Professional Documents
Culture Documents
=6 kW
EKHBHE008BA3V3
EKHBXE008BA3V3
2
1 2 3 4 5 300
1x 1x 2x 1x 2x
500
≥350
≥
1 2
3 260
T T
895
922
830
B B
469
1-1/2" FBSP
4
90
°
361
96
48
39
35
48
2 4
3 142 101 5
502
3
EKHBHE008BA***
EKHBXE008BA***
Indoor unit for air to water heat pump system Installation manual
CONTENTS Page
READ THESE INSTRUCTIONS CAREFULLY BEFORE
Introduction........................................................................................ 1 INSTALLATION. KEEP THIS MANUAL IN A HANDY
General information ................................................................................... 1 PLACE FOR FUTURE REFERENCE.
Scope of this manual ................................................................................. 3
IMPROPER INSTALLATION OR ATTACHMENT OF
Model identification .................................................................................... 3
EQUIPMENT OR ACCESSORIES COULD RESULT IN
Accessories ....................................................................................... 3 ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
Accessories supplied with the indoor unit .................................................. 3 OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
Safety considerations ........................................................................ 3 TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
Typical application examples ............................................................. 4 SPECIFICALLY DESIGNED FOR USE WITH THE
Application 1 .............................................................................................. 4 EQUIPMENT AND HAVE THEM INSTALLED BY A
Application 2 .............................................................................................. 5 PROFESSIONAL.
Application 3 .............................................................................................. 5
ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL
Application 4 .............................................................................................. 6
Application 5 .............................................................................................. 7
BE CARRIED OUT BY A LICENSED TECHNICIAN.
Application 6 .............................................................................................. 8 BE SURE TO WEAR ADEQUATE PERSONEL PROTEC-
Overview of the indoor unit................................................................ 9 TION EQUIPMENT (PROTECTION GLOVES, SAFETY
Opening the indoor unit.............................................................................. 9 GLASSES, ...) WHEN PERFORMING INSTALLATION,
Main components..................................................................................... 10 MAINTENANCE OR SERVICE TO THE UNIT.
Switch box main components .................................................................. 11
Functional diagram .................................................................................. 12
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
Installation of the indoor unit............................................................ 12
ADVICE AND INFORMATION.
Selecting an installation location.............................................................. 12
Dimensions and service space ................................................................ 13 THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED
Inspecting, handling and unpacking the unit............................................ 13 FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT
Mounting the indoor unit .......................................................................... 13 TEMPERATURES RANGING 4°C~35°C.
Installation of the EKHBDP drain pan kit (only for EKHBX models)......... 14
Refrigerant pipework................................................................................ 14 The English text is the original instruction. Other languages are
Water pipework ........................................................................................ 14 translations of the original instructions.
Charging water......................................................................................... 16
Piping insulation....................................................................................... 17
Field wiring............................................................................................... 17
Relocation of the digital controller............................................................ 20 INTRODUCTION
Start-up and configuration ............................................................... 20
DIP switch settings overview.................................................................... 20
Room thermostat installation configuration.............................................. 21 General information
Pump operation configuration .................................................................. 21
Domestic hot water tank installation configuration ................................... 22 Thank you for purchasing this indoor unit.
Initial start-up at low outdoor ambient temperatures................................ 22
Re-start at low outdoor ambient temperatures......................................... 22 The unit is the indoor part of the air to water ERHQ or ERLQ heat
Pre-operation checks ............................................................................... 22 pumps. These units are designed for wall mounted indoor installation.
Powering up the indoor unit ..................................................................... 22 See "Selecting an installation location" on page 12. The units can be
Setting the pump speed ........................................................................... 23 combined with Daikin fan coil units, floor heating applications, low
Field settings............................................................................................ 23 temperature radiators, Daikin domestic water heating applications
Field settings table ................................................................................... 30 and Daikin solar kit for domestic hot water applications.
Test run and final check................................................................... 32
Final check............................................................................................... 32
Heating/cooling units and heating only units
Test run operation (manual) ..................................................................... 32 The unit range consists of two main versions: a heating/cooling
Maintenance and service ................................................................ 32 (EKHBX) version and a heating only (EKHBH) version.
Maintenance activities.............................................................................. 32
Both versions are delivered with an integrated backup heater. The
Troubleshooting ............................................................................... 33 backup heater only serves as a backup in case of malfunctioning of
General guidelines ................................................................................... 33 the outdoor unit.
General symptoms................................................................................... 34
Error codes .............................................................................................. 35 Backup heater
Technical specifications ................................................................... 37 Indoor unit model Backup heater capacity nominal voltage
An optional EKHW* domestic hot water tank with integrated 3 kW Remote thermostat kit (option)
electrical booster heater can be connected to the indoor unit. The An optional room thermostat EKRTW, EKRTWA, or EKRTR can be
domestic hot water tank is available in three sizes: 150, 200 and connected to the indoor unit. Refer to the installation manual of the
300 litre. Refer to the domestic hot water tank installation manual for room thermostat for more information.
further details.
Possible options
Simultaneous operation of compressor, backup heater and
EKBPHT08 EKBPHT08BA
booster heater is NOT possible. Read attentively following
warnings to understand the unit operation. EKHBH/XE008AA Possible Not allowed
EKHBH/XE008BA Possible Possible
This installation manual describes the procedures for handling, The precautions listed here are divided into the following two types.
installing and connecting all EKHBH/X indoor unit models. Both cover very important topics, so be sure to follow them carefully.
NOTE Installation of the ERHQ or ERLQ heat pump outdoor Meanings of DANGER, WARNING, CAUTION and NOTE symbols.
unit is described in the outdoor unit installation DANGER
manual.
Indicates an imminently hazardous situation which, if not
Operation of the indoor unit is described in the indoor avoided, will result in death or serious injury.
unit operation manual.
WARNING
■ Where acidic or alkaline vapour is present. Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 19) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 21).
M M
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
The ON/OFF setting of the heating/cooling operation is done by the Space heating and cooling
room thermostat and cannot be done by the user interface on the
According to the season, the customer will select heating or cooling
indoor unit.
through the user interface on the indoor unit.
Domestic water heating
The outdoor unit (1) will operate in heating mode or cooling mode to
Domestic water heating is as described under "Application 2" on achieve the target leaving water temperature.
page 5. With the unit in heating mode, the 2-way valve (13) is open. Hot water
is provided to both the fan coil units and the floor heating loops.
Application 4 With the unit in cooling mode, the 2-way valve (13) is closed to
prevent cold water running through the floor heating loops (FHL).
Space cooling and heating application without the room thermostat
connected to the indoor unit, but with the heating only room When closing several loops in the system by remotely
thermostat (set heating only) controlling the floor heating and the controlled valves, it might be required to install a by-pass
heating/cooling thermostat (set heating/cooling) controlling the fan valve (9) to avoid the flow switch safety device from being
coil units. Heating is provided through floor heating loops and fan coil activated. See also "Application 2" on page 5.
units. Cooling is provided through the fan coil units only.
Wiring of the 2-way valve (13) is different for a NC (normal
6 9
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.
M M
7 FHL1
FHL2
FHL3
Space heating application by either the Daikin indoor unit or by an EKHB* Boiler
auxiliary boiler connected in the system. The decision whether either EKHB*/auto / Boiler X2M thermostat input
the EKHB* indoor unit or the boiler will operate can be achieved by 1 2 3 4 X Y
A
an auxiliary contact or an EKHB* indoor controlled contact.
K1A K2A
The auxiliary contact can e.g. be an outdoor temperature thermostat, K1A K2A
an electricity tariff contact, a manually operated contact, etc. See N
"Field wiring configuration A" on page 7.
Boiler Boiler thermostat input
The EKHB* indoor unit controlled contact (also called ’permission thermostat input
signal for the auxiliary boiler") is determined by the outdoor A Auxiliary contact (normal closed)
temperature (thermistor located at the outdoor unit). See "Field wiring H Heating demand room thermostat (optional)
configuration B" on page 7.
K1A Auxiliary relay for activation of EKHB* unit (field
Bivalent operation is only possible for space heating operation, not supply)
for the domestic water heating operation. Domestic hot water in such K2A Auxiliary relay for activation of boiler (field supply)
an application is always provided by the domestic hot water tank
which is connected to the Daikin indoor unit. Field wiring configuration B
The auxiliary boiler must be integrated in the piping work and in the EKHB* EKHB* EKRP1HB
field wiring according to the illustrations below. X2M X2M
1 2 3 4 1 2 3 4 KCR
CAUTION X1 X2
K1A K1A
■ Be sure that the boiler and the integration of the boiler
K1A
in the system is in accordance with relevant European
H C Com C Com H X Y
and national regulations.
EKRTR* EKRTW* Boiler
■ Daikin can not be put responsible for incorrect or thermostat input
Operation
■ Configuration A
When the room thermostat requests heating, either the EKHB*
unit or the boiler starts operating, depending on the position of
the auxiliary contact (A).
7 16 15 17 ■ Configuration B
When the room thermostat requests heating, either the EKHB*
unit or the boiler starts operating, depending on the outdoor
temperature (status of "permission signal for the auxiliary
10 11 boiler").
When the permission is given towards the boiler, the space
FHL1 heating operation by the EKHB* unit will be automatically
FHL2 switched off.
FHL3
12 For more details see field setting [C-02~C-04].
17 4
5
6
3
1
3
3
16
7
15
3 14
21
13
2
10 8
9
1 13
10
12 11
1. Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
2. Emergency backup heater
The backup heater consists of an electrical heating element in
the backup heater vessel that will provide heating capacity to the
water circuit in case of malfunction of the outdoor unit.
3. Temperature sensors
Four temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
4. Switch box
The switch box contains the main electronic and electrical parts
of the indoor unit.
5. Heat exchanger
6. Expansion vessel (10 l)
7. User interface
The user interface allows the installer and user to set up, use
and maintain the unit.
8. Refrigerant liquid connection
9. Refrigerant gas connection
10. Shut-off valves (accessory)
The shut-off valves on the water inlet connection and water
outlet connection allow isolation of the indoor unit water circuit
side from the residential water circuit side. This facilitates
draining and filter replacement of the indoor unit.
11. Water inlet connection
12. Water outlet connection
13. Drain and fill valves
6
8
X1M X3M
CAUTION
If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water tank
installation manual.
Unit of measurement: mm
CAUTION
Dimensions of the unit, see figure 3
The weight of the indoor unit is approximately 46 kg. Two
1 Flexible drain hose 5 Refrigerant gas persons are required to mount the unit.
connection
2 Water outlet connection
1 Put the installation pattern (see packing) on the wall and mark
3 Water inlet connection FBSP Female British Standard the fixation positions (2 on top (● T) and 2 at the bottom (● B)).
Pipe
4 Refrigerant liquid Make sure that the marks (2 by 2) are completely level and the
connection
MBSP Male British Standard dimensions of the marks are corresponding according to
Pipe figure 4.
When the unit is not installed level, air might get trapped in the
Required service space, see figure 2 water circuit resulting in malfunctioning of the unit.
Pay special attention to this when installing an EKHBX model to
prevent overflow of the drain pan.
Inspecting, handling and unpacking the unit
2 Drill 4 holes and install 4 plugs (suitable for M10).
■ The indoor unit is packed in a cardboard box, fixed by straps on
a wooden pallet. 3 Put the screws in top plugs and hang the indoor unit on the top
screws.
■ At delivery, the unit must be checked and any damage must be
reported immediately to the carrier claims agent. 4 Put the screws in bottom plugs and fix the screws firmly.
■ Check if all indoor unit accessories (see "Accessories" on
page 3) are enclosed.
■ Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during 1 2 3
transport.
■ The indoor unit weighs approximately 46 kg and should be lifted
by two persons using the two lifting bars provided.
CAUTION
Do not grasp the switch box or piping to lift the unit! Two
lifting bars are provided to lift the unit.
1 4
CAUTION
NOTE Before continuing the installation of the unit, check the
Make sure to position the pressure relief valve hose end in following points:
the drain pan. Failure to do so might lead to water coming
into contact with electrical parts, resulting in electrical ■ The maximum water pressure = 3 bar + static
shocks or short-circuit of the electrical system. pressure of pump.
■ The maximum water temperature is 65°C (safety
device setting).
Refrigerant pipework
■ Two shut-off valves are delivered with the unit. To
facilitate service and maintenance, install one at
For all guidelines, instructions and specifications regarding
the water inlet and one at the water outlet of the
refrigerant pipework between the indoor unit and the outdoor unit,
indoor unit. Mind position of the shut-off valves.
please refer to the outdoor unit installation manual.
Orientation of the integrated drain and fill valves is
The location of the gas pipe and liquid pipe on the indoor unit is important for servicing. See figure 3.
shown under "Main components" on page 10. ■ Drain taps must be provided at all low points of
Refrigerant piping the system to permit complete drainage of the
specifications Indoor unit Outdoor unit circuit during maintenance.
Gas pipe connection 15.9 mm (5/8 inch) 15.9 mm (5/8 inch) Two drain valves integrated in the shut-off valves
are provided to drain the water from the indoor
Liquid pipe connection 6.4 mm (1/4 inch) 6.4 mm (1/4 inch)
unit water system.
■ Make sure to provide a proper drain for the
When connecting the refrigerant pipes, always use two
pressure relief valve to avoid any water coming
wrenches/spanners for tightening or loosening nuts!
into contact with electrical parts.
Failure to do so can result in damaged piping connections
and leaks. ■ Air vents must be provided at all high points of the
system. The vents should be located at points
which are easily accessible for servicing. An
automatic air purge is provided inside the indoor
unit. Check that this air purge valve is not tightened
too much so that automatic release of air in the wa-
ter circuit remains possible.
■ Take care that the components installed in the
field piping can withstand the water pressure and
water temperature.
■ Always use materials which are compatible with
water used in the system and with the materials
used on the indoor unit.
■ Select piping diameter in relation to required
water flow and available ESP of the pump.
■ The minimum required water flow for the indoor
unit operation is 12 l/min. When the water flow is
lower than this minimum value, flow error 7H will
be displayed and the operation of the indoor unit
will be stopped.
freezing.
2 The compressor does not start up after the defrost cycle
because the water temperature is too low.
In both cases the backup heater will operate instead of the 7 FHL1
FHL2
compressor to increase the water temperature.
FHL3
When the water temperature is high enough, the backup heater
stops and the compressor restarts. 1 Outdoor unit 8 By-pass valve (field
supply)
2 Indoor unit
If the heating load is higher than the backup heater
capacity, the water temperature can not increase. In 3 Heat exchanger FHL1..3 Floor heating loop
(field supply)
this case refer to "Re-start at low outdoor ambient 4 Pump
temperatures" on page 22 5 Shut-off valve T1..3 Individual room
thermostat
6 Collector (field (optional)
Repeated forced defrost stops can in some cases supply)
cause severe ice build-up on the outdoor unit. This will M1..3 Individual
7 Shut-off valve motorised valve to
lead to reduced unit performance. control loop FHL1
(field supply)
The minimum required water volume in the system is 20 l.
However, to minimize emergency backup heater operation it is
highly recommended to have a water volume of 40 l. 2 Using the table below, determine if the expansion vessel pre-
pressure requires adjustment.
In most applications this minimum water volume will have a
3 Using the table and instructions below, determine if the total
satisfying result.
water volume in the installation is below the maximum allowed
In critical processes or in rooms with a high heat load water volume.
though, extra water volume might be required.
Installation Water volume
height
difference(a) ≤280 l >280 l
Actions required:
• pre-pressure must be
decreased, calculate according
to "Calculating the pre-
No pre-pressure adjustment pressure of the expansion
≤7 m required. vessel"
• check if the water volume is
lower than maximum allowed
water volume (use graph
below)
Actions required:
• pre-pressure must be
increased, calculate according
to "Calculating the pre-
pressure of the expansion Expansion vessel of the unit
>7 m
vessel" too small for the installation.
• check if the water volume is
lower than maximum allowed
water volume (use graph
below)
(a) Installation height difference: height difference (m) between the highest point of
the water circuit and the indoor unit. If the indoor unit is located at the highest
point of the installation, the installation height is considered 0 m.
CAUTION
Select all cables and wire sizes in accordance with
relevant local and national regulations.
X2M 5 6 7 X2M 5 6 7
1x 230 V
X1M X3M
L1 N M M
NC NO
2 Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Wiring the 3-way valve
1 Using the appropriate cable, connect the valve control cable to
the appropriate terminals as shown on the wiring diagram.
L1 N
Connection of the thermostat cable NOTE Two types of 3-way valves can be connected.
Wiring is different for each type:
Connection of the thermostat cable depends on the application.
■ "Spring return 2-wire" type 3-way valve
See also "Typical application examples" on page 4 and "Room The 3-way valve should be fitted as such that
thermostat installation configuration" on page 21 for more information when the 3-way valve is idle (not activated),
and configuration options on pump operation in combination with a the space heating circuit is selected.
room thermostat.
■ "SPST 3-wire" type 3-way valve
Thermostat requirements The 3-way valve should be fitted as such that
■ Power supply: 230 V AC or battery operated when terminal ports 9 and 10 are electrified,
■ Contact voltage: 230 V. the domestic hot water circuit is selected.
Mounting 1
NOTE The digital controller has to be mounted indoors.
START-UP AND CONFIGURATION
1 Remove the front part of the digital controller. The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
Insert a slotted screwdriver into the slots (1)
user expertise.
in the rear part of the digital controller, and
remove the front part of the digital
It is important that all information in this chapter is read
controller.
1 sequentially by the installer and that the system is
2 Fasten the digital controller on a flat configured as applicable.
surface.
DIP switch settings overview
DIP switch SS2 is located on the switch box PCB (see "Switch box
NOTE Be careful not to distort the shape of the lower part of main components" on page 11) and allows configuration of domestic
the digital controller by over tightening the mounting hot water tank installation, room thermostat connection and pump
screws. operation.
16a
settings.
16
16
1 1
OFF ON
1 2 3 4
DIP
switch
SS2 Description ON OFF
P2 P1 P2 P1
OFF ON OFF ON
NOTE
1 2 3 4 To set the pump speed, refer to "Setting the pump
the indoor unit, toggle switch SS2-3 should be
speed" on page 23.
set to OFF.
Without room thermostat: DIP switch SS2-3 = OFF
■ When the room thermostat is connected to 1 2 3 4
the indoor unit, toggle switch SS2-3 should be When no thermostat is connected to the indoor unit, pump operation
set to ON. will be determined by the leaving water temperature.
To force continuous pump operation when no room thermostat is
■ On the room thermostat, confirm the correct settings (6®02=yes, connected do the following:
6®05=9, 6®06=5) to prevent the pump from repeatedly turning on
- set toggle switch SS2-3 to ON,
and off (i.e. chattering), and thereby impacting the lifetime of
- short-circuit the terminal numbers 1-2-4 on the terminal block
the pump.
in the switch box.
With room thermostat DIP switch: SS2-3 = ON
■ When the room thermostat is connected to the indoor
unit, the heating and cooling schedule timers are When the thermostat is connected to the indoor unit, the pump will
never available. Other schedule timers are not operate continuously whenever there is heating or cooling demand
affected. For more information on the schedule timers, requested by the thermostat.
refer to the operation manual. Dual set point
■ When the room thermostat is connected to the indoor
When dual set point is enabled, the pump operation will be
unit, and the = button or y button is pressed, the
determined depending on the status of the DIP switch SS2-3 and set
centralised control indicator e will flash to indicate
point selection contacts. Refer to the pump operation configurations
that the room thermostat has priority and controls
when the thermostat is connected or not as described above.
on/off operation and change over operation.
The following table summarizes the required configuration and When dual set point is enabled, the "forced continuous
thermostat wiring at the terminal block (X2M: 1, 2, 3, 4) in the switch pump operation" is not possible. When SS2-3 is ON while
box. Pump operation is listed in the third column. The three last SP1 and SP2 are both closed, the pump operation will be
columns indicate whether the following functionality is available on the same operation as "with room thermostat" and the
the user interface (UI) or handled by the thermostat (T): second set point will be the applicable set point. Refer to
• space heating or cooling on/off (y) "Dual set point control" on page 26.
• heating/cooling changeover (=)
The following table summarizes the required configuration and wiring
• heating and cooling schedule timers (pr)
at the terminal block (X2M: 1, 2, 4) in the switch box. Pump operation
Pump is listed in the third column. The three last columns indicate whether
Thermostat Configuration operation y = pr the following functionality is available on the user interface (UI) or
No thermostat • SS2-3 = OFF determined by UI UI UI handled by the set point selection contacts SP1 and SP2:
• wiring: (non) leaving water • space heating or cooling on/off (y)
temperature(a) • heating/cooling changeover (=)
X2M
• heating and cooling schedule timers (pr)
1 2 3 4
Dual set point
• SS2-3 = ON on when space UI UI UI
• wiring: heating or Configuration Pump operation y = pr
cooling is on • [7-02]=1 determined by UI UI UI
X2M (y) • SS2-3 = OFF leaving water
1 2 3 4 • wiring: temperature(a)
X2M
Heating only • SS2-3 = ON on when T — — 1 2 3 4
thermostat • wiring: (see heating
installation SP2 SP1
request by
manual of the room
room • [7-02]=1 on when main or/and SP2/SP1 UI —
thermostat • SS2-3 = ON
thermostat kit) sub set point is
• wiring: requested
Thermostat with • SS2-3 = ON on when T T —
heating/cooling • wiring: (see heating X2M
switch installation request or
manual of the cooling request 1 2 3 4
room by room SP2 SP1
thermostat kit) thermostat
(a) The pump will stop when space heating/cooling is turned off or when the water
SP1 = First set point contact
reaches the desired water temperature as set on the user interface. With space SP2 = Second set point contact
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature. (a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.
OFF ON
When no domestic hot water tank is 1 2 3 4 specifications" on page 37. Make sure that neither a fuse nor a
installed, toggle switch SS2-2 should be set to protection device has been bypassed.
OFF (default).
3 Backup heater circuit breaker F1B/F3B
■ When a domestic hot water tank is installed, Do not forget to turn on the backup heater circuit breaker F2B in
OFF ON
1 2 3 4
toggle switch SS2-2 should be set to ON. the switchbox (F1B/F3B depends on the backup heater type).
Refer to the wiring diagram.
During initial start-up and when water temperature is low, it is 6 Internal wiring
important that the water is heated gradually. Failure to do so may Visually check the switch box on loose connections or damaged
result in cracking of concrete floors due to rapid temperature change. electrical components.
Please contact the responsible cast concrete building contractor for
7 Fixation
further details.
Check that the unit is properly fixed, to avoid abnormal noises
To do so, the lowest leaving water set temperature can be decreased and vibrations when starting up the unit.
to a value between 15°C and 25°C by adjusting the field setting
[9-01] (heating set point lower limit). Refer to "Field settings" on 8 Damaged equipment
page 23. Check the inside of the unit on damaged components or
squeezed pipes.
If leaving water temperature is set between 15°C and
25°C, heating is performed by the backup heater only. 9 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
Re-start at low outdoor ambient temperatures refrigerant leak, call your local dealer.
For floor heating applications: start up circuit by circuit using a NOTE Operating the system with the backup heater not
(automatic) by-pass valve guaranteeing that water returning to the completely filled with water will damage the backup
unit is more than 20°C. heater!
13 Shut-off valves
Pre-operation checks
Make sure that the shut-off valves are correctly installed and
fully open.
Checks before initial start-up
NOTE Operating the system with closed valves will damage
DANGER the pump!
Switch off all relevant power supply before making any
connections.
Powering up the indoor unit
After the installation of the unit, check the following before switching
on the circuit breaker: When power supply to the indoor unit is turned on, "88" is displayed
1 Field wiring on the user interface during its initialisation, which might take up to
30 seconds. During this process the user interface cannot be
Make sure that the field wiring between local supply panel and
operated.
indoor unit, outdoor unit and indoor unit, indoor unit and valves
(when applicable), indoor unit and room thermostat (when
applicable), and indoor unit and domestic hot water tank has
been carried out according to the instructions described in the
chapter "Field wiring" on page 17, according to the wiring
diagrams and according to European and national regulations.
50
NOTE Changes made to a specific field setting are only
stored when the pr button is pressed. Navigating to a
ESP [kPa]
Detailed description
Field settings
[0] User permission level
The indoor unit shall be configured by the installer to match the
If required, certain user interface buttons can be made unavailable for
installation environment (outdoor climate, installed options, etc.) and
the user.
user demand. Thereto, a number of so called field settings are
available. These field settings are accessible and programmable Three permission levels are defined (see the table below). Switching
through the user interface on the indoor unit. between level 1 and level 2/3 is done by simultaneously pressing
Each field setting is assigned a 3-digit number or code, for example buttons pfi and pfj immediately followed by
[1-03], which is indicated on the user interface display. The first digit simultaneously pressing buttons s and ba, and keeping all 4
[1] indicates the 'first code' or field setting group. The second and buttons pressed for at least 5 seconds (in normal mode). Note that no
third digit [03] together indicate the 'second code'. indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
A list of all field settings and default values is given under "Field by the field setting [0-00].
settings table" on page 30. In this same list, we provided for 2
columns to register the date and value of altered field settings at Permission level
variance with the default value. Button 1 2 3
A detailed description of each field setting is given under "Detailed Quiet mode button s operable — —
description" on page 23. Weather dependent
set point button
ba operable — —
Procedure Schedule timer
enable/disable button
pr operable operable —
To change one or more field settings, proceed as follows.
Programming button < operable — —
Time adjust buttons pf
i
operable — —
pf
j
Inspection/test
operation button
z operable — —
3
1
2
Tt
The field setting [4-03]=2 or 3 is not relevant for this When setting [4-03]=0 or 2 special attention to setting
system. [6-00] is recommended. A good balance between the
required domestic hot water temperature and heat pump
■ [4-03]=1, then booster heater heater operation is only ON temperature (THP ON) is a must.
determined by booster heater OFF temperature (T BH OFF),
booster heater ON temperature (TBH ON) and/or schedule
timer. Refer to setting "[7-00]" on page 26 and "[7-01]" on
page 26.
TDHW ■ [7-04] Second set point cooling: specifies the second set
point temperature in cooling operation.
TBH OFF 73 [7-00] [7-01]
TBH ON 71 NOTE ■ The first set point heating/cooling is the set point
TU 70 selected on the user interface.
60 - In heating mode the first set point can be a
THP MAX 50 [6-01] fixed value or weather dependent.
THP OFF 48
[6-00] - In cooling mode the first set point is always a
THP ON 41
fixed value.
40
■ The second set point heating [7-03] should be
30 linked to the heat emitters which requires the
highest set point in heating mode. Example: fan
20 TU = 70°C coil unit.
[7-00] = 3°C
HP BH HP ■ The second set point cooling [7-04] should be
10 [6-01] = 2°C
[6-00] = 7°C
linked to the heat emitters which requires the
lowest set point in cooling mode. Example: fain
5
t
coil unit.
BH Booster heater ■ The actual second set point heating value
HP Heat pump. If heating up time by the heat pump takes too
depends on the selected value of setting [7-03].
long, auxiliary heating by the booster heater can take place - In case [7-03]=1~24, the actual second set
TBH OFF Booster heater OFF temperature (TU + [7-00]) point will be first set point heating increased
with [7-03] (the maximum is 55°C).
TBH ON Booster heater ON temperature (TBH OFF – [7-01])
In this way the second set point heating is
THP MAX Maximum heat pump temperature at sensor in domestic hot linked to the first set point heating.
water tank
- In case [7-03]=25~55, the actual second set
THP OFF Heat pump OFF temperature (THP MAX – [6-01])
point heating is equal to [7-03].
THP ON Heat pump ON temperature (THP OFF – [6-00])
■ The selection of second set point or first set point
TDHW Domestic hot water temperature
is determined by the terminals (X2M: 1, 2, 4).
TU User set point temperature (as set on the user interface) The second set point has always priority on the
t Time first set point.
Be aware that the domestic hot water temperature will be 1 2 3 4 SP2 Second set point
contact
automatically increased (always) with the value selected in SP2 SP1
field setting [7-00] compare to the user set point for
domestic hot water (TU). Refer to field setting [7-00] and
the operation manual to select preferable set point. When dual set point control is enabled, heating/cooling
selection always has to be done on the user interface.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field NOTE It is the responsibility of the installer to make sure no
supply) shall be installed at the hot water outlet connection
unwanted situations can occur.
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap It is very important that the water temperature to the
never rise above a set maximum value. This maximum floor heating loops never becomes too high in heating
allowable hot water temperature shall be selected mode or never too cold in cooling mode. Failure to
according to local and national regulations. observe this rule can result in construction damage or
discomfort. For example in cooling mode condensation
If the booster heater operation is limited ([4-03]=0), then on the floor can occur when water towards the floor
set point of field setting parameter [7-00] has only meaning heating loops is too cold (dew point).
for powerful domestic water heating.
t t
Applies only to installations with a domestic hot water tank.
[8-01]+ [8-01]+
The 'domestic water heating mode timer' field settings defines the [8-04] [8-04]
minimum and maximum domestic water heating times, minimum time
between two domestic water heating cycles by heat pump, and [8-02] [8-02]
booster heater delay time.
[8-01] [8-01]
■ [8-00] Minimum running time: specifies the minimum time
period during which heat pump domestic water heating mode 0 0
should be activated, even when the target domestic hot water [5-03] [4-02] TA [F-01] 35°C TA
temperature for heat pump (THP OFF) has already been
t Time
reached.
TA Ambient (outdoor) temperature
■ [8-01] Maximum running time: specifies the maximum time
period during which heat pump domestic water heating mode anti-recycle time
can be activated, even when the target domestic hot water maximum running time
temperature for heat pump (THP OFF) has not yet been
reached.
The actual maximum running time will automatically variate The full advantage of [8-04] will be applicable if setting
between [8-01] and [8-01]+[8-04] depending on the outdoor [4-03] is not 1.
temperature. See figure in chapter "[8-04]" on page 27.
[9] Cooling and heating set point ranges
Note that when the unit is configured to work with a The purpose of this field setting is to prevent the user from selecting
room thermostat (refer to "Room thermostat a wrong (i.e., too hot or too cold) leaving water temperature. Thereto
installation configuration" on page 21), the the heating temperature set point range and the cooling temperature
maximum running timer will only be taken into set point range available to the user can be configured.
account when there is a request for space cooling
or space heating. When there is no request for CAUTION
room cooling or room heating, domestic water
■ In case of a floor heating application, it is important to
heating by the heat pump will continue until the
limit the maximum leaving water temperature at
'heat pump OFF temperature' (see field settings [6]
heating operation according to the specifications of
on page 25) is reached. When no room thermostat
the floor heating installation.
is installed, the timer is always taken into account.
■ In case of a floor cooling application, it is important to
■ [8-02] Anti-recycling time: specifies the minimum required limit the minimum leaving water temperature at
interval between two heat pump domestic water heating cooling operation (field setting of parameter [9-03]) to
mode cycles. 16~18°C to prevent condensation on the floor.
The actual anti-recycling time will automatically variate
between [8-02] and 0 depending on the outdoor temperature. ■ [9-00] Heating set point upper limit: maximum leaving water
See figure in chapter "[8-04]" on page 27. temperature for heating operation.
■ [9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.
1
■ [9-02] Cooling set point upper limit: maximum leaving water
0 temperature for cooling operation.
■ [9-03] Cooling set point lower limit: minimum leaving water
1 temperature for cooling operation.
■ [9-04] Overshoot setting: defines how much the water
0
temperature may rise above the set point before the
[8-00] compressor stops. This function is only applicable in heating
mode.
t
[8-01] [8-02]
1 Heat pump domestic water heating mode
(1 = active, 0 = not active)
2 Hot water request for heat pump (1 = request, 0 = no request)
t Time
X1 X2 X3 X4
unit.
No power supply
[C-01] Alarm No alarm to unit OFF ON
Bivalent operation
X1M
Applies only to installations with an auxiliary boiler (alternating
operation, parallel connected). The purpose of this function is to
determine —based on the outdoor temperature— which heating
source can/will provide the space heating, either the Daikin indoor YC Y1 Y2 Y3 Y4
unit or an auxiliary boiler.
The field setting "bivalent operation" apply only the indoor unit space
[D] Restricted power supply condition mode/Local shift value
heating operation and the permission signal for the auxiliary boiler.
weather dependent
When the "bivalent operation" function is enabled, the indoor unit will
[D-02] is set to 1 by default: The restricted power supply condition
stop automatically in space heating operation when the outdoor
mode is enabled. Do not change this value.
temperature drops below "bivalent ON temperature" and the
permission signal for the auxiliary boiler becomes active. Local shift value weather dependent
When the bivalent operation function is disabled, the space heating The local shift value weather dependent field setting is only relevant
by indoor unit is possible at all outdoor temperatures (see operation in case weather dependent set point (see field setting "[1] Weather
ranges) and permission signal for auxiliary boiler is always dependent set point (heating operation only)" on page 24) is
disactivated. selected.
■ [C-02] Bivalent operation status: defines whether bivalent ■ [D-03] Local shift value weather dependent: determines the
operation is enabled (1) or disabled (0). shift value of the weather dependent set point around
outdoor temperature of 0°C.
■ [C-03] Bivalent ON temperature: defines the outdoor
temperature below which the permission signal for the Tt
auxiliary boiler will be active (closed, KCR on EKRP1HB) and
space heating by indoor unit will be stopped. [1-02]
■ [C-04] Bivalent hysteresis: defines the temperature difference
local shift value
between bivalent ON temperature and bivalent OFF
temperature. range
[1-03]
Permission signal X1–X2 (EKRP1HB)
closed
[1-00] 0°C [1-01] TA
[C-04]
open Tt Target water temperature
TA TA Outdoor temperature
[C-03]
range Range
TA Outdoor temperature
local shift Local shift value
value
CAUTION
[1-00], [1-01], Applicable field setting of the weather dependent set
Make sure to observe all rules mentioned in [1-02], [1-03] point [1]
application 5 when bivalent operation function is
enabled.
Outdoor temperature range
Daikin shall not be held liable for any damage [D-03] (TA) Local shift value
resulting from failure to observe this rule. 0 — —
1 2
–2°C~2°C
2 4
3 2
–4°C~4°C
4 4
X1 X2 X3 X4
again only.
TA Outdoor temperature
CAUTION
The bottom plate heater is controlled via X14A. Make sure
[F-04] is correctly set.
2 Disinfection function
3 Auto restart
00 Start 2 2~20 1 °C
01 Stop 2 0~10 1 °C
F Option setup
The installer is obliged to verify correct operation of the indoor and In order to ensure optimal availability of the unit, a number of checks
outdoor unit after installation. and inspections on the unit and the field wiring have to be carried out
at regular intervals.
This maintenance should be carried out by your local technician.
Final check
To execute the maintenance activities as mentioned below, it is only
Before switching on the unit, read following recommendations: required to remove the indoor unit cover. See "Opening the indoor
■ When the complete installation and all necessary settings have unit" on page 9.
been carried out, close all front panels of the unit and refit the
indoor unit cover.
Maintenance activities
■ The service panel of the switch box may only be opened by a
licensed electrician for maintenance purposes.
DANGER: ELECTRIC SHOCK
Test run operation (manual)
■ Before carrying out any maintenance or repair activity,
If required, the installer can perform a manual test run operation at always switch off the circuit breaker on the supply
any time to check correct operation of cooling, heating and domestic panel, remove the fuses or open the protection
water heating. devices of the unit.
■ Make sure that before starting any maintenance or
Procedure repair activity, also the power supply to the outdoor
1 Push the z button 4 times so the t icon will be displayed. unit is switched off.
■ Do not touch live parts for 10 minutes after the power
2 Depending on the indoor unit model, heating operation, cooling
supply is turned off because of high voltage risk.
operation or both must be tested as follows (when no action is
performed, the user interface will return to normal mode after 10 ■ The heater of the compressor may operate even in
seconds or by pressing the z button once): stop mode.
• To test the heating operation push the h/c button so the h ■ Please note that some sections of the electric
icon is displayed. To start the test run operation press the component box are hot.
y button. ■ Make sure you do not touch a conductive section.
• To test the cooling operation push the h/c button so the c ■ Do not rinse the indoor unit. This may cause electric
icon is displayed. To start the test run operation press the shocks or fire.
y button.
• To test the domestic water heating operation push the v ■ When service panels are removed, live parts can be
button. The test run operation will start without pressing the easily touched by accident.
y button. Never leave the unit unattended during installation or
servicing when service panel is removed.
3 The test run operation will end automatically after 30 minutes or
when reaching the set temperature. The test run operation can
Play it safe!
be stopped manually by pressing the z button once. If there are
misconnections or malfunctions, an error code will be displayed Touch a metal part by hand (such as the stop valve) in
on the user interface. Otherwise, the user interface will return to order to eliminate static electricity and to protect the PCB
normal operation. before performing service.
Symptom 1: The unit is turned on (y LED is lit) but the unit is not Dirt is blocking the water pressure Check for correct operation of the
heating or cooling as expected relief valve outlet. pressure relief valve by turning the
red knob on the valve counter
POSSIBLE CAUSES CORRECTIVE ACTION
clockwise:
• If you do not hear a clacking sound,
The temperature setting is not Check the controller set point. contact your local dealer.
correct. • In case the water keeps running out
of the unit, close both the water inlet
The water flow is too low. • Check that all shut off valves of the and outlet shut-off valves first and
water circuit are completely open. then contact your local dealer.
• Check if the water filter needs
cleaning.
n" when pressing
Symptom 6: The user interface displays "n
• Make sure there is no air in the
system (purge air). certain buttons
• Check on the manometer that there
is sufficient water pressure. The POSSIBLE CAUSES CORRECTIVE ACTION
water pressure must be >1 bar
(water is cold) The current permission level is set to Change the "user permission level"
• Check that the pump speed setting is a level that prevents using the field setting [0-00], see "Field
on the highest speed. pressed button. settings" on page 23.
• Make sure that the expansion vessel
is not broken. Symptom 7: Space heating capacity shortage at low outdoor
• Check that the resistance in the temperatures
water circuit is not too high for the
pump (refer to "Setting the pump
speed" on page 23). POSSIBLE CAUSES CORRECTIVE ACTION
The water volume in the installation Make sure that the water volume in Backup heater operation is not Check that the "backup heater
is too low. the installation is above the minimum activated. operation status" field setting [4-00]
required value (refer to "Checking is turned on, see "Field settings" on
the water volume and expansion page 23.
vessel pre-pressure" on page 15). Check whether or not the thermal
protector of the backup heater has
been activated (refer to Main
Symptom 2: The unit is turned on but the compressor is not starting
components, "Backup heater
(space heating or domestic water heating)
thermal protector" on page 11 for
location of the reset button).
POSSIBLE CAUSES CORRECTIVE ACTION Check whether or not the thermal
The unit must start up out of its In case of low water temperature, the fuse of the backup heater is blown
operation range (the water system utilizes the backup heater to (refer to "Main components",
temperature is too low). reach the minimum water "Backup heater thermal fuse" on
temperature first (15°C). page 11 for location of the reset
• Check that the backup heater power button).
supply is correct.
• Check that the backup heater Symptom 8: Unexpected backup heater operation
thermal fuse is closed.
• Check that the backup heater POSSIBLE CAUSES CORRECTIVE ACTION
thermal protector is not activated.
• Check that the backup heater Entering water temperature is too Increase the water flow.
contactors are not broken. low and leaving water temperature
>25°C.
Symptom 3: Pump is making noise (cavitation)
Too frequent use of the backup The water volume in the cicuit is too
heater during heating operation or low.
POSSIBLE CAUSES CORRECTIVE ACTION domestic water heating.
There is air in the system. Purge air.
Water pressure at pump inlet is too • Check on the manometer that there
low. is sufficient water pressure. The
water pressure must be >1 bar
(water is cold).
• Check that the manometer is not
broken.
• Check that the expansion vessel is
not broken.
• Check that the setting of the pre-
pressure of the expansion vessel is
correct (refer to "Setting the pre-
pressure of the expansion vessel" on
page 16).
When a safety device is activated, the user interface LED will be AA Backup heater thermal protector Reset the thermal protector by
is open pressing the reset button (refer
flashing, and an error code will be displayed. to "Main components" on
A list of all errors and corrective actions can be found in the table page 10 for location of the reset
button)
below.
Check the reset button of the Contact your local dealer.
Reset the safety by turning the unit OFF and back ON. thermal protector.
If both the thermal protector and
Instruction to turn the unit OFF the controller are reset, but the
AA error code persists, the
User interface mode Domestic water Push the y Push the
(heating/cooling =) heating mode (w) button v button backup heater thermal fuse has
blown.
ON ON 1 time 1 time
AC Booster heater thermal protector Reset the thermal protector
ON OFF 1 time — is open (applies only to
installations with a domestic hot
OFF ON — 1 time
water tank)
OFF OFF — —
Secondary thermal protector is Reset the thermal protector
open (applies only to units with a
In case this procedure for resetting the safety is not successful, EKHWSU domestic hot water
contact your local dealer. tank installed)
C0 Flow switch failure (flow switch Check that the flow switch is not
Error
code Failure cause Corrective action remains closed while pump is clogged with dirt.
stopped)
80 Inlet water temperature Contact your local dealer.
thermistor failure (inlet water C4 Heat exchanger thermistor Contact your local dealer.
thermistor broken) failure (heat exchanger
temperature sensor broken)
81 Outlet water temperature Contact your local dealer.
thermistor failure (outlet water E1 Outdoor unit PCB defective Contact your local dealer.
temperature sensor broken) E3 Abnormal high pressure Check that the unit is operating
89 Water heat exchanger freeze-up Refer to error code 7H. within its operating range (refer
failure (due to water flow too low) to "Technical specifications" on
page 37).
Water heat exchanger freeze-up Contact your local dealer. Contact your local dealer.
failure (due to refrigerant
shortage) E4 Actuation of low pressure sensor Check that the unit is operating
within its operating range (refer
7H Flow failure (water flow too low • Check that all shut off valves of to "Technical specifications" on
or no water flow at all, minimum the water circuit are completely page 37).
required water flow is 12 l/min) open. Contact your local dealer.
• Check if the water filter needs
cleaning. E5 Overload activation of Check that the unit is operating
• Check that the unit is operating compressor within its operating range (refer
within its operating range (refer to "Technical specifications" on
to "Technical specifications" on page 37).
page 37). Contact your local dealer.
• Also refer to "Charging water" on
page 16. E7 Fan lock failure (fan is locked) Check if the fan is not obstructed
• Make sure there is no air in the by dirt. If the fan is not
system (purge air). obstructed, contact your local
• Check on the manometer that dealer.
there is sufficient water
pressure. The water pressure E9 Malfunction of electronic Contact your local dealer.
must be >1 bar (water is cold). expansion valve
• Check that the pump speed
EC Domestic hot water temperature • Check that the contactor of the
setting is on the highest speed. electric booster heater is not
too high (>89°C)
• Make sure that the expansion short circuited.
vessel is not broken. • Check that the domestic hot
• Check that the resistance in the water thermistor is giving the
water circuit is not too high for correct read out.
the pump (refer to "Setting the
pump speed" on page 23). F3 Too high discharge temperature Clean the outdoor coil. If the coil
• If this error occurs at defrost (e.g. due to outdoor coil is clean, contact your local
operation (during space heating blockage) dealer.
or domestic water heating),
make sure that the backup H3 Malfunctioning HPS system Contact your local dealer.
heater power supply is wired H9 Outdoor temperature thermistor Contact your local dealer.
correctly and that fuses are not
failure (outdoor thermistor is
blown.
broken)
• If EKHWSU version of domestic
hot water tank is installed, check HC Domestic hot water tank Contact your local dealer.
if the setting of the additional thermistor failure
thermostat in the tank switch box
is correct (≥50°C). J1 Malfunction of pressure sensor Contact your local dealer.
8H Outlet water temperature of • Check that the contactor of the J3 Discharge pipe thermistor failure Contact your local dealer.
indoor unit too high (>65°C) electric backup heater is not J5 Suction pipe outdoor unit Contact your local dealer.
short circuited. thermistor failure
• Check that the outlet water
thermistor is giving the correct J6 Aircoil thermistor frost detection Contact your local dealer.
read out. failure
A1 Indoor unit PCB defective Contact your local dealer. J7 Aircoil thermistor mean Contact your local dealer.
temperature failure
A5 Too low (during cooling Contact your local dealer.
operation) or too high (during J8 Liquid pipe outdoor unit Contact your local dealer.
heating operation) refrigerant thermistor failure
temperature (measured by R3T)
L4 Electric component failure Contact your local dealer.
L5 Electric component failure Contact your local dealer.
L8 Electric component failure Contact your local dealer.
L9 Electric component failure Contact your local dealer.
General
Electrical specifications