Apparatus:
1. Hydrometer(Temperature
Compensating) -1No
2. Distilledwater&DilutedSulphuric
acid ( H2SO4) -1No
3. DigitalMultimeter/D.C.Voltmeter
-1No
4. Battery Charger
-1No
5. ElectricalToolKit/SpannerSet
-1No
6. Safety Glooves
-1No
7. SmoothBrushes
-1No
Theory:
Plates : Positive plates shall be made of flat pasted type using lead-cadmium antimony alloy for
durability, high corrosion resistant, maintenance free, long life both in cyclic as well as in float
applications. Negative platesshall be heavy duty, durable flat plate using lead calcium alloy pasted
box grid. Negative plates shall be designed to match the life of positive plates and combination of
negative and positive plates shall ensure long life, durability and trouble free operation of battery.
PLC (programmable logic control) operated equipment should be deployed for preparation of
paste to ensure consistency in paste quality. Conventional / manual type of paste preparation is
not allowed.
CONTAINER AND LID : The containers and lids shall be made of a special grade polypropylene
copolymer plastic material. They shall be sufficiently robust and not liable to deformation under
internal operating pressures and within the temperature range naturally encountered, leak proof,
non-absorbent and resistant to the acid with low water vapour permeability
Separators :The separators shall be of synthetic material conformingto the latest edition of IS-
6071-1986. These shall permit freeflow of electrolyteand would notbeaffectedby thechemical
reactioninsidethe cell and shall last for indefinite time. The internal resistance factor of the
separators shall assure high discharg characteristics under all operating conditions. Proper
arrangement to keep end plates in position shall be furnished by the bidder along with his offer.
Electrolyte : The electrolyte shall be prepared from the battery grade Sulphuric acid conforming
to IS-266- 1993 and shall have a specific gravity of 1.2 at 270 C. The Sulphuric acid of battery
grade shall be colorless liquid.The concentrated Sulphuric acidondilution with an equal volumeof
distilled water shall befree from suspended matter and other visible impurities.
Plate group bar with terminals : The plate group bar with terminals shall conform to IS-1652-
1991. The positive and negative terminals shall be clearly marked for easy identification. The legs
of the plates of like polarity shall be connected to the load, turned to a horizontal group bar having
an upstanding terminal post adopted for connection to the external circuit. The group bars shall
be sufficiently strong to hold the platesin position. Buffers/spring: Suitable buffers / springs shall
be provided in the cells to keep the end plates in position. These shall have adequate length and
strength.
Cell lids : Lids used with sealed or closed type cells shall be of glass, plastic or ebonite and shall
beprovided with vent plugs. Terminalpost shall be suitablysealed atthe lid to prevent escape of
acidspray, by means of rubber grommets, sealing compound or other suitable device. The positive
and negative terminal posts shall be clearly and indelibly marked for easy identification.
Water :- Water used for preparation of electrolyte and also to bring the level of electrolyte to
approximately correct height duringoperation/testingshall conformtorelevantstandards.
Venting device : The venting device shall be anti splash type and shall allow gases to escape
freely but shall effectively prevent acid particles or spray from coming out. There shall be two
vent holes, one serving as a guide for acid level indicator for checking the electrolyte level and
other to permit drawingof electrolyte samples, servicing, checking of specific gravity etc.
Marking : Acid level line shall be permanently and indelibly marked around on all the containers.
The following information shall be indelibly marked on the outside surface of each cell : [i]
Manufacturer’s name, type and trade mark. [ii] Nominal voltage. [iii] AH capacity at 10 hours rate
with specified end cell voltage. [iv] Cell number. [v] Upper and lower electrolyte level in case of
transparent containers. [vi]Type of positive plate. [vii] Type of container. [viii]Date of
manufacture [ month and year] or [week and year].
CONNECTORS: Bars tinned copper lead connectors shall be employed for Inter-cell and interrow,
inter-tier connections. However, the tee-off connection from the battery unit shall be made with
acid resisting cables of suitable size. A suitable terminal box along with acid-resisting cable shall
be provided by the Contractor for this purpose. The connectors shall preferably be of bolted type
and the bolts and nuts shall be of similar material as that of connectors and shall be provided with
corrosion resisting lead coating. The connectors shall be of sufficient cross-section to withstand all
the working conditions including one minute discharge rate as well as short circuit conditions. [a]
Lead coated connection hardware such as bolts, nuts etc. 5% extra, or any other connector
suitable for VRLA type Battery. [b] Ampere-hour Meter [10 hour discharge rate] of 100 –120 AH
range-1 no. [c] Any other accessories, not specified but required for installation, satisfactory
operation and maintenance of batteries for a periodof 5 [five] years.
Procedure:
9. Remove the caps of the cells on the battery using the screw driver
10. Inspect for cracks or other damage at the parts of thebattery
11. Replacethedamagedorbuckledplatesandseparatorsfromthebattery.
12. Placeallthepartsatrightpositioninsidethebattery.
13. TightentheConnectionswithscrewdrivermeantforit.
Charged SpecificGravity
100% 1.265-1.275
75% 1.225-1.235
50% 1.190-1.200
25% 1.155-1.165
0% 1.120-1.130
ChargingtheBattery:
1.Turn the charger off before attaching,rocking or removing the terminal clamps