).

Wiring specifications 4 Reattach the upper part of the digital controller.


Wire specification Value
CAUTION
Type 2 wire
Section 0.75-1.25 mm 2 Be careful not to pinch the wiring when attaching.
Maximum length 500 m
First begin fitting from the clips at the
bottom.
NOTE The wiring for connection is not included.

Mounting 1
NOTE The digital controller has to be mounted indoors.
START-UP AND CONFIGURATION

1 Remove the front part of the digital controller. The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
Insert a slotted screwdriver into the slots (1)
user expertise.
in the rear part of the digital controller, and
remove the front part of the digital
It is important that all information in this chapter is read
controller.
1 sequentially by the installer and that the system is
2 Fasten the digital controller on a flat configured as applicable.
surface.
DIP switch settings overview

DIP switch SS2 is located on the switch box PCB (see "Switch box
NOTE Be careful not to distort the shape of the lower part of main components" on page 11) and allows configuration of domestic
the digital controller by over tightening the mounting hot water tank installation, room thermostat connection and pump
screws. operation.

3 Wire the unit. WARNING


Switch off the power supply before opening the switch box
6 service panel and making any changes to the DIP switch
16a

16a

settings.
16

16

1 1
OFF ON

1 2 3 4

DIP
switch
SS2 Description ON OFF
P2 P1 P2 P1

3 1 Not applicable for installer — (Default)


2 Domestic hot water tank Installed Not installed
installation (Default)
(see "Domestic hot water
tank installation
4 5 configuration" on page 22)
1 Unit 3 Room thermostat Room thermostat No room
2 Rear part of the digital controller connection connected thermostat
(see "Room thermostat connected
3 Front part of the digital controller installation configuration" (Default)
4 Wired from the rear on page 21)
5 Wired from the top 4 This setting(a) decides the Heating/cooling Priority to highest
6 Notch the part for the wiring to pass through with nippers, etc. operation mode of the priority demand side(b)
heat pump when there is a
simultaneous demand for
Connect the terminals on top of the front part of the digital
more space
controller and the terminals inside the unit (P1 to 16, P2 to 16a). heating/cooling and
domestic water heating.
(a) Only applicable in case DIP switch 2 = ON.
(b) Heating/cooling or domestic water heating mode can be restricted by schedule
timer and/or field settings (4, 5, 8).

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
20 4PW56301-1A
Room thermostat installation configuration Pump operation configuration

■ When no room thermostat is connected to

OFF ON OFF ON
NOTE
1 2 3 4 To set the pump speed, refer to "Setting the pump
the indoor unit, toggle switch SS2-3 should be
speed" on page 23.
set to OFF.
Without room thermostat: DIP switch SS2-3 = OFF
■ When the room thermostat is connected to 1 2 3 4
the indoor unit, toggle switch SS2-3 should be When no thermostat is connected to the indoor unit, pump operation
set to ON. will be determined by the leaving water temperature.
To force continuous pump operation when no room thermostat is
■ On the room thermostat, confirm the correct settings (6®02=yes, connected do the following:
6®05=9, 6®06=5) to prevent the pump from repeatedly turning on
- set toggle switch SS2-3 to ON,
and off (i.e. chattering), and thereby impacting the lifetime of
- short-circuit the terminal numbers 1-2-4 on the terminal block
the pump.
in the switch box.
With room thermostat DIP switch: SS2-3 = ON
■ When the room thermostat is connected to the indoor
unit, the heating and cooling schedule timers are When the thermostat is connected to the indoor unit, the pump will
never available. Other schedule timers are not operate continuously whenever there is heating or cooling demand
affected. For more information on the schedule timers, requested by the thermostat.
refer to the operation manual. Dual set point
■ When the room thermostat is connected to the indoor
When dual set point is enabled, the pump operation will be
unit, and the = button or y button is pressed, the
determined depending on the status of the DIP switch SS2-3 and set
centralised control indicator e will flash to indicate
point selection contacts. Refer to the pump operation configurations
that the room thermostat has priority and controls
when the thermostat is connected or not as described above.
on/off operation and change over operation.
The following table summarizes the required configuration and When dual set point is enabled, the "forced continuous
thermostat wiring at the terminal block (X2M: 1, 2, 3, 4) in the switch pump operation" is not possible. When SS2-3 is ON while
box. Pump operation is listed in the third column. The three last SP1 and SP2 are both closed, the pump operation will be
columns indicate whether the following functionality is available on the same operation as "with room thermostat" and the
the user interface (UI) or handled by the thermostat (T): second set point will be the applicable set point. Refer to
• space heating or cooling on/off (y) "Dual set point control" on page 26.
• heating/cooling changeover (=)
The following table summarizes the required configuration and wiring
• heating and cooling schedule timers (pr)
at the terminal block (X2M: 1, 2, 4) in the switch box. Pump operation
Pump is listed in the third column. The three last columns indicate whether
Thermostat Configuration operation y = pr the following functionality is available on the user interface (UI) or
No thermostat • SS2-3 = OFF determined by UI UI UI handled by the set point selection contacts SP1 and SP2:
• wiring: (non) leaving water • space heating or cooling on/off (y)
temperature(a) • heating/cooling changeover (=)
X2M
• heating and cooling schedule timers (pr)
1 2 3 4
Dual set point
• SS2-3 = ON on when space UI UI UI
• wiring: heating or Configuration Pump operation y = pr
cooling is on • [7-02]=1 determined by UI UI UI
X2M (y) • SS2-3 = OFF leaving water
1 2 3 4 • wiring: temperature(a)

X2M
Heating only • SS2-3 = ON on when T — — 1 2 3 4
thermostat • wiring: (see heating
installation SP2 SP1
request by
manual of the room
room • [7-02]=1 on when main or/and SP2/SP1 UI —
thermostat • SS2-3 = ON
thermostat kit) sub set point is
• wiring: requested
Thermostat with • SS2-3 = ON on when T T —
heating/cooling • wiring: (see heating X2M
switch installation request or
manual of the cooling request 1 2 3 4
room by room SP2 SP1
thermostat kit) thermostat
(a) The pump will stop when space heating/cooling is turned off or when the water
SP1 = First set point contact
reaches the desired water temperature as set on the user interface. With space SP2 = Second set point contact
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature. (a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 21
2 Fuses or protection devices
Domestic hot water tank installation configuration
Check that the fuses or the locally installed protection devices
are of the size and type specified in the chapter "Technical

OFF ON
When no domestic hot water tank is 1 2 3 4 specifications" on page 37. Make sure that neither a fuse nor a
installed, toggle switch SS2-2 should be set to protection device has been bypassed.
OFF (default).
3 Backup heater circuit breaker F1B/F3B

■ When a domestic hot water tank is installed, Do not forget to turn on the backup heater circuit breaker F2B in

OFF ON
1 2 3 4
toggle switch SS2-2 should be set to ON. the switchbox (F1B/F3B depends on the backup heater type).
Refer to the wiring diagram.

4 Booster heater circuit breaker F2B


When SS2-3 was set to ON without all necessary and Do not forget to turn on the booster heater circuit breaker F2B in
correct wiring connections between indoor unit and the switch box (applies only to units with optional domestic hot
switchbox of the domestic hot water tank, the error code AC water tank installed).
will be displayed on the user interface. 5 Earth wiring
Make sure that the earth wires have been connected properly
Initial start-up at low outdoor ambient temperatures and that the earth terminals are tightened.

During initial start-up and when water temperature is low, it is 6 Internal wiring
important that the water is heated gradually. Failure to do so may Visually check the switch box on loose connections or damaged
result in cracking of concrete floors due to rapid temperature change. electrical components.
Please contact the responsible cast concrete building contractor for
7 Fixation
further details.
Check that the unit is properly fixed, to avoid abnormal noises
To do so, the lowest leaving water set temperature can be decreased and vibrations when starting up the unit.
to a value between 15°C and 25°C by adjusting the field setting
[9-01] (heating set point lower limit). Refer to "Field settings" on 8 Damaged equipment
page 23. Check the inside of the unit on damaged components or
squeezed pipes.
If leaving water temperature is set between 15°C and
25°C, heating is performed by the backup heater only. 9 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
Re-start at low outdoor ambient temperatures refrigerant leak, call your local dealer.

10 Power supply voltage


When re-starting at low ambient temperature, it is important to
Check the power supply voltage on the local supply panel. The
ensure that the unit operates within its operation range as soon as
voltage must correspond to the voltage on the identification label
possible (water temperature ≥30°C) by reducing the load as much as
of the unit.
possible during start-up. This procedure is applicable whenever the
water temperature is out of the operation range (e.g. after long period 11 Air purge valve
of stand still, ...).
Make sure the air purge valve is open (at least 2 turns).
For example:
12 Pressure relief valve
You can do this by switching off the fans of the fan coil units until the Check if the backup heater is completely filled with water by
water temperature has increased to 30°C. operating the pressure relief valve. It should purge water instead
OR of air.

For floor heating applications: start up circuit by circuit using a NOTE Operating the system with the backup heater not
(automatic) by-pass valve guaranteeing that water returning to the completely filled with water will damage the backup
unit is more than 20°C. heater!

13 Shut-off valves
Pre-operation checks
Make sure that the shut-off valves are correctly installed and
fully open.
Checks before initial start-up
NOTE Operating the system with closed valves will damage
DANGER the pump!
Switch off all relevant power supply before making any
connections.
Powering up the indoor unit
After the installation of the unit, check the following before switching
on the circuit breaker: When power supply to the indoor unit is turned on, "88" is displayed
1 Field wiring on the user interface during its initialisation, which might take up to
30 seconds. During this process the user interface cannot be
Make sure that the field wiring between local supply panel and
operated.
indoor unit, outdoor unit and indoor unit, indoor unit and valves
(when applicable), indoor unit and room thermostat (when
applicable), and indoor unit and domestic hot water tank has
been carried out according to the instructions described in the
chapter "Field wiring" on page 17, according to the wiring
diagrams and according to European and national regulations.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
22 4PW56301-1A
2 Press the bgi button to select the appropriate field
Setting the pump speed
setting first code.
The pump speed can be selected on the pump (see "Main 3 Press the bgj button to select the appropriate field
components" on page 10). setting second code.
The default setting is high speed (III). If the water flow in the system 4 Press the pfi button and pfj button to change
is too high (e.g., noise of running water in the installation) the speed the set value of the select field setting.
can be set to medium speed (II) or low speed (I).
5 Save the new value by pressing the pr button.
The available external static pressure (ESP, expressed in kPa) in
function of the water flow (l/min) is shown in the graph below. 6 Repeat step 2 through 4 to change other field settings as
required.
70
7 When finished, press the z button to exit FIELD SET MODE.
60

50
NOTE Changes made to a specific field setting are only
stored when the pr button is pressed. Navigating to a
ESP [kPa]

40 new field setting code or pressing the z button will


III
discard the change made.
30
II
20 ■ Before shipping, the set values have been set as
I shown under "Field settings table" on page 30.
10
■ When exiting FIELD SET MODE, "88" may be
0
displayed on the user interface LCD while the unit
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 initialises itself.
[l/min]
■ Only relevant field settings are explained.

Detailed description
Field settings
[0] User permission level
The indoor unit shall be configured by the installer to match the
If required, certain user interface buttons can be made unavailable for
installation environment (outdoor climate, installed options, etc.) and
the user.
user demand. Thereto, a number of so called field settings are
available. These field settings are accessible and programmable Three permission levels are defined (see the table below). Switching
through the user interface on the indoor unit. between level 1 and level 2/3 is done by simultaneously pressing
Each field setting is assigned a 3-digit number or code, for example buttons pfi and pfj immediately followed by
[1-03], which is indicated on the user interface display. The first digit simultaneously pressing buttons s and ba, and keeping all 4
[1] indicates the 'first code' or field setting group. The second and buttons pressed for at least 5 seconds (in normal mode). Note that no
third digit [03] together indicate the 'second code'. indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
A list of all field settings and default values is given under "Field by the field setting [0-00].
settings table" on page 30. In this same list, we provided for 2
columns to register the date and value of altered field settings at Permission level
variance with the default value. Button 1 2 3
A detailed description of each field setting is given under "Detailed Quiet mode button s operable — —
description" on page 23. Weather dependent
set point button
ba operable — —
Procedure Schedule timer
enable/disable button
pr operable operable —
To change one or more field settings, proceed as follows.
Programming button < operable — —
Time adjust buttons pf
i
operable — —
pf
j
Inspection/test
operation button
z operable — —
3
1
2

1 Press the z button for a minimum of 5 seconds to enter FIELD


SET MODE.
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to
the right - (1).

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 23
[1] Weather dependent set point (heating operation only) [2] Disinfection function
The weather dependent set point field settings define the parameters Applies only to installations with a domestic hot water tank.
for the weather dependent operation of the unit. When weather
The disinfection function disinfects the domestic hot water tank by
dependent operation is active the water temperature is determined
periodically heating the domestic hot water to a specific temperature.
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During CAUTION
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C. See the The disinfection function field settings must be configured
operation manual for more details on weather dependent operation. by the installer according to local and national regulations.
■ [1-00] Low ambient temperature (Lo_A): low outdoor ■ [2-00] Operation interval: day(s) of the week at which the
temperature. domestic hot water should be heated.
■ [1-01] High ambient temperature (Hi_A): high outdoor ■ [2-01] Status: defines whether the disinfection function is
temperature. turned on (1) or off (0).
■ [1-02] Set point at low ambient temperature (Lo_Ti): the ■ [2-02] Start time: time of the day at which the domestic hot
target outgoing water temperature when the outdoor water should be heated.
temperature equals or drops below the low ambient ■ [2-03] Set point: high water temperature to be reached.
temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for ■ [2-04] Interval: time period defining how long the set point
colder outdoor temperatures (i.e. Lo_A) warmer water is temperature should be maintained.
required.
TDHW
■ [1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor [2-03] [2-04]
temperature equals or rises above the high ambient
temperature (Hi_A). TH
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water TU
suffices.

Tt

00.00 01.00 22.00 23.00 24.00 t


Lo_Ti
[2-02]
+ 05
TDHW Domestic hot water temperature
Hi_Ti 00 Shift value
TU User set point temperature (as set on the user interface)
– 05
TH High set point temperature [2-03]
t Time
Lo_A Hi_A TA
WARNING
Tt Target water temperature
Be aware that the domestic hot water temperature at the
TA Ambient (outdoor) temperature
hot water tap will be equal to the value selected in field
= Shift value setting [2-03] after a disinfection operation.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to local and national regulations.

Space cooling/heating always has priority over the


disinfection function.
The disinfection function is only possible when the unit is
not operating for space cooling/heating.
To allow the disinfection function, the schedule timers must
be used. Set the disinfection function settings so that it is
combined with the domestic hot water function that is
running during disabled space heating/cooling interval. It is
advised to run the disinfection function for minimum 1 hour.
Refer to the extra addendum of the operation manual for
an example pattern.
Refer to the operation manual for a detailed explanation
how to program the schedule timer.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
24 4PW56301-1A
[6] DT for heat pump domestic water heating mode
If using a room thermostat, the disinfection function is not
possible as long as the room thermostat demands cooling Before changing field settings for domestic water heating,
or heating. In this case, de-activate the room thermostat read attentively the warnings mentioned in the paragraph
demand by its schedule timer. Refer to the manual of the "Domestic hot water tank (option)" on page 2.
room thermostat for a detailed explanation on how to
de-activate space cooling/heating by schedule timer. Applies only to installations with a domestic hot water tank.
The 'DT (temperature difference) for heat pump domestic water
[3] Auto restart
heating mode' field settings determine the temperatures at which
When power returns after a power supply failure, the auto restart heating of the domestic hot water by the heat pump will be started
function reapplies the user interface settings at the time of the power (i.e., the heat pump ON temperature) and stopped (i.e., the heat
supply failure. pump OFF temperature).
When the domestic hot water temperature drops below the heat
NOTE It is therefore recommended to leave the auto restart pump ON temperature (THP ON), heating of the domestic hot water by
function enabled. the heat pump can be started. As soon as the domestic hot water
temperature reaches the heat pump OFF temperature ( THP OFF) or
Note that with the function disabled the schedule timer will not be the user set point temperature (TU), heating of the domestic hot water
activated when power returns to the unit after a power supply failure. by the heat pump will be stopped (by switching the 3-way valve).
Press the pr button to enable the schedule timer again. The heat pump OFF temperature, and the heat pump ON
■ [3-00] Status: defines whether the auto restart function is temperature, and its relation with field settings [6-00] and [6-01] are
turned ON (0) or OFF (1). explained in the illustration below.
■ [6-00] Start: temperature difference determining the heat
Before changing field settings for domestic water heating, pump ON temperature (THP ON). See illustration.
read attentively the warnings mentioned in the paragraph
"Introduction" on page 1. ■ [6-01] Stop: temperature difference determining the heat
pump OFF temperature (THP OFF). See illustration.
[4] Booster heater operation and space heating off temperature
TU > THP MAX TU < THP MAX
Space heating off temperature
TU = 70°C TU = 45°C
■ [4-02] Space heating off temperature: outdoor temperature T(°C) T(°C)
[6-01] = 2°C [6-01] = 2°C
above which space heating is turned off, to avoid [6-00] = 7°C [6-00] = 7°C
70 TU
overheating.
Booster heater operation
Applies only to installations with a domestic hot water tank.
50 THP MAX [6-01] 50 THP MAX
The operation of the booster heater can be enabled or limited 48 THP OFF
[6-00] 45 TU = THP OFF
depending on outdoor temperature (TA), domestic hot water [6-00]
41 THP ON
temperature (TDHW) or operation mode of the heat pump. 38 THP ON

■ [4-03] Booster heater operation: defines whether the optional


booster heater operation is enabled (1) or has certain TU User set point temperature (as set on the user interface)
limitations (0/2/3).
THP MAX Maximum heat pump temperature at sensor in domestic hot
Explanation of settings of [4-03] water tank (50°C)(depending on TA)(a)
Booster heater will/can only operate if domestic hot water mode
THP OFF Heat pump OFF temperature
is activated (w).
THP ON Heat pump ON temperature
■ [4-03]=0, then booster heater operation is only allowed
during "[2] Disinfection function" and "Powerful domestic (a) 45°C = THP MAX at TA>25°C.
50°C = THP MAX at 5°C≤TA≤25°C.
water heating" (see operation manual). 48°C = THP MAX at TA<5°C.
This setting is only recommended in case the capacity of the
heat pump can cover the heating requirements of the house
and domestic hot water over the complete heating season. The maximum domestic hot water temperature that can be
The result of this setting is that the domestic hot water will reached with the heat pump is 50°C. It is advised to select
never be heated by the booster heater except for THP OFF not higher than 48°C in order to improve
"[2] Disinfection function" and "Powerful domestic water performance of the heat pump during domestic water
heating" (see operation manual). heating mode.

The field setting [4-03]=2 or 3 is not relevant for this When setting [4-03]=0 or 2 special attention to setting
system. [6-00] is recommended. A good balance between the
required domestic hot water temperature and heat pump
■ [4-03]=1, then booster heater heater operation is only ON temperature (THP ON) is a must.
determined by booster heater OFF temperature (T BH OFF),
booster heater ON temperature (TBH ON) and/or schedule
timer. Refer to setting "[7-00]" on page 26 and "[7-01]" on
page 26.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 25
[7] DT for booster heater and dual set point control ■ [7-01] Hysteresis value booster heater: temperature
difference determining the booster heater ON temperature
DT for booster heater
(TBH ON). TBH ON = TBH OFF – [7-01]
Applies only to installations with a domestic hot water tank.
The minimum value for booster heater ON
When the domestic hot water is heated and the domestic hot water
temperature (TBH ON) is 2°C (fixed) below heat pump
set point temperature (as set by the user) has been reached, the
booster heater will continue to heat the domestic hot water to a OFF temperature (THP OFF).
temperature a few degrees above the set point temperature, i.e. the
booster heater OFF temperature. These extra degrees are specified Dual set point control
by the domestic hot water step length field setting. Correct setting Applies only to installations with different heat emitter which require
prevents the booster heater from repeatedly turning on and off (i.e. different set points.
chattering) to maintain the domestic hot water set point temperature.
Note: the booster heater will turn back on when the domestic hot Dual set point control makes it possible to generate 2 different set
water temperature drops [7-01] (field setting) below the booster points.
heater OFF temperature.
NOTE There is no indication available which set point is
If the schedule timer for booster heater (see the operation active!
manual) is active, the booster heater will only operate if
allowed by this schedule timer. ■ [7-02] Dual set point control status: defines whether the dual
set point control is enabled (1) or disabled (0).
■ [7-00] Domestic hot water step length: temperature
difference above the domestic hot water set point ■ [7-03] Second set point heating: specifies the second set
temperature before the booster heater is turned off. point temperature in heating operation.

TDHW ■ [7-04] Second set point cooling: specifies the second set
point temperature in cooling operation.
TBH OFF 73 [7-00] [7-01]
TBH ON 71 NOTE ■ The first set point heating/cooling is the set point
TU 70 selected on the user interface.
60 - In heating mode the first set point can be a
THP MAX 50 [6-01] fixed value or weather dependent.
THP OFF 48
[6-00] - In cooling mode the first set point is always a
THP ON 41
fixed value.
40
■ The second set point heating [7-03] should be
30 linked to the heat emitters which requires the
highest set point in heating mode. Example: fan
20 TU = 70°C coil unit.
[7-00] = 3°C
HP BH HP ■ The second set point cooling [7-04] should be
10 [6-01] = 2°C
[6-00] = 7°C
linked to the heat emitters which requires the
lowest set point in cooling mode. Example: fain
5
t
coil unit.
BH Booster heater ■ The actual second set point heating value
HP Heat pump. If heating up time by the heat pump takes too
depends on the selected value of setting [7-03].
long, auxiliary heating by the booster heater can take place - In case [7-03]=1~24, the actual second set
TBH OFF Booster heater OFF temperature (TU + [7-00]) point will be first set point heating increased
with [7-03] (the maximum is 55°C).
TBH ON Booster heater ON temperature (TBH OFF – [7-01])
In this way the second set point heating is
THP MAX Maximum heat pump temperature at sensor in domestic hot linked to the first set point heating.
water tank
- In case [7-03]=25~55, the actual second set
THP OFF Heat pump OFF temperature (THP MAX – [6-01])
point heating is equal to [7-03].
THP ON Heat pump ON temperature (THP OFF – [6-00])
■ The selection of second set point or first set point
TDHW Domestic hot water temperature
is determined by the terminals (X2M: 1, 2, 4).
TU User set point temperature (as set on the user interface) The second set point has always priority on the
t Time first set point.

WARNING X2M SP1 First set point contact

Be aware that the domestic hot water temperature will be 1 2 3 4 SP2 Second set point
contact
automatically increased (always) with the value selected in SP2 SP1
field setting [7-00] compare to the user set point for
domestic hot water (TU). Refer to field setting [7-00] and
the operation manual to select preferable set point. When dual set point control is enabled, heating/cooling
selection always has to be done on the user interface.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field NOTE It is the responsibility of the installer to make sure no
supply) shall be installed at the hot water outlet connection
unwanted situations can occur.
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap It is very important that the water temperature to the
never rise above a set maximum value. This maximum floor heating loops never becomes too high in heating
allowable hot water temperature shall be selected mode or never too cold in cooling mode. Failure to
according to local and national regulations. observe this rule can result in construction damage or
discomfort. For example in cooling mode condensation
If the booster heater operation is limited ([4-03]=0), then on the floor can occur when water towards the floor
set point of field setting parameter [7-00] has only meaning heating loops is too cold (dew point).
for powerful domestic water heating.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
26 4PW56301-1A
[8] Domestic water heating mode timer ■ [8-04] Additional running time at [4-02]/[F-01]: specifies the
additional running time on the maximum running time at
Before changing field settings for domestic water heating, outdoor temperature [4-02] or [F-01]. See figure below.
read attentively the warnings mentioned in the paragraph
"Domestic hot water tank (option)" on page 2. Heating Cooling

t t
Applies only to installations with a domestic hot water tank.
[8-01]+ [8-01]+
The 'domestic water heating mode timer' field settings defines the [8-04] [8-04]
minimum and maximum domestic water heating times, minimum time
between two domestic water heating cycles by heat pump, and [8-02] [8-02]
booster heater delay time.
[8-01] [8-01]
■ [8-00] Minimum running time: specifies the minimum time
period during which heat pump domestic water heating mode 0 0
should be activated, even when the target domestic hot water [5-03] [4-02] TA [F-01] 35°C TA
temperature for heat pump (THP OFF) has already been
t Time
reached.
TA Ambient (outdoor) temperature
■ [8-01] Maximum running time: specifies the maximum time
period during which heat pump domestic water heating mode anti-recycle time
can be activated, even when the target domestic hot water maximum running time
temperature for heat pump (THP OFF) has not yet been
reached.
The actual maximum running time will automatically variate The full advantage of [8-04] will be applicable if setting
between [8-01] and [8-01]+[8-04] depending on the outdoor [4-03] is not 1.
temperature. See figure in chapter "[8-04]" on page 27.
[9] Cooling and heating set point ranges
Note that when the unit is configured to work with a The purpose of this field setting is to prevent the user from selecting
room thermostat (refer to "Room thermostat a wrong (i.e., too hot or too cold) leaving water temperature. Thereto
installation configuration" on page 21), the the heating temperature set point range and the cooling temperature
maximum running timer will only be taken into set point range available to the user can be configured.
account when there is a request for space cooling
or space heating. When there is no request for CAUTION
room cooling or room heating, domestic water
■ In case of a floor heating application, it is important to
heating by the heat pump will continue until the
limit the maximum leaving water temperature at
'heat pump OFF temperature' (see field settings [6]
heating operation according to the specifications of
on page 25) is reached. When no room thermostat
the floor heating installation.
is installed, the timer is always taken into account.
■ In case of a floor cooling application, it is important to
■ [8-02] Anti-recycling time: specifies the minimum required limit the minimum leaving water temperature at
interval between two heat pump domestic water heating cooling operation (field setting of parameter [9-03]) to
mode cycles. 16~18°C to prevent condensation on the floor.
The actual anti-recycling time will automatically variate
between [8-02] and 0 depending on the outdoor temperature. ■ [9-00] Heating set point upper limit: maximum leaving water
See figure in chapter "[8-04]" on page 27. temperature for heating operation.
■ [9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.
1
■ [9-02] Cooling set point upper limit: maximum leaving water
0 temperature for cooling operation.
■ [9-03] Cooling set point lower limit: minimum leaving water
1 temperature for cooling operation.
■ [9-04] Overshoot setting: defines how much the water
0
temperature may rise above the set point before the
[8-00] compressor stops. This function is only applicable in heating
mode.
t
[8-01] [8-02]
1 Heat pump domestic water heating mode
(1 = active, 0 = not active)
2 Hot water request for heat pump (1 = request, 0 = no request)
t Time

If the outdoor temperature is higher than the field setting to


which parameter [4-02] is set, then field settings of
parameters [8-01], [8-02], and [8-04] are not considered.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 27
[C] Setup on EKRP1HB digital I/O PCB
■ The combination of setting [4-03]=0/2 with
Solar priority mode bivalent operation at low outdoor temperature
■ [C-00] Solar priority mode setting: for information concerning can result in domestic hot water shortage.
the EKSOLHW solar kit, refer to the installation manual of ■ The bivalent operation function has no impact on
that kit. the domestic water heating mode. The domestic
Alarm output logic hot water is still and only heated by the indoor
unit.
■ [C-01] Alarm output logic: defines the logic of the alarm
output on the EKRP1HB digital I/O PCB. ■ The permission signal for the auxiliary boiler is
[C-01]=0, the alarm output will be powered when an alarm located on the EKRP1HB (digital I/O PCB).
occurs (default). When it is activated, the contact X1, X2 is closed
[C-01]=1, the alarm output will not be powered when an and open when it is disactivated. See figure for
alarm occurs. This field setting allows for distinction between the schematic location of this contact.
detection of an alarm and detection of a power failure to the
X2M

X1 X2 X3 X4
unit.

No power supply
[C-01] Alarm No alarm to unit OFF ON

0 Closed output Open output Open output


(default) SS1
1 Open output Closed output Open output

Bivalent operation
X1M
Applies only to installations with an auxiliary boiler (alternating
operation, parallel connected). The purpose of this function is to
determine —based on the outdoor temperature— which heating
source can/will provide the space heating, either the Daikin indoor YC Y1 Y2 Y3 Y4
unit or an auxiliary boiler.
The field setting "bivalent operation" apply only the indoor unit space
[D] Restricted power supply condition mode/Local shift value
heating operation and the permission signal for the auxiliary boiler.
weather dependent
When the "bivalent operation" function is enabled, the indoor unit will
[D-02] is set to 1 by default: The restricted power supply condition
stop automatically in space heating operation when the outdoor
mode is enabled. Do not change this value.
temperature drops below "bivalent ON temperature" and the
permission signal for the auxiliary boiler becomes active. Local shift value weather dependent
When the bivalent operation function is disabled, the space heating The local shift value weather dependent field setting is only relevant
by indoor unit is possible at all outdoor temperatures (see operation in case weather dependent set point (see field setting "[1] Weather
ranges) and permission signal for auxiliary boiler is always dependent set point (heating operation only)" on page 24) is
disactivated. selected.
■ [C-02] Bivalent operation status: defines whether bivalent ■ [D-03] Local shift value weather dependent: determines the
operation is enabled (1) or disabled (0). shift value of the weather dependent set point around
outdoor temperature of 0°C.
■ [C-03] Bivalent ON temperature: defines the outdoor
temperature below which the permission signal for the Tt
auxiliary boiler will be active (closed, KCR on EKRP1HB) and
space heating by indoor unit will be stopped. [1-02]
■ [C-04] Bivalent hysteresis: defines the temperature difference
local shift value
between bivalent ON temperature and bivalent OFF
temperature. range
[1-03]
Permission signal X1–X2 (EKRP1HB)
closed
[1-00] 0°C [1-01] TA
[C-04]
open Tt Target water temperature
TA TA Outdoor temperature
[C-03]
range Range
TA Outdoor temperature
local shift Local shift value
value
CAUTION
[1-00], [1-01], Applicable field setting of the weather dependent set
Make sure to observe all rules mentioned in [1-02], [1-03] point [1]
application 5 when bivalent operation function is
enabled.
Outdoor temperature range
Daikin shall not be held liable for any damage [D-03] (TA) Local shift value
resulting from failure to observe this rule. 0 — —
1 2
–2°C~2°C
2 4
3 2
–4°C~4°C
4 4

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
28 4PW56301-1A
[E] Unit information readout Functionality of X14A
■ [E-00] Readout of the software version (example: 23) ■ [F-04] Functionality of X14A: specifies if the logic of X14A
follows the output signal for the solar kit model (EKSOLHW)
■ [E-01] Readout of the EEPROM version (example: 23)
EKHBH/X_AA/AB (0) or if the logic of X14A follows the
■ [E-02] Readout of the unit model identification (example: 11) output for the bottom plate heater (1).
■ [E-03] Readout of the liquid refrigerant temperature
NOTE Independent from field setting [F-04], the contact
■ [E-04] Readout of the inlet water temperature X3-X4 (EKRP1HB) follows the logic of the output
signal for the solar kit model (EKSOLHW). See figure
NOTE [E-03] and [E-04] readouts are not permanently below for the schematic location of this contact.
refreshed. Temperature readouts are updated
after looping through the field setting first codes
X2M

X1 X2 X3 X4
again only.

[F] Option setup OFF ON


Pump operation
SS1
The pump operation field setting apply to the pump operation logic
only when DIP switch SS2-3 is OFF.
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [4-02] or if the X1M
outdoor temperature drops below the value set by [F-01]. When the
pump operation is enabled, the pump operation is possible at all
outdoor temperatures. Refer to "Pump operation configuration" on
page 21. YC Y1 Y2 Y3 Y4
■ [F-00] Pump operation: specifies wether the pump operation
function is enabled (1) or disabled (0).
Space cooling permission
■ [F-01] Space cooling permission temperature: defines the
outdoor temperature below which space cooling is turned off.

This function is only valid for EKHBX when space


cooling is selected.
Bottom plate heater control
Applies only to installation with an outdoor unit ERLQ or in case the
option bottom plate heater kit is installed.
■ [F-02] Bottom plate heater ON temperature: defines the
outdoor temperature below which the bottom plate heater will
be activated by indoor unit in order to prevent ice build-up in
the bottom plate of the outdoor unit at lower outdoor
temperatures.
■ [F-03] Bottom plate heater hysteresis: defines the
temperature difference between bottom plate heater ON
temperature and the bottom plate heater OFF temperature.
Bottom plate heater
ON
[F-03]
OFF
TA
[F-02]

TA Outdoor temperature

CAUTION
The bottom plate heater is controlled via X14A. Make sure
[F-04] is correctly set.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 29
Field settings table

Installer setting at variance with default value


First Second Default
code code Setting name Date Value Date Value value Range Step Unit

0 User permission level

00 User permission level 3 2/3 1 —

1 Weather dependent set point

00 Low ambient temperature (Lo_A) –10 –20~5 1 °C

01 High ambient temperature (Hi_A) 15 10~20 1 °C

02 Set point at low ambient temperature (Lo_TI) 40 25~55 1 °C

03 Set point at high ambient temperature (Hi_TI) 25 25~55 1 °C

2 Disinfection function

00 Operation interval Mon~Sun,


Fri — —
All

01 Status 1 (ON) 0/1 — —

02 Start time 23:00 0:00~23:00 1:00 hour

03 Set point 70 40~80 5 °C

04 Interval 10 5~60 5 min

3 Auto restart

00 Status 0 (ON) 0/1 — —

4 Backup/booster heater operation and space heating off temperature

00 Not applicable. Do not change the default value! 1 (ON) 0/1 — —

01 Not applicable. Do not change the default value! 0 (OFF) 0/1/2 — —

02 Space heating off temperature 25 14~25 1 °C

03 Booster heater operation 3 0/1/2/3 — —

04 Not applicable 2 Read only — —

5 Equilibrium temperature and space heating priority temperature

00 Not applicable. Do not change the default value! 1 (ON) 0/1 — —

01 Not applicable. Do not change the default value! 0 –15~35 1 °C

02 Not applicable. Do not change the default value! 0 (OFF) 0/1 — —

03 Not applicable. Do not change the default value! 0 –15~20 1 °C

04 Not applicable. Do not change the default value! 10 0~20 1 °C

6 DT for heat pump domestic water heating mode

00 Start 2 2~20 1 °C

01 Stop 2 0~10 1 °C

7 DT for booster heater and dual set point control

00 Domestic hot water step length 0 0~4 1 °C

01 Hysteresis value booster heater 2 2~40 1 °C

02 Dual set point control status 0 0/1 — —

03 Second set point heating 1~24 /


10 1 °C
25~55

04 Second set point cooling 7 5~22 1 °C

8 Domestic water heating mode timer

00 Minimum running time 5 0~20 1 min

01 Maximum running time 30 5~60 5 min

02 Anti-recycling time 3 0~10 0.5 hour

03 Not applicable. Do not change the default value! 50 20~95 5 min

04 Additional running time at [4-02]/[F-01] 95 0~95 5 min

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
30 4PW56301-1A
Installer setting at variance with default value
First Second Default
code code Setting name Date Value Date Value value Range Step Unit

9 Cooling and heating set point ranges

00 Heating set point upper limit 55 37~55 1 °C

01 Heating set point lower limit 25 15~37 1 °C

02 Cooling set point upper limit 22 18~22 1 °C

03 Cooling set point lower limit 5 5~18 1 °C

04 Overshoot setting(a) 1 1~4 1 °C

C Setup on EKRP1HB digital I/O PCB

00 Solar priority mode setting 0 0/1 1 —

01 Alarm output logic 0 0/1 — —

02 Bivalent operation status 0 0/1 — —

03 Bivalent ON temperature 0 –25~25 1 °C

04 Bivalent hysteresis 3 2~10 1 °C

D Restricted power supply condition mode/local shift value weather dependent

00 Not applicable. Do not change the default value! 0 0/1/2/3 — —

01 Not applicable. Do not change the default value! 0 (OFF) 0/1/2 — —

02 Not applicable. Do not change the default value! 1 — — —

03 Local shift value weather dependent 0 0/1/2/3/4 — —

E Unit information readout

00 Software version Read


— — —
only

01 EEPROM version Read


— — —
only

02 Unit model identification Read


— — —
only

03 Liquid refrigerant temperature Read


— — °C
only

04 Inlet water temperature Read


— — °C
only

F Option setup

00 Pump operation 0 0/1 — —

01 Space cooling permission temperature 20 10~35 1 °C

02 Bottom plate heater ON temperature 3 3~10 1 °C

03 Bottom plate heater hysteresis 5 2~5 1 °C

04 Functionality of X14A 1 0/1 — —


(a) Only possible to modify the first 3 minutes after power ON.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 31
TEST RUN AND FINAL CHECK MAINTENANCE AND SERVICE

The installer is obliged to verify correct operation of the indoor and In order to ensure optimal availability of the unit, a number of checks
outdoor unit after installation. and inspections on the unit and the field wiring have to be carried out
at regular intervals.
This maintenance should be carried out by your local technician.
Final check
To execute the maintenance activities as mentioned below, it is only
Before switching on the unit, read following recommendations: required to remove the indoor unit cover. See "Opening the indoor
■ When the complete installation and all necessary settings have unit" on page 9.
been carried out, close all front panels of the unit and refit the
indoor unit cover.
Maintenance activities
■ The service panel of the switch box may only be opened by a
licensed electrician for maintenance purposes.
DANGER: ELECTRIC SHOCK
Test run operation (manual)
■ Before carrying out any maintenance or repair activity,
If required, the installer can perform a manual test run operation at always switch off the circuit breaker on the supply
any time to check correct operation of cooling, heating and domestic panel, remove the fuses or open the protection
water heating. devices of the unit.
■ Make sure that before starting any maintenance or
Procedure repair activity, also the power supply to the outdoor
1 Push the z button 4 times so the t icon will be displayed. unit is switched off.
■ Do not touch live parts for 10 minutes after the power
2 Depending on the indoor unit model, heating operation, cooling
supply is turned off because of high voltage risk.
operation or both must be tested as follows (when no action is
performed, the user interface will return to normal mode after 10 ■ The heater of the compressor may operate even in
seconds or by pressing the z button once): stop mode.
• To test the heating operation push the h/c button so the h ■ Please note that some sections of the electric
icon is displayed. To start the test run operation press the component box are hot.
y button. ■ Make sure you do not touch a conductive section.
• To test the cooling operation push the h/c button so the c ■ Do not rinse the indoor unit. This may cause electric
icon is displayed. To start the test run operation press the shocks or fire.
y button.
• To test the domestic water heating operation push the v ■ When service panels are removed, live parts can be
button. The test run operation will start without pressing the easily touched by accident.
y button. Never leave the unit unattended during installation or
servicing when service panel is removed.
3 The test run operation will end automatically after 30 minutes or
when reaching the set temperature. The test run operation can
Play it safe!
be stopped manually by pressing the z button once. If there are
misconnections or malfunctions, an error code will be displayed Touch a metal part by hand (such as the stop valve) in
on the user interface. Otherwise, the user interface will return to order to eliminate static electricity and to protect the PCB
normal operation. before performing service.

4 To resolve the error codes, see "Error codes" on page 35.


DANGER
To display the last resolved error code, push the z button Do not touch water pipes during and immediately after
1 time. Push the z button again 4 times to return to operation as the pipes may be hot. Your hand may suffer
normal mode. burns. To avoid injury, give the piping time to return to
normal temperature or be sure to wear proper gloves.
NOTE It is not possible to perform a test run if a forced
operation from the outdoor unit is in progress. Should
forced operation be started during a test run, the test WARNING
run will be aborted. ■ Do not touch the refrigerant pipes during and
immediately after operation as the refrigerant pipes
may be hot or cold, depending on the condition of the
refrigerant flowing through the refrigerant piping,
compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the
refrigerant pipes. To avoid injury, give the pipes time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
■ Do not touch the internal parts (pump, backup heater,
etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal
parts. To avoid injury, give the internal parts time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
32 4PW56301-1A
The described checks must be executed at least once a year. TROUBLESHOOTING
1 Water pressure
This section provides useful information for diagnosing and
Check if the water pressure is above 1 bar. If necessary add
correcting certain troubles which may occur in the unit.
water.
This troubleshooting and related corrective actions may only be
2 Water filter
carried out by your local technician.
Clean the water filter.

3 Water pressure relief valve


General guidelines
Check for correct operation of the pressure relief valve by
turning the red knob on the valve counter-clockwise: Before starting the troubleshooting procedure, carry out a thorough
■ If you do not hear a clacking sound, contact your local dealer. visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.
■ In case the water keeps running out of the unit, close both
the water inlet and outlet shut-off valves first and then contact DANGER
your local dealer.
When carrying out an inspection on the switch box of the
4 Pressure relief valve hose unit, always make sure that the main switch of the unit is
Check that the pressure relief valve hose is positioned switched off.
appropriately to drain the water. When a safety device was activated, stop the unit and find out why
If the (optional) drain pan kit is installed, make sure that the the safety device was activated before resetting it. Under no
pressure relief valve hose end is positioned in the drain pan. circumstances safety devices may be bridged or changed to a value
5 Backup heater vessel insulation cover other than the factory setting. If the cause of the problem cannot be
found, call your local dealer.
Check that the backup heater insulation cover is fastened tightly
around the backup heater vessel. If the pressure relief valve is not working correctly and is to be
replaced, always reconnect the flexible hose attached to the pressure
6 Domestic hot water tank pressure relief valve (field supply) relief valve, to avoid water dripping out of the unit!
Applies only to installations with a domestic hot water tank.
Check for correct operation of the pressure relief valve on the NOTE For problems related to the optional solar kit for
domestic hot water tank. domestic water heating, refer to the troubleshooting in
the installation manual of that kit.
7 Domestic hot water tank booster heater
Applies only to installations with a domestic hot water tank.
DANGER
It is advisable to remove lime buildup on the booster heater to
extend its life span, especially in regions with hard water. To do Do not touch water pipes during and immediately after
so, drain the domestic hot water tank, remove the booster heater operation as the pipes may be hot. Your hand may suffer
from the domestic hot water tank and immerse in a bucket (or burns. To avoid injury, give the piping time to return to
similar) with lime-removing product for 24 hours. normal temperature or be sure to wear proper gloves.

8 Indoor unit switch box


■ Carry out a thorough visual inspection of the switch box and WARNING
look for obvious defects such as loose connections or ■ Do not touch the refrigerant pipes during and
defective wiring. immediately after operation as the refrigerant pipes
may be hot or cold, depending on the condition of the
■ Check for correct operation of contactors K1M, K3M, K5M
refrigerant flowing through the refrigerant piping,
(applications with domestic hot water tank only) by use of an
compressor, and other refrigerant cycle parts. Your
ohmmeter. All contacts of these contactors must be in open
hands may suffer burns or frostbite if you touch the
position.
refrigerant pipes. To avoid injury, give the pipes time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
■ Do not touch the internal parts (pump, backup heater,
etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal
parts. To avoid injury, give the internal parts time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 33
Symptom 5: The water pressure relief valve leaks
General symptoms
POSSIBLE CAUSES CORRECTIVE ACTION

Symptom 1: The unit is turned on (y LED is lit) but the unit is not Dirt is blocking the water pressure Check for correct operation of the
heating or cooling as expected relief valve outlet. pressure relief valve by turning the
red knob on the valve counter
POSSIBLE CAUSES CORRECTIVE ACTION
clockwise:
• If you do not hear a clacking sound,
The temperature setting is not Check the controller set point. contact your local dealer.
correct. • In case the water keeps running out
of the unit, close both the water inlet
The water flow is too low. • Check that all shut off valves of the and outlet shut-off valves first and
water circuit are completely open. then contact your local dealer.
• Check if the water filter needs
cleaning.
n" when pressing
Symptom 6: The user interface displays "n
• Make sure there is no air in the
system (purge air). certain buttons
• Check on the manometer that there
is sufficient water pressure. The POSSIBLE CAUSES CORRECTIVE ACTION
water pressure must be >1 bar
(water is cold) The current permission level is set to Change the "user permission level"
• Check that the pump speed setting is a level that prevents using the field setting [0-00], see "Field
on the highest speed. pressed button. settings" on page 23.
• Make sure that the expansion vessel
is not broken. Symptom 7: Space heating capacity shortage at low outdoor
• Check that the resistance in the temperatures
water circuit is not too high for the
pump (refer to "Setting the pump
speed" on page 23). POSSIBLE CAUSES CORRECTIVE ACTION

The water volume in the installation Make sure that the water volume in Backup heater operation is not Check that the "backup heater
is too low. the installation is above the minimum activated. operation status" field setting [4-00]
required value (refer to "Checking is turned on, see "Field settings" on
the water volume and expansion page 23.
vessel pre-pressure" on page 15). Check whether or not the thermal
protector of the backup heater has
been activated (refer to Main
Symptom 2: The unit is turned on but the compressor is not starting
components, "Backup heater
(space heating or domestic water heating)
thermal protector" on page 11 for
location of the reset button).
POSSIBLE CAUSES CORRECTIVE ACTION Check whether or not the thermal
The unit must start up out of its In case of low water temperature, the fuse of the backup heater is blown
operation range (the water system utilizes the backup heater to (refer to "Main components",
temperature is too low). reach the minimum water "Backup heater thermal fuse" on
temperature first (15°C). page 11 for location of the reset
• Check that the backup heater power button).
supply is correct.
• Check that the backup heater Symptom 8: Unexpected backup heater operation
thermal fuse is closed.
• Check that the backup heater POSSIBLE CAUSES CORRECTIVE ACTION
thermal protector is not activated.
• Check that the backup heater Entering water temperature is too Increase the water flow.
contactors are not broken. low and leaving water temperature
>25°C.
Symptom 3: Pump is making noise (cavitation)
Too frequent use of the backup The water volume in the cicuit is too
heater during heating operation or low.
POSSIBLE CAUSES CORRECTIVE ACTION domestic water heating.
There is air in the system. Purge air.
Water pressure at pump inlet is too • Check on the manometer that there
low. is sufficient water pressure. The
water pressure must be >1 bar
(water is cold).
• Check that the manometer is not
broken.
• Check that the expansion vessel is
not broken.
• Check that the setting of the pre-
pressure of the expansion vessel is
correct (refer to "Setting the pre-
pressure of the expansion vessel" on
page 16).

Symptom 4: The water pressure relief valve opens

POSSIBLE CAUSES CORRECTIVE ACTION

The expansion vessel is broken. Replace the expansion vessel.


The water volume in the installation Make sure that the water volume in
is too high. the installation is under the
maximum allowed value (refer to
"Checking the water volume and
expansion vessel pre-pressure" on
page 15).

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
34 4PW56301-1A
Error codes Error
code Failure cause Corrective action

When a safety device is activated, the user interface LED will be AA Backup heater thermal protector Reset the thermal protector by
is open pressing the reset button (refer
flashing, and an error code will be displayed. to "Main components" on
A list of all errors and corrective actions can be found in the table page 10 for location of the reset
button)
below.
Check the reset button of the Contact your local dealer.
Reset the safety by turning the unit OFF and back ON. thermal protector.
If both the thermal protector and
Instruction to turn the unit OFF the controller are reset, but the
AA error code persists, the
User interface mode Domestic water Push the y Push the
(heating/cooling =) heating mode (w) button v button backup heater thermal fuse has
blown.
ON ON 1 time 1 time
AC Booster heater thermal protector Reset the thermal protector
ON OFF 1 time — is open (applies only to
installations with a domestic hot
OFF ON — 1 time
water tank)
OFF OFF — —
Secondary thermal protector is Reset the thermal protector
open (applies only to units with a
In case this procedure for resetting the safety is not successful, EKHWSU domestic hot water
contact your local dealer. tank installed)
C0 Flow switch failure (flow switch Check that the flow switch is not
Error
code Failure cause Corrective action remains closed while pump is clogged with dirt.
stopped)
80 Inlet water temperature Contact your local dealer.
thermistor failure (inlet water C4 Heat exchanger thermistor Contact your local dealer.
thermistor broken) failure (heat exchanger
temperature sensor broken)
81 Outlet water temperature Contact your local dealer.
thermistor failure (outlet water E1 Outdoor unit PCB defective Contact your local dealer.
temperature sensor broken) E3 Abnormal high pressure Check that the unit is operating
89 Water heat exchanger freeze-up Refer to error code 7H. within its operating range (refer
failure (due to water flow too low) to "Technical specifications" on
page 37).
Water heat exchanger freeze-up Contact your local dealer. Contact your local dealer.
failure (due to refrigerant
shortage) E4 Actuation of low pressure sensor Check that the unit is operating
within its operating range (refer
7H Flow failure (water flow too low • Check that all shut off valves of to "Technical specifications" on
or no water flow at all, minimum the water circuit are completely page 37).
required water flow is 12 l/min) open. Contact your local dealer.
• Check if the water filter needs
cleaning. E5 Overload activation of Check that the unit is operating
• Check that the unit is operating compressor within its operating range (refer
within its operating range (refer to "Technical specifications" on
to "Technical specifications" on page 37).
page 37). Contact your local dealer.
• Also refer to "Charging water" on
page 16. E7 Fan lock failure (fan is locked) Check if the fan is not obstructed
• Make sure there is no air in the by dirt. If the fan is not
system (purge air). obstructed, contact your local
• Check on the manometer that dealer.
there is sufficient water
pressure. The water pressure E9 Malfunction of electronic Contact your local dealer.
must be >1 bar (water is cold). expansion valve
• Check that the pump speed
EC Domestic hot water temperature • Check that the contactor of the
setting is on the highest speed. electric booster heater is not
too high (>89°C)
• Make sure that the expansion short circuited.
vessel is not broken. • Check that the domestic hot
• Check that the resistance in the water thermistor is giving the
water circuit is not too high for correct read out.
the pump (refer to "Setting the
pump speed" on page 23). F3 Too high discharge temperature Clean the outdoor coil. If the coil
• If this error occurs at defrost (e.g. due to outdoor coil is clean, contact your local
operation (during space heating blockage) dealer.
or domestic water heating),
make sure that the backup H3 Malfunctioning HPS system Contact your local dealer.
heater power supply is wired H9 Outdoor temperature thermistor Contact your local dealer.
correctly and that fuses are not
failure (outdoor thermistor is
blown.
broken)
• If EKHWSU version of domestic
hot water tank is installed, check HC Domestic hot water tank Contact your local dealer.
if the setting of the additional thermistor failure
thermostat in the tank switch box
is correct (≥50°C). J1 Malfunction of pressure sensor Contact your local dealer.

8H Outlet water temperature of • Check that the contactor of the J3 Discharge pipe thermistor failure Contact your local dealer.
indoor unit too high (>65°C) electric backup heater is not J5 Suction pipe outdoor unit Contact your local dealer.
short circuited. thermistor failure
• Check that the outlet water
thermistor is giving the correct J6 Aircoil thermistor frost detection Contact your local dealer.
read out. failure
A1 Indoor unit PCB defective Contact your local dealer. J7 Aircoil thermistor mean Contact your local dealer.
temperature failure
A5 Too low (during cooling Contact your local dealer.
operation) or too high (during J8 Liquid pipe outdoor unit Contact your local dealer.
heating operation) refrigerant thermistor failure
temperature (measured by R3T)
L4 Electric component failure Contact your local dealer.
L5 Electric component failure Contact your local dealer.
L8 Electric component failure Contact your local dealer.
L9 Electric component failure Contact your local dealer.

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 35
Error
code Failure cause Corrective action
LC Electric component failure Contact your local dealer.
P1 PCB failure Contact your local dealer.
P4 Electric component failure Contact your local dealer.
PJ Failure of capacity setting Contact your local dealer.
U0 Refrigerant failure (due to Contact your local dealer.
refrigerant leak)
U2 Main circuit voltage failure Contact your local dealer.
U4 Communication failure Contact your local dealer.
U5 Communication failure Contact your local dealer.
U7 Communication failure Contact your local dealer.
UA Communication failure Contact your local dealer.

Installation manual EKHBH/XE008BA


Indoor unit for air to water heat pump system
36 4PW56301-1A
TECHNICAL SPECIFICATIONS

General

Heating/cooling models (EKHBXE) Heating only models (EKHBHE)


Nominal capacity
• cooling Refer to the Technical Data
• heating Refer to the Technical Data
Dimensions H x W x D 922 x 502 x 361 922 x 502 x 361
Weight
• machine weight 46 kg 46 kg
• operation weight 59 kg 59 kg
Connections
• water inlet/outlet 1" MBSP(a) 1" MBSP(a)
• water drain hose nipple hose nipple
• refrigerant liquid side Ø6.4 mm (1/4 inch) Ø6.4 mm (1/4 inch)
• refrigerant gas side Ø15.9 mm (5/8 inch) Ø15.9 mm (5/8 inch)
Expansion vessel
• volume 10 l 10 l
• maximum working pressure (MWP) 3 bar 3 bar
Pump
• type water cooled water cooled
• no. of speed 3 3
Sound pressure level Refer to technical data Refer to technical data
Internal water volume 5.5 l 5.5 l
Pressure relief valve water circuit 3 bar 3 bar
Operation range - water side
• heating +15~+50°C +15~+50°C
• cooling +5~+22°C —
Operation range - air side
• heating –20~+25°C –20~+25°C
• cooling +10~+43°C —
• domestic hot water by heat pump –15~+35°C –15~+35°C
(a) MBSP = Male British Standard Pipe

Electrical specifications

Heating/cooling models (EKHBXE) Heating only models (EKHBHE)


Standard unit (power supply via outdoor unit)
• power supply 230 V 50 Hz 1P
Backup heater
• power supply See "Connection of the backup heater power supply" on page 18
• maximum running current See "Connection of the backup heater power supply" on page 18

EKHBH/XE008BA Installation manual


Indoor unit for air to water heat pump system
4PW56301-1A 37
4PW56301-1A
Copyright 2009 Daikin

You might also like