You are on page 1of 58

Cutler-Hammer I.B.

3A74791H06

Instructions for Installation, Operation and Maintenance


of Type W-VAC and W-VACR 36kV Vacuum Circuit Breakers

Type W-VAC (Drawout)

Type W-VACR (Fixed)

Effective March 2001 Supersedes I.B. 3A74791H05 dated July 2000


I.B. 3A74791H06 Page iii

! WARNING ! WARNING

IMPROPERLY INSTALLING OR MAINTAINING THE CIRCUIT BREAKERS DESCRIBED IN THIS


THESE PRODUCTS CAN RESULT IN DEATH, SERI- BOOK ARE DESIGNED AND TESTED TO OPERATE
OUS PERSONAL INJURY, OR PROPERTY DAMAGE. WITHIN THEIR NAMEPLATE RATINGS. OPERATION
OUTSIDE OF THESE RATINGS MAY CAUSE THE
READ AND UNDERSTAND THESE INSTRUCTIONS EQUIPMENT TO FAIL, RESULTING IN DEATH, BOD-
BEFORE ATTEMPTING ANY UNPACKING, ASSEM- ILY INJURY AND PROPERTY DAMAGE.
BLY, OPERATION OR MAINTENANCE OF THE CIR-
CUIT BREAKERS. ALL SAFETY CODES, SAFETY STANDARDS
AND/OR REGULATIONS AS THEY MAY BE
INSTALLATION OR MAINTENANCE SHOULD BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE
ATTEMPTED ONLY BY QUALIFIED PERSONNEL. STRICTLY ADHERED TO.
THIS INSTRUCTION BOOK SHOULD NOT BE CON-
SIDERED ALL INCLUSIVE REGARDING INSTALLA- THE FIXED CIRCUIT BREAKER ELEMENTS ARE
TION OR MAINTENANCE PROCEDURES. IF FUR- DESIGNED TO BE INSTALLED PURSUANT TO ALL
THER INFORMATION IS REQUIRED, YOU SHOULD APPLICABLE ANSI STANDARDS. SERIOUS
CONTACT CUTLER-HAMMER. INJURY, INCLUDING DEATH, CAN RESULT FROM
FAILURE TO FOLLOW PROCEDURES OUTLINED IN
THIS MANUAL, OR COMPLY WITH THE REQUIRE-
MENTS OF APPLICABLE STANDARDS. THE CUS-
TOMER IS RESPONSIBLE FOR PROVIDING ALL
REQUIRED PHASE TO PHASE INSULATION, PHASE
TO GROUND INSULATION AND ALL BREAKER
INTERLOCKS. THESE CIRCUIT BREAKER ELE-
MENTS ARE SOLD PURSUANT TO A NON-STAN-
DARD PURCHASING AGREEMENT WHICH LIMITS
THE LIABILITY OF THE MANUFACTURER.

Cutler-Hammer
Pittsburgh, PA 15220

All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding his particular installation, operation or maintenance of particular equipment,
contact a Cutler-Hammer representative.

Effective 3/01
Page iv I.B. 3A74791H06

TABLE OF CONTENTS

Page
SECTION 1: INTRODUCTION

1-1 Preliminary Comments and Safety Precautions..................................................................................................1


1-1.1 Warranty and Liability Information ..........................................................................................................1
1-1.2 Safety Precautions .................................................................................................................................1
1-2 General Information.............................................................................................................................................1
1-3 Type W-VAC and W-VACR Vacuum Circuit Breaker Ratings ............................................................................2
1-4 Outlines and Dimensions ....................................................................................................................................3

SECTION 2: SAFE PRACTICES

2-1 Recommendations ..............................................................................................................................................5

SECTION 3: RECEIVING, HANDLING AND STORAGE

3-1 General ...............................................................................................................................................................6


3-2 Receiving.............................................................................................................................................................6
3-3 Handling ..............................................................................................................................................................6
3-4 Storage ...............................................................................................................................................................7
3-5 Tools and Accessories ........................................................................................................................................8
3-6 Type W-VAC and W-VACR Vacuum Circuit Breaker Weights ...........................................................................8

SECTION 4: INITIAL INSPECTION AND INSTALLATION

4-1 Introduction........................................................................................................................................................14
4-2 Manual Operation Check...................................................................................................................................14
4-3 Vacuum Interrupter Integrity..............................................................................................................................14
4-4 Insulation ...........................................................................................................................................................14
4-5 Contact Erosion and Wipe.................................................................................................................................14
4-6 Primary Circuit Resistance ................................................................................................................................14
4-7 Nameplate .........................................................................................................................................................14
4-8 Electrical Operation Check................................................................................................................................14
4-8.1 Circuit Breaker Insertion and Removal.................................................................................................15
4-8.2 Operation Check Performance .............................................................................................................16
4-9 Breaker/Structure Interfacing ............................................................................................................................16
4-9.1 Interface Interlocks ...............................................................................................................................16
4-9.2 Drawout Breaker Interfacing Check (W-VAC) ......................................................................................16

SECTION 5: DESCRIPTION AND OPERATION

5-1 Introduction........................................................................................................................................................18
5-2 Interrupter Assembly .........................................................................................................................................18
5-2.1 Vacuum Interrupter...............................................................................................................................19
5-2.2 Contact Erosion Indication ...................................................................................................................19
5-2.3 Loading Spring Indication.....................................................................................................................20
5-2.4 Contact Wipe and Stroke .....................................................................................................................20
5-3 Stored Energy Mechanism ................................................................................................................................20

Effective 3/01
I.B. 3A74791H06 Page v

Page

5-3.1 Operation of Stored Energy Mechanism ..............................................................................................20


5-3.2 Charging ...............................................................................................................................................20
5-3.3 Closing Operation.................................................................................................................................22
5-3.4 Tripping Operation................................................................................................................................22
5-4 Control Schemes...............................................................................................................................................22
5-4.1 Timing...................................................................................................................................................22
5-4.2 Secondary Disconnects........................................................................................................................22
5-4.3 Secondary Terminal Blocks..................................................................................................................26
5-4.4 Undervoltage Trip Device .....................................................................................................................26
5-5 Interlocks and Interfacing ..................................................................................................................................27
5-6 Levering Mechanism (W-VAC Only) .................................................................................................................27
5-7 Operations Counter ...........................................................................................................................................27
5-8 Ground Contact .................................................................................................................................................27
5-9 MOC and TOC Switch Operations ....................................................................................................................27

SECTION 6: INSPECTION, MAINTENANCE AND TROUBLESHOOTING

6-1 Introduction........................................................................................................................................................29
6-2 Frequency of Inspection and Maintenance .......................................................................................................29
6-2.1 Qualified Personnel ..............................................................................................................................29
6-2.2 Helpful Tools and Accessory Items ......................................................................................................29
6-2.3 General Torque Guidelines ..................................................................................................................29
6-3 Inspection and Maintenance Procedures ..........................................................................................................32
6-4 Vacuum Interrupter Integrity Test......................................................................................................................33
6-5 Contact Erosion.................................................................................................................................................33
6-6 Contact Wipe.....................................................................................................................................................33
6-7 Insulation ...........................................................................................................................................................34
6-8 Insulation Integrity Check ..................................................................................................................................34
6-9 Primary Circuit Resistance Check.....................................................................................................................34
6-10 Mechanism Check.............................................................................................................................................36
6-10.1 CloSureTM Test ......................................................................................................................................36
6-11 Lubrication.........................................................................................................................................................40
6-12 Troubleshooting Chart.......................................................................................................................................40

SECTION 7: RENEWAL PARTS

7-1 General .............................................................................................................................................................43


7-1.1 Ordering Instructions ............................................................................................................................43

FIGURES
Figure Title Page

1-1 Type W-VAC 36kV Drawout Circuit Breaker Outlines and Dimensions ....................................................3
1-2 Type W-VACR 36kV Fixed Circuit Breaker Outlines and Dimensions ......................................................4
3-1 Circuit Breaker Shown Mounted with Ramp Still in Shipping Position (W-VAC Only) ..............................6
3-2 Circuit Breaker Shown Being Moved Carefully Down Attached Ramp (W-VAC Only) .............................7
3-3 Optional Fifth Wheel Shown in Use (W-VAC Only)...................................................................................7
3-4 Front View W-VAC 36kV Drawout Vacuum Circuit Breaker ......................................................................9
3-5 W-VAC or W-VACR 36kV Vacuum Circuit Breaker with Front Cover Removed .....................................10
3-6 Rear View W-VAC 36kV Drawout Vacuum Circuit Breaker.....................................................................11
3-7 Rear View W-VACR Fixed Vacuum Circuit Breaker................................................................................12

Effective 3/01
Page vi I.B. 3A74791H06

FIGURES

Figure Title Page

3-8 Typical W-VAC 36kV Escutcheon ...........................................................................................................13


4-1 Type W-VAC Circuit Breaker Manual Charging Handle in Use ...............................................................15
4-2 Drawout Circuit Breaker (Bottom View) ...................................................................................................17
5-1 Rear View Showing Pole Unit Enclosure (W-VAC Only) .........................................................................18
5-2 Plate Over Rear Truck Opening 2000A Breakers and Above (W-VAC Shown) ......................................18
5-3 Graphic Representation of Arc Interruption .............................................................................................19
5-4 Closing Cam and Trip Linkage ................................................................................................................21
5-5 Charging Schematic ................................................................................................................................23
5-6 Typical W-VAC “DC” and “AC” Control Schematics (Drawout) ...............................................................24
5-7 Typical W-VACR “DC” and “AC” Control Schematics (Fixed) .................................................................23
5-8 Secondary Plug Shown Mounted Lower Left Drawout Circuit Breaker ...................................................26
5-9 Secondary Terminal Blocks Shown Mounted Bottom Front Fixed Circuit Breaker..................................27
5-10 Undervoltage Trip Device Configuration..................................................................................................28
6-1 Lubrication Points (Drawout Circuit Breaker Shown)...............................................................................31
6-2 Rear Measurement for Contact Erosion Being Made (Circuit Breaker Closed).......................................34
6-3 Graphical Representation of Contact Erosion Measurement ..................................................................34
6-4 Side View of Loading Spring Indicator (Circuit Breaker Closed) .............................................................35
6-5 Graphical Representation of Contact Wipe Measurement of Loading Spring Indicator ..........................35
6-6 Resistance Measurement Locations .......................................................................................................35
6-7 Status Indicators .....................................................................................................................................36
6-8 Starting Tape at Bottom...........................................................................................................................36
6-9 Wrapping Tape up around Cam ..............................................................................................................36
6-10 Attaching Tape Around to Back of Cam ..................................................................................................37
6-11 Attaching CloSureTM Test Tool at Hole “A” ...............................................................................................37
6-12 Attaching CloSureTM Test Tool at H Pole “B”............................................................................................37
6-13 Manually Charging Closing Springs.........................................................................................................37
6-14 Manually Closing Circuit Breaker with Marker in Hole “C”.......................................................................38
6-15 Top View of Cam and Marker Interface ...................................................................................................38
6-16 Move Marker 15O to Right ........................................................................................................................38
6-17 Move Marker 15O to Left ..........................................................................................................................38
6-18 Remove Marked Masking Tape from Cam ..............................................................................................38
6-19 Place Tape on Right Side Panel of Breaker ............................................................................................38
6-20 Illustrative Testing Tape Sample .............................................................................................................39
6-21 Front View of CloSureTM Tool Showing Mounting/Testing Hole Locations...............................................39
6-22 Typical Circuit Breaker Front View with CloSureTM Tool Attached ...........................................................39

TABLES

Table Title Page

1.1 Vacuum Circuit Breaker Ratings in Accordance with IEC-56....................................................................2


3.1 Approximate Circuit Breaker Weights .......................................................................................................8
5.1 Circuit Breaker Timing.............................................................................................................................26
6.1 Torque Guidelines...................................................................................................................................30
6.2 Test Voltage ............................................................................................................................................33
6.3 CloSureTM Tool Mounting /Testing Locations by Circuit Breaker Type ....................................................39
6.4 Approximate Resistance Measurements ................................................................................................40
7.1 Recommended Renewal Parts for IEC Rated Breakers .........................................................................43

Effective 3/01
I.B. 3A74791H06 Page 1

SECTION 1: INTRODUCTION ING IS SHOWN ABOVE IN REVERSE TYPE TO


FAMILIARIZE PERSONNEL WITH THE STYLE OF
1-1 PRELIMINARY COMMENTS AND SAFETY PRE- PRESENTATION. THIS WILL HELP TO INSURE
CAUTIONS THAT PERSONNEL ARE ALERT TO WARNINGS,
WHICH MAY APPEAR THROUGHOUT THE DOCU-
This technical document is intended to cover most MENT. IN ADDITION, CAUTIONS ARE ALL UPPER
aspects associated with the installation, application, CASE AND BOLDFACE AS SHOWN BELOW.
operation and maintenance of the W-VAC and W-VACR
Vacuum Circuit Breakers. It is provided as a guide for
authorized and qualified personnel only. Please refer to ! CAUTION
the specific WARNING and CAUTION in Section 1-1.2
before proceeding. If further information is required by COMPLETELY READ AND UNDERSTAND THE MA-
the purchaser regarding a particular installation, applica- TERIAL PRESENTED IN THIS DOCUMENT BEFORE
tion or maintenance activity, a Cutler-Hammer represen- ATTEMPTING INSTALLATION, OPERATION OR
tative should be contacted. APPLICATION OF THE EQUIPMENT. IN ADDITION,
ONLY QUALIFIED PERSONS SHOULD BE PERMIT-
TED TO PERFORM ANY WORK ASSOCIATED WITH
1-1.1 WARRANTY AND LIABILITY THE EQUIPMENT. ANY WIRING INSTRUCTIONS
INFORMATION PRESENTED IN THIS DOCUMENT MUST BE FOL-
LOWED PRECISELY. FAILURE TO DO SO COULD
NO WARRANTIES, EXPRESSED OR IMPLIED, CAUSE PERMANENT EQUIPMENT DAMAGE.
INCLUDING WARRANTIES OF FITNESS FOR A PAR-
TICULAR PURPOSE OF MERCHANTABILITY, OR
WARRANTIES ARISING FROM COURSE OF DEAL- 1-2 GENERAL INFORMATION
ING OR USAGE OF TRADE, ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS AND The purpose of this book is to provide instructions for
DESCRIPTIONS CONTAINED HEREIN. In no event will unpacking, storage, use, operation and maintenance of
Cutler-Hammer be responsible to the purchaser or user Type W-VAC Drawout and Type W-VACR Fixed 36kV
in contract, in tort (including negligence), strict liability or Vacuum Circuit Breakers. They are similar in many
otherwise for any special, indirect, incidental or conse- ways with the main differences centering around the
quential damage or loss whatsoever, including but not secondary/primary connection methods and the mount-
limited to damage or loss of use of equipment, plant or ing methods used. The differences are specifically
power system, cost of capital, loss of power, additional addressed in this book. The Type W-VAC is a horizontal
expenses in the use of existing power facilities, or drawout, roll on the floor type removable interrupter ele-
claims against the purchaser or user by its customers ment. The Type W-VACR is a fixed interrupter element
resulting from the use of the information and descrip- with the customer responsible for all required opera-
tions contained herein. tional and safety interfaces. Designed to IEC Standards
for reliable performance, ease of handling, and simpli-
fied maintenance, W-VAC and W-VACR circuit breakers
1-1.2 SAFETY PRECAUTIONS provide reliable control and protection for electrical
equipment and circuits. In addition, these technological-
All safety codes, safety standards and/or regulations ly advanced circuit breakers provide higher insulation
must be strictly observed in the installation, operation levels in less space, thus reducing the overall
and maintenance of this device. switchgear size.

! WARNING ! WARNING

SATISFACTORY PERFORMANCE OF THESE CIR-


THE WARNINGS AND CAUTIONS INCLUDED AS CUIT BREAKERS IS CONTINGENT UPON PROPER
PART OF THE PROCEDURAL STEPS IN THIS DOCU- APPLICATION, CORRECT INSTALLATION AND
MENT ARE FOR PERSONNEL SAFETY AND PRO- ADEQUATE MAINTENANCE. THIS INSTRUCTION
TECTION OF EQUIPMENT FROM DAMAGE. AN BOOK MUST BE CAREFULLY READ AND FOL-
EXAMPLE OF A TYPICAL WARNING LABEL HEAD- LOWED IN ORDER TO OBTAIN OPTIMUM PERFOR-
MANCE FOR LONG USEFUL LIFE OF THE CIRCUIT
BREAKERS.

Effective 3/01
Page 2 I.B. 3A74791H06

1-3 TYPE W-VAC AND W-VACR VACUUM CIRCUIT BREAKER RATINGS (TABLE 1.1)

EQUIPMENT TO FAIL, RESULTING IN DEATH, BODI-


! WARNING LY INJURY AND PROPERTY DAMAGE.

THE CIRCUIT BREAKERS DESCRIBED IN THIS ALL SAFETY CODES, SAFETY STANDARDS
BOOK ARE DESIGNED AND TESTED TO OPERATE AND/OR REGULATIONS AS THEY MAY BE APPLIED
WITHIN THEIR NAMEPLATE RATINGS. OPERATION TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY
OUTSIDE OF THESE RATINGS MAY CAUSE THE ADHERED TO.

Table 1.1 Vacuum Circuit Breaker Ratings in Accordance with IEC-56 ➀


Identification Rated Values
Circuit Voltage Insulation Level Current Duration Transient Current Values
Breaker Withstand Voltage Normal Short of Short Recovery Short Out of Capacitor Switching Ratings
Type Current at Circuit Circuit Voltage (TRV) Circuit Phase Cable Single Back to Back
50 Hz Breaking Peak Time Making Switching Charging Capacitor Capacitor
Current Value Current Current Current Bank Switching
➃ Current Current
➂ ➂➄

Power Lightning
Frequency Impulse
(1 Minute)

U Uw In Isc tth Uc t3 Id Ic Isb Ibb
kV rms kV rms kV Peak Amperes, rms kA rms Seconds kV Peak µs kA Peak kA Amperes,rms
360 W-VAC 16 36 80 170 630 16 3 62 108 40 4 50 630 630
and 1250 630 630
360 W-VACR 16 1600 630 630
2000 1000 1000
360 W-VAC 20 36 80 170 630 20 3 62 108 50 5 50 630 630
and 1250 630 630
360 W-VACR 20 1600 630 630
2000 1000 1000
360 W-VAC 25 36 80 170 630 25 3 62 108 63 6.3 50 630 630
and 1250 630 630
360 W-VACR 25 1600 630 630
2000 1000 1000
360 W-VAC 32 36 80 170 630 31.5 3 62 108 79 7.9 50 630 630
and 1250 630 630
360 W-VACR 32 1600 630 630
2000 1000 1000

➀ KEMA tested to applicable IEC-56 Standards (rated operating sequence 0 - .3 sec - CO - 15 sec - CO). Typical operating time
values: opening 45 ms, closing 75 ms, and reclosing 18 cycles.
➁ IEC Standards require 70kV. All ratings tested to 80kV.
➂ Also qualified for 250 ampere rating.
➃ U=52kV, Uc=92kV, t3=216µ seconds.
➄ Tested at 20 kA, 5 kHz inrush current.

Effective 3/01
I.B. 3A74791H06 Page 3

1-4 OUTLINES AND DIMENSIONS

35.7 [908 REF]


17.8 [454]
11.8 [300] 11.8 [300]

OPEN/CLOSE M.O.C. OPERATOR


FLOOR TRIPPERS

1.563 [39.7]
.6 [14]

1.938 [49]
64.6 [1641]

4.50 [114]
6.22 [158]
1.0 [26]

SEE PLAN VIEW .63 [16] MIN TRAVEL


IN DIRECTION OF TO TRIP
11.1 [283 REF]

1.7 ARROW "X"


[44]
2.9 [75]

5.4 4.6
[137] [117]
DETAIL PLAN VIEW
9.88 [251] IN DIRECTION OF ARROW “X”
.2 [5] 11.5 (TYP)
12.4 [314] [293]
16.4 [417] 16.4 [417]
17.9 [454]
35.7 [908]

47.1 [1197 REF]


45.8 [1164]
1.70 [43] 16.0 [407]
7.7 [197]
1.0 [26] 27.6 [702]

600A - 1600A CONDUCTORS


OTHERWISE SAME LENGTH
21.00 [533]

AS 2000A CONDUCTORS

DIMENSIONS ARE
17.3 [440]

TO BASE PLATE

THESE DIMENSIONS ARE


TO INTERMEDIATE PAN
7.7 [195]

7.5 [191]

TOC Operator
15.6 [397]
17.4 [441]

17.4 [441]
11.1 [283]

1.8 [46] 1.3 [33] EARTH


CONTACTS
3.3 [85] 9.3 [236]
15.9 [405]
18.2 [462]
24.1 [611]

Figure 1-1 Type W-VAC 36kV Drawout Circuit Breaker Outlines and Dimensions (inches and [mm])

Effective 3/01
Page 4 I.B. 3A74791H06

35.75 [908]
35.13 [892]
11.81 [300] 11.81 [300]

L.H. Pole CTR. Pole R.H. Pole Open / Close


Floor Trippers M.O.C. Switch

87 [17]

1.34 [34]
Travel
171 [43]
.63 [16]
Travel
.63 [16]
4.51 [115]
Minimum Travel
REF.
To Trip
8.22 [158] REF.

View Shows Right Side Inner and Outer Wheel


Channel Removed For Clarity

Terminal Blocks

Proposed Floor Mounting Angles


(Not Furnished by Cutler-
Hammer)
1.77 [44]

15.6 [396]
31.2 [793]

Figure 1-2 Type W-VACR 36kV Fixed Circuit Breaker Outlines and Dimensions (inches and [mm])

Effective 3/01
I.B. 3A74791H06 Page 5

SECTION 2: SAFE PRACTICES • Do not work on a drawout circuit breaker with a sec-
ondary test coupler engaged. Failure to disconnect
2-1 RECOMMENDATIONS the test coupler could result in an electrical shock
leading to death, personal injury or property damage.
Type W-VAC and W-VACR Vacuum Circuit Breakers
are equipped with high speed, high energy operating • Do not work on a closed circuit breaker or a breaker
mechanisms. They are designed with several built-in with closing springs charged. The closing springs
interlocks and safety features to provide safe and proper should be discharged and the main circuit contacts
operating sequences. Cell interlocks used with drawout open before working on the circuit breaker. Failure to
circuit breakers are meant to interact with the appropri- do so could result in cutting or crushing injuries.
ate cell interface and levering mechanism.
• Do not use an open circuit breaker by itself as the sole
means of isolating a high voltage circuit. Remove the
circuit breaker to the Disconnect position and follow all
! WARNING lock-out and tagging rules of the National Electrical
Code and any other applicable codes, regulations and
TO PROTECT THE PERSONNEL ASSOCIATED WITH work rules.
INSTALLATION, OPERATION, AND MAINTENANCE
OF THESE CIRCUIT BREAKERS, THE FOLLOWING • Do not leave a drawout circuit breaker in an intermedi-
PRACTICES MUST BE FOLLOWED: ate position in the cell. Always have the circuit breaker
either in the Disconnect/Test or Connected position.
• Only qualified persons, as defined in the National Failure to do so could result in a flash over and possi-
Electrical Safety Code, who are familiar with the ble death, personal injury or property damage.
installation and maintenance of medium voltage cir-
cuits and equipment, should be permitted to work on • Always remove the maintenance tool from the circuit
these circuit breakers. breaker after charging the closing springs.

• Read these instructions carefully before attempting • Circuit breakers are equipped with safety interlocks.
any installation, operation or maintenance of these cir- Do Not remove, interfere with or in any manner defeat
cuit breakers. them. This may result in death, bodily injury or equip-
ment damage.
• If the final breaker design is drawout, always remove
the breaker from the enclosure before performing any • Do not work on a circuit breaker suspended from a lift-
maintenance. If the breaker is applied in a fixed con- ing yoke or chains. Maintenance work should be per-
figuration, always make sure that primary and sec- formed on a solid work surface, such as the floor.
ondary power are disconnected from the breaker.
Failure to do so could result in electrical shock leading
to death, severe personal injury or property damage.

Effective 3/01
Page 6 I.B. 3A74791H06

SECTION 3: RECEIVING, HANDLING AND OR FOR OPENING, CLOSING THE CONTACTS OR


STORAGE CHARGING THE SPRINGS. THE CIRCUIT BREAKER
MAY SLIP OR FALL CAUSING SEVERE PERSONAL
INJURY. ALWAYS PERFORM MAINTENANCE,
3-1 GENERAL
REPAIR AND ADJUSTMENTS ON A SOLID WORK
SURFACE CAPABLE OF SUPPORTING THE CIR-
Type W-VAC and W-VACR Vacuum Circuit Breakers
CUIT BREAKER.
are subjected to complete factory production tests in
accordance with IEC 56 and inspection before being
W-VAC and W-VACR 36kV Vacuum Circuit Breakers
packed. They are shipped in packages designed to pro-
are shipped mounted to a skid specially designed to
vide maximum protection to the equipment during ship-
facilitate removal of the breaker. Refer to Figures 3-1
ment and storage and at the same time to provide con-
and 3-2 and proceed with the following steps:
venient handling. Tools and accessories, such as the
maintenance tool, are shipped separately.

3-2 RECEIVING
! WARNING

AFTER REMOVING THE BRACKETS USED TO HOLD


If the circuit breaker is not to be used immediately but is
THE CIRCUIT BREAKER SECURELY TO THE SHIP-
to be placed in storage, maximum protection can be
PING SKID AND ALL DURING THE PROCESS OF
obtained by keeping it packed as shipped.
MOVING THE CIRCUIT BREAKER OFF OF THE SHIP-
PING SKID AND DOWN THE RAMP TO THE FLOOR,
Upon receipt of the equipment, inspect the containers
TAKE SPECIAL PRECAUTIONS TO INSURE THAT
for any signs of damage or rough handling. Open the
THE CIRCUIT BREAKER IS MOVED SLOWLY AND
containers carefully to avoid any damage to the con-
UNDER CONTROL TO AVOID ANY ACCIDENTS. THE
tents. Use a nail puller rather than a crow bar when
CIRCUIT BREAKER IS A LARGE DEVICE WHICH
required. When opening the containers, be careful to
COULD CAUSE SERIOUS BODILY INJURY IF IT IS
save any loose items or hardware that may be other-
TIPPED OVER OR PERMITTED TO ROLL IN AN
wise discarded with the packing material. Check the
UNCONTROLLED MANNER.
contents of each package against the packing list.

Examine the circuit breaker for any signs of shipping Lifting


damage such as broken, missing or loose hardware, Yoke
damaged or deformed insulation and other components. Opening
File claims immediately with the carrier if damage or loss
is detected and notify the nearest Cutler-Hammer Office.

NOTICE

The W-VAC and W-VACR 36kV shipping container


and pallet were specifically designed to facilitate
removal of the circuit breaker from its pallet and
container. Before proceeding, installation personnel
should be familiar with the procedures outlined in
Paragraph 3-3 entitled “Handling.”

3-3 HANDLING

! WARNING

DO NOT USE ANY LIFTING DEVICE AS A PLAT-


FORM FOR PERFORMING MAINTENANCE, REPAIR Figure 3-1 Circuit Breaker Shown Mounted with Ramp
OR ADJUSTMENT OF THE CIRCUIT BREAKER OR Still in Shipping Position (W-VAC Only)

Effective 3/01
I.B. 3A74791H06 Page 7

Step 1: W-VACR breakers must be lifted from the


shipping pallet. Refer to paragraph 3-5 for the
optional lifting yoke used with an overhead lift-
ing device after all shipping hardware used to
hold the breaker to the skid is removed.

Step 2: For W-VAC breakers, remove the vertically


mounted ramp from the shipping skid and
place it on the floor next to the skid. It should
be positioned with the highest part of the
ramp next to the side of the skid with the front
of the circuit breaker.

Step 3: Remove the shipping brackets used to hold


the circuit breaker to the skid. Use the same
shipping brackets and hardware to attach the
ramp to the shipping skid.

Step 4: Slowly move the circuit breaker forward and


down the ramp. Make certain that the circuit
breaker moves down the ramp slowly and
straight in line with the ramp. Once the circuit
breaker is on the floor, it can be easily ma-
neuvered via its integral wheels. Figure 3-3 Optional Fifth Wheel Shown in Use
(W-VAC Only)
W-VAC breakers can also be lifted using the
optional lifting yoke described in Step 1.

3-4 STORAGE

If the circuit breaker is to be placed in storage, maxi-


mum protection can be obtained by keeping it packed
as shipped. Before placing it in storage, checks should
be made to make sure that the circuit breaker is free
from shipping damage and is in satisfactory operating
condition.

The circuit breaker is shipped with its contacts open and


closing springs discharged. The indicators on the front
panel should confirm this. Insert the maintenance tool in
the manual charge socket opening (Figure 3-8).

Charge the closing springs by pumping the handle up


and down approximately 38 times until a crisp metallic
“click” is heard. This indicates that the closing springs
are charged and is shown by the closing spring
“charged” (yellow) indicator. Remove the maintenance
tool. Push the “manual close” button. The circuit breaker
will close as shown by the circuit breaker contacts
“closed” (red) indicator. Push the “manual trip” button.
The circuit breaker will trip as shown by the circuit
breaker contacts “open” (green) indicator. After complet-
ing this initial check, leave the closing springs “dis-
Figure 3-2 Circuit Breaker Shown Being Moved charged” and circuit breaker contacts “open”.
Carefully Down Attached Ramp (W-VAC Only)

Effective 3/01
Page 8 I.B. 3A74791H06

Outdoor storage is NOT recommended. If unavoidable, 3-6 TYPE W-VAC AND W-VACR VACUUM CIRCUIT
the outdoor location must be well drained and a tempo- BREAKER WEIGHTS (TABLE 3.1)
rary shelter from sun, rain, snow, corrosive fumes, dirt,
falling objects and excessive moisture must be provid- Table 3.1 Approximate Circuit Breaker Weights ➀
ed. Containers should be arranged to permit free circu- Rating Pounds
lation of air on all sides and temporary heaters should
be used to minimize condensation. Moisture can cause 360 W-VAC 16 630 1070
rusting of metal parts and deterioration of high voltage 1250 1080
insulation. A heat level of approximately 400 watts for 1600 1090
each 100 cubic feet of volume is recommended with the 2000 1140
heaters distributed uniformly throughout the structure
near the floor. 360 W-VACR 16 630 937
1250 948
Indoor storage should be in a building with sufficient 1600 958
heat and air circulation to prevent condensation. If the 2000 1025
building is not heated, the same general rule for heat as
for outdoor storage should be applied. 360 W-VAC 20 630 1070
1250 1080
1600 1090
3-5 TOOLS AND ACCESSORIES 2000 1140

Several tools and accessories, both standard and 360 W-VACR 20 630 937
optional are available for use with the circuit breaker. 1250 948
1600 958
Maintenance Tool (Standard): Used to charge closing 2000 1025
springs.
360 W-VAC 25 630 1070
Lifting Yoke (Optional): Used to lift circuit breaker with 1250 1080
overhead lifting device. 1600 1090
2000 1140
Fifth Wheel (Optional): Used to maneuver a circuit
breaker on a flat, hard surface (Figure 3-3). 360 W-VACR 25 630 937
1250 948
1600 958
2000 1025

380 W-VAC 32 630 1070


1250 1080
1600 1090
2000 1140

360 W-VACR 32 630 937


1250 948
1600 958
2000 1025
➀ Does not include shipping carton.

Effective 3/01
I.B. 3A74791H06 Page 9

4
3

1 Front Cover
2 Lift/Pull Handle
3 Circuit Breaker Wheel
4 Secondary Contact Block
5 Alignment Rollers

Figure 3-4 Front View W-VAC 36kV Drawout Vacuum Circuit Breaker

Effective 3/01
Page 10 I.B. 3A74791H06

1 2 3

5
13
6

12

8
11

10 9

1 L.H. Closing Spring 8 Shock Absorber


2 Motor Cutoff Switch 9 Shunt Trip Assembly
3 R.H. Closing Spring 10 Spring Release (Close Coil) Assembly
4 Opening Spring 11 Closing Cam
5 Manual Charge Socket 12 Open/Close Indicator
6 Ratchet Wheel 13 Operations Counter
7 Charging Motor

Figure 3-5 W-VAC or W-VACR 36kV Vacuum Circuit Breaker with Front Cover Removed

Effective 3/01
I.B. 3A74791H06 Page 11

6
7 5

1 Pole Unit
2 Primary Disconnect
3 Insulation Shroud
4 Opening to View Contact Erosion Mark
5 Circuit Breaker Wheel
6 Alignment Rollers
7 TOC Operator

Figure 3-6 Rear View W-VAC 36kV Drawout Vacuum Circuit Breaker

Effective 3/01
Page 12 I.B. 3A74791H06

1 Pole Unit
2 Opening to View Contact Erosion Mark
3 Conductor Mounting Surface

Figure 3-7 Rear View W-VACR 36kV Fixed Vacuum Circuit Breaker

Effective 3/01
I.B. 3A74791H06 Page 13

6 3

5 4

1 Manual Charge Socket


2 Spring Charged/Discharged Indicator
3 Rating Nameplate
4 Manual Open Button
5 Manual Close Button
6 Open/Close Indicator
7 Operations Counter

Figure 3-8 Typical W-VAC 36kV Escutcheon

Effective 3/01
Page 14 I.B. 3A74791H06

SECTION 4: INITIAL INSPECTION AND 4-4 INSULATION


INSTALLATION
Check the circuit breaker’s primary and secondary insu-
lation as described in Section 6.
4-1 INTRODUCTION

4-5 CONTACT EROSION AND WIPE


! WARNING
Manually charge the closing springs and close the cir-
BEFORE PLACING THE CIRCUIT BREAKER IN SER- cuit breaker. Check contact erosion and wipe as
VICE, CAREFULLY FOLLOW THE INSTALLATION described in Section 6.
PROCEDURE GIVEN BELOW. NOT FOLLOWING
THE PROCEDURE CAN FAIL TO UNCOVER SHIP-
PING DAMAGE THAT MAY RESULT IN INCORRECT 4-6 PRIMARY CIRCUIT RESISTANCE
CIRCUIT BREAKER OPERATION LEADING TO
DEATH, BODILY INJURY, AND EQUIPMENT DAM- Check the primary circuit resistance as described in
AGE. Section 6. The resistance should not exceed the values
specified. Record the values obtained for future refer-
Before attempting to put a circuit breaker in service, it ence.
should be carefully examined and operated manually
and electrically. In addition, carefully examine the break-
er for loose or obviously damaged parts. The following 4-7 NAMEPLATE
information is a guide for performing recommended
checks and tests. Compare the circuit breaker nameplate information with
switchgear drawings for compatibility.

4-2 MANUAL OPERATION CHECK


4-8 ELECTRICAL OPERATION CHECK
Refer to Figures 3-8 and 4-1 and then proceed by plac-
ing the maintenance tool into the manual charge socket After having completed all previous checks and tests,
opening. Charge the closing springs with about 38 up the circuit breaker is ready to be operated electrically. It
and down strokes of the handle. When charging is com- is preferred that this check be made with the circuit
plete the closing crank goes over center with an audible
CLICK and the springs Charged/Discharged indicator
shows “Charged.”

NOTICE
If the springs are to be charged on a closed circuit
breaker, no click is heard at the end of charging
operation. Discontinue charging and remove the
maintenance tool as soon as “Charged” flag is fully
visible. Continued attempts to charge further may
result in damage to the mechanism.

Remove the maintenance tool. Close and trip the circuit


breaker. Repeat several times.

4-3 VACUUM INTERRUPTER INTEGRITY

Using a dry, lint free cloth or paper towel, clean all the
accessible insulating surfaces of the pole units. Conduct
a vacuum interrupter integrity check as described in Figure 4-1 Type W-VAC Circuit Breaker Manual
Section 6. Charging Handle in Use

Effective 3/01
I.B. 3A74791H06 Page 15

breaker in a TEST position or by using a test cable, if cuit breaker, manually engaging the secondary contacts
the circuit breaker is outside the cell structure. now makes this the TEST position.

For fixed breaker applications, an electrical operations To engage the secondary contacts, grasp the structure
check should be performed after the breaker is appropri- mounted secondary disconnect cage handle located
ately mounted, secondary wiring completed, and appro- below the left side of the circuit breaker, and pull it for-
priate interphase barriers installed. ward as far as possible to make the secondary engage-
ment. As soon as control power is available, the motor
will charge the closing springs.
! CAUTION
To move the circuit breaker to the CONNECTED posi-
BEFORE INSERTING THE CIRCUIT BREAKER EXAM- tion, engage the levering crank with the structure mount-
INE THE INSIDE OF THE CELL STRUCTURE FOR ed levering shaft and begin turning the handle in a
EXCESSIVE DIRT OR ANYTHING THAT MIGHT INTER- clockwise direction. Keep in mind that the levering crank
FERE WITH THE CIRCUIT BREAKER MOVEMENT. cannot be engaged with the circuit breaker closed.
Structure mounted positive guidance rails interface with
the circuit breaker alignment rollers to insure proper pri-
mary and secondary connections.
! WARNING

EXTREME CAUTION MUST BE EXERCISED TO


INSURE THAT PRIMARY CIRCUITS ARE NOT ENER- NOTICE
GIZED WHILE CHECKS ARE PERFORMED IN THE
CIRCUIT BREAKER COMPARTMENT. FAILURE TO The circuit breaker includes all necessary interlocks
DO SO MAY RESULT IN PERSONAL INJURY OR that when interfaced with a compatible structure will
DEATH. render the circuit breaker mechanism mechanically
and electrically trip-free during the levering process
The circuit breaker is normally tested electrically in its into or out of the structure. For detailed information
cell structure in the TEST position. To achieve the TEST pertaining to individual circuit breaker interlocks,
position, the circuit breaker must first be placed in the refer to Paragraph 4-9 in this section.
cell structure and the secondary contacts engaged. To
complete this testing procedure, the operator should first As the handle is turned, the circuit breaker will move
be familiar with inserting and removing the circuit break- slowly toward the rear of the structure and the integrally
er into and from the cell structure. mounted floor movement wheels will be lifted from the
floor of the structure. Eventually, the integrally mounted
wheels are separated from the structure floor by approx-
4-8.1 CIRCUIT BREAKER INSERTION AND imately 1/8 inch, and the circuit breaker is suspended in
REMOVAL the structure. This design insures positive primary and
secondary connections, even if the assembly’s mount-
The drawout W-VAC circuit breaker is designed to be in ing conditions are less than ideal.
one of three different positions within the structure with
the door closed, DISCONNECT, TEST and CONNECT- When the circuit breaker reaches the CONNECTED
ED. While in the structure, the circuit breaker should position, it will become impossible to continue turning
never be allowed to remain at an intermediate position the levering crank in the clockwise direction. The sec-
between two of the three above mentioned designed ondary contacts will automatically engage in the CON-
positions. NECTED position, if not already engaged manually in
the TEST position.
Position the circuit breaker squarely in front of the struc-
ture. Integrally mounted wheels facilitate circuit breaker To remove the circuit breaker from the structure,
movement outside of and into the structure. Once the reverse the procedure just described by turning the lev-
side mounted circuit breaker alignment rollers are ering crank in a counterclockwise direction. Keep in
aligned with structure mounted alignment rails, push the mind that safety interlocks may cause the circuit breaker
circuit breaker into the structure as far as it will move. to open and/or springs discharge during the removal
The levering latch must be fully engaged or the circuit procedure. It depends on what condition the circuit
breaker will not be able to be inserted. This first position breaker was in as removal began.
is the DISCONNECT position. Without moving the cir-

Effective 3/01
Page 16 I.B. 3A74791H06

4-8.2 OPERATION CHECK PERFORMANCE Close and Trip Floor Trippers


Mounted on the bottom of the circuit breaker, these
Move the W-VAC circuit breaker to the TEST position interlocks interface with compatible structure interlocks
and engage the secondary contacts following the proce- to render the circuit breaker mechanism mechanically
dure described in Paragraph 4-8.1. As soon as control and electrically trip free during the levering process.
power becomes available, the motor will charge the
closing springs with this condition indicated by a Spring Anti-Close Interlock
Charged/Discharged Indicator on the front of the circuit
breaker (Figure 3-8). In addition, the status of the main This interlock prevents releasing the closing springs
contacts, open or closed, is indicated on the front of the electrically or manually if the circuit breaker is already
circuit breaker. closed (Figure 5-5). On a closed circuit breaker, the
interlock lever moves toward the rear. In this position,
Using the close and trip buttons on the front of the cir- the movement of the spring release clapper does not lift
cuit breaker, close and trip the circuit breaker several the lever and thus the spring release latch cannot be
times to verify the closing and tripping operations. moved.
Conclude the check by closing the circuit breaker.

The W-VACR fixed circuit breaker can be checked in a 4-9.2 DRAWOUT BREAKER INTERFACING CHECK
similar fashion as long as the circuit breaker is isolated (W-VAC)
with no primary power present. The operation perfor-
mance can be conducted as long as secondary control Keep in mind that an interfacing check will be made with
power is present. a compatible structure. As such, the instructions provid-
ed with the assembly will suggest other interfacing con-
ditions that should be observed and/or checked, such as
4-9 BREAKER/STRUCTURE INTERFACING primary shutter operation, MOC/TOC operation and lev-
ering handle insertion. A complete, coordinated inter-
Type W-VAC Vacuum Circuit Breakers are supplied with face check, therefore, will be a blend of the circuit
a series of interlocks to insure safe and proper interfac- breaker instructions and those provided with the struc-
ing between the circuit breaker and a compatible struc- tural assembly. Together all required standards are met
ture compartment. The specific interlocks are described and the ultimate in safety is achieved.
in the next paragraph to provide the proper familiariza-
tion. Once the interlocks are reviewed, an interfacing Insert the circuit breaker into the structure and lever it
check can be performed as described in Paragraph into and out of each different position by following the
4-9.2. procedures described in Paragraph 4-8.1.

When the secondary contacts are manually engaged in


4-9.1 INTERFACE INTERLOCKS the TEST position, the motor will charge the closing
springs. Close the circuit breaker. Attempt to engage the
Each circuit breaker is supplied with the following inter- levering crank to begin moving the circuit breaker to the
locks to insure safe and proper operation (Figure 4-2): CONNECTED position. It will first be noticed that the
levering crank cannot be engaged with the breaker
Code Plates (W-VAC Only) closed. In addition, charged springs will be discharged
as the circuit breaker starts to move.
Code plates are mounted at the bottom of the circuit
breaker to prevent the insertion of a circuit breaker into Once in the CONNECTED position, remove the levering
a structure of higher power rating. A set of two code handle, close the circuit breaker and the motor will begin
plates on the circuit breaker and two in the compartment charging the closing springs if control power is available.
form this interlock. Once again engage the levering handle which can only
be accomplished with the circuit breaker open.
NOTICE
Lever the circuit breaker toward the TEST position. The
circuit breaker will be in a trip-free condition. Continue to
Code plates do not block out control voltage or lever the circuit breaker all the way to the TEST position
scheme incompatibility. and the secondary contacts will be disengaged, now
making it the DISCONNECT position

Effective 3/01
I.B. 3A74791H06 Page 17

1 2 3 4 5

1 Secondary Disconnect Plug 4 MOC Operator


2 Close Floor Tripper 5 Code Plates
3 Trip Floor Tripper 6 Position of Optional Second
Secondary Disconnect

Figure 4-2 Drawout Circuit Breaker (Bottom View)

Manually engage the secondary contacts and the motor


will charge the closing springs. Close the circuit breaker
and begin to remove the circuit breaker to the WITH-
DRAWN position by lifting and pulling on the Lift/Pull
handle. The circuit breaker will trip, close and trip as it
moves from the TEST position.

The suggested combination of interface checks outlined


in the circuit breaker manual and structural assembly
manual are intended to verify safe and proper operation.
If observed conditions are not as described, contact
Cutler-Hammer for assistance.

Effective 3/01
Page 18 I.B. 3A74791H06

SECTION 5: DESCRIPTION AND cross-linked polyolefin insulation is used throughout the


OPERATION control circuits with all terminals being of the screw type.
This section describes the overall operation of the circuit
breaker as well as the function and operation of all
5-1 INTRODUCTION
major sub-assemblies and/or parts.
The Type W-VAC 36kV Vacuum Circuit Breaker is a
horizontal drawout roll on the floor design for use in new
5-2 INTERRUPTER ASSEMBLY
switchgear, as well as for modernization and life exten-
sion of existing switchgear. The Type W-VACR Vacuum
The W-VAC and W-VACR 36kV designs utilize three
Circuit Breaker is a fixed design, with the customer
individually mounted and removable pole units. Each
responsible for all required interfaces and barriers.
pole unit is enclosed in a four sided continuous chimney
Either design is for use in new switchgear, as well as for
type cycloaliphatic epoxy support molding. Black insulat-
modernization and life extension of existing switchgear.
ing shrouds cover and seal the openings where upper
The circuit breakers meet or exceed all applicable IEC
and lower primary conductors enter and exit the
Standards.
cycloali-phatic epoxy enclosure (Figure 5-1). The dis-
connecting ends of the primary conductors utilize round,
Circuit breakers are operated by a motor charged spring
floating type primary disconnecting finger clusters for
type stored energy mechanism, charged normally by an
interfacing with the switchgear structure mounted prima-
electric motor or manually by a manual charging tool.
ry conductors.
The primary disconnecting contacts are self-aligning, sil-
ver plated copper. VCP-W Circuit Breakers are of a mod-
The rear portion of the circuit breaker, on which the pole
ular type construction containing a front accessible
units are mounted, utilizes a bolted on plate to cover a
mechanism with unobstructed access to control compo-
rectangular opening in the truck for circuit breakers
nents. Self-contained vacuum interrupter pole unit
above 1600 amperes. Closure of the opening provides
assemblies are removable as complete individual units.
for proper air circulation up through each pole unit
enclosure on 2000 ampere and above circuit breakers
The primary insulation used in the circuit breaker design is
(Figure 5-2).
cycloaliphatic epoxy. Type SIS, AWG #14 control wire with

Figure 5-1 Rear View Showing Pole Unit Enclosure Figure 5-2 Plate Over Rear Truck Opening 2000A
(W-VAC Shown) Breakers and Above (W-VAC Shown)

Effective 3/01
I.B. 3A74791H06 Page 19

! CAUTION
Shield Involvement
Interruption
THE PLATE BOLTED TO THE REAR RECTANGU- Arc Current
LAR OPENING ON ALL 2000 AMPERE AND ABOVE Initiation High Current Zero
CIRCUIT BREAKERS AND IDENTIFIED IN FIGURE 5- Arc Mode
2 MUST BE BOLTED IN POSITION BEFORE PLAC-
Fault
ING A CIRCUIT BREAKER IN SERVICE TO INSURE Current
PROPER OPERATION WITHIN TEST PROVEN
PARAMETERS.

Vacuum interrupters are mounted vertically and support-


ed from the fixed stem which is clamped to the top con-
ductor. The exclusive current transfer system consists of
a series of plated, high-conductivity copper leaf conduc-
tors that are pressed on the movable interrupter stem. Recovery
This design provides a multipoint contact resulting in low Voltage
electrical and thermal resistance. Utilizing this non-slid-
ing current transfer system between the movable stem
and the circuit breaker main conductor eliminates main-
tenance of this joint.

Direct acting insulated operating rods in conjunction with Figure 5-3 Graphic Representation of Arc Interruption
the circuit breaker’s mechanism provide a fixed amount
of interrupter movable stem motion. This motion is
directly related to the interrupter’s “Wipe” and “Stroke,”
each of which is discussed in detail later in this section. At current zero, the arc is extinguished and vapor produc-
tion ceases. Very rapid dispersion, cooling, recombina-
tion, and deionization of the metal vapor plasma, togeth-
5-2.1 VACUUM INTERRUPTER erwith the fast condensation of metal vapor products,
cause the vacuum to be quickly restored. Hence, the
W-VAC and W-VACR 36kV Vacuum Circuit Breakers opened contacts withstand the transient recovery voltage.
utilize vacuum interrupters for interruption and switching
functions. The vacuum interrupters use axial-magnetic,
copper chrome contacts for superior dielectric strength, 5-2.2 CONTACT EROSION INDICATION
better performance characteristics, and lower chop cur-
rent. Vacuum interruption provides the advantages of The purpose of a contact erosion indicator is to monitor
enclosed interrupters, reduced size and weight, short the erosion of the vacuum interrupter contacts, which is
interrupting time, long life, reduced maintenance, and very minimal over time with vacuum interrupters utilizing
environmental compatibility. copper-chrome contact material. If contact erosion
reaches 1/8 inch, the interrupter must be replaced.
Arc interruption is simple and fast (Figure 5-3). In the
closed position, current flows through the interrupter. NOTICE
When the contacts are opened, the arc is drawn
between the contact surfaces. It is moved rapidly
around the slotted contact surfaces by a self-induced Each phase of the circuit breaker is monitored inde-
magnetic force which prevents gross contact erosion as pendently.
well as the formation of hot spots on contact surfaces.
The arc burns in an ionized metal vapor which continu- Contact erosion is monitored from the rear of the circuit
ally leaves the contact area and condenses on the sur- breaker. It provides a very accurate indication of contact
rounding metal shield. erosion, and is the primary determinant of contact condi-
tion. A contact erosion indicator mark is located on the
insulated drive rod of each interrupter (Figure 6-2).

Effective 3/01
Page 20 I.B. 3A74791H06

5-2.3 LOADING SPRING INDICATION AND OPEN THE CIRCUIT BREAKERS BEFORE PER-
FORMING ANY CIRCUIT BREAKER MAINTENANCE,
The contact loading spring indicator is an additional INSPECTION OR REPAIR.
method provided to indicate conditions within the vacuum
interrupter, as well as the overall system condition. The vis- The spring stored energy operating mechanism is
ible indication, on each phase, is used to indicate whether arranged vertically in front of all W-VAC and W-VACR
the contact loading springs are maintaining the proper con- circuit breakers (Figure 3-5). It includes all the elem-
tact pressure to keep the contacts closed. Severe contact ents for storing the energy, closing and tripping of the
erosion or an adjustment need after an interrupter assem- circuit breaker, as well as manual and electrical con-
bly replacement would result in an unacceptable indication trols. The manual controls are all front accessible.
from this indicator (Figures 6-4 and 6-5). Motion to close and open the interrupter contacts is
provided through operating rods connecting the
mechanism pole shaft to the bell cranks of the inter-
5-2.4 CONTACT WIPE AND STROKE rupter assemblies.

Contact wipe is the indication of (1) the force holding the


vacuum interrupter contacts closed and (2) the energy 5-3.1 OPERATION OF STORED ENERGY
available to hammer the contacts open with sufficient MECHANISM
speed for interruption.
The mechanism stores the closing energy by charging
Stroke is the gap between fixed and moving contacts of the closing springs. The mechanism may rest in any one
a vacuum interrupter with the circuit breaker open. of the four positions shown in Figure 5-4 and as follows:
a. Circuit breaker open, closing springs discharged
The circuit breaker mechanism provides a fixed amount
of motion to the operating rods. The first portion of the b. Circuit breaker open, closing springs charged
motion is used to close the contacts (i.e. stroke) and the c. Circuit breaker closed, closing springs discharged
remainder is used to further compress the preloaded d. Circuit breaker closed, closing springs charged
wipe spring. This additional compression is called wipe.
Wipe and Stroke are thus related to each other. As the
stroke increases due to the erosion of contacts, the wipe 5-3.2 CHARGING
decreases. A great deal of effort has been spent in the
design of all Cutler-Hammer vacuum circuit breakers, in Figure 5-5 is a schematic view of the spring charging
order to eliminate the need for field adjustments of wipe parts of the stored energy mechanism.
or stroke.
The major component of the mechanism is a cam shaft
assembly which consists of a drive shaft to which are
! CAUTION attached two closing spring cranks (one on each end),
the closing cam, drive plates, and a free-wheeling ratch-
et wheel. The ratchet wheel is actuated by an oscillating
THERE IS NO PROVISION FOR IN SERVICE mechanism driven by the motor eccentric. As the ratchet
ADJUSTMENTS OF CONTACT WIPE AND STROKE. wheel rotates, it pushes the drive plates which in turn
ALL SUCH ADJUSTMENTS ARE FACTORY SET rotate the closing spring cranks and the closing cam
AND SHOULD NOT BE ATTEMPTED IN THE FIELD. with it.

5-3 STORED ENERGY MECHANISM The closing spring cranks have spring ends connected
to them, which are in turn coupled to the closing springs.
As the cranks rotate, the closing springs are charged.
! WARNING When the closing springs are completely charged, the
spring cranks go over dead center, and the closing stop
KEEP HANDS AND FINGERS AWAY FROM THE CIR- roller comes against the spring release latch. The clos-
CUIT BREAKER’S INTERNAL PARTS WHILE THE ing springs are now held in the fully charged position.
CIRCUIT BREAKER CONTACTS ARE CLOSED OR
THE CLOSING SPRINGS ARE CHARGED. THE CIR- Closing springs may also be charged manually. Insert
CUIT BREAKER CONTACTS MAY OPEN OR THE the maintenance tool in the manual charging socket.
CLOSING SPRINGS DISCHARGE CAUSING A Move it up and down approximately 38 times until a
CRUSHING INJURY. DISCHARGE THE SPRINGS clicking sound is heard, and the closing springs charg-
ing indicator indicates “Charged.” Any further motion of

Effective 3/01
I.B. 3A74791H06 Page 21

5
1

6 2

7 3

8 4

10

Figure 5-4a Breaker open Figure 5-4b Breaker open


and closing spring discharged and closing spring charged

Figure 5-4c Breaker closed Figure 5-4d Breaker closed


and closing spring discharged and closing spring charged

1 Cam Shaft 5 Main Link Roller 8 Pole Shaft


2 Closing Cam 6 Main Link 9 Pole Unit Actuating Lever
3 Trip Latch 7 Trip Bar “D” Shaft 10 Shock Absorber
4 Banana Link

Figure 5-4 Closing Cam and Trip Linkage

Effective 3/01
Page 22 I.B. 3A74791H06

the maintenance tool will result in free wheeling of the As soon as the control power is applied, the spring
ratchet wheel. charging motor automatically starts charging the closing
springs. When the springs are charged, the motor cut off
LS1/bb switch turns the motor off. The circuit breaker
5-3.3 CLOSING OPERATION may be closed by making the control switch close
(CS/C) contact. Automatically upon closing of the circuit
Figure 5-4 shows the position of the closing cam and breaker, the motor starts charging the closing springs.
tripping linkage. Note that in Figure 5-4a in which the The circuit breaker may be tripped any time by making
circuit breaker is open and the closing springs are dis- the control switch trip (CS/T) contact.
charged, the trip “D” shaft and trip latch are in the
unlatched position. Note the position switch (PS1) contact in the spring
release circuit in the scheme. This contact remains
Once charged, the closing springs can be released to made while the circuit breaker is being levered between
close the circuit breaker by moving the spring release the TEST and CONNECTED positions. Consequently, it
latch out of the way. This is done electrically or manually prevents the circuit breaker from closing automatically,
by depressing the spring release lever, which turns the even though the control close contact (CS/C) may have
spring release latch out of the way of the closing stop been made while the circuit breaker is levered to the
roller. The force of the closing spring rotates the cam CONNECTED position.
shaft through the spring cranks. The closing cam, being
attached to the cam shaft, in turn rotates the pole shaft The position switch (PS2) contact is in the motor circuit.
through the main link to close the circuit breaker. It prevents the motor from starting until the fully CON-
NECTED position is reached and the secondary con-
In Figure 5-4c the linkage is shown with the circuit tacts are firmly engaged.
breaker in the closed position before the closing springs
have been recharged. Interference of the trip “D” shaft When the CS/C contact is made, the SR closes the cir-
with the trip latch prevents the linkage from collapsing, cuit breaker. If the CS/C contact is maintained after the
and the circuit breaker is held closed. circuit breaker closes, the Y relay is picked up. The Y/a
contact seals in Y until CS/C is opened. The Y/b contact
Figure 5-4d shows the circuit breaker in the closed posi- opens the SR circuit, so that even though the circuit
tion after the closing springs have been recharged. Note breaker would subsequently open, it could not be
that the spring charging rotates the closing cam by one reclosed before CS/C was released and remade. This is
half turn. Since the cam surface in contact with the main the anti-pump function.
link roller is cylindrical in this region, the spring charging
operation does not affect the mechanism linkage.
5-4.1 TIMING
Since the primary contacts are completely enclosed in
the vacuum interrupter and not adjustable in any way, a The opening and closing times for the circuit breakers
“Slow Close” capability is not provided with W-VAC or vary depending upon the control voltage and the power
W-VACR circuit breakers. rating. Typical values for 36kV W-VAC and W-VACR
circuit breakers are shown in Table 5.1.

5-3.4 TRIPPING OPERATION


5-4.2 SECONDARY DISCONNECTS
When the trip “D” shaft is turned either by the trip button
or trip coil, all links return to the original “open” condition The W-VAC drawout circuit breaker control wiring is
shown in Figure 5-4a. arranged to connect a standard 24 point male plug with
a corresponding switchgear compartment mounted
female plug. An additional 24 point plug is optional.
5-4 CONTROL SCHEMES
Drawout circuit breakers utilize fixed mounted male
There are two basic control schemes for 36kV W-VAC plugs located under the left bottom portion of the circuit
and W-VACR circuit breakers, one for DC control and breaker truck. When two 24 point plugs are supplied,
one for AC control voltages (Figures 5-6 and 5-7). There they are mounted in a stacked arrangement (Figure 5-
may be different control voltages or more than one trip- 8). Fixed mounted circuit breaker secondary plugs con-
ping element, but the principal mode of operation is as nect to corresponding movable female plugs mounted in
follows: the bottom of the switchgear compartment.

Effective 3/01
I.B. 3A74791H06 Page 23

12
8

11 14

10

3
9

1
13

Breaker Open, Springs Discharged Breaker Closed, Springs Charged

1 Pole Shaft 8 Cam Shaft


2 Anti-Close Interlock 9 Motor Ratchet Lever
3 Spring Release (Close) Latch 10 Drive Pawl
4 Spring Crank 11 Ratchet Wheel
5 Closing Spring 12 Holding Pawl
6 Closing Spring Fixed End 13 Spring Release (Close) Clapper
7 Spring Release (Close) Coil 14 Spring Release Latch (Close Roller)

Figure 5-5 Charging Schematic

Effective 3/01
Page 24 I.B. 3A74791H06

BREAKER DC CONTROL SCHEMATIC


8796C77H01 U1 U2 U3 U4 U5 U6 U7 U8 U9 U10

P a b a b a b a b a b
11

SPRING WL CS GL RL CS PR

9UV
CHARGED C T U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
INDICATING
LIGHT AUXILIARY SWITCH #2 OPTIONAL
UV

10UV
1 2 4 5 6
7 7 8 9 10 3
14
3A

OPTIONS
3

13
Y

9
LS1
DC SOURCE

Y 12

51
53

55

57
bb SR b a
ST a b a b b

9A
M 1
a a
b

52
54

56

58
PS2 LC
14

ST
PS1 Y LS2 LS2 2
bb aa 18 17 16 15 22

10A
10

6 13
21 20 19
4

CUSTOMER MUST FURNISH


24 a THIS “a” CONTACT FROM
AUXILIARY SWITCH WHEN
SECOND TRIP COIL OPTION
N IS CHOSEN AND MAKE THE
APPROPRIATE CONNECTIONS.

BREAKER AC CONTROL SCHEMATIC


U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
8796C77H02
a b a b a b a b a b
1 11

SPRING WL CS GL RL CS PR

9UV
C T U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
CHARGED
INDICATING
LIGHT AUXILIARY SWITCH #2 OPTIONAL
UV

11

9UV
10UV

1 2 4
7 5 9 6 7 8 10 3
14
13

UV
55

Y
9

AC (+)
3A

OPTIONS
3

b 12
AC SOURCE

Y
51
53

57

a CAP TRIP DEV a


SR b
10UV

LS1 AC (-)
ST a b b b
9A

bb
1
a 14
a
52
54

58

M b
LC FOR AC UV
56
14

ST TRIP ONLY
PS2 PSI Y LS2 LS2 2
18 17 15 22
10A

bb aa
10

6 13
21 20 16 19
4

CUSTOMER MUST FURNISH


24 a THIS “a” CONTACT FROM
AUXILIARY SWITCH WHEN
SECOND TRIP COIL OPTION
2 IS CHOSEN AND MAKE THE
APPROPRIATE CONNECTIONS.

CS – Breaker Control Switch – close OPERATION SWITCH TERMINAL


C
LS1 Open until springs ‘C’ and ‘NC’
CS – Breaker Control Switch – trip aa are fully charged Brown Switch
T
Y – Anti Pump Relay LS1 Closed until springs ‘C’ and ‘NO’
SR – Spring Release Coil (Close Coil) bb are fully charged
M – Spring Charging Motor LS2 Open until springs ‘C’ and ‘NC’
ST – Shunt Trip aa are fully charged Black Switch
PR – Protective Relay
– Secondary Disconnect LS2 Closed until springs ‘C’ and ‘NO’
bb are fully charged
LC Open until mechanism ‘C’ and ‘NO’
is reset
PS1 Open in all except between ‘C’ and ‘NC’
‘Test’ and ‘Connected’ positions
PS2 Closed in all except between ‘C’ and ‘NO’
‘Test’ and ‘Connected’ positions

Figure 5-6 Typical W-VAC “DC” and “AC” Control Schematics (Drawout)

Effective 3/01
I.B. 3A74791H06 Page 25

BREAKER DC CONTROL SCHEMATIC


8796C77H01

BREAKER AC CONTROL SCHEMATIC


8796C77H02

CS – Breaker Control Switch – close OPERATION SWITCH TERMINAL


C
LS1 Open until springs ‘C’ and ‘NC’
CS – Breaker Control Switch – trip aa are fully charged Brown Switch
T
Y – Anti Pump Relay LS1 Closed until springs ‘C’ and ‘NO’
SR – Spring Release Coil (Close Coil) bb are fully charged
M – Spring Charging Motor LS2 Open until springs ‘C’ and ‘NC’
ST – Shunt Trip aa are fully charged Black Switch
PR – Protective Relay
– Secondary Disconnect LS2 Closed until springs ‘C’ and ‘NO’
bb are fully charged
LC Open until mechanism ‘C’ and ‘NO’
is reset
PS1 Open in all except between ‘C’ and ‘NC’
‘Test’ and ‘Connected’ positions
PS2 Closed in all except between ‘C’ and ‘NO’
‘Test’ and ‘Connected’ positions

Figure 5-7 Typical W-VACR “DC” and “AC” Control Schematics (Fixed)

Effective 3/01
Page 26 I.B. 3A74791H06

The switchgear compartment mounted secondaries are For a basic understanding of the operation of the under-
of a movable carriage design. Once the circuit breaker voltage trip device refer to the specific items identified in
is in the TEST position, the structure mounted sec- Figure 5-10 and the following operation description.
ondary plug carriage can be manually unlatched and
pulled forward until mating with the circuit breaker 1. With the circuit breaker closed and sufficient voltage
mounted male plugs. To disengage the secondary plugs on the Undervoltage Trip Device coil, the moving
from the TEST position, simply push the carriage to the clapper (1) is held to the stationary yoke (2) by the
rear. Secondary connections are automatically engaged magnetic force produced by the coil (3) against the
or disengaged when moving into or out of the CON- extension springs (4) pulling the moving clapper
NECTED position. apart from the yoke.

2. The moving clapper is connected to the mechanism


5-4.3 SECONDARY TERMINAL BLOCKS Trip D Shaft Lever (5) by a slotted link (6).

W-VACR fixed circuit breakers are supplied with 2 3. When the voltage to the Undervoltage Trip Coil goes
12-point screw type secondary control terminal blocks down as described earlier, the extension springs
for simple secondary control access. A number of points force overcomes the reduced magnetic force and
are used for breaker operation with a number of spare pulls the moving clapper up. The slotted link in turn
contacts for customer use. The terminal blocks are upsets the Trip D Shaft and the circuit breaker trips
located at the lower front of the circuit breaker (5-9). open.
Two additional terminal blocks are available for a sec-
ond auxilliary switch. 4. As the circuit breaker opens, the reset lever (8) con-
nected to the pole shaft lever (7) operates to reset
the moving clapper. As long as the circuit breaker
5-4.4 UNDERVOLTAGE TRIP DEVICE remains open, the reset lever holds down the moving
clapper to the yoke.
The undervoltage trip device for W-VAC and W-VACR
circuit breakers is an electromechanical device that
operates to open the circuit breaker at 30% or less of
the voltage rating of the trip coil. The device does not
open the circuit breaker at values above 60% of the volt-
age rating of its trip coil. It may operate, however, to
open the circuit breaker when the voltage across the trip
coil is greater than 30%, but less than 60% of the volt-
age rating of its trip coil. The circuit breaker can be
closed as long as the voltage to the trip coil is main-
tained at 85% or above the rated level. The undervolt-
age trip device is available only as an instantaneous
type with rated voltages of 48VDC, 125VDC, 250VDC
120VAC and 240VAC.

Table 5.1 Circuit Breaker Timing


Event Milliseconds (maximum)

Closing Time
(From Initiation of Close 75
Signal to Contact Make)

Opening Time
(Initiation of Trip Signal 45
to Contact Break)

Reclosing Time
(Initiation of Trip Signal 190
to Contact Make) Figure 5-8 Secondary Plug Shown Mounted Lower Left
Drawout Circuit Breaker

Effective 3/01
I.B. 3A74791H06 Page 27

5. When the circuit breaker closes, the reset lever 5-7 OPERATIONS COUNTER
moves away from the moving clapper. If the Under-
voltage Trip Device coil has at least 85% of the rated All circuit breakers are equipped with a mechanical
voltage applied, the moving clapper is held to the operations counter. As the circuit breaker opens, the
yoke by the magnetic force, even though the reset linkage connected to the pole shaft lever advances the
lever has moved up. counter reading by one (Figure 3-8).

5-5 INTERLOCKS AND INTERFACING 5-8 GROUND CONTACT

Refer to Paragraph 4-9 of this manual for detailed infor- The ground contact used with the drawout W-VAC cir-
mation concerning circuit breaker interlocks and their cuit breaker is an assembly of spring loaded fingers pro-
interfacing with a switchgear structure compartment. In viding a disconnectable means for grounding the circuit
addition, refer to the instruction manual supplied with breaker chassis, after it has been inserted into a
the switchgear assembly. Customers are responsible for switchgear structure. The ground contact is located on
providing W-VACR interfaces. the lower left portion of the truck chassis. An extension
of the switchgear ground bus is secured to the cell floor
in such a position to engage the ground contact auto-
5-6 LEVERING MECHANISM (W-VAC ONLY) matically, when the circuit breaker is moved into the
DISCONNECT/TEST position. It remains engaged in all
The purpose of the levering mechanism is to move the other circuit breaker positions within the cell. The lever
drawout W-VAC circuit breaker into and out of the CON- is supplied on the W-VACR breaker, but the customer is
NECTED position within the assembly structure. The responsible for supplying the proper interface.
levering mechanism used to move the circuit breaker is
a minimum effort recirculating ball drive design, and is
part of the assembly structure cradle. For additional 5-9 MOC AND TOC SWITCH OPERATIONS
information concerning the levering mechanism, refer to
the instruction manual supplied with the switchgear A MOC operator integral to the circuit breaker engages
assembly. Paragraph 4-8.1 of this manual provides an operating lever of the Mechanism Operated Cell
details concerning the use of the levering mechanism to Switch (MOC) located in the switchgear cell. This MOC
move the circuit breaker into and out of the CONNECT- operator permits the contacts of the MOC Switch to be
ED position within the assembly structure. correlated with the circuit breaker’s contact position.

The cell mounted Truck Operated Cell Switch (TOC) is


operated by movement of the circuit breaker truck into
or out of the CONNECTED position with the W-VAC
only.

Figure 5-9 Secondary Terminal Blocks Shown Mounted


Bottom Front Fixed Circuit Breaker (Shown With
Terminal Blocks for Second Auxilliary Switch)

Effective 3/01
Page 28 I.B. 3A74791H06

4
1

2 3

1 Moving Clapper 5 Trip D Shaft Lever


2 Stationary Yoke 6 Slotted Link
3 UV Trip Device Coil 7 Pole Shaft Lever
4 Extension Springs 8 Reset Lever

Figure 5-10 Undervoltage Trip Device Configuration

Effective 3/01
I.B. 3A74791H06 Page 29

SECTION 6: INSPECTION, MAINTENANCE 4. Follow the steps presented in Paragraph 6-3 entitled
AND TROUBLESHOOTING “Inspection and Maintenance Procedures” for sched-
uled programs.
6-1 INTRODUCTION
5. Create and maintain a dated permanent record of all
inspections, maintenance performed, actions taken,
observations made, and measurements taken. Not
! WARNING only will this provide valuable historical information, it
can help to establish whether or not the present
• DO NOT WORK ON A CIRCUIT BREAKER IN THE schedule needs to be adjusted.
“CONNECTED” POSITION.
6. Perform ongoing visual inspections, when possible,
• DO NOT WORK ON A CIRCUIT BREAKER WITH of all equipment on a regular basis. Be alert for an
SECONDARY DISCONNECTS ENGAGED. accumulation of dirt in and around the circuit break-
• DO NOT WORK ON A CIRCUIT BREAKER WITH ers, loose hardware or discolored insulation.
SPRINGS CHARGED OR CONTACTS CLOSED.
• DO NOT DEFEAT ANY SAFETY INTERLOCKS. 6-2.1 QUALIFIED PERSONNEL
• DO NOT LEAVE MAINTENANCE TOOL IN THE
SOCKET AFTER CHARGING THE CLOSING For the purpose of operating switchgear equipment and
SPRINGS. associated circuit breakers, only individuals thoroughly
trained in the operation of power circuit breakers and
• DO NOT STAND LESS THAN FOUR METERS associated equipment, and having knowledge of con-
AWAY FROM THE BREAKER WHEN TESTING nected loads may be considered to be qualified. Refer
FOR VACUUM INTEGRITY. to further definitions in the National Electrical Safety
Code.
FAILURE TO FOLLOW ANY OF THESE INSTRUC-
TIONS MAY CAUSE DEATH, SERIOUS BODILY For the purpose of inspecting and maintaining such
INJURY, OR PROPERTY DAMAGE. SEE SECTION 2- equipment, a qualified person must also be trained in
SAFE PRACTICES FOR MORE INFORMATION. regard to the hazards inherent to working with electricity
and the proper way to perform such work. Such an indi-
vidual should be able to de-energize, clear and tag cir-
6-2 FREQUENCY OF INSPECTION AND cuits in accordance with established safety practices. In
MAINTENANCE addition, these individuals should have access to and be
trained in the use of protective equipment, such as rub-
Periodic inspections and associated maintenance are ber gloves and flash clothes.
essential to the safe and reliable operation of W-VAC
and W-VACR Vacuum Circuit Breakers. The inspection All personnel should be familiar with and understand the
frequency and associated maintenance recommended material presented in this instruction manual and other
are intended to insure the best possible ongoing ser- related manuals.
vice. It is imperative that an established schedule be fol-
lowed. To establish an exact schedule for a specific
installation, use the following guidelines: 6-2.2 HELPFUL TOOLS AND ACCESSORY ITEMS
1. In a clean, non-corrosive environment, inspect and To simplify the performance of inspection and mainte-
maintain each circuit breaker annually or every 500 nance programs, the items described in Section 3-5 are
operations, which ever comes first. recommended.
2. For special conditions such as frequent circuit break-
er operation, contaminated environments, and high 6-2.3 GENERAL TORQUE GUIDELINES
temperature/humidity conditions, the inspection fre-
quency should be twice a year. Bolts and screws must be properly torqued. This is
especially true if parts and/or accessories are added or
3. Inspect a circuit breaker every time it interrupts fault replaced. Table 6.1 provides guidelines on torque lev-
current. els. The table is intended as a general guideline and

Effective 3/01
Page 30 I.B. 3A74791H06

should be applied in conjunction with the experience Table 6.1 Torque Guidelines
and good judgment of the individual performing the
work. Bolt Size Torque (nm)

8 - 32 2.7

! CAUTION 10 - 32

1/4 - 20
4

8
OVER TORQUING CAN CAUSE PERMANENT DAM-
AGE WHILE UNDER TORQUING WILL NOT PRO- 5/16 - 18 16
VIDE THE PROPER CLAMPING FORCE AND MAY
EVENTUALLY WORK LOOSE. 3/8 - 16 34

1/2 - 13 61

Effective 3/01
I.B. 3A74791H06 Page 31

● Apply one drop of light


machine oil such as
Mobil One at locations
shown.

Figure 6-1 Lubrication Points (Drawout Circuit Breaker Shown)

Effective 3/01
Page 32 I.B. 3A74791H06

6-3 INSPECTION AND MAINTENANCE PROCEDURES

No./Section Inspection Item Criteria Inspection Method Corrective Action

1. Insulation Drive Insulator No dirt Visual Check Clean with lint-free cloth
and and or
Molded Pole Unit Support No cracking Visual Check Replace cracked unit

Insulation Main Circuit to Ground Withstand Hipot Tester Clean and retest or replace
Integrity
Between Main Circuit Withstand Hipot Tester Clean and retest or replace
Terminals

Control Circuit to Ground Withstand Hipot Tester Clean and retest or replace

2. Power Vacuum Interrupters Precise Measure- Measurement - Close the circuit If the front indicator marks are
Elements ment from rear breaker and proceed as described in the red area and the rear
in Paragraph 6-5 measurement is not acceptable,
replace pole unit assembly

Contact wipe Measurement of Loading Spring as If measurement is not acceptable,


measurement described in Paragraph 6-6 replace pole unit assembly

Adequate Vacuum Proceed with integrity check as If integrity check is not satisfactory,
described in Paragraph 6-4 replace pole unit assembly

Primary Disconnects No burning or damage Visual Check Replace if burned, damaged


(W-VAC Only) or eroded

3. Control Closing and Tripping Device Smooth and correct Test closing and tripping of the Replace any defective device. Identify
Circuit Including Disconnects operation by control circuit breaker twice per trouble-shooting chart
Parts power

Wiring Securely tied in Visual Check Repair or tie as necessary


proper place

Terminals Tight Visual Check Tighten or replace if necessary

Motor Smooth, Normal Functional Test Replace brushes or motor


Operation

4. Operating Tightness of Hardware No loose or missing Visual and by feel Refer to Table 6.1 and tighten
Mechanism parts or reinstate if necessary with
appropriate tools

Dust or Foreign Matter No dust or foreign Visual Check Clean as necessary


matter

Lubrication Smooth operation Sight, feel and per maintenance Refer to Figure 6-1, Paragraph
and no excessive schedule 6-11 and lubricate very spar-
wear ingly with light machine oil

Deformation or Excessive No excessive Visual and operational Remove cause and replace parts
Wear deformation or wear

Manual Operation Smooth operation Manual charging, closing Correct per troubleshooting
and tripping chart if necessary

Effective 3/01
I.B. 3A74791H06 Page 33

6-4 VACUUM INTERRUPTER INTEGRITY TEST In this case the equipment must be capable of delivering
5 milliamperes for one minute to avoid ambiguity due to
Vacuum interrupters used in Type W-VAC and W-VACR field emission or leakage currents and the test voltage
36kV Vac-uum Circuit Breakers are highly reliable inter- shall be as shown in Table 6.2.
rupting elements. Satisfactory performance of these
devices is dependent upon the integrity of the vacuum in The current delivery capability of 25 ma ac and 5 ma dc
the interrupter and the internal dielectric strength. Both apply when all three VIs are tested in parallel. If individ-
of these parameters can be readily checked by a one ual VIs are tested, current capability may be one third of
minute ac high potential test. Refer to Table 6.2 for the these values.
appropriate test voltage. During this test, the following
warning must be observed:
! CAUTION

! WARNING SOME DC HIGH POTENTIAL UNITS, OPERATING AS


UNFILTERED HALF-WAVE RECTIFIERS, ARE NOT
APPLYING ABNORMALLY HIGH VOLTAGE ACROSS SUITABLE FOR USE TO TEST VACUUM INTER-
A PAIR OF CONTACTS IN VACUUM MAY PRODUCE RUPTERS BECAUSE THE PEAK VOLTAGE AP-
X-RADIATION. THE RADIATION MAY INCREASE PEARING ACROSS THE INTERRUPTERS CAN BE
WITH THE INCREASE IN VOLTAGE AND/OR DE- SUBSTANTIALLY GREATER THAN THE VALUE
CREASE IN CONTACT SPACING. X-RADIATION READ ON THE METER.
PRODUCED DURING THIS TEST WITH RECOM-
MENDED VOLTAGE AND NORMAL CONTACT
SPACING IS EXTREMELY LOW AND WELL BELOW 6-5 CONTACT EROSION
MAXIMUM PERMITTED BY STANDARDS. HOWEV-
ER, AS A PRECAUTIONARY MEASURE AGAINST In order to determine if the contacts have eroded to the
POSSIBILITY OF APPLICATION OF HIGHER THAN extent that the interrupter must be replaced, close the
RECOMMENDED VOLTAGE AND/OR BELOW NOR- circuit breaker and observe the erosion mark on each
MAL CONTACT SPACING, IT IS RECOMMENDED operating rod from the rear of the circuit breaker. If the
THAT ALL OPERATING PERSONNEL STAND AT mark on the interrupter stem is measured to be more
LEAST FOUR METERS AWAY IN FRONT OF THE than 12 inches from the base of the interrupter, the
CIRCUIT BREAKER. interrupter is satisfactory. If the mark is 12 inches or
less, the interrupter assembly must be replaced (Figures
With the circuit breaker open and sitting solidly on the 6-2 and 6-3).
floor or secured in a fixed position, connect all top pri-
mary studs (bars) together and to the high potential
machine lead. Connect all bottom studs together and 6-6 CONTACT WIPE
ground them along with the circuit breaker frame. Start
the machine at zero potential, increase to appropriate The adequacy of contact wipe can be determined by a
test voltage and maintain for one minute. simple measurement of each loading spring indicator
with the circuit breaker closed. Refer to Figures 6-4 and
A successful withstand indicates that all interrupters 6-5 and measure the indicator distance shown for each
have a satisfactory vacuum level. If there is a break- interrupter. If the measurement taken is in the range of
down, the defective interrupter or interrupters should be 23 to 31 mm, the contact wipe is adequate.
identified by an individual test and replaced before plac-
ing the circuit breaker in service.
Table 6.2 Test Voltage
Vacuum Interrupter Integrity Test Voltage
After the high potential is removed, discharge any elec-
Circuit Breaker Rated
trical charge that may be retained. To avoid any ambi- ac 60 Hz dc
Maximum Voltage
guity in the ac high potential test due to leakage or dis-
placement (capacitive) current, the test unit should have 36 kV rms 60 kV rms 85 kV
sufficient volt-ampere capacity. It is recommended that
the equipment be capable of delivering 25 milliamperes
for one minute.

Although an ac high potential test is recommended, a dc


test may be performed if only a dc test unit is available.

Effective 3/01
Page 34 I.B. 3A74791H06

Base of Interrupter

Standard 300 mm
Metal Scale
Inch
Measurement Line

Figure 6-2 Rear Measurement for Contact Erosion


Being Made (Circuit Breaker Closed) Figure 6-3 Graphical Representation of Contact Erosion
Measurement (Circuit Breaker Closed)

6-7 INSULATION lead of the test machine to one of the poles of the circuit
breaker. Connect the remaining poles and circuit break-
Type W-VAC and W-VACR 36kV Vacuum Circuit er frame to ground. Start the machine with output poten-
Breakers primarily utilize cycloaliphatic epoxy insulation tial at zero and increase to the test voltage. Maintain the
except, for example, the black insulating shrouds. test voltage for one minute. Repeat for the remaining
Insulation maintenance primarily consists of keeping all poles. Successful withstand indicates satisfactory insu-
insulating surfaces clean. This can be done by wiping lation strength of the primary circuit.
off all insulating surfaces with a dry lint free cloth or dry
paper towel. In case there is any tightly adhering dirt If a DC high potential machine is used, make certain
that will not come off by wiping, it can be removed with a that the peak voltage does not exceed the peak of the
mild solvent or distilled water. Be sure that the surfaces corresponding AC rms test voltage.
are dry before placing the circuit breaker in service. If a
solvent is required to cut dirt, use Stoddard’s Solvent Secondary Circuit:
Cutler-Hammer 55812CA or commercial equivalent. Connect all points of the secondary terminal block with
Second-ary control wiring requires inspection for tight- shooting wire. Connect this wire to the high potential
ness of all connections and damage to insulation. lead of the test machine. Ground the circuit breaker
frame. Starting with zero, increase the voltage to 1500
volts rms. Maintain the voltage for one minute. Suc-
6-8 INSULATION INTEGRITY CHECK cessful withstand indicates satisfactory insulation
strength of the secondary control circuit. Remove the
Primary Circuit: shooting wire.
The integrity of primary insulation may be checked by
the 50Hz AC high potential test. The test voltage
depends upon the maximum rated voltage of the circuit 6-9 PRIMARY CIRCUIT RESISTANCE CHECK
breaker. For circuit breakers rated 36kV the test voltage
is 60kV rms. Conduct the test as follows: Since the main contacts are inside the vacuum cham-
ber, they remain clean and require no maintenance at
Close the circuit breaker. Connect the high potential any time. Unlike many typical circuit breaker designs,
W-VAC and W-VACR circuit breakers do not have slid-

Effective 3/01
I.B. 3A74791H06 Page 35

CONTACT WIPE
(23.1 mm to
31.0 mm)

Figure 6-4 Side View of Loading Spring Indicator


(Circuit Breaker Closed)

Figure 6-5 Graphical Representation of Contact Wipe


Measurement of Loading Spring Indicator (Circuit
Breaker Closed)

Measure
Resistance here
(Do not measure
across contact
fingers, only main
conductors)

Measure
Resistance at 2
Identified Points

(W-VAC) (W-VACR)

Figure 6-6 Resistance Measurement Locations

Effective 3/01
Page 36 I.B. 3A74791H06

ing contacts at the moving stem either. Instead they use NO VOLTAGE IS PRESENT BEFORE PROCEEDING
a highly reliable and unique flexible clamp design that WITH THE TASK, AND ALWAYS FOLLOW GENER-
eliminates the need for lubrication and inspection for wear. ALLY ACCEPTED SAFETY PROCEDURES.
If desired, the DC resistance of the primary circuit may Safety Precautions: Read and understand these
be measured as follows: close the circuit breaker, pass instructions before attempting any maintenance, repair
at least 100 amps DC current through the circuit break- or testing on the breaker. The user is cautioned to
er. With a low resistance instrument, measure resis-
tance across the studs on the circuit breaker for each observe all recommendations, warnings and cautions
pole (Figure 6-6).The resistance should not exceed the relating to the safety of personnel and equipment.
values shown in Table 6.4.

6-10 MECHANISM CHECK


B
Make a careful visual inspection of the mechanism for
any loose parts such as bolts, nuts, pins and rings. A Discharged

Check for excessive wear or damage to the circuit


breaker components. Operate the circuit breaker sever-
al times manually and electrically. Check the closing
and opening times to verify that they are in accordance Open

with the limits in Table 5.1.

6-10.1 CLOSURE™ TEST

Introduction: The CloSureTM Test is a simple yet extreme-


ly effective means to determine and monitor the ability of
the mechanism to close the breaker contacts fully. It pro-
vides a quantitative measure of the extra energy available
in terms of over travel in inches to close the breaker con- Figure 6-7 Status Indicators (“A” shows the contact
tacts to their full extent. It may be used periodically to status indication and “B” shows the spring indication.)
monitor the health of the mechanism.
At times, circuit breakers are called upon to operate
MOC switches (mechanism operated control switches)
that place extra load upon the closing mechanism of the
circuit breaker. If this load is excessive, it can prevent
the circuit breaker from closing fully. In such a case, it
is important to determine that the circuit breaker will
close fully. The CloSureTM Test provides this assurance.

General Information: The CloSureTM Test can be per-


formed on the VCP-W, VCP-WR, VCPW-ND, DHP-VR, W-
VACR, W-VAC, W-VACW and W-VACWR lines of vacu-
um circuit breakers Refer to Table 6.3 for a list of circuit
breakers. If the CloSureTM travel obtained is as specified,
the mechanism performance is satisfactory. If the
Figure 6-8 Starting Tape at Bottom of Cam
CloSureTM travel does not conform as shown in Figure 6-
14, contact Cutler-Hammer for further information. (See
Step 13).

! WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM
MAINTENANCE OR TESTS ON THE EQUIPMENT
WHILE IT IS ENERGIZED. NEVER PUT YOUR
HANDS NEAR THE MECHANISM WHEN THE CIR-
CUIT BREAKER IS IN THE CHARGED OR CLOSED
POSITION. DEATH OR SEVERE PERSONAL
INJURY CAN RESULT FROM CONTACT WITH
ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT Figure 6-9 Wrapping Tape Up Around Cam

Effective 3/01
I.B. 3A74791H06 Page 37

The recommendations and information contained herein Step 7 - Charge the closing springs with the mainte-
are based on Cutler-Hammer experience and judgment, nance tool. Continue charging the closing springs
but should not be considered to be all-inclusive or cov- until a “click” is heard and the status indicator shows
ering every application or circumstance which may “Charged” (Figure 6-13).
arise. If further information is required, you should
consult Cutler-Hammer. Step 8 - While holding the marker tip on the tape, close
the breaker (Figure 6-14).
Testing Procedures: Assuming that the breaker is
safely pulled out to the Test/Disconnect position in the Step 9 - Move the marker back and forth horizontally
enclosure or placed on the workbench, follow this proce- approximately 15o in both directions to create a line on
dure to perform the CloSureTM Test. For further instruc- the tape that identifies the closed rest position (Figures
tions on disconnecting the circuit breaker consult 6-15, 6-21 and 6-17).
Section 4 of this manual. If the enclosure is equipped
with the MOC operating in the test position also, make A
certain that the MOC is connected to operate.

Step 1 - On the front cover identify the status indicators.


MAKE SURE THE CLOSING SPRING STATUS INDI-
CATES “Discharged” AND THE MAIN CONTACT
INDICATOR SHOWS “Open” (Figure 6-7).

Step 2 - Remove the circuit breaker front cover. Be sure


to save the original fasteners for reassembly.

Step 3 - Cut a piece of one inch wide drafting/masking


tape approximately 8 to 10 inches long. Figure 6-11 Attaching CloSureTM Test Tool at Hole “A”

Step 4 - Place the tape around the cam starting from the
bottom up. Make certain that the tape adheres well to
the cam surface. (See Figures 6-8, 6-9 and 6-10).

Step 5 - Mount the transparent CloSureTM Test Tool with


two bolts and washers. Refer to Figures 6-21, 6-22 and
Table 6.3 for appropriate mounting holes. Hand tighten
the bolts (Figures 6-11, 6-12, 6-21 and 6-22).
B
Step 6 - A Sanford® Sharpie® black fine point perma-
nent marker, item no. 30001, is recommended for this
next step. Place the marker tip in the proper hole (“C”).
Refer to Figure 6-21 and make a heavy mark on the
tape as shown in Figure 6-14. Figure 6-12 Attaching CloSureTM Test Tool at HPole “B”

Figure 6-10 Attaching Tape Around to Back of Cam Figure 6-13 Manually Charging Closing Springs

Effective 3/01
Page 38 I.B. 3A74791H06

Figure 6-14 Manually Closing Circuit Breaker with Figure 6-17 Move Marker 15o to Left
Marker in Hole “C”.

Cam

ClosureTM Tool

Marker

15o
Figure 6-18 Remove Marked Masking Tape from Cam
15o

Figure 6-15 Top View of Cam and Marker Interface

Figure 6-16 Move Marker 15o to Right Figure 6-19 Place Tape on Right Side Panel of
Breaker
Step 10 - Remove the marker from hole “C”. open position and the closing springs are discharged.
Remove the transparent CloSureTM Tool. Remove the
Step 11 - Push the “push to open” clapper to open the tape from the cam and stick the tape on the front right
circuit breaker. side sheet of the circuit breaker. Record the date of the
Step 12 - Inspect the circuit breaker to assure it is in the test and the operations counter reading on the tape
(Figures 6-18 and 6-19 and 6-20).

Effective 3/01
I.B. 3A74791H06 Page 39

*Figure not to scale


Width
*Note: Use the center of

Date, # of Breaker Operations, ClosureTM Distance


the marker diameter to

Date, # of Breaker Operations, ClosureTM Distance

Date, # of Breaker Operations, ClosureTM Distance


determine “X” distance

5 3/16” Approx

5 3/16” Approx
5 3/16” Approx

8.0 to 10
Inches

“X” Inches
CloSureTM Overtravel

CloSureTM Distance

CloSureTM Position

A B C
Figure 6-20 Illustrative Testing Tape Sample Figure 6-22 Typical Circuit Breaker Front View with
CloSureTM Tool Attached (approximate mechanism
chassis width)
A-1
Breaker Approximate Upper Lower Marker
A-2
Line Mechanism Mounting Mounting Placement
C-2
A-3 Cabinet Hole Hole Hole
C-1 C-3 C-4 C-5 C-6
A-4 Width (inch)
20 A1 B2 C2
DHP-VR
27 A1 B1 C5
VCPW-ND 20/21 A1 B2 C2
27 A1 B2 C5
VCP-W
33 A2 B2 C6
18 A1 B2 C1
VCP-WR 20 A1 B2 C2
B-1 27 A1 B2 C5
B-2 18 A1 B2 C1
W-VAC,
25 A1 B1 C4
Figure 6-21 Front View of CloSureTM Tool Showing W-VACR
Mounting/Testing Hole Locations (6352C49H01) 33 A2 B2 C6

Table 6.3 ClosureTM Tool Mounting/Testing Locations by


Step 13 - Evaluate the CloSure performance by com- TM”
Circuit Breaker Type
paring the test tape with the illustrations in Figure 6-20.
If the marking is similar to 6-20A, measure the over trav- for Technical Support at (412) 787-6518.
el “x”: If “x” is greater than or equal to 0.6 inches, the
circuit breaker performance is satisfactory. If “x” is less Step 14 - Remove the CloSureTM Tool. Reassemble the
than 0.6 inches or if the marking is similar to 6-20B or 6- front cover onto the circuit breaker. Return the circuit
20C, immediately contact the Product Integrity Center breaker to it’s original configuration and setup.

Effective 3/01
Page 40 I.B. 3A74791H06

6-11 LUBRICATION If it becomes necessary to disassemble the mechanism,


the bearings and related parts should be thoroughly
All parts that require lubrication have been lubricated cleaned. Remove old grease in a good grease solvent.
during the assembly with molybdenum disulphide Do not use carbon tetrachloride. They should then be
grease (Cutler-Hammer Material No. 53701QB). Over a washed in light machine oil until the cleaner is removed.
period of time, this lubricant may be pushed out of the After the oil has been drawn off, the bearings should be
way or degrade. Proper lubrication at regular intervals is packed with Cutler-Hammer Grease 53701QB or equiv-
essential for maintaining the reliable performance of the alent.
mechanism. Once a year or every 500 operations
whichever comes first, the circuit breaker should be
relubricated. The locations shown in Figure 6-1 should
be lubricated with a drop of light machine oil.

After lubrication, operate the circuit breaker several Table 6.4 Approximate Resistance Measurements
times manually and electrically.
Rated Continuous Resistance
Roller bearings are used on the pole shaft, the cam Current (amperes) (microohms)
shaft, the main link and the motor eccentric. These
bearings are packed at the factory with a top grade slow 600A 92
oxidizing grease which normally should be effective for 1200A 90
many years. They should not be disturbed unless there 1600A 88
is definite evidence of sluggishness, dirt or parts are dis- 2000A 72
mantled for some reason.

6-12 TROUBLESHOOTING CHART (Continued Next Page)

SYMPTOM INSPECTION AREA PROBABLE DEFECTS

Fails To Close

• Closing Springs not charged • Control Circuit • Control Power


(fuse blown or switch off)

• Secondary Disconnects

• Motor Cut-off Switch


(Poor or burned contacts,
Lever not operational)

• Terminals and connectors


(Poor or burned contacts)

• Motor
(Brushes worn or commutator
segment open)

• Mechanism • Pawls
(Slipping or Broken)

• Ratchet Wheel
(Teeth worn or broken)

• Cam Shaft Assembly


(Sluggish or jammed)

• Oscillator
(Reset spring off or broken)

Effective 3/01
I.B. 3A74791H06 Page 41

6-12 TROUBLESHOOTING CHART (Continued Next Page)

SYMPTOM INSPECTION AREA PROBABLE DEFECTS

Fails To Close

• Closing Spring charged but • No Closing Sound • Control Power


circuit breaker does not close (Close Coil does (Fuse blown or switch off)
not pick up)
• Secondary Disconnects

• Anti-Pump Relay
(Y relay N. C. contact open or
burned or relay picks up)

• Close Coil
(Open or burned)

• Latch Check Switch


(Contact open-bad switch or
trip bar not reset)

• Auxiliary Switch
(b contact open or burned)

• Motor Cut-off
(Contacts open or burned)

• Trip Coil Assembly


(Clapper fails to reset)

• Closing Sound • Pole Shaft


but no close (Not open fully)

• Trip Latch Reset Spring


(Damaged or Missing)

• Trip Bar-D Shaft


(Fails to remain reset)

• Trip Latch-Hatchet
(Fails to remain reset)

• Trip Floor Tripper


(Fails to remain reset)

• Close Latch
(Binding)

• Close Latch Roller


(Binding)

• Trip Circuit Energized

Effective 3/01
Page 42 I.B. 3A74791H06

6-12 TROUBLESHOOTING CHART

SYMPTOM INSPECTION AREA PROBABLE DEFECTS

Undesirably Closes

• Control Circuit • Close Circuit


(CS/C Getting Shorted)

• Mechanism • Close Release Latch


(Fails to reset)

• Close Floor Tripper


(Fails to reset)

Fails To Trip

• No Trip Sound • Control Circuit • Control Power


(Fuse blown or switch off)

• Secondary Disconnect

• Auxiliary Switch
(a contact not making, poor or burned)

• Trip Coil
(Burned or open)

• Terminals and Connections


(Poor or burned or open)

• Trip Mechanism • Trip Clapper


(Jammed)

• Trip Sound • Trip Mechanism • Trip Bar, Trip Latch


But No Trip (Jammed)

• Pole Shaft
(Jammed)

• Operating Rod Assembly


(Broken or pins out)

• Vacuum Interrupter
(One or more welded)

Undesirably Trips

• Control Circuit • Control Power


(CS/T Switch, remains made)

• Mechanism • Trip Coil Clapper


(Not resetting)

• Trip Bar or Trip Latch


(Poor engagement of mating
or worn surfaces)

• Trip Bar Reset Spring


(Loss of torque)

Effective 3/01
I.B. 3A74791H06 Page 43

SECTION 7: RENEWAL PARTS 7-1.1 ORDERING INSTRUCTIONS

7-1 GENERAL a. Always specify the breaker rating information and


shop order number.
In order to minimize production downtime, it is recom- b. Describe the item, give the style number, and specify
mended that an adequate quantity of spare parts be car- the quantity required.
ried in stock. The quantity will vary from customer to c. Specify the voltage for electrical components.
customer, depending upon the service severity and con- d. Specify the method of shipping desired
tinuity requirements. Each customer should develop his e. Send all orders or correspondence to the nearest
own stock level based on operating experience. Refer to Cutler-Hammer sales office.
Table 7.1 for guidance.
7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)

LINE DESCRIPTION STYLE NUMBER QTY


NO. W-VAC and/or W-VACR

Interrupter Assembly W-VAC

1 360/16, 630A - 16kA 3A74837H01 3


2 360/16, 1250A - 16kA 3A74838H01 3
3 360/16, 1600A - 16kA 3A74839H01 3

W-VAC

4 360/16, 2000A - 16kA 3A74840H01 3

W-VACR

5 360/16, 630A - 16kA 3A74686H01 3


6 360/16, 1250A - 16kA 3A74686H02 3
7 360/16, 1600A - 16kA 3A74686H03 3
8 360/16, 2000A - 16kA 3A74686H04 3

W-VAC

9 360/20, 630A - 20kA 3A74807H01 3


10 360/20, 1250A - 20kA 3A74808H01 3
11 360/20, 1600A - 20kA 3A74809H01 3

W-VAC

12 360/20, 2000A - 20kA 3A74810H01 3

W-VACR
13 360/20, 630A - 20kA 3A74686H11 3
14 360/20, 1250A - 20kA 3A74686H12 3
15 360/20, 1600A - 20kA 3A74686H13 3
16 360/20, 2000A - 20kA 3A74686H14 3

Effective 3/01
Page 44 I.B. 3A74791H06

7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)

LINE DESCRIPTION STYLE NUMBER QTY


NO. W-VAC and/or W-VACR
W-VAC

17 360/25, 630A - 25kA 3A74851H01 3


18 360/25, 1250A - 25kA 3A74852H01 3
19 360/25, 1600A - 25kA 3A74853H01 3

W-VAC

20 360/25, 2000A - 25kA 3A74854H01 3

W-VACR

21 360/25, 630A - 25kA 3A74686H21 3


22 360/25, 1250A - 25kA 3A74686H22 3
23 360/25, 1600A - 25kA 3A74686H23 3
24 360/25, 2000A - 25kA 3A74686H24 3

W-VAC

25 360/32, 630A - 31.5kA 3A74858H01 3


26 360/32, 1250A - 31.5kA 3A74859H01 3
27 360/32, 1600A - 31.5kA 3A74860H01 3

W-VAC

28 360/32, 2000A - 31.5kA 3A74861H01 3

W-VACR

29 360/32, 630A - 31.5kA 3A74686H31 3


30 360/32, 1250A - 31.5kA 3A74686H32 3
31 360/32, 1600A - 31.5kA 3A74686H33 3
32 360/32, 2000A - 31.5kA 3A74686H34 3

Effective 3/01
I.B. 3A74791H06 Page 45

7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)

LINE DESCRIPTION STYLE NUMBER QTY


NO. W-VAC and/or W-VACR

33 48VDC 699B196G06 1
34 125VDC/120VAC 699B196G04 1
35 250VDC.240VAC 699B196G05 1

36 MOTOR BRUSH KIT 8063A77G01 1

Spring Release Coils

37 48VDC 3759A76G11 1
38 125VDC/120VAC 3759A76G12 1
39 250VDC/240VAC 3759A76G13 1

40 RECTIFIER (120/240VAC) 3759A76G02 1

Anti Pump (Y) Relay

41 48VDC 8237A27H03 1
42 125VDC 8237A27H04 1
43 250VDC 8237A27H05 1
44 120VAC 8237A27H01 1
45 240VAC 8237A27H02 1

Shunt Trip Coils

46 24VDC 3759A76G14 1
47 48VDC 3759A76G11 1
48 125VDC/125VAC Cap Trip 3759A76G12 1
49 250VDC/240VAC Cap Trip 3759A76G13 1

Primary Disconnects
(W-VAC Only)
50 630A 5680B59G01 6
51 1250A 5680B60G01 6
52 1600A 5680B61G01 6
53 2000A 692C037G03 6

Effective 3/01
Page 46 I.B. 3A74791H06

7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)

LINE DESCRIPTION STYLE NUMBER QTY


NO. W-VAC and/or W-VACR

UV Trip Coils

54 48VDC 8064A19G01 1
55 125VDC 8064A19G02 1
56 250VDC 8064A19G03 1
57 120VAC 8064A19G07 1
58 240VAC 8064A19G08 1

59 Motor Cutoff Switch 699B199G04 1

60 Latch Check Switch 699B147H04 1

61 Position Switch 699B147H01 1


62 Position Switch 3759A93H02 1

63 Auxiliary Switch 5697B20H01 1

64 Trip D-Shaft 694C638G01 1

65 Trip Latch (Hatchet) 699B040G03 1

Ground Contact Assy.


(W-VAC Only)
66 16kA 8796C85G01 1
67 25kA 8796C85G02 1
68 31.5kA 8796C85G03 1
69 21/35kA 8796C85G04 1

Effective 3/01
I.B. 3A74791H06 Page 47

7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)

LINE DESCRIPTION STYLE NUMBER QTY


NO. W-VAC and/or W-VACR

70 Shock Absorber 5677B26H01 2

71 Front Panel (w/o ESCN) 4D13655H02 1

72 Breaker Rail Wheel 5680B22G01 4

73 Shutter Drive Roller 5680B24H02 2

74 Breaker Floor Wheel 3A74342H01 4

75 Fastener Kit 8061A01G01 1

Closed Open

Push to
Open

76 Labels Kit 8295A45G01 1


Discharged

Push to
Close
Charged

Effective 3/01
Page 48 I.B. 3A74791H06

7.1 Recommended Renewal Parts for ANSI Rated Breakers

LINE DESCRIPTION STYLE NUMBER QTY


NO. VCP-W and/or VCP-WR

Wiring Harness
77 Repair Kit 8796C82G01 1

Complete Replacement
78 STD 8796C82G02 1
79 With #2 AUX SW 8798C82G03 1

Undervoltage Kit
80 48VDC 8794C81G01 1
81 125VDC 8794C81G02 1
82 250VDC 8794C81G03 1
83 120VAC 8794C81G04 1
84 240VAC 8794C81G05 1

Effective 3/01
I.B. 3A74791H06 Page 49

Effective 3/01
Page 50 I.B. 3A74791H06

Effective 3/01
I.B. 3A74791H06 Page 51

Effective 3/01
I.B. 3A74792H06

This instruction booklet is published solely for informa-


tion purposes and should not be considered all inclu-
sive. If further information is required, you should con-
sult Cutler-Hammer.

Sale of product shown in this literature is subject to


terms and conditions outlined in appropriate Cutler-
Hammer selling policies or other contractual agreement
between the parties. This literature is not intended to
and does not enlarge or add to any such contract. The
sole source governing the rights and remedies of any
purchaser of this equipment is the contract between the
purchaser and Cutler-Hammer.

NO WARRANTIES, EXPRESSED OR IMPLIED,


INCLUDING WARRANTIES OF FITNESS FOR A PAR-
TICULAR PURPOSE OR MERCHANTABILITY, OR
WARRANTIES ARISING FROM COURSE OF DEAL-
ING OR USAGE OF TRADE, ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS AND
DESCRIPTIONS CONTAINED HEREIN. In no event
will Cutler-Hammer be responsible to the purchaser or
user in contract, in tort (including negligence), strict lia-
bility or otherwise for any special, indirect, incidental or
consequential damage or loss whatsoever, including but
not limited to damage or loss of use of equipment, plant
or power system, cost of capital, loss of power, addition-
al expenses in the use of existing power facilities, or
claims against the purchaser or user by its customers
resulting from the use of the information, recommenda-
tions and description contained herein.

Cutler-Hammer
Pittsburgh, PA 15220
Effective 3/01 (ISI)
Style 3A74792H06
Printed in U.S.A.

You might also like