Professional Documents
Culture Documents
IB131009EN
Instruction Book
Page 3
WARNING WARNING
Eaton Corporation
Power Components Division
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding his particular installation, operation or maintenance of particular equipment,
contact an Eaton representative.
IB131009EN
Instruction Book
Page 4
TABLE OF CONTENTS
PAGE
SECTION 1 INTRODUCTION
SECTION 4 INSTALLATION
IB131009EN
Instruction Book
Page 5
FIGURES
1-1 Type W-VACR 630A Breaker Element Only Outline Dimensions (millimeters) & Weights (Kilograms) .... 3
1-2 Type W-VACR 630A Breaker Element Only Outline Dimensions (millimeters) & Weights (Kilograms) .... 4
1-3 Type W-VACR 800/1250A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) ....... 5
1-4 Type W-VACR 800/1250A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) ....... 6
1-5 Type W-VACR 800/1250A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) ....... 7
1-6 Type W-VACR 2000A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) .............. 8
1-7 Type W-VACR 2500A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) .............. 9
1-8 Type W-VAC Breaker Element Only Outline Dimensions (millimeters) and Weights (Kilograms) .......... 10
1-9 Outline and Dimensions (mm) Type W-VAC Breaker Element with Carriage
Assembly and Cradle Assembly ........................................................................................................................ 11
1-10 Outline and Dimensions (mm) Type W-VAC 3150 Breaker with Carriage Assembly.............................. 12
IB131009EN
Instruction Book
Page 6
4-1 Type W-VAC Breaker Manual Operation (Single Tier Breaker Shown) .................................................. 23
TABLES
1.1 Type W-VAC and W-VACW Vacuum Circuit Breaker Ratings .................................................................... 1
1.2 Type W-VACR Vacuum Circuit Breaker Ratings ......................................................................................... 2
IB131009EN
Instruction Book
Page 1
SECTION 1: INTRODUCTION
WARNING
The purpose of this book is to provide instructions for
unpacking, storage, installation, operation and mainte- SATISFACTORY PERFORMANCE OF THESE
nance of Types W-VAC, W-VACR, and W-VACW BREAKERS IS CONTINGENT UP-ON PROPER
Vacuum Circuit Breakers. They are a horizontal drawout APPLICATION, CORRECT INSTALLATION AND
type removable interrupting element design, unless ADEQUATE MAINTENANCE. THIS INSTRUCTION
there is an “R” in the designation.The “R” as in W-VACR BOOK MUST BE CAREFULLY READ AND FOL-
indicates a fixed breaker configuration. They were LOWED IN ORDER TO OBTAIN OPTIMUM PERFOR-
designed specifically to IEC 56 Standards for reliable MANCE FOR LONG USEFUL LIFE OF THE CIRCUIT
performance. All types can be applied in single tier or BREAKERS.
double tier switchgear applications, with the basic
breaker element applicable to retrofitting. Reliable con- TYPES W-VAC, W-VACR AND W-VACW BREAKERS
trol and protection are achieved though the use of the ARE PROTECTIVE DEVICES, AS SUCH, THEY ARE
W-VAC family of breakers. MAXIMUM RATED DEVICES. THEREFORE, THEY
SHOULD NOT UNDER ANY CIRCUMSTANCES BE
1-1 W-VAC, W-VACR AND W-VACW RATINGS APPLIED OUTSIDE THEIR NAMEPLATE RATINGS.
Table 1.1 Type W-VAC and W-VACW Vacuum Circuit Breaker Ratings
Circuit Rated Frequency Rated Short Circuit Rated Insulation Level Rated Nominal Current
Breaker Voltage Breaking Current Lighting Power Short
Type at & Short Circuit Pulse Frequency Circuit
50-60HZ Duration Withstand Withstand Making
Voltage Voltage Current
kV Hz kA Sec kV kV kA (Peak) Amperes
36W-VAC25 3.6 50/60 25 3 40 10 63 630, 1250, 2000,3150
72W-VAC16 7.2 50/60 16 3 60 20 40 630, 800, 1250
72W-VAC20 7.2 50/60 20 3 60 20 50 630, 800, 1250, 1600
72W-VAC25 7.2 50/60 25 3 60 20 63 630, 800, 1250, 1600, 2000,3150
72W-VAC32 7.2 50/60 31.5 3 60 20 79 1250, 2000
72W-VAC40 7.2 50/60 40 3 60 20 100 3150
120W-VAC16 12 50/60 16 3 75 28 40 630, 800, 1250
120W-VAC20 12 50/60 20 3 75 28 50 630, 800, 1250, 1600
120W-VAC25 12 50/60 25 3 75 28 63 630, 800, 1250, 1600, 2000,3150
120W-VAC32 12 50/60 31.5 3 75 28 79 1250, 2000
120W-VAC40 12 50/60 40 3 75 28 100 1250, 2000,3150
120W-VAC50 12 50/60 50 3 75 28 125 3150
150W-VAC16 15 50/60 16 3 95 36 40 630, 800, 1250
150W-VAC20 15 50/60 20 3 95 36 50 630, 800, 1250, 1600
150W-VAC25 15 50/60 25 3 95 36 63 630, 800, 1250, 1600, 2000,3150
150W-VAC32 15 50/60 31.5 3 95 36 79 1250, 2000
150W-VAC40 15 50/60 40 3 95 36 100 3150
150W-VAC50 15 50/60 50 3 95 36 125 3150
175W-VAC16 17.5 50/60 16 3 95 38 40 630, 800, 1250
175W-VAC20 17.5 50/60 20 3 95 38 50 630, 800, 1250, 1600
175W-VAC25 17.5 50/60 25 3 95 38 63 630, 800, 1250, 1600, 2000,3150
175W-VAC32 17.5 50/60 31.5 3 95 38 79 630, 800, 1250, 1600
175W-VAC40 17.5 50/60 40 3 95 38 100 3150
120W-VACW16 12 50/60 16 3 75 42 40 630, 800, 1250
120W-VACW20 12 50/60 20 3 75 42 50 630, 800, 1250, 1600
120W-VACW25 12 50/60 25 3 75 42 63 630, 800, 1250, 1600, 2000
120W-VACW32 12 50/60 31.5 3 75 42 79 1250, 1600, 2000
120W-VACW40 12 50/60 40 3 75 42 100 1250, 2000
150W-VACW16 15 50/60 16 3 95 42 40 630, 800, 1250
150W-VACW20 15 50/60 20 3 95 42 50 630, 800, 1250, 1600
150W-VACW25 15 50/60 25 3 95 42 63 630, 800, 1250, 1600, 2000
150W-VACW32 15 50/60 31.5 3 95 42 79 1250, 2000
150W-VACW40 15 50/60 40 3 95 42 100 1250, 2000
IB131009EN
Instruction Book
Page 2
Circuit Rated Frequency Rated Short Circuit Rated Insulation Level Rated Nominal Current
Breaker Voltage Breaking Current Lighting Power Short
Type at & Short Circuit Pulse Frequency Circuit
50-60HZ Duration Withstand Withstand Making
Voltage Voltage Current
kV Hz kA Sec kV kV kA (Peak) Amperes
36W-VACR16 3.6 50/60 16 3 40 20 40 630, 800, 1250,
36W-VACR20 3.6 50/60 20 3 40 20 50 630, 800, 1250
36W-VACR25 3.6 50/60 25 3 40 20 63 630, 800, 1250, 2000
72W-VACR16 7.2 50/60 16 3 60 20 40 630, 800, 1250
72W-VACR20 7.2 50/60 20 3 60 20 50 630, 800, 1250
72W-VACR25 7.2 50/60 25 3 60 20 63 630, 800, 1250, 2000
72W-VACR32 7.2 50/60 31.5 3 60 20 80 1250, 2000
72W-VACR40 7.2 50/60 40 3 60 20 100 1250, 2000
120W-VACR16 12 50/60 16 3 75 28 40 630, 800, 1250
120W-VACR20 12 50/60 20 3 75 28 50 630, 800, 1250
120W-VACR25 12 50/60 25 3 75 28 63 630, 800, 1250, 2000
120W-VACR32 12 50/60 31.5 3 75 28 80 1250, 2000
120W-VACR40 12 50/60 40 3 75 28 100 1250, 2000
120W-VACR50 12 50/60 50 3 75 28 125 1250, 2000, 2500
150W-VACR16 12 50/60 16 3 95 36 40 630, 800, 1250
150W-VACR20 12 50/60 20 3 95 36 50 630, 800, 1250
150W-VACR25 12 50/60 25 3 95 36 63 630, 800, 1250, 2000
150W-VACR32 12 50/60 31.5 3 95 36 80 1250, 2000
150W-VACR40 12 50/60 40 3 95 36 100 1250, 2000
IB131009EN
Instruction Book
Page 3
630A Element
630A = 105kg
Figure 1-1 Type W-VACR 630A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
Page 4
630A Element
630A = 105kg
Figure 1-2 Type W-VACR 630A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
Page 5
800/1250A Element
800A/1250A = 110kg
Figure 1-3 Type W-VACR 800/1250A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
Page 6
800/1250A Element
800A/1250A = 110kg
Figure 1-4 Type W-VACR 800/1250A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
Page 7
2000A Element
2000A = 149kg
Figure 1-5 Type W-VACR 2000A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
Page 8
2000A Element
2000A = 149kg
Figure 1-6 Type W-VACR 2000A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
Page 9
2500A Element
2500A = 154kg
Figure 1-7 Type W-VACR up to 2500A, 50kA. breaker element only outline dimensions (millimeters) and weights (kg.).
IB131009EN
Instruction Book
Page 10
Up to 1250A Element
630A = 115kg
800A/1250A = 121kg
(Front View)
1600A & 2000A Elements (Side View)
1600A/2000A = 160kg
Figure 1-8 Type W-VAC breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
Page 11
33.3 570 A
350 G
325 F F
373
197 202
“C” POLE
“A” POLE
“B” POLE
B
9.5
19.34
E
C
1160
D
795.7
520
480
Earthing Contacts
A
33.3 570 G
373 F F
197 202
“C” POLE
D
C
E
720
355.7
80
48.3
Earthing Contacts
44.6
84.4
440 269 228.3
701 456.6
538
Figure 1-9 Outline and Dimensions (mm) Type W-VAC breaker element with carriage assembly and cradle assembly
IB131009EN
Instruction Book
Page 12
Figure 1-10 Outline and Dimensions (mm) Type W-VAC 3150 breaker with carriage assembly
IB131009EN
Instruction Book
Page 13
SECTION 2: SAFE PRACTICES • Do not work on a breaker with the secondary test cou-
pler engaged or fixed secondary connections made.
W-VAC, W-VACR, and W-VACW breakers are Failure to disconnect the test coupler could result in an
equipped with high speed, high energy operating mech- electrical shock leading to death, personal injury or
anisms. They are designed with several built-in inter- property damage.
locks and safety features to provide safe and proper
operating sequences. • Do not work on a closed breaker or a breaker with
closing springs charged. The closing spring should be
discharged and the main contacts open before working
WARNING on the breaker. Failure to do so could result in cutting or
crushing injuries.
TO PROTECT THE PERSONNEL ASSOCIATED WITH
INSTALLATION, OPERATION, AND MAINTENANCE • Do not use a drawout circuit breaker by itself as the
OF THESE BREAKERS, THE FOLLOWING PRAC- sole means of isolating a high voltage circuit, Remove
TICES MUST BE FOLLOWED: the breaker to the Disconnect position and follow good
lock-out and tagging rules, as well as all applicable
• Only qualified persons, as defined in the local electri- codes, regulations and work rules.
cal code who are familiar with the installation and main-
tenance of medium voltage circuits and equipment, • Do not leave a drawout breaker in an intermediate
should be permitted to work on these breakers. position in the cell. Always have the breaker either in the
Test or Connected position. Failure to do so could result
• Read these instructions carefully before attempting in a flash over and possible death, personal injury or
any installation, operation or maintenance of these property damage.
breakers.
• Always remove the maintenance tool from the breaker
• Always remove the removable breakers from their after charging the closing springs.
enclosures or disconnect the fixed primary connections
associated with fixed breakers before performing any • Circuit breaker elements are equipped with safety
maintenance. Failure to do so could result in electrical interlocks. Do Not remove, interfere with or in any
shock leading to death, severe personal injury or prop- manner defeat them. This may result in death, bodily
erty damage. injury or equipment damage.
IB131009EN
Instruction Book
Page 14
SECTION 3: RECEIVING, HANDLING AND When opening the container, be careful that any loose
STORAGE items or hardware are not discarded with the packing
material. Check the contents of each package against
The entire W-VAC family of circuit breakers is subjected the packing list.
to complete factory production tests and inspection
before being packed. They are shipped in packages Examine the breaker for any signs of shipping damage
designed to provide maximum protection to the equip-
such as broken, missing or loose hardware, damaged or
ment during shipment and storage, and, at the same
time, to provide convenient handing. Accessories, such deformed insulation and other components. File claims
as the maintenance tool and levering crank are shipped immediately with the carrier if damage or loss is detect-
separately. ed and notify the nearest Eaton Sales Office.
Until the breaker is ready to be delivered to the Maintenance Tool: Used to charge the closing springs.
switchgear site for installation, DO NOT remove it from (Style 8064A02G01)
its container. If the breaker is to be placed in storage,
maximum protection can be obtained by keeping it in its Lifting Yoke: Optional item used to lift the breaker.
container. (Style 8794C67G01 for up to 1250A breakers)
(Style 8794C68G01 for 1600A, 2000A breakers)
Upon receipt of the equipment, inspect the container for (Style 1C95990G01 for 3150A breakers)
any signs of damage or rough handing. Open the con-
tainer carefully to avoid any damage to the contents. Primary Disconnect Plier: Used to install and remove
breaker primary disconnects.
(Style 591C901G02)
IB131009EN
Instruction Book
Page 15
When a breaker is ready for installation, a lifting yoke in Outdoor storage is NOT recommended. If unavoidable,
conjunction with an overhead lifter or portable floor lifter the outdoor location must be well drained and a tempo-
can be used to move a breaker. In some instances, this rary shelter from sun, rain, snow, corrosive fumes, dust,
is preferable to rolling the breaker on the floor using self dirt falling objects and excessive moisture must be pro-
contained wheels when provided on the cradle or car- vided. Containers should be arranged to permit free cir-
riage. If the breaker is to be lifted, position the lifting culation of air on all sides and temporary heaters should
yoke over the breaker and insert lifters into the breaker be used to minimize condensation. Moisture can cause
side openings with the lifting hole toward the inter- rusting of metal parts and deterioration of high voltage
rupters. Once the lifting yoke is securely seated in the insulation. A heat level of approximately 400 watts for
lifting holes, the breaker can be carefully lifted and each 3 cubic meters of volume is recommended with the
moved. heaters distributed uniformly throughout the structure
near the floor.
IB131009EN
Instruction Book
Page 16
1 2 3
8 7
IB131009EN
Instruction Book
Page 17
15
1
13
2
12
4
14
5
11
10
16
9
8
6 7
➀ L.H. Closing Spring ➈ Charging Motor
➁ Anti-pump Relay ➉ Charging Pawl
➂ Auxiliary Switch 11 Ratchet Wheel
➃ Motor Cutoff Switch 12 R.H. Closing Spring
➄ Closing Cam 13 Opening Spring
➅ Spring Release (Close Coil) Assembly 14 Manual Charge Socket
➆ Shunt Trip Assembly 15 Secondary Disconnect
➇ Position Switch 16 Operation Counter
IB131009EN
Instruction Book
Page 18
2 4
3
5
IB131009EN
Instruction Book
Page 19
2
1
4
9
7
5
6
Side View
4
Rear View
Figure 3-5 Side and rear external view W-VAC breaker with carriage assembly for single tier switchgear
IB131009EN
Instruction Book
Page 20
Front View
Rear View
Figure 3-6 Front and rear external view W-VAC breaker with cradle assembly for double tier switchgear
IB131009EN
Instruction Book
Page 21
Front View 6
3
1
5
4
Rear View
➀ Mechanism Enclosure ➅ Carriage Wheel
➁ Support Insulator ➆ Shoot Bolt Lever
➂ Primary Disconnect ➇ Shutter Operator
➃ Levering in Screw ➈ Levering Device Socket
➄ Carriage
Figure 3-7 Front and rear external view W-VAC 3150A breaker with carriage assembly for single tier switchgear
IB131009EN
Instruction Book
Page 22
NOTICE
WARNING
If the springs are to be charged on a closed breaker,
no click is heard at the end of charging operation. EXTREME CAUTION MUST BE EXERCISED TO
Discontinue charging and remove the maintenance INSURE THAT PRIMARY CIRCUITS ARE NOT ENER-
tool as soon as "Charged" flag is fully visible. GIZED WHILE CHECKS ARE PREFORMED IN THE
Continued attempts to further charge may result in BREAKER COMPARTMENT. FAILURE TO DO SO
damage to the mechanism. Remove the mainte- MAY RESULT IN PERSONAL INJURY OR DEATH.
nance tool. Close and trip the breaker several
times (Figure 4.1). When testing the breaker electrically, a TEST position
is accomplished with drawout breakers using several
4-3 VACUUM INTERRUPTER INTEGRITY methods. The method used depends on the switchgear
structure approach being utilized.
Using a dry lint free cloth or paper towel, clean all the
insulating surfaces of the pole units. Conduct a vacuum a1) If the breaker is being used in the behind the door
interrupter integrity check as described in Section 6.4. configuration, the structure mounted secondary contact
blocks can be manually engaged with the breaker's sec-
4-4 INSULATION ondary contacts. This is accomplished with the breaker
still inside the structure and the primary contacts dis-
Check breaker primary and secondary insulation per connected.
Section 6.7.
a2) If the breaker is being used in a flushmounted con-
4-5 CONTACT EROSION AND WIPE figuration, the breaker must be moved to the discon-
nected position for testing. It is recommended that a test
Manually charge the closing springs and close the cable be used to connect the female and male sec-
IB131009EN
Instruction Book
Page 23
a. Inserting the maintenance tool into b. Lifting shoot lever permits insertion
the manual charging socket of levering crank
Figure 4-1 Type W-VAC breaker manual operation (single tier breaker shown)
IB131009EN
Instruction Book
Page 24
ondary contacts when in the disconnected position. The d) Anti-Latch Interlock: This interlock prevents the
structure mounted secondary contact blocks are perma- breaker from being closed between the Connected and
nently mounted and cannot be moved out for direct con- Test positions.
nection with the breaker mounted secondary contacts.
e) Shutter Drive Interlock:
b) For the behind the door configuration, carefully load The metallic switchgear shutters are independently
the breaker into the structure until it reaches the Test operated permitting them to be locked in the open posi-
position. For the flush mounted configuration, carefully tion for servicing the primary disconnects. The locking
move the breaker toward the structure until it reaches system is disabled when the breaker is being connected
the Test position. permitting the shutters to operate in the normal manner.
c) If a lifting yoke was used to move and/or load the f) Earthing Drive Interlock:
breaker, remove the yoke at this time. If the switchgear is equipped with an earthing switch,
the breaker can only be inserted into the switchgear if
the earthing switch is open.
d) For the behind the door configuration, manually
engage the secondary contact blocks by pulling the
movable blocks forward as far as possible. For the flush Check for the correct operation of the interlocks just
mounted configuration, connect the test cable to both described by starting with the breaker in the Test posi-
the breaker and structure secondary contact blocks. As tion and completing the following steps:
soon as control power is available, the motor will
charge the closing springs. Step 1: Engagement of Levering Crank:
1. For the single tier configuration carriage assembly
e) Close and trip the breaker several times to verify the version, the shoot bolt should be fitted into the first
closing and tripping operations slot of the interlock plate located on the floor of the
switchgear. Charge the closing springs and close
f) Conclude by closing the breaker. the breaker. The slider cannot be pushed far
enough to engage the levering crank.
4-9 BREAKER / COMPARTMENT INTERFACE CHECK
2. For the double tier configuration cradle assembly
The following interlocks are provided to insure safe and version, the horizontal shoot bolts should be fitted
correct operation: into the slots of interlock plates located at the sides
of the switchgear. Charge the closing springs and
a) Floor Tripping and Spring Release Interlock: close the breaker. The slider cannot be pushed far
This optional interlock closes and trips the breaker if the enough to engage the levering crank.
closing springs are charged as the breaker is moved
from the Test position to the Withdrawn position and Step 2 :
vice versa. Open the breaker, engage the levering crank and lever
the breaker into the Connected position. Remove the
b) Levering Interlocks: levering crank.
1. Carriage Assembly Version: This version is used for
single tier switchgear configurations. The levering Step 3:
crank can only be engaged when the breaker is Close the breaker. The motor starts charging the closing
open and the shoot bolt lever is lifted (Figure 4-1b) springs if control power is available.
The breaker will not close manually or electrically
while the levering crank is engaged. Step 4:
Open the breaker, engage the levering crank and
2. Cradle Assembly Version: This version is used for attempt to close the breaker manually or electrically.
double tier switchgear configurations. The levering The breaker will go trip free (spring discharge but break-
crank can only be engaged when the breaker is er does not close).
open and the horizontal shoot bolts are engaged
(fully extended). The breaker will not close manually Step 5:
or electrically while the levering crank is engaged. Lever the breaker out approximately half way towards
the Test position. Remove the levering crank and
c) Anti-Close Interlock: This interlock prevents releasing attempt to close the breaker by pushing the manual
the closing springs electrically or manually if the breaker close button. The breaker will go trip free. Lever the
is already closed (drawout and fixed configurations). breaker all the way into the Test position. The sec-
ondary disconnects will disengage automatically.
IB131009EN
Instruction Book
Page 25
IB131009EN
Instruction Book
Page 26
W-VAC breakers utilize Eaton vacuum inter- rupters to 5-1.1 VACUUM INTERRUPTER
close and open the primary circuit. The mech- anism is
a front mounted, spring stored energy type, which is All the circuit breakers utilize vacuum interrupters for
common to all ratings. This one front mounted interruption and switching functions. The primary differ-
mechanism is easy to inspect, accessible for servicing ence between the different breaker types is the vacuum
and requires a minimum of spare parts. Because of the interrupter configuration, which results in different rat-
inherent long life characteristics of the vacuum inter- ings (Tables 1.1 and 1.2). Vacuum interruption offers
rupters and the highly reliable spring stored energy the advantages of enclosed interrupters, reduced size
mechanism, W-VAC and W-VACW circuit breakers pro- and weight, short interrupting time, long life, reduced
IB131009EN
Instruction Book
Page 27
WARNING
IB131009EN
Instruction Book
Page 29
IB131009EN
Instruction Book
Page 30
➁ ➉➂ ➆
11 ➇
➀
➃
12
➈ ➄
Figure 5-5a Breaker open and closing spring Figure 5-5b Breaker open and closing spring
discharged discharged
Figure 5-5c Breaker closed and closing Figure 5-5d Breaker closed and closing
spring discharged spring charged
IB131009EN
Instruction Book
Page 31
12
➃
➂ 11
➇
14
➉
➈
➀
13
IB131009EN
Instruction Book
Page 32
turn. Since the cam surface in contact with the main link 5-3.1 TIMING
roller is cylindrical in this region, the spring charging
operation does not affect the mechanism linkage. The opening and closing times for the circuit breakers
vary depending upon the control voltage and the power
Since the primary contacts are completely enclosed in rating. However, the typical values are as follows in
the vacuum interrupter and not adjustable in any way, a Table 5.1.
"Slow Close" capability is not provided with W-VAC and
W-VACW breakers. Table 5.1 Typical Opening and Closing Times
5-2.4 TRIPPING OPERATION Event Time in Milliseconds
When the trip "D" shaft is turned either by the trip button Closing Time
75
or trip coil, all links return to the original "open" condition (From Initiation of Close
shown in (Figure 5-5a). Signal to Contact Make)
Opening Time
5-2.5 TRIP FREE OPERATION (Initiation of Trip Signal 45
to Contact Break)
When the manual trip button is held depressed, any
Reclosing Time
attempt to close the breaker results in the closing
(Initiation of Trip Signal
springs discharging without any movement of the pole 190
to Contact Make)
shaft or vacuum interrupter stem.
There are two basic control schemes for all the circuit- The drawout breaker control wiring is arranged to con-
breakers, one for DC control and one for AC control nect a 25 point male plug as standard with a corre-
voltages or more than one tripping element, but the prin- sponding female plug mounted in the switchgear com-
cipal mode of operation is as follows: partment. An additional 25 point plug is optional and can
be supplied when an additional auxiliary switch beyond
As soon as the secondary disconnects engage, the the standard is supplied. The fixed circuit breaker uti-
spring charging motor automatically starts charging the lizes a similar fixed secondary connection scheme.
closing spring, provided control power is available.
When the springs are charged, the motor cut off LS1/bb The drawout breaker plugs are mounted in small enclo-
switch turns the motor off. The breaker may be closed sure located on the upper left front portion of the basic
by making the control switch close (CS/c) contact. breaker element (Figure 3-4). This male plug automati-
Automatically upon closing of the breaker, the motor cally connects or disconnects with a structure mounted
starts charging the closing springs. The breaker may be female plug as the breaker is racked into or out of the
tripped any time by making the control switch (CS/T) connected position.
contacts.
If the drawout breaker is being used in a flush mounted
Note the position switch (PS) contact in the spring configuration, the breaker must be moved to the discon-
release circuit in the scheme. This contact remains nected position for testing. It is recommended that a test
made while the breaker is being levered between the cable be used to connect the female and male sec-
TEST and CONNECTED positions. Consequently, it ondary contacts when in the disconnected position. The
prevents the breaker from closing automatically, even structure mounted secondary contact blocks are perma-
though the control switch close contact may have been nently mounted and cannot be moved out for direct con-
made while the breaker is levered to the CONNECTED nection with the breaker mounted secondary contacts.
position.
The behind the door drawout design utilizes movable
When the CS/C contact is made, the SR closes the carriage mounted female plugs in the structure. A
breaker. If the CS/C contact is maintained after the "TEST" position is available within the structure. Once
breaker closes, the Y relay is picked up. The Y/a contact the breaker is racked out to the test position, the struc-
seals in Y until CS/C is opened. The Y/b contact opens ture mounted secondary plug carriage can be manually
the SR circuit, so that even though the breaker would unlatched, and pulled forward until the female plugs
subsequently open, it could not be reclosed before mate with the breaker mounted male plugs. To disen-
CS/C was released and remade. This is the anti-pump gage the secondary plugs from the "TEST" position,
function. simply push the carriage to the rear.
IB131009EN
Instruction Book
Page 33
IB131009EN
Instruction Book
Page 34
IB131009EN
Instruction Book
Page 35
➁
➀ ➇
➁
➅
➆
IB131009EN
Instruction Book
Page 36
5-5 MISCELLANEOUS
IB131009EN
Instruction Book
Page 37
•DO NOT DEFEAT ANY SAFETY INTERLOCKS. Vacuum interrupters used in all circuit breakers are
highly reliable interrupting elements. Satisfactory per-
•DO NOT LEAVE MAINTENANCE TOOL IN THE formance of these devices is dependent upon the
SOCKET AFTER CHARGING THE CLOSING integrity of the vacuum in the interrupter and the internal
SPRINGS. dielectric strength. Both of these parameters can be
readily checked by a one minute ac high potential test.
•DO NOT STAND LESS THAN ONE METER AWAY (See Table 6.1 for appropriate test voltage.) During this
FROM THE BREAKER WHEN TESTING FOR VACU- test, the following warning must be observed:
UM INTEGRITY.
View A-A
IB131009EN
Instruction Book
Page 38
1. Insulation Drive Insulator No dirt Visual Check Clean with lint-free cloth
and
Molded Pole Unit Support No cracking Visual Check Replace cracked unit
Insulation Main Circuit to Ground Withstand Hipot Tester Clean and retest or replace
Integrity
Between Main Circuit Withstand Hipot Tester Clean and retest or replace
Terminals
Controls Circuit to Ground Withstand Hipot Tester Clean and retest or replace
Contact wipe visible Visual (Figures 6-6 & 6-7) Replace pole unit assembly
Dirt on ceramic body Visual Check Clean with dry lint-free cloth
Pole Unit Black Clips Every 1000 Operations Operation Counter Replace Black Clips
3. Control Closing and Tripping Device Smooth and correct Test closing and tripping Replace any defective device,
Circuit Including Disconnects operation by control of the breaker twice identify per trouble-shooting
power chart
IB131009EN
Instruction Book
Page 39
4. Operating Dust or Foreign Matter No dust or foreign Visual Check Clean as necessary
Mechanism matter
Manual Operation Smooth operation Manual charging closing Correct per trouble-shooting
and tripping chart if necessary
IB131009EN
Instruction Book
Page 40
Figure 6-2 Vacuum interrupter showing contact erosion Figure 6-3 Vacuum interrupter showing contact erosion
indicator with breaker open (shown here for clarity pur- indicator with breaker closed (indicators are checked
poses only). only when breaker is closed).
IB131009EN
Instruction Book
Page 41
Erosion gauge
Erosion mark
Pointer portion of the gauge Pole unit support Pointer portion of the gauge is
is below the erosion mark aligned or above the erosion mark
Figure 6-4 Breaker shown closed and interrupter Figure 6-5 Breaker shown closed and interrupter
erosion satisfactory (3150A) erosion unsatisfactory (3150A)
IB131009EN
Instruction Book
Page 42
Rated Resistance
Continuous (microohms)
Current
(amperes)
Figure 6-7 Wipe indicaton.
630 46
800 39
1250 39
1600 26
2000 26
2500 20
3150 10
IB131009EN
Instruction Book
Page 43
the circuit breaker from closing fully. In such a case, it to save the original fasteners for reassembly.
is important to determine that the circuit breaker will
close fully. The CloSureTM Test provides this assurance. Step 3 - Cut a piece of one inch wide drafting/masking
tape approximately 8 to 10 inches long.
General Information: The CloSureTM Test can be per- Step 4 - Place the tape around the cam starting from the
formed on the VCP-W, VCP-WR, VCPW-ND, DHP-VR, W- bottom up. Make certain that the tape adheres well to
VACR, W-VAC, and W-VACW lines of vacuum circuit the cam surface. (See Figures 6-9, 6-10 and 6-11).
breakers Refer to Table 6.3 for a list of circuit breakers. If
the CloSureTM travel obtained is as specified, the mecha- Step 5 - Mount the transparent CloSureTM Test Tool with
nism performance is satisfactory. If the CloSureTM travel two bolts and washers. Refer to Figures 6-22, 6-23 and
does not conform as shown in Figure 6-15, contact
Table 6.3 for appropriate mounting holes. Hand tighten
Eaton for further information. (See Step 13).
the bolts (Figures 6-12, 6-13, 6-22 and 6-23).
CAN RESULT FROM CONTACT WITH ENERGIZED Step 8 - While holding the marker tip on the tape, close
EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE the breaker (Figure 6-15).
IS PRESENT BEFORE PROCEEDING WITH THE
TASK, AND ALWAYS FOLLOW GENERALLY Step 9 - Move the marker back and forth horizontally
ACCEPTED SAFETY PROCEDURES. approximately 15o in both directions to create a line on
the tape that identifies the closed rest position (Figures
Safety Precautions: Read and understand these 6-16, 6-22 and 6-18).
instructions before attempting any maintenance, repair
or testing on the breaker. The user is cautioned to
Step 10 - Remove the marker from hole “C”.
observe all recommendations, warnings and cautions
relating to the safety of personnel and equipment.
The recommendations and information contained herein Step 11 - Push the “push to open” clapper to open the
are based on Eaton experience and judgment, but circuit breaker.
should not be considered to be all-inclusive or cov-
ering every application or circumstance which may Step 12 - Inspect the circuit breaker to assure it is in the
arise. If further information is required, you should open position and the closing springs are discharged.
consult Eaton. Remove the transparent CloSureTM Tool. Remove the
tape from the cam and stick the tape on the front right
Testing Procedures: Assuming that the breaker is side sheet of the circuit breaker. Record the date of the
safely pulled out to the Test/Disconnect position in the test and the operations counter reading on the tape
enclosure or placed on the workbench, follow this proce- (Figures 6-19 and 6-20 and 6-21).
dure to perform the CloSureTM Test. For further instruc-
tions on disconnecting the circuit breaker consult Step 13 - Evaluate the CloSureTM” performance by com-
Section 4 of this manual. If the enclosure is equipped paring the test tape with the illustrations in Figure 6-21.
with the MOC operating in the test position also, make If the marking is similar to 6-21A measure the over trav-
certain that the MOC is connected to operate. el “x”: If “x” is greater than or equal to 0.6 inches, the
circuit breaker performance is satisfactory. If “x” is less
Step 1 - On the front cover identify the status indicators. than 0.6 inches or if the marking is similar to 6-21B or
MAKE SURE THE CLOSING SPRING STATUS INDI- 6-21C, immediately contact your Eaton Rep.
CATES “Discharged” AND THE MAIN CONTACT
INDICATOR SHOWS “Open” (Figure 6-9). Step 14 - Remove the CloSureTM Tool. Reassemble the
front cover onto the circuit breaker. Return the circuit
Step 2 - Remove the circuit breaker front cover. Be sure breaker to it’s original configuration and setup.
IB131009EN
Instruction Book
Page 44
IB131009EN
Instruction Book
Page 45
ClosureTM Tool
Marker
15o
15o
Figure 6-19 Remove Marked Masking Tape from Cam
Figure 6-16 Top View of Cam and Marker Interface
IB131009EN
Instruction Book
Page 46
Width
center
of the marker
diameter
to determine “X”
distance Figure 6-23 Typical Circuit Breaker Front View with
CloSureTM Tool Attached (approximate mechanism
5 3/16” Approx
“X” Inches
CloSureTM
Overtravel Table 6.3 ClosureTM Tool Mounting/Testing Locations by
Circuit Breaker Type
CloSureTM Distance
Breaker Approximate Upper Lower Marker
CloSureTM Position
Line Mechanism Mounting Mounting Placement
A C
Cabinet Hole Hole Hole
Figure 6-21 Illustrative Testing Tape Sample Width (inch)
A-1 20 A1 B2 C2
DHP-VR
A-2 C-2 27 A1 B1 C5
A-3 C-1C-3 C-4 C-5 C-6 VCPW-ND 20/21 A1 B2 C2
A-4
27 A1 B2 C5
VCP-W
33 A2 B2 C6
18 A1 B2 C1
VCP-WR 20 A1 B2 C2
27 A1 B2 C5
B-1 18 A1 B2 C1
B-2 W-VAC,
25 A1 B1 C4
W-VACR
Figure 6-22 Front View of CloSureTM Tool Showing 33 A2 B2 C6
Mounting/Testing Hole Locations (6352C49H01)
IB131009EN
Instruction Book
Page 47
6-10 LUBRICATION Roller bearings are used on the pole shaft, the cam
shaft, the main link and the motor eccentric. These
All parts that require lubrication have been lubricated bearings are packed at the factory with a top grade slow
during the assembly with molybdenum disulphide oxidizing grease which normally should be effective for
grease. Eaton No. 53701QB. Over a period of time, this many years. They should not be disturbed unless there
lubricant may be pushed out of the way or degrade. is definite evidence of sluggishness, dirt or parts are dis-
Proper lubrication at regular intervals is essential for mantled for some reason.
maintaining the reliable performance of the mechanism.
Once a year or every 2000 operations whichever If it becomes necessary to disassemble the mecha-
comes first, the breaker should be relubricat- ed. The nism, the bearings and related parts should be thor-
locations shown in Figure 6-1 should be lubri- cated oughly cleaned. Remove old grease in a good grease
with a drop of light machine oil. After lubrication, solvent. Do not use carbon tetrachloride. They should
operate the breaker several times manually and electri- then be washed in light machine oil until the cleaner is
cally. removed. After the oil has been drawn off, the bear-
ings should be packed with Eaton Grease 53701QB
or equivalent.
Fails To Close
• Secondary Disconnects
• Motor
(Brushes worn or commutator
segment open)
• Mechanism • Pawls
(Slipping or Broken)
• Ratchet Wheel
(Teeth worn or broken)
• Oscillator
(Reset spring off or broken)
IB131009EN
Instruction Book
Page 48
Fails To Close
• Secondary Disconnects
• Anti-Pump Relay
(Y relay N.C. contact open
or burned or relay picks up
• Close Coil
(Open or Burned)
• Auxiliary Switch
(b contact open or burned)
• Motor Cut-off
(Contacts open or burned)
• Pole Shaft
(Not open fully)
• Trip Latch-Hatchet
(Fails to remain reset)
• Close Latch
(Binding)
Undesirably Closes
IB131009EN
Instruction Book
Page 49
Fails to Trip
• Secondary Disconnect
• Auxiliary Switch
(a contact no making,
poor or burned)
• Trip Coil
(Burned or open)
• Vacuum Interrupter
(One or more Welded)
Undesirably Trips
IB131009EN
Instruction Book
Page 50
7-1 GENERAL a.) Always specify the breaker rating information and
shop order number.
In order to minimize production downtime, it is recom- b.) Describe the item, give the style number, and specify
mended that an adequate quantity of spare parts be car- the quantity required.
ried in stock. The quantity will vary from customer to
customer, depending upon the service severity and con- c.) Specify the voltage for electrical components.
tinuity requirements. Each customer should develop his
own stock level based on operating experience. Refer to d.) Specify the method of shipping desired.
Table 7.1 for guidance.
e.) Send all orders or correspondence to the nearest
Eaton sales office.
Table 7.1 Recommended W-VAC, W-VACR and W-VACW Spare Parts
Line No. Description Style Qty
IB131009EN
Instruction Book
Page 51
4D13307G02
16. W-VAC Pole Unit Assy, 1250A, 3
Up to 15 kV, 31.5 kA, 95 kV BIL
4D13343H01
(Plus) Cover
IB131009EN
Instruction Book
Page 52
IB131009EN
Instruction Book
Page 53
Rectifier
29. 110-120/220-240 VAC 3759A79G01 3
Anti-Pump Relay
30. 48 VDC 3759A74G03 3
110/125 VDC 3759A74G04
220/250 VDC 3759A74G05
110/120 VAC 50/60 Hz 3759A74G05
220/240 VAC 50/60 Hz 3759A74G02
IB131009EN
Instruction Book
Page 54 Effective: October 2005
UV Trip Coils
32. 48 VDC 8064A19G01 1
110/125 VDC 8064A19G02 1
220/250 VDC 8064A19G03 1
120 VAC 8064A19G09 1
240 VAC 8064A19G10 1
Cluster Assembly
39. 630A 699B104G02 6
800/1250A 508B022G02 6
1600/2000A 5677B31G11 6
IB131009EN
Instruction Book Instructions for Installation, Operation and Maintenance of
Types W‐VAC, W‐VACR, and W‐VACW Vacuum Circuit
Breakers