Professional Documents
Culture Documents
3A74791H06
! WARNING ! WARNING
Cutler-Hammer
Pittsburgh, PA 15220
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding his particular installation, operation or maintenance of particular equipment,
contact a Cutler-Hammer representative.
Effective 3/01
Page iv I.B. 3A74791H06
TABLE OF CONTENTS
Page
SECTION 1: INTRODUCTION
4-1 Introduction........................................................................................................................................................14
4-2 Manual Operation Check...................................................................................................................................14
4-3 Vacuum Interrupter Integrity..............................................................................................................................14
4-4 Insulation ...........................................................................................................................................................14
4-5 Contact Erosion and Wipe.................................................................................................................................14
4-6 Primary Circuit Resistance ................................................................................................................................14
4-7 Nameplate .........................................................................................................................................................14
4-8 Electrical Operation Check................................................................................................................................14
4-8.1 Circuit Breaker Insertion and Removal.................................................................................................15
4-8.2 Operation Check Performance .............................................................................................................16
4-9 Breaker/Structure Interfacing ............................................................................................................................16
4-9.1 Interface Interlocks ...............................................................................................................................16
4-9.2 Drawout Breaker Interfacing Check (W-VAC) ......................................................................................16
5-1 Introduction........................................................................................................................................................18
5-2 Interrupter Assembly .........................................................................................................................................18
5-2.1 Vacuum Interrupter...............................................................................................................................19
5-2.2 Contact Erosion Indication ...................................................................................................................19
5-2.3 Loading Spring Indication.....................................................................................................................20
5-2.4 Contact Wipe and Stroke .....................................................................................................................20
5-3 Stored Energy Mechanism ................................................................................................................................20
Effective 3/01
I.B. 3A74791H06 Page v
Page
6-1 Introduction........................................................................................................................................................29
6-2 Frequency of Inspection and Maintenance .......................................................................................................29
6-2.1 Qualified Personnel ..............................................................................................................................29
6-2.2 Helpful Tools and Accessory Items ......................................................................................................29
6-2.3 General Torque Guidelines ..................................................................................................................29
6-3 Inspection and Maintenance Procedures ..........................................................................................................32
6-4 Vacuum Interrupter Integrity Test......................................................................................................................33
6-5 Contact Erosion.................................................................................................................................................33
6-6 Contact Wipe.....................................................................................................................................................33
6-7 Insulation ...........................................................................................................................................................34
6-8 Insulation Integrity Check ..................................................................................................................................34
6-9 Primary Circuit Resistance Check.....................................................................................................................34
6-10 Mechanism Check.............................................................................................................................................36
6-10.1 CloSureTM Test ......................................................................................................................................36
6-11 Lubrication.........................................................................................................................................................40
6-12 Troubleshooting Chart.......................................................................................................................................40
FIGURES
Figure Title Page
1-1 Type W-VAC 36kV Drawout Circuit Breaker Outlines and Dimensions ....................................................3
1-2 Type W-VACR 36kV Fixed Circuit Breaker Outlines and Dimensions ......................................................4
3-1 Circuit Breaker Shown Mounted with Ramp Still in Shipping Position (W-VAC Only) ..............................6
3-2 Circuit Breaker Shown Being Moved Carefully Down Attached Ramp (W-VAC Only) .............................7
3-3 Optional Fifth Wheel Shown in Use (W-VAC Only)...................................................................................7
3-4 Front View W-VAC 36kV Drawout Vacuum Circuit Breaker ......................................................................9
3-5 W-VAC or W-VACR 36kV Vacuum Circuit Breaker with Front Cover Removed .....................................10
3-6 Rear View W-VAC 36kV Drawout Vacuum Circuit Breaker.....................................................................11
3-7 Rear View W-VACR Fixed Vacuum Circuit Breaker................................................................................12
Effective 3/01
Page vi I.B. 3A74791H06
FIGURES
TABLES
Effective 3/01
I.B. 3A74791H06 Page 1
! WARNING ! WARNING
Effective 3/01
Page 2 I.B. 3A74791H06
1-3 TYPE W-VAC AND W-VACR VACUUM CIRCUIT BREAKER RATINGS (TABLE 1.1)
THE CIRCUIT BREAKERS DESCRIBED IN THIS ALL SAFETY CODES, SAFETY STANDARDS
BOOK ARE DESIGNED AND TESTED TO OPERATE AND/OR REGULATIONS AS THEY MAY BE APPLIED
WITHIN THEIR NAMEPLATE RATINGS. OPERATION TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY
OUTSIDE OF THESE RATINGS MAY CAUSE THE ADHERED TO.
Power Lightning
Frequency Impulse
(1 Minute)
➁
U Uw In Isc tth Uc t3 Id Ic Isb Ibb
kV rms kV rms kV Peak Amperes, rms kA rms Seconds kV Peak µs kA Peak kA Amperes,rms
360 W-VAC 16 36 80 170 630 16 3 62 108 40 4 50 630 630
and 1250 630 630
360 W-VACR 16 1600 630 630
2000 1000 1000
360 W-VAC 20 36 80 170 630 20 3 62 108 50 5 50 630 630
and 1250 630 630
360 W-VACR 20 1600 630 630
2000 1000 1000
360 W-VAC 25 36 80 170 630 25 3 62 108 63 6.3 50 630 630
and 1250 630 630
360 W-VACR 25 1600 630 630
2000 1000 1000
360 W-VAC 32 36 80 170 630 31.5 3 62 108 79 7.9 50 630 630
and 1250 630 630
360 W-VACR 32 1600 630 630
2000 1000 1000
➀ KEMA tested to applicable IEC-56 Standards (rated operating sequence 0 - .3 sec - CO - 15 sec - CO). Typical operating time
values: opening 45 ms, closing 75 ms, and reclosing 18 cycles.
➁ IEC Standards require 70kV. All ratings tested to 80kV.
➂ Also qualified for 250 ampere rating.
➃ U=52kV, Uc=92kV, t3=216µ seconds.
➄ Tested at 20 kA, 5 kHz inrush current.
Effective 3/01
I.B. 3A74791H06 Page 3
1.563 [39.7]
.6 [14]
1.938 [49]
64.6 [1641]
4.50 [114]
6.22 [158]
1.0 [26]
5.4 4.6
[137] [117]
DETAIL PLAN VIEW
9.88 [251] IN DIRECTION OF ARROW “X”
.2 [5] 11.5 (TYP)
12.4 [314] [293]
16.4 [417] 16.4 [417]
17.9 [454]
35.7 [908]
AS 2000A CONDUCTORS
DIMENSIONS ARE
17.3 [440]
TO BASE PLATE
7.5 [191]
TOC Operator
15.6 [397]
17.4 [441]
17.4 [441]
11.1 [283]
Figure 1-1 Type W-VAC 36kV Drawout Circuit Breaker Outlines and Dimensions (inches and [mm])
Effective 3/01
Page 4 I.B. 3A74791H06
35.75 [908]
35.13 [892]
11.81 [300] 11.81 [300]
87 [17]
1.34 [34]
Travel
171 [43]
.63 [16]
Travel
.63 [16]
4.51 [115]
Minimum Travel
REF.
To Trip
8.22 [158] REF.
Terminal Blocks
15.6 [396]
31.2 [793]
Figure 1-2 Type W-VACR 36kV Fixed Circuit Breaker Outlines and Dimensions (inches and [mm])
Effective 3/01
I.B. 3A74791H06 Page 5
SECTION 2: SAFE PRACTICES • Do not work on a drawout circuit breaker with a sec-
ondary test coupler engaged. Failure to disconnect
2-1 RECOMMENDATIONS the test coupler could result in an electrical shock
leading to death, personal injury or property damage.
Type W-VAC and W-VACR Vacuum Circuit Breakers
are equipped with high speed, high energy operating • Do not work on a closed circuit breaker or a breaker
mechanisms. They are designed with several built-in with closing springs charged. The closing springs
interlocks and safety features to provide safe and proper should be discharged and the main circuit contacts
operating sequences. Cell interlocks used with drawout open before working on the circuit breaker. Failure to
circuit breakers are meant to interact with the appropri- do so could result in cutting or crushing injuries.
ate cell interface and levering mechanism.
• Do not use an open circuit breaker by itself as the sole
means of isolating a high voltage circuit. Remove the
circuit breaker to the Disconnect position and follow all
! WARNING lock-out and tagging rules of the National Electrical
Code and any other applicable codes, regulations and
TO PROTECT THE PERSONNEL ASSOCIATED WITH work rules.
INSTALLATION, OPERATION, AND MAINTENANCE
OF THESE CIRCUIT BREAKERS, THE FOLLOWING • Do not leave a drawout circuit breaker in an intermedi-
PRACTICES MUST BE FOLLOWED: ate position in the cell. Always have the circuit breaker
either in the Disconnect/Test or Connected position.
• Only qualified persons, as defined in the National Failure to do so could result in a flash over and possi-
Electrical Safety Code, who are familiar with the ble death, personal injury or property damage.
installation and maintenance of medium voltage cir-
cuits and equipment, should be permitted to work on • Always remove the maintenance tool from the circuit
these circuit breakers. breaker after charging the closing springs.
• Read these instructions carefully before attempting • Circuit breakers are equipped with safety interlocks.
any installation, operation or maintenance of these cir- Do Not remove, interfere with or in any manner defeat
cuit breakers. them. This may result in death, bodily injury or equip-
ment damage.
• If the final breaker design is drawout, always remove
the breaker from the enclosure before performing any • Do not work on a circuit breaker suspended from a lift-
maintenance. If the breaker is applied in a fixed con- ing yoke or chains. Maintenance work should be per-
figuration, always make sure that primary and sec- formed on a solid work surface, such as the floor.
ondary power are disconnected from the breaker.
Failure to do so could result in electrical shock leading
to death, severe personal injury or property damage.
Effective 3/01
Page 6 I.B. 3A74791H06
3-2 RECEIVING
! WARNING
NOTICE
3-3 HANDLING
! WARNING
Effective 3/01
I.B. 3A74791H06 Page 7
3-4 STORAGE
Effective 3/01
Page 8 I.B. 3A74791H06
Outdoor storage is NOT recommended. If unavoidable, 3-6 TYPE W-VAC AND W-VACR VACUUM CIRCUIT
the outdoor location must be well drained and a tempo- BREAKER WEIGHTS (TABLE 3.1)
rary shelter from sun, rain, snow, corrosive fumes, dirt,
falling objects and excessive moisture must be provid- Table 3.1 Approximate Circuit Breaker Weights ➀
ed. Containers should be arranged to permit free circu- Rating Pounds
lation of air on all sides and temporary heaters should
be used to minimize condensation. Moisture can cause 360 W-VAC 16 630 1070
rusting of metal parts and deterioration of high voltage 1250 1080
insulation. A heat level of approximately 400 watts for 1600 1090
each 100 cubic feet of volume is recommended with the 2000 1140
heaters distributed uniformly throughout the structure
near the floor. 360 W-VACR 16 630 937
1250 948
Indoor storage should be in a building with sufficient 1600 958
heat and air circulation to prevent condensation. If the 2000 1025
building is not heated, the same general rule for heat as
for outdoor storage should be applied. 360 W-VAC 20 630 1070
1250 1080
1600 1090
3-5 TOOLS AND ACCESSORIES 2000 1140
Several tools and accessories, both standard and 360 W-VACR 20 630 937
optional are available for use with the circuit breaker. 1250 948
1600 958
Maintenance Tool (Standard): Used to charge closing 2000 1025
springs.
360 W-VAC 25 630 1070
Lifting Yoke (Optional): Used to lift circuit breaker with 1250 1080
overhead lifting device. 1600 1090
2000 1140
Fifth Wheel (Optional): Used to maneuver a circuit
breaker on a flat, hard surface (Figure 3-3). 360 W-VACR 25 630 937
1250 948
1600 958
2000 1025
Effective 3/01
I.B. 3A74791H06 Page 9
4
3
1 Front Cover
2 Lift/Pull Handle
3 Circuit Breaker Wheel
4 Secondary Contact Block
5 Alignment Rollers
Figure 3-4 Front View W-VAC 36kV Drawout Vacuum Circuit Breaker
Effective 3/01
Page 10 I.B. 3A74791H06
1 2 3
5
13
6
12
8
11
10 9
Figure 3-5 W-VAC or W-VACR 36kV Vacuum Circuit Breaker with Front Cover Removed
Effective 3/01
I.B. 3A74791H06 Page 11
6
7 5
1 Pole Unit
2 Primary Disconnect
3 Insulation Shroud
4 Opening to View Contact Erosion Mark
5 Circuit Breaker Wheel
6 Alignment Rollers
7 TOC Operator
Figure 3-6 Rear View W-VAC 36kV Drawout Vacuum Circuit Breaker
Effective 3/01
Page 12 I.B. 3A74791H06
1 Pole Unit
2 Opening to View Contact Erosion Mark
3 Conductor Mounting Surface
Figure 3-7 Rear View W-VACR 36kV Fixed Vacuum Circuit Breaker
Effective 3/01
I.B. 3A74791H06 Page 13
6 3
5 4
Effective 3/01
Page 14 I.B. 3A74791H06
NOTICE
If the springs are to be charged on a closed circuit
breaker, no click is heard at the end of charging
operation. Discontinue charging and remove the
maintenance tool as soon as “Charged” flag is fully
visible. Continued attempts to charge further may
result in damage to the mechanism.
Using a dry, lint free cloth or paper towel, clean all the
accessible insulating surfaces of the pole units. Conduct
a vacuum interrupter integrity check as described in Figure 4-1 Type W-VAC Circuit Breaker Manual
Section 6. Charging Handle in Use
Effective 3/01
I.B. 3A74791H06 Page 15
breaker in a TEST position or by using a test cable, if cuit breaker, manually engaging the secondary contacts
the circuit breaker is outside the cell structure. now makes this the TEST position.
For fixed breaker applications, an electrical operations To engage the secondary contacts, grasp the structure
check should be performed after the breaker is appropri- mounted secondary disconnect cage handle located
ately mounted, secondary wiring completed, and appro- below the left side of the circuit breaker, and pull it for-
priate interphase barriers installed. ward as far as possible to make the secondary engage-
ment. As soon as control power is available, the motor
will charge the closing springs.
! CAUTION
To move the circuit breaker to the CONNECTED posi-
BEFORE INSERTING THE CIRCUIT BREAKER EXAM- tion, engage the levering crank with the structure mount-
INE THE INSIDE OF THE CELL STRUCTURE FOR ed levering shaft and begin turning the handle in a
EXCESSIVE DIRT OR ANYTHING THAT MIGHT INTER- clockwise direction. Keep in mind that the levering crank
FERE WITH THE CIRCUIT BREAKER MOVEMENT. cannot be engaged with the circuit breaker closed.
Structure mounted positive guidance rails interface with
the circuit breaker alignment rollers to insure proper pri-
mary and secondary connections.
! WARNING
Effective 3/01
Page 16 I.B. 3A74791H06
The W-VACR fixed circuit breaker can be checked in a 4-9.2 DRAWOUT BREAKER INTERFACING CHECK
similar fashion as long as the circuit breaker is isolated (W-VAC)
with no primary power present. The operation perfor-
mance can be conducted as long as secondary control Keep in mind that an interfacing check will be made with
power is present. a compatible structure. As such, the instructions provid-
ed with the assembly will suggest other interfacing con-
ditions that should be observed and/or checked, such as
4-9 BREAKER/STRUCTURE INTERFACING primary shutter operation, MOC/TOC operation and lev-
ering handle insertion. A complete, coordinated inter-
Type W-VAC Vacuum Circuit Breakers are supplied with face check, therefore, will be a blend of the circuit
a series of interlocks to insure safe and proper interfac- breaker instructions and those provided with the struc-
ing between the circuit breaker and a compatible struc- tural assembly. Together all required standards are met
ture compartment. The specific interlocks are described and the ultimate in safety is achieved.
in the next paragraph to provide the proper familiariza-
tion. Once the interlocks are reviewed, an interfacing Insert the circuit breaker into the structure and lever it
check can be performed as described in Paragraph into and out of each different position by following the
4-9.2. procedures described in Paragraph 4-8.1.
Effective 3/01
I.B. 3A74791H06 Page 17
1 2 3 4 5
Effective 3/01
Page 18 I.B. 3A74791H06
Figure 5-1 Rear View Showing Pole Unit Enclosure Figure 5-2 Plate Over Rear Truck Opening 2000A
(W-VAC Shown) Breakers and Above (W-VAC Shown)
Effective 3/01
I.B. 3A74791H06 Page 19
! CAUTION
Shield Involvement
Interruption
THE PLATE BOLTED TO THE REAR RECTANGU- Arc Current
LAR OPENING ON ALL 2000 AMPERE AND ABOVE Initiation High Current Zero
CIRCUIT BREAKERS AND IDENTIFIED IN FIGURE 5- Arc Mode
2 MUST BE BOLTED IN POSITION BEFORE PLAC-
Fault
ING A CIRCUIT BREAKER IN SERVICE TO INSURE Current
PROPER OPERATION WITHIN TEST PROVEN
PARAMETERS.
Direct acting insulated operating rods in conjunction with Figure 5-3 Graphic Representation of Arc Interruption
the circuit breaker’s mechanism provide a fixed amount
of interrupter movable stem motion. This motion is
directly related to the interrupter’s “Wipe” and “Stroke,”
each of which is discussed in detail later in this section. At current zero, the arc is extinguished and vapor produc-
tion ceases. Very rapid dispersion, cooling, recombina-
tion, and deionization of the metal vapor plasma, togeth-
5-2.1 VACUUM INTERRUPTER erwith the fast condensation of metal vapor products,
cause the vacuum to be quickly restored. Hence, the
W-VAC and W-VACR 36kV Vacuum Circuit Breakers opened contacts withstand the transient recovery voltage.
utilize vacuum interrupters for interruption and switching
functions. The vacuum interrupters use axial-magnetic,
copper chrome contacts for superior dielectric strength, 5-2.2 CONTACT EROSION INDICATION
better performance characteristics, and lower chop cur-
rent. Vacuum interruption provides the advantages of The purpose of a contact erosion indicator is to monitor
enclosed interrupters, reduced size and weight, short the erosion of the vacuum interrupter contacts, which is
interrupting time, long life, reduced maintenance, and very minimal over time with vacuum interrupters utilizing
environmental compatibility. copper-chrome contact material. If contact erosion
reaches 1/8 inch, the interrupter must be replaced.
Arc interruption is simple and fast (Figure 5-3). In the
closed position, current flows through the interrupter. NOTICE
When the contacts are opened, the arc is drawn
between the contact surfaces. It is moved rapidly
around the slotted contact surfaces by a self-induced Each phase of the circuit breaker is monitored inde-
magnetic force which prevents gross contact erosion as pendently.
well as the formation of hot spots on contact surfaces.
The arc burns in an ionized metal vapor which continu- Contact erosion is monitored from the rear of the circuit
ally leaves the contact area and condenses on the sur- breaker. It provides a very accurate indication of contact
rounding metal shield. erosion, and is the primary determinant of contact condi-
tion. A contact erosion indicator mark is located on the
insulated drive rod of each interrupter (Figure 6-2).
Effective 3/01
Page 20 I.B. 3A74791H06
5-2.3 LOADING SPRING INDICATION AND OPEN THE CIRCUIT BREAKERS BEFORE PER-
FORMING ANY CIRCUIT BREAKER MAINTENANCE,
The contact loading spring indicator is an additional INSPECTION OR REPAIR.
method provided to indicate conditions within the vacuum
interrupter, as well as the overall system condition. The vis- The spring stored energy operating mechanism is
ible indication, on each phase, is used to indicate whether arranged vertically in front of all W-VAC and W-VACR
the contact loading springs are maintaining the proper con- circuit breakers (Figure 3-5). It includes all the elem-
tact pressure to keep the contacts closed. Severe contact ents for storing the energy, closing and tripping of the
erosion or an adjustment need after an interrupter assem- circuit breaker, as well as manual and electrical con-
bly replacement would result in an unacceptable indication trols. The manual controls are all front accessible.
from this indicator (Figures 6-4 and 6-5). Motion to close and open the interrupter contacts is
provided through operating rods connecting the
mechanism pole shaft to the bell cranks of the inter-
5-2.4 CONTACT WIPE AND STROKE rupter assemblies.
5-3 STORED ENERGY MECHANISM The closing spring cranks have spring ends connected
to them, which are in turn coupled to the closing springs.
As the cranks rotate, the closing springs are charged.
! WARNING When the closing springs are completely charged, the
spring cranks go over dead center, and the closing stop
KEEP HANDS AND FINGERS AWAY FROM THE CIR- roller comes against the spring release latch. The clos-
CUIT BREAKER’S INTERNAL PARTS WHILE THE ing springs are now held in the fully charged position.
CIRCUIT BREAKER CONTACTS ARE CLOSED OR
THE CLOSING SPRINGS ARE CHARGED. THE CIR- Closing springs may also be charged manually. Insert
CUIT BREAKER CONTACTS MAY OPEN OR THE the maintenance tool in the manual charging socket.
CLOSING SPRINGS DISCHARGE CAUSING A Move it up and down approximately 38 times until a
CRUSHING INJURY. DISCHARGE THE SPRINGS clicking sound is heard, and the closing springs charg-
ing indicator indicates “Charged.” Any further motion of
Effective 3/01
I.B. 3A74791H06 Page 21
5
1
6 2
7 3
8 4
10
Effective 3/01
Page 22 I.B. 3A74791H06
the maintenance tool will result in free wheeling of the As soon as the control power is applied, the spring
ratchet wheel. charging motor automatically starts charging the closing
springs. When the springs are charged, the motor cut off
LS1/bb switch turns the motor off. The circuit breaker
5-3.3 CLOSING OPERATION may be closed by making the control switch close
(CS/C) contact. Automatically upon closing of the circuit
Figure 5-4 shows the position of the closing cam and breaker, the motor starts charging the closing springs.
tripping linkage. Note that in Figure 5-4a in which the The circuit breaker may be tripped any time by making
circuit breaker is open and the closing springs are dis- the control switch trip (CS/T) contact.
charged, the trip “D” shaft and trip latch are in the
unlatched position. Note the position switch (PS1) contact in the spring
release circuit in the scheme. This contact remains
Once charged, the closing springs can be released to made while the circuit breaker is being levered between
close the circuit breaker by moving the spring release the TEST and CONNECTED positions. Consequently, it
latch out of the way. This is done electrically or manually prevents the circuit breaker from closing automatically,
by depressing the spring release lever, which turns the even though the control close contact (CS/C) may have
spring release latch out of the way of the closing stop been made while the circuit breaker is levered to the
roller. The force of the closing spring rotates the cam CONNECTED position.
shaft through the spring cranks. The closing cam, being
attached to the cam shaft, in turn rotates the pole shaft The position switch (PS2) contact is in the motor circuit.
through the main link to close the circuit breaker. It prevents the motor from starting until the fully CON-
NECTED position is reached and the secondary con-
In Figure 5-4c the linkage is shown with the circuit tacts are firmly engaged.
breaker in the closed position before the closing springs
have been recharged. Interference of the trip “D” shaft When the CS/C contact is made, the SR closes the cir-
with the trip latch prevents the linkage from collapsing, cuit breaker. If the CS/C contact is maintained after the
and the circuit breaker is held closed. circuit breaker closes, the Y relay is picked up. The Y/a
contact seals in Y until CS/C is opened. The Y/b contact
Figure 5-4d shows the circuit breaker in the closed posi- opens the SR circuit, so that even though the circuit
tion after the closing springs have been recharged. Note breaker would subsequently open, it could not be
that the spring charging rotates the closing cam by one reclosed before CS/C was released and remade. This is
half turn. Since the cam surface in contact with the main the anti-pump function.
link roller is cylindrical in this region, the spring charging
operation does not affect the mechanism linkage.
5-4.1 TIMING
Since the primary contacts are completely enclosed in
the vacuum interrupter and not adjustable in any way, a The opening and closing times for the circuit breakers
“Slow Close” capability is not provided with W-VAC or vary depending upon the control voltage and the power
W-VACR circuit breakers. rating. Typical values for 36kV W-VAC and W-VACR
circuit breakers are shown in Table 5.1.
Effective 3/01
I.B. 3A74791H06 Page 23
12
8
11 14
10
3
9
1
13
Effective 3/01
Page 24 I.B. 3A74791H06
P a b a b a b a b a b
11
SPRING WL CS GL RL CS PR
9UV
CHARGED C T U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
INDICATING
LIGHT AUXILIARY SWITCH #2 OPTIONAL
UV
10UV
1 2 4 5 6
7 7 8 9 10 3
14
3A
OPTIONS
3
13
Y
9
LS1
DC SOURCE
Y 12
51
53
55
57
bb SR b a
ST a b a b b
9A
M 1
a a
b
52
54
56
58
PS2 LC
14
ST
PS1 Y LS2 LS2 2
bb aa 18 17 16 15 22
10A
10
6 13
21 20 19
4
SPRING WL CS GL RL CS PR
9UV
C T U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
CHARGED
INDICATING
LIGHT AUXILIARY SWITCH #2 OPTIONAL
UV
11
9UV
10UV
1 2 4
7 5 9 6 7 8 10 3
14
13
UV
55
Y
9
AC (+)
3A
OPTIONS
3
b 12
AC SOURCE
Y
51
53
57
LS1 AC (-)
ST a b b b
9A
bb
1
a 14
a
52
54
58
M b
LC FOR AC UV
56
14
ST TRIP ONLY
PS2 PSI Y LS2 LS2 2
18 17 15 22
10A
bb aa
10
6 13
21 20 16 19
4
Figure 5-6 Typical W-VAC “DC” and “AC” Control Schematics (Drawout)
Effective 3/01
I.B. 3A74791H06 Page 25
Figure 5-7 Typical W-VACR “DC” and “AC” Control Schematics (Fixed)
Effective 3/01
Page 26 I.B. 3A74791H06
The switchgear compartment mounted secondaries are For a basic understanding of the operation of the under-
of a movable carriage design. Once the circuit breaker voltage trip device refer to the specific items identified in
is in the TEST position, the structure mounted sec- Figure 5-10 and the following operation description.
ondary plug carriage can be manually unlatched and
pulled forward until mating with the circuit breaker 1. With the circuit breaker closed and sufficient voltage
mounted male plugs. To disengage the secondary plugs on the Undervoltage Trip Device coil, the moving
from the TEST position, simply push the carriage to the clapper (1) is held to the stationary yoke (2) by the
rear. Secondary connections are automatically engaged magnetic force produced by the coil (3) against the
or disengaged when moving into or out of the CON- extension springs (4) pulling the moving clapper
NECTED position. apart from the yoke.
W-VACR fixed circuit breakers are supplied with 2 3. When the voltage to the Undervoltage Trip Coil goes
12-point screw type secondary control terminal blocks down as described earlier, the extension springs
for simple secondary control access. A number of points force overcomes the reduced magnetic force and
are used for breaker operation with a number of spare pulls the moving clapper up. The slotted link in turn
contacts for customer use. The terminal blocks are upsets the Trip D Shaft and the circuit breaker trips
located at the lower front of the circuit breaker (5-9). open.
Two additional terminal blocks are available for a sec-
ond auxilliary switch. 4. As the circuit breaker opens, the reset lever (8) con-
nected to the pole shaft lever (7) operates to reset
the moving clapper. As long as the circuit breaker
5-4.4 UNDERVOLTAGE TRIP DEVICE remains open, the reset lever holds down the moving
clapper to the yoke.
The undervoltage trip device for W-VAC and W-VACR
circuit breakers is an electromechanical device that
operates to open the circuit breaker at 30% or less of
the voltage rating of the trip coil. The device does not
open the circuit breaker at values above 60% of the volt-
age rating of its trip coil. It may operate, however, to
open the circuit breaker when the voltage across the trip
coil is greater than 30%, but less than 60% of the volt-
age rating of its trip coil. The circuit breaker can be
closed as long as the voltage to the trip coil is main-
tained at 85% or above the rated level. The undervolt-
age trip device is available only as an instantaneous
type with rated voltages of 48VDC, 125VDC, 250VDC
120VAC and 240VAC.
Closing Time
(From Initiation of Close 75
Signal to Contact Make)
Opening Time
(Initiation of Trip Signal 45
to Contact Break)
Reclosing Time
(Initiation of Trip Signal 190
to Contact Make) Figure 5-8 Secondary Plug Shown Mounted Lower Left
Drawout Circuit Breaker
Effective 3/01
I.B. 3A74791H06 Page 27
5. When the circuit breaker closes, the reset lever 5-7 OPERATIONS COUNTER
moves away from the moving clapper. If the Under-
voltage Trip Device coil has at least 85% of the rated All circuit breakers are equipped with a mechanical
voltage applied, the moving clapper is held to the operations counter. As the circuit breaker opens, the
yoke by the magnetic force, even though the reset linkage connected to the pole shaft lever advances the
lever has moved up. counter reading by one (Figure 3-8).
Refer to Paragraph 4-9 of this manual for detailed infor- The ground contact used with the drawout W-VAC cir-
mation concerning circuit breaker interlocks and their cuit breaker is an assembly of spring loaded fingers pro-
interfacing with a switchgear structure compartment. In viding a disconnectable means for grounding the circuit
addition, refer to the instruction manual supplied with breaker chassis, after it has been inserted into a
the switchgear assembly. Customers are responsible for switchgear structure. The ground contact is located on
providing W-VACR interfaces. the lower left portion of the truck chassis. An extension
of the switchgear ground bus is secured to the cell floor
in such a position to engage the ground contact auto-
5-6 LEVERING MECHANISM (W-VAC ONLY) matically, when the circuit breaker is moved into the
DISCONNECT/TEST position. It remains engaged in all
The purpose of the levering mechanism is to move the other circuit breaker positions within the cell. The lever
drawout W-VAC circuit breaker into and out of the CON- is supplied on the W-VACR breaker, but the customer is
NECTED position within the assembly structure. The responsible for supplying the proper interface.
levering mechanism used to move the circuit breaker is
a minimum effort recirculating ball drive design, and is
part of the assembly structure cradle. For additional 5-9 MOC AND TOC SWITCH OPERATIONS
information concerning the levering mechanism, refer to
the instruction manual supplied with the switchgear A MOC operator integral to the circuit breaker engages
assembly. Paragraph 4-8.1 of this manual provides an operating lever of the Mechanism Operated Cell
details concerning the use of the levering mechanism to Switch (MOC) located in the switchgear cell. This MOC
move the circuit breaker into and out of the CONNECT- operator permits the contacts of the MOC Switch to be
ED position within the assembly structure. correlated with the circuit breaker’s contact position.
Effective 3/01
Page 28 I.B. 3A74791H06
4
1
2 3
Effective 3/01
I.B. 3A74791H06 Page 29
SECTION 6: INSPECTION, MAINTENANCE 4. Follow the steps presented in Paragraph 6-3 entitled
AND TROUBLESHOOTING “Inspection and Maintenance Procedures” for sched-
uled programs.
6-1 INTRODUCTION
5. Create and maintain a dated permanent record of all
inspections, maintenance performed, actions taken,
observations made, and measurements taken. Not
! WARNING only will this provide valuable historical information, it
can help to establish whether or not the present
• DO NOT WORK ON A CIRCUIT BREAKER IN THE schedule needs to be adjusted.
“CONNECTED” POSITION.
6. Perform ongoing visual inspections, when possible,
• DO NOT WORK ON A CIRCUIT BREAKER WITH of all equipment on a regular basis. Be alert for an
SECONDARY DISCONNECTS ENGAGED. accumulation of dirt in and around the circuit break-
• DO NOT WORK ON A CIRCUIT BREAKER WITH ers, loose hardware or discolored insulation.
SPRINGS CHARGED OR CONTACTS CLOSED.
• DO NOT DEFEAT ANY SAFETY INTERLOCKS. 6-2.1 QUALIFIED PERSONNEL
• DO NOT LEAVE MAINTENANCE TOOL IN THE
SOCKET AFTER CHARGING THE CLOSING For the purpose of operating switchgear equipment and
SPRINGS. associated circuit breakers, only individuals thoroughly
trained in the operation of power circuit breakers and
• DO NOT STAND LESS THAN FOUR METERS associated equipment, and having knowledge of con-
AWAY FROM THE BREAKER WHEN TESTING nected loads may be considered to be qualified. Refer
FOR VACUUM INTEGRITY. to further definitions in the National Electrical Safety
Code.
FAILURE TO FOLLOW ANY OF THESE INSTRUC-
TIONS MAY CAUSE DEATH, SERIOUS BODILY For the purpose of inspecting and maintaining such
INJURY, OR PROPERTY DAMAGE. SEE SECTION 2- equipment, a qualified person must also be trained in
SAFE PRACTICES FOR MORE INFORMATION. regard to the hazards inherent to working with electricity
and the proper way to perform such work. Such an indi-
vidual should be able to de-energize, clear and tag cir-
6-2 FREQUENCY OF INSPECTION AND cuits in accordance with established safety practices. In
MAINTENANCE addition, these individuals should have access to and be
trained in the use of protective equipment, such as rub-
Periodic inspections and associated maintenance are ber gloves and flash clothes.
essential to the safe and reliable operation of W-VAC
and W-VACR Vacuum Circuit Breakers. The inspection All personnel should be familiar with and understand the
frequency and associated maintenance recommended material presented in this instruction manual and other
are intended to insure the best possible ongoing ser- related manuals.
vice. It is imperative that an established schedule be fol-
lowed. To establish an exact schedule for a specific
installation, use the following guidelines: 6-2.2 HELPFUL TOOLS AND ACCESSORY ITEMS
1. In a clean, non-corrosive environment, inspect and To simplify the performance of inspection and mainte-
maintain each circuit breaker annually or every 500 nance programs, the items described in Section 3-5 are
operations, which ever comes first. recommended.
2. For special conditions such as frequent circuit break-
er operation, contaminated environments, and high 6-2.3 GENERAL TORQUE GUIDELINES
temperature/humidity conditions, the inspection fre-
quency should be twice a year. Bolts and screws must be properly torqued. This is
especially true if parts and/or accessories are added or
3. Inspect a circuit breaker every time it interrupts fault replaced. Table 6.1 provides guidelines on torque lev-
current. els. The table is intended as a general guideline and
Effective 3/01
Page 30 I.B. 3A74791H06
should be applied in conjunction with the experience Table 6.1 Torque Guidelines
and good judgment of the individual performing the
work. Bolt Size Torque (nm)
8 - 32 2.7
! CAUTION 10 - 32
1/4 - 20
4
8
OVER TORQUING CAN CAUSE PERMANENT DAM-
AGE WHILE UNDER TORQUING WILL NOT PRO- 5/16 - 18 16
VIDE THE PROPER CLAMPING FORCE AND MAY
EVENTUALLY WORK LOOSE. 3/8 - 16 34
1/2 - 13 61
Effective 3/01
I.B. 3A74791H06 Page 31
Effective 3/01
Page 32 I.B. 3A74791H06
1. Insulation Drive Insulator No dirt Visual Check Clean with lint-free cloth
and and or
Molded Pole Unit Support No cracking Visual Check Replace cracked unit
Insulation Main Circuit to Ground Withstand Hipot Tester Clean and retest or replace
Integrity
Between Main Circuit Withstand Hipot Tester Clean and retest or replace
Terminals
Control Circuit to Ground Withstand Hipot Tester Clean and retest or replace
2. Power Vacuum Interrupters Precise Measure- Measurement - Close the circuit If the front indicator marks are
Elements ment from rear breaker and proceed as described in the red area and the rear
in Paragraph 6-5 measurement is not acceptable,
replace pole unit assembly
Adequate Vacuum Proceed with integrity check as If integrity check is not satisfactory,
described in Paragraph 6-4 replace pole unit assembly
3. Control Closing and Tripping Device Smooth and correct Test closing and tripping of the Replace any defective device. Identify
Circuit Including Disconnects operation by control circuit breaker twice per trouble-shooting chart
Parts power
4. Operating Tightness of Hardware No loose or missing Visual and by feel Refer to Table 6.1 and tighten
Mechanism parts or reinstate if necessary with
appropriate tools
Lubrication Smooth operation Sight, feel and per maintenance Refer to Figure 6-1, Paragraph
and no excessive schedule 6-11 and lubricate very spar-
wear ingly with light machine oil
Deformation or Excessive No excessive Visual and operational Remove cause and replace parts
Wear deformation or wear
Manual Operation Smooth operation Manual charging, closing Correct per troubleshooting
and tripping chart if necessary
Effective 3/01
I.B. 3A74791H06 Page 33
6-4 VACUUM INTERRUPTER INTEGRITY TEST In this case the equipment must be capable of delivering
5 milliamperes for one minute to avoid ambiguity due to
Vacuum interrupters used in Type W-VAC and W-VACR field emission or leakage currents and the test voltage
36kV Vac-uum Circuit Breakers are highly reliable inter- shall be as shown in Table 6.2.
rupting elements. Satisfactory performance of these
devices is dependent upon the integrity of the vacuum in The current delivery capability of 25 ma ac and 5 ma dc
the interrupter and the internal dielectric strength. Both apply when all three VIs are tested in parallel. If individ-
of these parameters can be readily checked by a one ual VIs are tested, current capability may be one third of
minute ac high potential test. Refer to Table 6.2 for the these values.
appropriate test voltage. During this test, the following
warning must be observed:
! CAUTION
Effective 3/01
Page 34 I.B. 3A74791H06
Base of Interrupter
Standard 300 mm
Metal Scale
Inch
Measurement Line
6-7 INSULATION lead of the test machine to one of the poles of the circuit
breaker. Connect the remaining poles and circuit break-
Type W-VAC and W-VACR 36kV Vacuum Circuit er frame to ground. Start the machine with output poten-
Breakers primarily utilize cycloaliphatic epoxy insulation tial at zero and increase to the test voltage. Maintain the
except, for example, the black insulating shrouds. test voltage for one minute. Repeat for the remaining
Insulation maintenance primarily consists of keeping all poles. Successful withstand indicates satisfactory insu-
insulating surfaces clean. This can be done by wiping lation strength of the primary circuit.
off all insulating surfaces with a dry lint free cloth or dry
paper towel. In case there is any tightly adhering dirt If a DC high potential machine is used, make certain
that will not come off by wiping, it can be removed with a that the peak voltage does not exceed the peak of the
mild solvent or distilled water. Be sure that the surfaces corresponding AC rms test voltage.
are dry before placing the circuit breaker in service. If a
solvent is required to cut dirt, use Stoddard’s Solvent Secondary Circuit:
Cutler-Hammer 55812CA or commercial equivalent. Connect all points of the secondary terminal block with
Second-ary control wiring requires inspection for tight- shooting wire. Connect this wire to the high potential
ness of all connections and damage to insulation. lead of the test machine. Ground the circuit breaker
frame. Starting with zero, increase the voltage to 1500
volts rms. Maintain the voltage for one minute. Suc-
6-8 INSULATION INTEGRITY CHECK cessful withstand indicates satisfactory insulation
strength of the secondary control circuit. Remove the
Primary Circuit: shooting wire.
The integrity of primary insulation may be checked by
the 50Hz AC high potential test. The test voltage
depends upon the maximum rated voltage of the circuit 6-9 PRIMARY CIRCUIT RESISTANCE CHECK
breaker. For circuit breakers rated 36kV the test voltage
is 60kV rms. Conduct the test as follows: Since the main contacts are inside the vacuum cham-
ber, they remain clean and require no maintenance at
Close the circuit breaker. Connect the high potential any time. Unlike many typical circuit breaker designs,
W-VAC and W-VACR circuit breakers do not have slid-
Effective 3/01
I.B. 3A74791H06 Page 35
CONTACT WIPE
(23.1 mm to
31.0 mm)
Measure
Resistance here
(Do not measure
across contact
fingers, only main
conductors)
Measure
Resistance at 2
Identified Points
(W-VAC) (W-VACR)
Effective 3/01
Page 36 I.B. 3A74791H06
ing contacts at the moving stem either. Instead they use NO VOLTAGE IS PRESENT BEFORE PROCEEDING
a highly reliable and unique flexible clamp design that WITH THE TASK, AND ALWAYS FOLLOW GENER-
eliminates the need for lubrication and inspection for wear. ALLY ACCEPTED SAFETY PROCEDURES.
If desired, the DC resistance of the primary circuit may Safety Precautions: Read and understand these
be measured as follows: close the circuit breaker, pass instructions before attempting any maintenance, repair
at least 100 amps DC current through the circuit break- or testing on the breaker. The user is cautioned to
er. With a low resistance instrument, measure resis-
tance across the studs on the circuit breaker for each observe all recommendations, warnings and cautions
pole (Figure 6-6).The resistance should not exceed the relating to the safety of personnel and equipment.
values shown in Table 6.4.
! WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM
MAINTENANCE OR TESTS ON THE EQUIPMENT
WHILE IT IS ENERGIZED. NEVER PUT YOUR
HANDS NEAR THE MECHANISM WHEN THE CIR-
CUIT BREAKER IS IN THE CHARGED OR CLOSED
POSITION. DEATH OR SEVERE PERSONAL
INJURY CAN RESULT FROM CONTACT WITH
ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT Figure 6-9 Wrapping Tape Up Around Cam
Effective 3/01
I.B. 3A74791H06 Page 37
The recommendations and information contained herein Step 7 - Charge the closing springs with the mainte-
are based on Cutler-Hammer experience and judgment, nance tool. Continue charging the closing springs
but should not be considered to be all-inclusive or cov- until a “click” is heard and the status indicator shows
ering every application or circumstance which may “Charged” (Figure 6-13).
arise. If further information is required, you should
consult Cutler-Hammer. Step 8 - While holding the marker tip on the tape, close
the breaker (Figure 6-14).
Testing Procedures: Assuming that the breaker is
safely pulled out to the Test/Disconnect position in the Step 9 - Move the marker back and forth horizontally
enclosure or placed on the workbench, follow this proce- approximately 15o in both directions to create a line on
dure to perform the CloSureTM Test. For further instruc- the tape that identifies the closed rest position (Figures
tions on disconnecting the circuit breaker consult 6-15, 6-21 and 6-17).
Section 4 of this manual. If the enclosure is equipped
with the MOC operating in the test position also, make A
certain that the MOC is connected to operate.
Step 4 - Place the tape around the cam starting from the
bottom up. Make certain that the tape adheres well to
the cam surface. (See Figures 6-8, 6-9 and 6-10).
Figure 6-10 Attaching Tape Around to Back of Cam Figure 6-13 Manually Charging Closing Springs
Effective 3/01
Page 38 I.B. 3A74791H06
Figure 6-14 Manually Closing Circuit Breaker with Figure 6-17 Move Marker 15o to Left
Marker in Hole “C”.
Cam
ClosureTM Tool
Marker
15o
Figure 6-18 Remove Marked Masking Tape from Cam
15o
Figure 6-16 Move Marker 15o to Right Figure 6-19 Place Tape on Right Side Panel of
Breaker
Step 10 - Remove the marker from hole “C”. open position and the closing springs are discharged.
Remove the transparent CloSureTM Tool. Remove the
Step 11 - Push the “push to open” clapper to open the tape from the cam and stick the tape on the front right
circuit breaker. side sheet of the circuit breaker. Record the date of the
Step 12 - Inspect the circuit breaker to assure it is in the test and the operations counter reading on the tape
(Figures 6-18 and 6-19 and 6-20).
Effective 3/01
I.B. 3A74791H06 Page 39
5 3/16” Approx
5 3/16” Approx
5 3/16” Approx
8.0 to 10
Inches
“X” Inches
CloSureTM Overtravel
CloSureTM Distance
CloSureTM Position
A B C
Figure 6-20 Illustrative Testing Tape Sample Figure 6-22 Typical Circuit Breaker Front View with
CloSureTM Tool Attached (approximate mechanism
chassis width)
A-1
Breaker Approximate Upper Lower Marker
A-2
Line Mechanism Mounting Mounting Placement
C-2
A-3 Cabinet Hole Hole Hole
C-1 C-3 C-4 C-5 C-6
A-4 Width (inch)
20 A1 B2 C2
DHP-VR
27 A1 B1 C5
VCPW-ND 20/21 A1 B2 C2
27 A1 B2 C5
VCP-W
33 A2 B2 C6
18 A1 B2 C1
VCP-WR 20 A1 B2 C2
B-1 27 A1 B2 C5
B-2 18 A1 B2 C1
W-VAC,
25 A1 B1 C4
Figure 6-21 Front View of CloSureTM Tool Showing W-VACR
Mounting/Testing Hole Locations (6352C49H01) 33 A2 B2 C6
Effective 3/01
Page 40 I.B. 3A74791H06
After lubrication, operate the circuit breaker several Table 6.4 Approximate Resistance Measurements
times manually and electrically.
Rated Continuous Resistance
Roller bearings are used on the pole shaft, the cam Current (amperes) (microohms)
shaft, the main link and the motor eccentric. These
bearings are packed at the factory with a top grade slow 600A 92
oxidizing grease which normally should be effective for 1200A 90
many years. They should not be disturbed unless there 1600A 88
is definite evidence of sluggishness, dirt or parts are dis- 2000A 72
mantled for some reason.
Fails To Close
• Secondary Disconnects
• Motor
(Brushes worn or commutator
segment open)
• Mechanism • Pawls
(Slipping or Broken)
• Ratchet Wheel
(Teeth worn or broken)
• Oscillator
(Reset spring off or broken)
Effective 3/01
I.B. 3A74791H06 Page 41
Fails To Close
• Anti-Pump Relay
(Y relay N. C. contact open or
burned or relay picks up)
• Close Coil
(Open or burned)
• Auxiliary Switch
(b contact open or burned)
• Motor Cut-off
(Contacts open or burned)
• Trip Latch-Hatchet
(Fails to remain reset)
• Close Latch
(Binding)
Effective 3/01
Page 42 I.B. 3A74791H06
Undesirably Closes
Fails To Trip
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip Coil
(Burned or open)
• Pole Shaft
(Jammed)
• Vacuum Interrupter
(One or more welded)
Undesirably Trips
Effective 3/01
I.B. 3A74791H06 Page 43
W-VAC
W-VACR
W-VAC
W-VAC
W-VACR
13 360/20, 630A - 20kA 3A74686H11 3
14 360/20, 1250A - 20kA 3A74686H12 3
15 360/20, 1600A - 20kA 3A74686H13 3
16 360/20, 2000A - 20kA 3A74686H14 3
Effective 3/01
Page 44 I.B. 3A74791H06
7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)
W-VAC
W-VACR
W-VAC
W-VAC
W-VACR
Effective 3/01
I.B. 3A74791H06 Page 45
7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)
33 48VDC 699B196G06 1
34 125VDC/120VAC 699B196G04 1
35 250VDC.240VAC 699B196G05 1
37 48VDC 3759A76G11 1
38 125VDC/120VAC 3759A76G12 1
39 250VDC/240VAC 3759A76G13 1
41 48VDC 8237A27H03 1
42 125VDC 8237A27H04 1
43 250VDC 8237A27H05 1
44 120VAC 8237A27H01 1
45 240VAC 8237A27H02 1
46 24VDC 3759A76G14 1
47 48VDC 3759A76G11 1
48 125VDC/125VAC Cap Trip 3759A76G12 1
49 250VDC/240VAC Cap Trip 3759A76G13 1
Primary Disconnects
(W-VAC Only)
50 630A 5680B59G01 6
51 1250A 5680B60G01 6
52 1600A 5680B61G01 6
53 2000A 692C037G03 6
Effective 3/01
Page 46 I.B. 3A74791H06
7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)
UV Trip Coils
54 48VDC 8064A19G01 1
55 125VDC 8064A19G02 1
56 250VDC 8064A19G03 1
57 120VAC 8064A19G07 1
58 240VAC 8064A19G08 1
Effective 3/01
I.B. 3A74791H06 Page 47
7.1 Recommended Renewal Parts for IEC Rated Breakers (Continued Next Page)
Closed Open
Push to
Open
Push to
Close
Charged
Effective 3/01
Page 48 I.B. 3A74791H06
Wiring Harness
77 Repair Kit 8796C82G01 1
Complete Replacement
78 STD 8796C82G02 1
79 With #2 AUX SW 8798C82G03 1
Undervoltage Kit
80 48VDC 8794C81G01 1
81 125VDC 8794C81G02 1
82 250VDC 8794C81G03 1
83 120VAC 8794C81G04 1
84 240VAC 8794C81G05 1
Effective 3/01
I.B. 3A74791H06 Page 49
Effective 3/01
Page 50 I.B. 3A74791H06
Effective 3/01
I.B. 3A74791H06 Page 51
Effective 3/01
I.B. 3A74792H06
Cutler-Hammer
Pittsburgh, PA 15220
Effective 3/01 (ISI)
Style 3A74792H06
Printed in U.S.A.