Professional Documents
Culture Documents
1. Introduction to Eurocodes
R S Narayanan FREng O Brooker BEng, CEng, MICE, MIStructE
The development of the Eurocodes started in 1975; since then they have
evolved significantly and are now claimed to be the most technically
advanced structural codes in the world. The many benefits of using Eurocode 2
are summarised below. There are ten Eurocodes covering all the main structural
materials (see Figure 1). They are produced by the European Committee for
Standardization (CEN), and will replace existing national standards in 28
countries.
Each country is required to publish a Eurocode with a national title page and
forward but the original text of the Eurocode must appear as produced by
CEN as the main body of the document. A National Annex (NA) can be
included at the back of the document (see Figure 2). Throughout this
publication it is assumed that the UK National Annexes will be used.
Figure 1
The Eurocodes Eurocode: Basis of
BS EN 1990, Eurocode:
Basis of structural design
Structural safety,
serviceability and durability
structural design
BS EN 1991, Eurocode 1: This Eurocode underpins all structural design irrespective of the
Actions on structures
Actions on structures material of construction. It establishes principles and requirements for
safety, serviceability and durability of structures. (Note, the correct title
BS EN 1992, Eurocode 2: Concrete
BS EN 1993, Eurocode 3: Steel
is Eurocode not Eurocode 0.) The Eurocode uses a statistical approach
BS EN 1994, Eurocode 4: Composite Design and detailing to determine realistic values for actions that occur in combination with
BS EN 1995, Eurocode 5: Timber
BS EN 1996, Eurocode 6: Masonry each other.
BS EN 1999, Eurocode 9: Aluminium
Geotechnical
There is no equivalent British Standard for Eurocode: Basis of structural
BS EN 1997, Eurocode 7: BS EN 1998, Eurocode 8:
Geotechnical design Seismic design and seismic design and the corresponding information has traditionally been
design
replicated in each of the material Eurocodes. It also introduces new
definitions (see Glossary) and symbols (see Tables 2a and 2b), which
will be used throughout this publication to assist familiarity. Partial
Figure 2 factors for actions are given in this Eurocode, whilst partial factors for
Typical Eurocode layout
materials are prescribed in their relevant Eurocode.
Representative values
For each variable action there are four representative values. The
principal representative value is the characteristic value and this can be
B determined statistically or, where there is insufficient data, a nominal
A C
D value may be used. The other representative values are combination,
D
D frequent and quasi-permanent; these are obtained by applying to the
A: National title page D: Main text D
B: National Foreword E: Main Annex(es) E characteristic value the factors c 0 , c 1 and c 2 respectively (see Figure 3).
F
C: CEN title page F: National Annex A semi-probabilistic method is used to derive the c factors, which vary
depending on the type of imposed load (see Table 3). Further information
Table 1 on derivation of the c factors can be found in Appendix C of the Eurocode.
Concrete related Eurocodes and their equivalent current standards
Eurocode Title Superseded standards The combination value (c 0 Qk) of an action is intended to take
BS EN 1990 Basis of structural design BS 8110: Part 1 – section 2 account of the reduced probability of the simultaneous occurrence of
BS EN 1991–1–1 Densities, self-weight and BS 6399: Part 1 and BS 648 two or more variable actions. The frequent value (c 1 Qk) is such that it
imposed loads
BS EN 1991–1–2 Actions on structures – should be exceeded only for a short period of time and is used
exposed to fire primarily for the serviceability limit states (SLS) and also the accidental
BS EN 1991–1–3 Snow loads BS 6399: Part 2 ultimate limit state (ULS). The quasi-permanent value (c 2 Qk) may be
BS EN 1991–1–4 Wind actions BS 6399: Part 3 exceeded for a considerable period of time; alternatively it may be
BS EN 1991–1–5 Thermal actions – considered as an average loading over time. It is used for the long-term
BS EN 1991–1–6 Actions during execution –
affects at the SLS and also accidental and seismic ULS.
BS EN 1991–1–7 Accidental actions –
BS EN 1991–2 Traffic loads on bridges BD 37/88
Combinations of actions
BS EN 1991–3 Actions induced by cranes –
and machinery In the Eurocodes the term ‘combination of actions’ is specifically used
BS EN 1991–4 Silos and tanks – for the definition of the magnitude of actions to be used when a limit
BS EN 1992–1–1 General rules for buildings BS 8110: Parts 1, 2 and 3 state is under the influence of different actions. It should not be
BS EN 1992–1–2 Fire resistance of concrete BS 8110: Part 1,Table 3.2 and confused with ‘load cases’, which are concerned with the arrangement
structures BS 8110: Part 2, section 4
of the variable actions to give the most unfavourable conditions and
BS EN 1992–2 Bridges BS 5400: Part 4
are given in the material Eurocodes. The following process can be used
BS EN 1992–3 Liquid-retaining and BS 8007
containment structures to determine the value of actions used for analysis:
BS EN 1997–1 Geotechnical design – BS 6031, BS 8002, BS 8004, 1. Identify the design situation (e.g. persistent, transient, accidental).
General rules BS 8006, BS 8008 & BS 8081
2. Identify all realistic actions.
BS EN 1997–2 Geotechnical design – Ground BS 5930
investigation and testing 3. Determine the partial factors (see below) for each applicable
BS EN 1998 Design of structures for – combination of actions.
earthquake resistance (6 parts) 4. Arrange the actions to produce the most critical conditions.
2
1. Introduction to Eurocodes
Table 2a
Where there is only one variable action (e.g. imposed load) in a Selected symbols for Eurocode
combination, the magnitude of the actions can be obtained by Symbol Definition
multiplying them by the appropriate partial factors. Gk Characteristic value of permanent action
Qk Characteristic value of single variable action
Where there is more than one variable action in a combination, it is gG Partial factor for permanent action
necessary to identify the leading action (Qk,1) and other accompanying gQ Partial factor for variable action
actions (Qk,i). The accompanying action is always taken as the c0 Factor for combination value of a variable action
combination value. c1 Factor for frequent value of a variable action
c2 Factor for quasi-permanent value of a variable action
Ultimate limit state j Combination factor for permanent actions
The ultimate limit states are divided into the following categories:
EQU Loss of equilibrium of the structure. Table 2b
Selected subscripts
STR Internal failure or excessive deformation of the structure
Subscript Definition
or structural member.
A Accidental situation
GEO Failure due to excessive deformation of the ground.
c Concrete
FAT Fatigue failure of the structure or structural members.
d Design
The Eurocode gives different combinations for each of these ultimate E Effect of action
limit states. For the purpose of this publication only the STR ultimate fi Fire
limit state will be considered. k Characteristic
R Resistance
For persistent and transient design situations under the STR limit w Shear reinforcement
state, the Eurocode defines three possible combinations, which are given y Yield strength
in Expressions (6.10), (6.10a) and (6.10b) of the Eurocode (see Tables 4
and 5). The designer (for UK buildings) may use either (6.10) or the less Figure 3
favourable of (6.10a) and (6.10b). Representative values of variable actions ⁵
Characteristic value of QK
required to determine the appropriate load combination; however, with Combination value of c0 QK
experience the designer will be able to determine this by inspection.
Frequent value of c1 QK
Expression (6.10) is always equal to or more conservative than the less
Quasi-
favourable of Expressions (6.10a) and (6.10b). Expression (6.10b) will permanent
value of c2 QK
normally apply when the permanent actions are not greater than 4.5
times the variable actions (except for storage loads (category E, Table 3)
where Expression (6.10a) always applies).
Time
Therefore, for a typical concrete frame building, Expression (6.10b) will Table 3
give the most structurally economical combination of actions. Recommended values of c factors for buildings (from UK National Annex)
Action c0 c1 c2
Imposed loads in buildings (see BS EN 1991–1–1)
For members supporting one variable action the combination
Category A: domestic, residential areas 0.7 0.5 0.3
1.25 Gk + 1.5 Qk (derived from (Exp 6.10b))
Category B: office areas 0.7 0.5 0.3
can be used provided the permanent actions are not greater
Category C: congregation areas 0.7 0.7 0.6
than 4.5 times the variable actions (except for storage loads). Category D: shopping areas 0.7 0.7 0.6
Category E: storage areas 1.0 0.9 0.8
Category F: traffic area, vehicle weight < 30 kN 0.7 0.7 0.6
Serviceability limit state
Category G: traffic area, 30 kN < vehicle weight < 160 kN 0.7 0.5 0.3
There are three combinations of actions that can be used to check the
Category H: roofs* 0.7 0 0
serviceability limit states (see Tables 6 and 7). Eurocode 2 indicates
Snow loads on buildings (see BS EN 1991–3)
which combination should be used for which phenomenon (e.g.
For sites located at altitude H > 1000 m above sea level 0.7 0.5 0.2
deflection is checked using the quasi-permanent combination). Care For sites located at altitude H < 1000 m above sea level 0.5 0.2 0
should be taken not to confuse the SLS combinations of characteristic, Wind loads on buildings (see BS EN 1991–1–4) 0.5 0.2 0
frequent and quasi-permanent, with the representative values that Temperature (non-fire) in buildings (see BS EN 1991–1–5) 0.6 0.5 0
have the same titles. Key
*See also 1991–1–1: Clause 3.3.2
3
How to design concrete structures using Eurocode 2
Table 4
Design values of actions, ultimate limit state – persistent and transient design situations (table A1.2 (B) Eurocode)
Combination Expression reference Permanent actions Leading variable action Accompanying variable actions
Unfavourable Favourable Main (if any) Others
Exp. (6.10) g G, j, sup Gk , j , sup g G , j, inf G k , j , inf g Q,1 Qk,1 g Q,1 c 0 ,1 Q k,i
Exp. (6.10a) g G, j, sup Gk , j , sup g G , j, inf G k , j , inf g Q,1 c 0 ,1 Qk,1 g Q,1 c 0 ,1 Q k,i
Exp. (6.10b) jg G, j, sup Gk , j , sup g G , j, inf G k , j , inf g Q,1 Qk,1 g Q,1 c 0 ,1 Q k,i
Note
1 Design for either Expression (6.10) or the less favourable of Expressions (6.10a) and (6.10b).
Table 5
Design values of actions, derived for UK design, ultimate limit state – persistent and transient design situations
Combination Expression reference Permanent actions Leading variable action Accompanying variable actions
Unfavourable Favourable Main (if any) Others
Combination of permanent and variable actions
Exp. (6.10) 1.35 Gk a 1.0 Gk a 1.5c Qk
Exp. (6.10a) 1.35 Gk a 1.0 Gk a 1.5 c 0,1b Qk
Exp. (6.10b) 0.925 d x 1.35 Gk a
1.0 Gk a
1.5c Qk
Combination of permanent, variable and accompanying variable actions
Exp. (6.10) 1.35 Gk a 1.0 Gk a 1.5c Qk,1 1.5 c c 0,i b Q k,i
Exp. (6.10a) 1.35 Gk a 1.0 Gk a 1.5 c 0,1b Qk 1.5 c c 0,i b Q k,i
Exp. (6.10b) 0.925 d x 1.35 Gk a 1.0 Gk a 1.5c Qk,1 1.5 c c 0,i b Q k,i
Key
a Where the variation in permanent action is not considered significant, Gk,j,sup and Gk,j,inf may be taken as Gk c Where the accompanying load is favourable, g Q,i = 0
b The value of c 0 can be obtained from Table NA A1.1 of the UK National Annex (reproduced here as Table 3) d The value of j in the UK National Annex is 0.925
Table 6
Design values of actions, serviceability limit states
Table 7
Example design combinations for deflection (quasi-permanent) derived for typical UK reinforced concrete design
4
1. Introduction to Eurocodes
Eurocode 1 Table 8
Eurocode 1, its parts and dates of publication
not all the parts of Eurocode 1 and their National Annexes are BS EN 1991–1–4 Wind actions April Due
2005 January
available, in which case it is advised that the loads recommended in 2007a
the current British Standards are used. BS EN 1991–1–5 Thermal actions March Due
2004 December
2006a
5
How to design concrete structures using Eurocode 2
6
1. Introduction to Eurocodes
7
1. Introduction to Eurocodes
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1992, Eurocode 2: Design of concrete structures. BSI (4 parts).
2 BRITISH STANDARDS INSTITUTION. BS EN 1990, Eurocode: Basis of structural design. BSI, 2002.
3 BRITISH STANDARDS INSTITUTION. BS EN 1991, Eurocode 1: Actions on structures. BSI (10 parts).
4 BRITISH STANDARDS INSTITUTION. BS 8110: The structural use of concrete. BSI (3 parts).
5 GULVANESSIAN, H, CALGARO, J A & HOLICÝ, M T. Designers’ guide to EN 1990. Thomas Telford, 2002.
6 BRITISH STANDARDS INSTITUTION. BS 6399: Loading for buildings. BSI (3 parts).
7 BRITISH STANDARDS INSTITUTION. BS 648: Schedule of weights of building materials. BSI, 1964.
8 BRITISH STANDARDS INSTITUTION. Web page: www.bsi-global.com/Eurocodes/Progress/index.xalter. BSI.
9 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–1, Eurocode 2: Design of concrete structures. General rules and rules for buildings. BSI, 2004.
10 BRITISH STANDARD INSTITUTION. PD 6687. Background paper to the UK National Annex to BS EN 1992–1–1. BSI, 2006.
11 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Beams (TCC/03/19). The Concrete Centre, 2006.
12 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–2, Eurocode 2: Design of concrete structures. Structural fire design. BSI, 2004.
13 BROOKER, O. How to design concrete structures using Eurocode 2: Getting started (TCC/03/17). The Concrete Centre, 2005.
14 BRITISH STANDARDS INSTITUTION. BS EN 1992–2, Eurocode 2: Design of concrete structures. Bridges. BSI, 2005.
15 BRITISH STANDARDS INSTITUTION. BS EN 1992–3, Eurocode 2: Design of concrete structures. Liquid-retaining and containment structures.
BSI, due 2006.
16 BRITISH STANDARDS INSTITUTION. BS 8007: Code of practice for design of concrete structures for retaining aqueous liquids. BSI, 1987.
17 BRITISH STANDARDS INSTITUTION. BS EN 1997, Eurocode 7: Geotechnical design. BSI (2 parts).
18 WEBSTER, R & BROOKER, O. How to design concrete structures using Eurocode 2: Foundations (TCC/03/21). The Concrete Centre, 2006.
19 BRITISH STANDARDS INSTITUTION. BS EN 1998, Eurocode 8: Design of structures for earthquake resistance. BSI (6 parts).
20 BRITISH STANDARDS INSTITUTION. BS 8500: Concrete – Complementary British Standard to BS EN 206–1, 2002 (2 parts).
21 HARRISON, T A & BROOKER, O. How to use BS 8500 with BS 8110 (TCC/03/11). The Concrete Centre, 2005.
22 BRITISH STANDARDS INSTITUTION. BS 4449: Specification for carbon steel bars for the reinforcement of concrete. BSI, 2005.
23 BRITISH STANDARDS INSTITUTION. BS EN 10080: Steel for the reinforcement of concrete – Weldable reinforcing steel – General. BSI, 2005.
24 BRITISH STANDARDS INSTITUTION. EN 13670: Execution of concrete structures – Part 1: Common. BSI, due 2008.
25 THE CONCRETE SOCIETY. CS 152: National structural concrete specification for building construction, third edition. The Society, 2004.
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/16 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-26-9 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
published November 2005, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ and British Cement Association views expressed are not necessarily those of the DTI.
How to design concrete structures using Eurocode 2
2. Getting started
O Brooker BEng, CEng, MICE, MIStructE
Similarly, the process of detailing will not vary significantly from current
practice. Guidance can be found in Chapter 10 or in Standard method of
detailing 2. With regard to specification, advice can be found in Chapter 1,
originally published as Introduction to Eurocodes3. Concept designs
prepared assuming that detailed design would be to BS 8110 may be
continued through to detailed design using Eurocode 2.
Design life
The design life for a structure is given in Eurocode: Basis of structural
design 4. The UK National Annex (NA) to Eurocode presents UK values
for design life; these are given in Table 1 (overleaf). These should be used
to determine the durability requirements for the design of reinforced
concrete structures.
The key change to current practice is that the bulk density of reinforced
concrete has been increased to 25 kN/m3. The draft National Annex to
this Eurocode gives the imposed loads for UK buildings and a selection is
How to design concrete structures using Eurocode 2
Table 1
Indicative design working life (from UK National Annex to Eurocode) reproduced in Table 3. It should be noted that there is no advice given
for plant rooms.
Design life (years) Examples
10 Temporary structures
10–30 Replaceable structural parts At the time of writing not all the parts of Eurocode 1 and their National
15–25 Agricultural and similar structures Annexes are available; it is advised that existing standards are considered
50 Buildings and other common structures for use where European standards have not yet been issued.
120 Monumental buildings, bridges and other civil
engineering structures
Load arrangements
Table 2
Selected bulk density of materials (from Eurocode 1, Part 1–1) The term load arrangements refers to the arranging of variable actions
(e.g. imposed and wind loads) to give the most onerous forces in a
Material Bulk density (kN/m3)
Normal weight concrete 24.0 member or structure and are given in Eurocode 2 and its UK NA.
Reinforced normal weight concrete 25.0
Wet normal weight reinforced concrete 26.0 For building structures, the UK NA to Eurocode 2, Part 1–1 allows any
of the following sets of load arrangements to be used for both the
ultimate limit state and serviceability limit state:
Figure 1
Alternate spans loaded
Load set 1. Alternate or adjacent spans loaded
The design values should be obtained from the more critical of:
� Alternate spans carrying the design variable and permanent loads
with other spans loaded with only the design permanent load (see
Figure 1). The value of gG should be the same throughout.
� Any two adjacent spans carrying the design variable and
permanent loads with other spans loaded with only the design
permanent load (see Figure 2). The value of gG should be the
same throughout.
Generally, load set 2 will be used for beams and slabs in the UK as it
requires three load arrangements to be considered, while load set 1
will often require more than three arrangements to be assessed.
Alternatively, the UK NA makes the following provision for slabs.
2
10
2. Getting started
Combination of actions Standard to BS EN 206–17 (e.g. for class C28/35 concrete the cylinder
strength is 28 MPa, whereas the cube strength is 35 MPa). Typical
The term combination of actions refers to the value of actions to be concrete properties are given in Table 4.
used when a limit state is under the influence of different actions.
Concrete up to class C90/105 can be designed using Eurocode 2.
The numerical values of the partial factors for the ULS combination can For classes above C50/60, however, there are additional rules and
be obtained by referring to Eurocode: Basis of structural design or to variations. For this reason, the design of these higher classes is not
Chapter 1. considered in this publication.
For members supporting one variable action the ULS combination It should be noted that designated concretes (e.g. RC30) still refer
.( 1.25 Gk + 1.5 Qk (derived from Exp. (6.10b), Eurocode) to the cube strength.
can be used provided the permanent actions are not greater than
4.5 times the variable actions (except for storage loads). Reinforcing steel
Eurocode 2 can be used with reinforcement of characteristic
There are three SLS combinations of actions – characteristic, frequent strengths ranging from 400 to 600 MPa. The properties of steel
and quasi-permanent. The numerical values are given in Eurocode: Basis reinforcement in the UK for use with Eurocode 2 are given in
of structural design. BS 4449 (2005): Specification for carbon steel bars for the
reinforcement of concrete 8 and are summarised in Table 5 (on page 4).
A characteristic yield strength of 500 MPa has been adopted by the
Material properties UK reinforcement industry. There are three classes of reinforcement,
A, B and C, which provide increasing ductility. Class A is not suitable
Concrete where redistribution of 20% and above has been assumed in the
In Eurocode 2 the design of reinforced concrete is based on the design. There is no provision for the use of plain bar or mild steel
characteristic cylinder strength rather than cube strength and should reinforcement, but guidance is given in the background paper to the
be specified according to BS 8500: Concrete – complementary British National Annex9.
Table 3
Selected imposed loads for buildings (from draft UK National Annex to Eurocode 1, Part 1–1)
Table 4
Selected concrete properties based on Table 3.1 of Eurocode 2, Part 1–1
3
11
How to design concrete structures using Eurocode 2
Table 5
Characteristic tensile properties of reinforcement Structural analysis
Class (BS 4449) and designation (BS 8666) A B C
The primary purpose of structural analysis in building structures is to
Characteristic yield strength fyk or f 0.2k (MPa) 500 500 500
establish the distribution of internal forces and moments over the
Minimum value of k = ( ft /fy ) k ≥ 1.05 ≥ 1.08 ≥ 1.15 < 1.35
whole or part of a structure and to identify the critical design
Characteristic strain at maximum force e uk (%) ≥ 2.5 ≥ 5.0 ≥ 7.5
conditions at all sections. The geometry is commonly idealised by
Notes
1 Table derived from BS EN 1992–1–1 Annex C, BS 4449: 2005 and BS EN 1008010 . considering the structure to be made up of linear elements and plane
2 The nomenclature used in BS 4449: 2005 differs from that used in BS EN 1992–1–1 two-dimensional elements.
Annex C and used here.
3 In accordance with BS 8666, class H may be specified, in which case class A, B or C
may be supplied. The type of analysis should be appropriate to the problem being
considered. The following may be used: linear elastic analysis, linear
Table 6 elastic analysis with limited redistribution, and plastic analysis. Linear
Bending moment and shear co-efficients for beams elastic analysis may be carried out assuming cross sections are
Moment Shear uncracked (i.e. concrete section properties); using linear stress-strain
Outer support 25% of span moment 0.45 (G + Q) relationships, and assuming mean values of elastic modulus.
Near middle of end span 0.090 Gl + 0.100 Ql
At first interior support – 0.094 (G + Q) l 0.63 (G + Q)a For the ultimate limit state only, the moments derived from elastic
At middle of interior spans 0.066 Gl + 0.086 Ql analysis may be redistributed (up to a maximum of 30%) provided
At interior supports – 0.075 (G + Q) l 0.50 (G + Q) that the resulting distribution of moments remains in equilibrium with
Key the applied loads and subject to certain limits and design criteria (e.g.
a 0.55 (G + Q) may be used adjacent to the interior span.
limitations of depth to neutral axis).
Notes
1 Redistribution of support moments by 15% has been included.
2 Applicable to 3 or more spans only and where Qk ≤ G k. Regardless of the method of analysis used, the following principles apply:
3 Minimum span ≥ 0.85 longest span.
4 l is the effective length, G is the total of the ULS permanent actions, Q is the total � Where a beam or slab is monolithic with its supports, the critical
of the ULS variable actions.
design hogging moment may be taken as that at the face of the
support, but should not be taken as less than 0.65 times the full
Table 7 fixed end moment.
Exposure classes
� Where a beam or slab is continuous over a support that may be
Class Description considered not to provide rotational restraint, the moment
No risk of corrosion or attack calculated at the centre line of the support may be reduced by
X0 For concrete without reinforcement or embedded metal where there (FEd,sup t/8), where FEd,sup is the support reaction and t is the breadth
is no significant freeze/thaw, abrasion or chemical attack. of the support.
Corrosion induced by carbonation � For the design of columns the elastic moments from the frame
XC1 Dry or permanently wet action should be used without any redistribution.
XC2 Wet, rarely dry
XC3/4 Moderate humidity or cyclic wet and dry Bending moment and shear force co-efficients for beams are given in
Corrosion induced by chlorides other than from seawater
Table 6; these are suitable where spans are of similar length and the
other notes to the table are observed.
XD1 Moderate humidity
XD2 Wet, rarely dry
XD3 Cyclic wet and dry
Corrosion induced by chlorides from seawater
Minimum concrete cover
XS1 Exposed to airborne salt but not in direct contact with sea water The nominal cover can be assessed as follows:
XS2 Permanently submerged
cnom = cmin + D cdev Exp. (4.1)
XS3 Tidal, splash and spray zones
Freeze/thaw with or without de-icing agents Where cmin should be set to satisfy the requirements below:
XF1 Moderate water saturation without de-icing agent � safe transmission of bond forces
4
12
2. Getting started
Figure 4
Sections through structural members, showing nominal axis distance, a National Annex (Table 4.3 (N) (BS)) gives durability requirements that
comply with BS 8500, but which significantly modify the approach
taken in Eurocode 2. To determine the minimum cover for durability
(and also the strength class and minimum water cement ratio) either
the UK National Annex or BS 8500 can be used.
The various exposure classes from BS 8500 are given in Table 7. Selected
recommendations are given in Table 8 (on page 6) for the concrete
strength, minimum cement ratio, minimum concrete cover and maximum
cement content for various elements in a structure based on the exposure
of that element. This is taken from Chapter 11, originally published as
How to use BS 8500 with BS 811013.
Table 9
Minimum column dimensions and axis distances for columns with
rectangular or circular section – method A
Design for fire resistance
Eurocode 2 Part 1–2: Structural fire design14, gives several methods
Standard fire Minimum dimensions (mm)
resistance Column width ( bmin)/axis distance (a) of the main bars for determining the fire resistance of concrete elements; further
Column exposed on more Exposed on one side guidance can be obtained from specialist literature. Design for
than one side ( m f i = 0.7) ( m f i = 0.7) fire resistance may still be carried out by referring to tables to
R 60 250/46 155/25 determine the minimum cover and dimensions for various elements,
350/40 as set out below.
R 120 350/57* 175/35
450/51*
Rather than giving the minimum cover, the tabular method is based
R 240 † 295/70
on nominal axis distance, a (see Figure 4). This is the distance from the
Notes
1 Refer to BS EN 1992–1–2 for design limitations.
centre of the main reinforcing bar to the surface of the member. It is
2 m fi is the ratio of the design axial load under fire conditions to the design resistance a nominal (not minimum) dimension. The designer should ensure that
of the column at normal temperature conditions. Conservatively m fi may be taken
as 0.7
a ≥ cnom + f link + f bar /2.
* Minimum 8 bars
† Method B indicates 600/70 for R 240 and m fi = 0.7 and may be used.
See EN 1992–1–2 Table 5.2b
There are three standard fire exposure conditions that may be satisfied:
R Mechanical resistance for load bearing
E Integrity of separation
Minimum cover for bond I Insulation
The minimum cover to ensure adequate bond should not be less than
the bar diameter, or equivalent bar diameter for bundled bars, unless Tables 9 and 10 give the minimum dimensions for columns and slabs
the aggregate size is over 32 mm. to meet the above conditions. The tables offer more flexibility than
BS 8110 in that there are options available to the designer e.g. section
Minimum cover for durability sizes can be reduced by increasing the axis distance. Further information
The recommendations for durability in Eurocode 2 are based on is given in Eurocode 2 and subsequent chapters, including design
BS EN 206–112. In the UK the requirements of BS EN 206 –1 are limitations and data for walls and beams.
applied through the complementary standard BS 8500. The UK
Table 10
Minimum dimensions and axis distances for reinforced concrete slabs
5
13
How to design concrete structures using Eurocode 2 BS 8500 for building structures
8
Table 2
Selected a recommendations for normal-weight reinforced concrete quality for combined exposure classes and cover to reinforcement for at least a
50-year intended working life and 20 mm maximum aggregate size
Exposure conditions Cement/ Strength classc, maximum w/c ratio, minimum cement or combination
combination content (kg/m3), and equivalent designated concrete (where applicable)
designationsb
Typical example Primary Secondary Nominal cover to reinforcementd
15 + D c dev 20 + D c dev 25 + D c dev 30 + D c dev 35 + D c dev 40 + D c dev 45 + D c dev 50 + D c dev
Internal mass
X0 ___ All Recommended that this exposure is not applied to reinforced concrete
concrete
Internal elements C20/25,
(except humid XC1 ___ All 0.70, 240 or <<< <<< <<< <<< <<< <<< <<<
locations) RC20/25
Buried concrete C25/30,
in AC-1 ground XC2 AC-1 All ___ ___ 0.65, 260 or <<< <<< <<< <<< <<<
conditions e RC25/30
Vertical surface C40/50, C30/37, C28/35, C25/30,
protected from ___ All except
All except IVB ___ 0.45, 340 or 0.55, 300 0.60, 280 or 0.65, 260 or <<< <<< <<<
IVB-V
direct rainfall RC40/50 or RC30/37 RC28/35 RC25/30
C40/50, C30/37, C28/35,
Exposed vertical
XF1
All except
All except IVB ___ 0.45, 340 or 0.55, 300 0.60, 280 or <<< <<< <<< <<<
surfaces IVB-V
XC3 RC40/50 or RC30/37 RC28/35
& C40/50,0.45,
XC4 XF3
All except
All except IVB ___ 340 g or <<< <<< <<< <<< <<< <<<
IVB-V
RC40/50XFg
Exposed horizontal
surfaces C30/37, C28/35, C25/30,
C32/40,
XF3 (air All except
All except IVB ___ ___ 0.55,
0.55, 300
300
0.60, 280 0.60, 280
<<< <<< <<<
entrained) IVB-V plus g,h plus air g,h plus air g, h, j
plus air
air g,h
or PAV2 or PAV1
Elements subject
to airborne XD1f ___ All ___ ___ C40/50, C32/40, C28/35,
<<< <<< <<<
0.45, 360 0.55, 320 0.60, 300
chlorides
IIB-V, IIIA ___ ___ ___ ___ ___ C35/45, C32/40, C28/35,
0.40, 380 0.45, 360 0.50, 340
Car park decks and
areas subject to ___ CEM I, IIA, ___ ___ ___ ___ ___ See C40/50, C35/45,
IIB-S, SRPC BS 8500 0.40, 380 0.45, 360
de-icing spray
IIIB, IVB-V ___ ___ ___ ___ ___ C32/40, C28/35, C25/30,
0.40, 380 0.45, 360 0.50, 340
IIB-V, IIIA ___ ___ ___ ___ ___ C35/45, C32/40, C32/40,
0.40, 380 0.45, 360 0.50, 340
Vertical elements XD3f
subject to de-icing XF2
CEM I, IIA, ___ ___ ___ ___ ___ See C40/50, C35/45,
IIB-S, SRPC BS 8500 0.40, 380 0.45, 360
spray and freezing
IIIB, IVB-V ___ ___ ___ ___ ___ C32/40, C32/40 C32/40,
0.40, 380 0.45, 360 0.50, 340
6
14 3
2. Getting started
Table 11
Maximum bar size or spacing to limit crack width
7
15
2. Getting started
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1992, Eurocode 2: Design of concrete structures. BSI (4 parts).
2 INSTITUTION OF STRUCTURAL ENGINEERS/THE CONCRETE SOCIETY. Standard method of detailing. ISE/CS. 2006.
3 NARAYANAN, R S & BROOKER, O. How to design concrete structures using Eurocode 2: Introduction to Eurocodes (TCC/03/16). The Concrete Centre, 2005.
4 BRITISH STANDARDS INSTITUTION. BS EN 1990, Eurocode: Basis of structural design. BSI, 2002.
5 BRITISH STANDARDS INSTITUTION. BS EN 1991, Eurocode 1: Actions on structures. BSI (10 parts).
6 BRITISH STANDARDS INSTITUTION. BS EN 1991, Eurocode 1: Actions on structures Part 1–1: General actions – Densities, self-weight, imposed loads
for buildings. BSI, 2002.
7 BRITISH STANDARDS INSTITUTION. BS 8500–1: Concrete – Complementary British Standard to BS EN 206–1– Part 1: Method of specifying and
guidance for the specifier. BSI, 2002.
8 BRITISH STANDARDS INSTITUTION. BS 4449: Specification for carbon steel bars for the reinforcement of concrete. BSI, 2005.
9 BRITISH STANDARDS INSTITUTION. Background paper to the UK National Annex to BS EN 1992–1–1. BSI, 2006.
10 BRITISH STAND ARDS INSTITUTION. BS EN 10080: Steel for the reinforcement of concrete – Weldable reinforcing steel – General. BSI, 2005.
11 BUILDING RESEARCH ESTABLISHMENT. Special Digest 1: Concrete in aggressive ground. BRE, 2005.
12 BRITISH STANDARDS INSTITUTION. BS EN 206–1: Concrete – Part: Specification, performance, production and conformity. BSI, 2000.
13 HARRISON, T A BROOKER, O. How to use BS 8500 with BS 8110 (TCC/03/11). The Concrete Centre, 2005.
14 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–2, Eurocode 2: Design of concrete structures. General rules – structural fire design, BSI, 2004.
15 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Columns, (TCC/03/20). The Concrete Centre, 2006.
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/17 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-27-7 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
16 published December 2005, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ views expressed are not necessarily those of the DTI.
4. Beams
structures using
How to design concrete structures using Eurocode
Eurocode 22
4. Beams
M Moss
R Moss BSc, ;L\%
PhD,Ia=%
DIC, =B<%
CEng,<>g`%
MICE,FB<>%
MIStructE O Brooker
FBLmkn\m>O Brooker BEng,;>g`%
CEng,<>g`%
MICE,FB<>% FBLmkn\m>
MIStructE
Designing to Eurocode 2
This chapter covers the analysis and design of concrete beams to Eurocode 21
which is essentially the same as with BS 81102' Ahp^o^k% ma^eZrhnmZg]
\hgm^gmh_>nkh\h]^+fZrZii^ZkngnlnZemh]^lb`g^kl_ZfbebZkpbma;L1**)'
>nkh\h]^+]h^lghm\hgmZbgma^]^kbo^]_hkfneZ^hkli^\b_b\`nb]Zg\^hg
]^m^kfbgbg`fhf^gmlZg]la^Zk_hk\^l' MablaZlZkbl^g[^\Znl^bmaZl
[^^g>nkhi^ZgikZ\mb\^mh`bo^ikbg\bie^lbgma^\h]^lZg]_hkma^]^mZbe^]
Ziieb\Zmbhgmh[^ik^l^gm^]bghma^klhnk\^lln\aZlm^qm[hhdl'
<aZim^k*%hkb`bgZeerin[ebla^]ZlBgmkh]n\mbhgmh>nkh\h]^l%ab`aeb`am^]ma^
3
d^r]b__^k^g\^l[^mp^^g>nkh\h]^+Zg];L1**)% bg\en]bg`m^kfbgheh`r'
Bmlahne][^ghm^]maZmoZen^l_khfma^NDGZmbhgZe:gg^q!G:"aZo^[^^g
nl^]makhn`ahnm% bg\en]bg`oZen^lmaZmZk^^f[^]]^]bg]^kbo^] _hkfneZ^
!]^kboZmbhgl\Zg[^_hng]Zmppp'^nkh\h]^+'bg_h"' :eblmh_lrf[hel k^eZm^]
mh[^Zf]^lb`gbl`bo^gZmma^^g]h_mabl\aZim^k'
Design procedure
:ikh\^]nk^_hk\Zkkrbg`hnmma^]^mZbe^]]^lb`gh_[^ZflbllahpgbgMZ[e^*'
MablZllnf^lmaZmma^[^Zf]bf^glbhglaZo^ik^obhnler[^^g]^m^kfbg^]
]nkbg`\hg\^imnZe]^lb`g' <hg\^im]^lb`glik^iZk^]Zllnfbg`]^mZbe^]]^lb`g
phne][^mh;L1**)fZr[^\hgmbgn^]makhn`amh]^mZbe^]]^lb`gnlbg`
>nkh\h]^+' Fhk^]^mZbe^]Z]ob\^hg]^m^kfbgbg`]^lb`geb_^% Z\mbhgl% fZm^kbZe
ikhi^kmb^l% f^mah]lh_ZgZerlbl% fbgbfnf\hg\k^m^\ho^k_hk]nkZ[bebmrZg]
\hgmkheh_\kZ\dpb]mal\Zg[^_hng]bg<aZim^k+%hkb`bgZeerin[ebla^]Zl
@^mmbg`lmZkm^] %Zg] in<aZim^k*'
<hgmbgn^liZ`^+0
How to design concrete structures using Eurocode 2
Table 1
Beam design procedure
Table 2
Minimum dimensions and axis distances for beams made with reinforced concrete for fire resistance
Standard fire resistance Minimum dimensions (mm)
Possible combinations of a and bmin where a is the average axis distance and bmin is the width of the beam
Simply supported beams Continuous beams
A B C D E F G H
R60 bmin = 120 160 200 300 120 200
a= 40 35 30 25 25 12a
R90 bmin = 150 200 300 400 150 250
a= 55 45 40 35 35 25
R120 bmin = 200 240 300 500 200 300 450 500
a= 65 60 55 50 45 35 35 30
R240 bmin = 280 350 500 700 280 500 650 700
a= 90 80 75 70 75 60 60 50
Notes
1 This table is taken from BS EN 1992–1–2 Tables 5.5 and 5.6.
2 The axis distance, asd , from the side of the beam to the corner bar should be a +10 mm except where bmin is greater than the values in columns C and F.
3 The table is valid only if the detailing requirements (see note 4) are observed and, in normal temperature design, redistribution of bending moments does not exceed 15%.
4 For fire resistance of R90 and above, for a distance of 0.3l eff from the centre line of each intermediate support, the area of top reinforcement should not be less than the following:
A s,req (x) = A s,req ( 0 )( 1– 2.5 ( x/ l eff ) )
where:
x is the distance of the section being considered from the centre line of the support.
A s,req ( 0 ) is the area of reinforcement required for normal temperature design.
A s,req (x) is the minimum area of reinforcement required at the section being considered but not less than that required for normal temperature design.
l eff is the greater of the effective lengths of the two adjacent spans.
5 For fire resistances R120 – R240, the width of the beam at the first intermediate support should be at least that in column F, if both the following conditions exist:
a there is no fixity at the end support; and
b the acting shear at normal temperature Vsd > 0.67 V Rd,max .
Key
a Normally the requirements of BS EN 1992–1–1 will determine the cover.
Figure 1 Figure 3
Section through structural member, Simplified rectangular stress block for
showing nominal axis distances a and asd concrete up to class C50/60 from Eurocode 2
b εc fcd
ε sc
d2
x As2 0.8x Fsc
Fc
h>b Neutral axis
d
h z
a
As Fst
asd εs
b
Section Strain Stress block and forces
2
26
4. Beams
Figure 2
member. It is a nominal (not minimum) dimension, so the designer Procedure for determining flexural reinforcement
should ensure that:
a ≥ cnom + f link + f bar /2 and asd = a + 10 mm START
Table 2 gives the minimum dimensions for beams to meet the
standard fire periods. Carry out analysis of beam to determine
design moments (M) (see Table 3)
Moment Shear
Outer support 25% of span moment 0.45 (G + Q) No Compression reinforcement
Is K ≤ K ’ ? required
G^Zkfb]]e^h_^g]liZg )')2)Gl + 0.100 Ql
At first interior support – 0.094 (G + Q) l 0.63 (G + Q)a
Yes
At middle of interior spans 0.066 Gl + 0.086 Ql Calculate lever arm z from
At interior supports – 0.075 (G + Q) l 0.50 (G + Q)
No compression reinforcement required 2 [
z = d 1 + 1 – 3.53 K ’ ]
Key
a 0.55 (G + Q) may be used adjacent to the interior span.
Notes
1 Redistribution of support moments by 15% has been included. Obtain lever arm z from Table 5 or use Calculate compression
2 Applicable to 3 or more spans only and where Qk ≤ G k. reinforcement required from
3 Minimum span ≥ 0.85 longest span. z= d
2 [1 + 1 – 3.53 K ] ≤ 0.95d As2 =
(K– K’) fck bd 2
4 l is the span, G is the total of the ULS permanent actions, Q is the total fsc(d– d2)
of the ULS variable actions.
where
Calculate tension reinforcement
Table 4
Values for K ’
required from
As =
M
fsc = 700
[ x – d2
x ] ≤ fyd
fyd z
% redistribution d (redistribution ratio) K ’
) *')) )'+)1Z Calculate tension
Check minimum reinforcement
reinforcement required from
*) )'2) )'*1+Z requirements (see Table 6)
0.26 fctm bt d K’fck bd 2 fsc
*. )'1. )'*/1 As,min = where fck ≥ 25 As = + As2
fyk fyd z fyd
+) )'1) )'*.,
+. )'0. )'*,0
,) )'0) )'*+) Check maximum reinforcement requirements As,max = 0.04 Ac
for tension or compression reinforcement outside lap locations
Key
a Bmblh_m^gk^\hf^g]^]bgma^NDmaZm D£lahne][^ebfbm^]mh)'*/1mh^glnk^]n\mbe^_Zbenk^'
Table 5 Table 6
z/d for singly reinforced rectangular sections Minimum percentage of required reinforcement
273
How to design concrete structures using Eurocode 2
Figure 4
Strut inclination method Eurocode 2 offers various methods for determining the stress-strain
relationship of concrete. For simplicity and familiarity the method
Concrete strut in compression
presented here is the simplified rectangular stress block, which is
similar to that found in BS 8110 (see Figure 3).
Vertical shear
Figure 5
Procedure for determining vertical shear reinforcement Eurocode 2 introduces the strut inclination method for shear capacity
checks. In this method the shear is resisted by concrete struts acting in
START compression and shear reinforcement acting in tension.
Determine vEd where The angle of the concrete strut varies, depending on the shear force
vEd = design shear stress [ vEd = VEd /(bwz) = VEd /(0 9. bwd)] applied (see Figure 4). The procedure for determining the shear capacity
of a section is shown in Figure 5 (which includes UK NA values) and is
Determine the concrete strut capacity v Rd, max cot y = 2.5
in terms of shear stress in the vertical plane rather than a vertical force
from Table 7 as given in Eurocode 2. Where shear reinforcement is required, then
the angle of the concrete strut should be calculated. For many typical
beams the minimum angle of strut will apply (when cot y = 2.5 or y =
Is Is
21.8º) i.e. for class C30/37 concrete the strut angle exceeds 21.8º only
No No Redesign
vEd < vRd,max coty = 2.5? v Ed < v Rd,max cot y = 1.0? when the shear stress is greater than 3.27 N/mm2 (refer to Table 7).
section
(see Table 7)
As with BS 8110, there is a maximum permitted shear capacity, vRd,max ,
(when cot y = 1.0 or y = 45º), but this is not restricted to 5 MPa as in
Yes (cot y = 2.5) Yes
BS 8110.
Determine y from:
Ma^liZg&mh&]^imakZmbhllahne]^glnk^maZm]^_e^\mbhgblebfbm^]mh
liZg(+.)Zg]mablblma^ikh\^]nk^ik^l^gm^]bg?b`nk^/'
Table 7
Minimum and maximum concrete strut capacity in terms of stress
fck
20
v Rd,max cot y = 2.5
2.54
v Rd,max cot y = 1.0
3.68
Flanged beams
25 3.10 4.50
28 3.43 4.97 ?eZg`^][^Zfl\Zg[^mk^Zm^]bgfn\ama^lZf^pZrZlbg;L1**)'
30 3.64 5.28 Ma^fZbg]b__^k^g\^l\hfiZk^]pbma;L1**)Zk^maZmma^Zll^llf^gm
32 3.84 5.58 h_ma^_eZg`^pb]mablfhk^lhiablmb\Zm^]!l^^?b`nk^l2Zg]*)"Zg]
35 4.15 6.02
40 4.63 6.72 maZm>nkh\h]^+\hgmZbglZ\a^\dmh\hg_bkfmaZmma^la^Zklmk^llZm
45 5.08 7.38
50 5.51 8.00 <hgmbgn^liZ`^,*
4
28
4. Beams
Figure 6 Figure 8
Procedure for assessing deflection Determination of steel stress
START 320
180
Determine Factor 3 (F3) 1.0 2.0 3.0 4.0
F3 = 310/ss
Where ss = Stress in reinforcement at serviceability Ratio Gk /Qk
limit state (see Figure 8)
ss may assumed to be 310 MPa (i.e. F3 = 1.0)
c2 = 0.8, gG = 1.35 c2 = 0.6, gG = 1.25
Note: As,prov ≤ 1.5 As,req’d (UK National Annex) Increase
As,prov c2 = 0.6, gG = 1.35 c2 = 0.3, gG = 1.25
c2 = 0.3, gG = 1.35 c2 = 0.2, gG = 1.25
Is basic l/d x K x F1 x F2 x F3 ≥ Actual l/d ? c2 = 0.2, gG = 1.35
No
Yes
To determine stress in the reinforcement (ss), calculate the ratio
Check complete Gk/Qk, read up the graph to the appropriate curve and read across
to determine ssu .
† The Eurocode is ambiguous regarding linear interpolation. It is understood that
As,req
it was the intention of the drafting committee that linear interpolation be used
and this is in line with current UK practice.
ss can be calculated from the expression: ss = ssu
As,prov d
1
( )( )
Figure 7
Basic span-to-effective-depth ratios
36
Notes
34 1 Mabl`kZiaZllnf^llbfierlniihkm^]liZg\hg]bmbhg
!D 6*')"'
fck = 50 D 6*'._hkbgm^kbhkliZg\hg]bmbhg
32
fck = 45 D 6*',_hk^g]liZg\hg]bmbhg
D 6)'-_hk\Zgmbe^o^kl'
30 fck = 40
fck = 35 2 <hfik^llbhgk^bg_hk\^f^gm% rÃ% aZl[^^gmZd^gZl)'
28 fck = 32 3 <nko^l[Zl^]hgma^_heehpbg`^qik^llbhgl3
Span to depth ratio (l/d)
fck = 30
T ! "V
*'.
26 fck = 28 e *'. _\d r ) _\d
r)
6D ** $ $ ,'+ ¾*
] r r
fck = 25
24
fck = 20 pa^k^r ©r )
22
Zg]
20
18
e
] T
6D ** $
*'. _\d r )
! r ¾ r Ã"
$
_\d
*+
rÃ
r) V
pa^k^r 7r ) '
16
14
12
0.40% 0.60% 0.80% 1.00% 1.20% 1.40% 1.60% 1.80% 2.00%
Percentage of tension reinforcement (A s,req’d /bd)
295
How to design concrete structures using Eurocode 2
Figure 11 Figure 9
Procedure for determining flexural capacity of flanged beams Definition of lo, for calculation of effective flange width
START
bw
M b1 b1 b2 b2
Determine K from K =
bd 2 fck
where b = bw at support b
b = beff in span
Figure 12
Placing of tension reinforcement in flanged cross section
Determine K’ from Table 4 or
K’ = 0.60d – 0.18 d2 – 0.21 where d ≤ 1.0
beff
As
Calculate lever arm z from
z=
d
2 [1 + 1 – 3.53 K ≤ 0.95d ] hf
Neutral axis in
flange. Design
Yes as rectangular
Is x ≤ 1.25hf ? section (Figure 2)
and then check
longitudinal shear
(Figure 14)
No
Figure 13
Neutral axis in web
Calculate moment capacity of flange from:
Notations for the connection between flange and web
MR,f = 0.57 fck (beff – bw) hf (d – 0.5hf)
M – MR,f Fd A
and Kf = yf
fck bw d 2
Compressive struts
Fd beff
Dx
Asf
Sf
No
Is Kf ≤ K ’? Redesign section A hf
6
30
4. Beams
?b`nk^*-lahplZ_ehp\aZkm_hkZll^llbg`ma^ehg`bmn]bgZela^Zk
\ZiZ\bmr4 bgfZgr\Zl^lma^mkZglo^kl^k^bg_hk\^f^gmbgma^leZ[pbee[^ Determine y f from:
No No
ln__b\b^gmmhk^lblmma^la^Zk_hk\^' Mabl\a^\dblbg\en]^]mh^glnk^maZm
pa^k^iZkmb\neZkermabg_eZg`^lZk^nl^]ma^k^blZ]^jnZm^k^bg_hk\^f^gm'
Is v RD > vEd ?
yf = 0.5 sin-1 T vEd
0.2 fck (1 – fck /250) V Is v RD > vEd ?
317
4. Beams
Selected symbols
Symbol Definition Value Symbol Definition Value
:\ <khlll^\mbhgZeZk^Zh_\hg\k^m^ eh =blmZg\^[^mp^^gihbgmlh_s^khfhf^gm
:l :k^Zh_m^glbhglm^^e e(] LiZg&mh&]^imakZmbh
:l+ :k^Zh_\hfik^llbhglm^^e F =^lb`gfhf^gmZmma^NEL
:l% ikho :k^Zh_m^glbhglm^^eikhob]^] q =^imamhg^nmkZeZqbl !]&s"()'-
:l% k^jÃ] :k^Zh_m^glbhglm^^ek^jnbk^] qfZq Ebfbmbg`oZen^_hk]^imamhg^nmkZeZqbl !d ¾)'-"] pa^k^d ©*')
[^__ >__^\mbo^_eZg`^pb]ma s E^o^kZkf
[m F^Zgpb]mah_ma^m^glbhgshg^ a \\ <h^__b\b^gmmZdbg`Z\\hngmh_ehg`m^kf )'1._hk_e^qnk^Zg]
^__^\mlhg\hfik^llbo^lmk^g`maZg]h_ ZqbZeehZ]l
[fbg Pb]mah_[^Zfhkkb[
ng_ZohnkZ[e^^__^\mlk^lnembg`_khfma^ *')_hkhma^kia^ghf^gZ
[p Pb]mah_l^\mbhg% hkpb]mah_p^[hg_eZg`^][^Zfl pZrehZ]blZiieb^] !?khfNDGZmbhgZe:gg^q"
] >__^\mbo^]^ima d KZmbhh_ma^k^]blmkb[nm^]fhf^gmmhma^
]+ >__^\mbo^]^imamh\hfik^llbhgk^bg_hk\^f^gm ^eZlmb\[^g]bg`fhf^gm
_\] =^lb`goZen^h_\hg\k^m^\hfik^llbo^lmk^g`ma a\\ _\d (g\ _hk_\d ©<.)(/) gf IZkmbZe_Z\mhk_hkfZm^kbZeikhi^kmb^l *'*._hkk^bg_hk\^f^gm!gl"
*'._hk\hg\k^m^!g\"
_\d <aZkZ\m^kblmb\\rebg]^klmk^g`mah_\hg\k^m^
r) K^_^k^g\^k^bg_hk\^f^gmkZmbh R_\d (*)))
_\mf F^ZgoZen^h_ZqbZem^glbe^lmk^g`ma )',)_\d!+(," _hk_\d ©<.)(/)
!_khfMZ[e^,'*% >nkh\h]^+" r K^jnbk^]m^glbhgk^bg_hk\^f^gmZmfb]&liZg :l([] !_hkk^\mZg`neZk[^Zfl"
mhk^lblmma^fhf^gm]n^mhma^]^lb`g
a_ ?eZg`^mab\dg^ll ehZ]l!hkZmlniihkm_hk\Zgmbe^o^kl"
D ?Z\mhkmhmZd^Z\\hngmh_ma^]b__^k^gm L^^mZ[e^G:'-bg rà K^jnbk^]\hfik^llbhgk^bg_hk\^f^gmZm :l+([]
lmkn\mnkZelrlm^fl NDGZmbhgZe:gg^q fb]&liZgmhk^lblmma^fhf^gm]n^mhma^
e^__ >__^\mbo^liZgh_f^f[^k L^^L^\mbhg.','+'+!*" ]^lb`gehZ]l!hkZmlniihkm_hk\Zgmbe^o^kl"
References
1 ;KBMBLALM:G=:K=LBGLMBMNMBHG' ;L>G*22+¾*¾*% >nkh\h]^+3 =^lb`gh_\hg\k^m^lmkn\mnk^l¾IZkm*¾*@^g^kZekne^lZg]kne^l_hk
[nbe]bg`l' ;LB% +))-'
2 ;KBMBLALM:G=:K=LBGLMBMNMBHG' ;L1**)¾*3 Ma^lmkn\mnkZenl^h_\hg\k^m^¾IZkm*% <h]^h_ikZ\mb\^_hk]^lb`gZg]\hglmkn\mbhg' ;LB% *220'
3 G:K:R:G:G% KL;KHHD>K% H' Ahpmh]^lb`g\hg\k^m^lmkn\mnk^lnlbg`>nkh\h]^+3 Bgmkh]n\mbhgmh>nkh\h]^l' Ma^<hg\k^m^<^gmk^% +)).'
4 ;KHHD>K% H' Ahpmh]^lb`g\hg\k^m^lmkn\mnk^lnlbg`>nkh\h]^+3 @^mmbg`lmZkm^]' Ma^<hg\k^m^<^gmk^% +)).'
5 ;KBMBLALM:G=:K=LBGLMBMNMBHG' ;L>G*22+¾*¾+% >nkh\h]^+3 =^lb`gh_\hg\k^m^lmkn\mnk^l' @^g^kZekne^l¾lmkn\mnkZe_bk^]^lb`g' ;LB% +))-
6 =>I:KMF>GMH?<HFFNGBMB>L:G=EH<:E@HO>KGF>GM' AZg][hhdmh>G&*22+&*&+ ' =<E@%]n^+))/'
7 P>;LM>K% K;KHHD>K% H' Ahpmh]^lb`g\hg\k^m^lmkn\mnk^lnlbg`>nkh\h]^+3 =^_e^\mbhg\Ze\neZmbhgl' Ma^<hg\k^m^<^gmk^% +))/'
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/19 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-29-3 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
32 published February 2006, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ and British Cement Association views expressed are not necessarily those of the DTI.
How to design concrete structures using Eurocode 2
3. Slabs
R M Moss BSc, PhD, DIC, CEng, MICE, MIStructE O Brooker BEng, CEng, MICE, MIStructE
Designing to Eurocode 2
This chapter covers the analysis and design of slabs to Eurocode 21 which is
essentially the same as with BS 81102. However, the layout and content of
Eurocode 2 may appear unusual to designers familiar with BS 8110. Eurocode 2
does not contain the derived formulae or specific guidance on determining
moments and shear forces. This has arisen because it has been European
practice to give principles in the codes and for the detailed application to
be presented in other sources such as textbooks.
It should be noted that values from the UK National Annex (NA) have been
used throughout, including values that are embedded in derived formulae.
(Derivations can be found at www.eurocode2.info.) A list of symbols related to
slab design is given at the end of this chapter.
Design procedure
A procedure for carrying out the detailed design of slabs is shown in Table 1.
This assumes that the slab thickness has previously been determined during
conceptual design. More detailed advice on determining design life, actions,
material properties, methods of analysis, minimum concrete cover for
durability and control of crack widths can be found in Chapter 2, originally
published as Getting started 5.
Fire resistance
:cementZg]concretebg]nlmkrin[eb\Zmbhg This chapter is taken
from The Concrete Eurocode 2, Part 1–2: Structural fire design6, gives a choice of advanced,
Centre’s publication, simplified or tabular methods for determining the fire resistance. Using tables
Ahpmh=^lb`g<hg\k^m^ How to design
Lmkn\mnk^lnlbg`>nkh\h]^+ is the fastest method for determining the minimum dimensions and cover for
concrete structures
A J Bond F:FL\=B<Ia=FB<><>g`
O Brooker ;>g`<>g`FB<>FBLmkn\m>
A J Harris ;L\FL\=B<FB<><>g`?@L
T Harrison ;L\Ia=<>g`FB<>?B<M
R M Moss;L\Ia==B<<>g`FB<>FBLmkn\m>
R S Narayanan?K>g`
R Webster<>g`?BLmkn\m>
using Eurocode 2 slabs. There are, however, some restrictions which should be adhered to.
(Ref. CCIP–006) Further guidance on the advanced and simplified methods can be obtained
from specialist literature.
Table 1
Slab design procedure
Table 2
Minimum dimensions and axis distances for reinforced concrete slabs (excluding flat slabs)
Notes Key
1 This table is taken from BS EN 1992–1–2 Tables 5.8 to 5.11. For flat slabs refer to a The slab thickness hs is the sum of the slab thickness and the thickness of any
Chapter 7. non-combustible flooring.
2 The table is valid only if the detailing requirements (see note 3) are observed and in b For continuous solid slabs a minimum negative reinforcement As ≥ 0.005 A c
normal temperature design redistribution of bending moments does not exceed 15%. should be provided over intermediate supports if
3 For fire resistance of R90 and above, for a distance of 0.3l eff from the centre line of each 1) cold worked reinforcement is used; or
intermediate support, the area of top reinforcement should not be less than the following: 2) there is no fixity over the end supports in a two span slab; or
A s,req (x) = A s,req ( 0 ) ( 1 – 2.5 ( x/ l eff ) ) 3) where transverse redistribution of load effects cannot be achieved.
where: c In two way slabs the axis refers to the lower layer of reinforcement.
x is the distance of the section being considered from the centre
d The term two way slabs relates to slabs supported at all four edges. If this is
line of the support.
not the case, they should be treated as one-way spanning slabs.
A s,req ( 0 ) is the area of reinforcement required for normal temperature design.
e For two-way ribbed slabs the following notes apply:
A s,req (x) is the minimum area of reinforcement required at the section
The axis distance measured to the lateral surface of the rib should be at
being considered but not less than that required for normal
least (a + 10).
temperature design.
The values apply where there is predominantly uniformly distributed loading.
l eff is the greater of the effective lengths of the two adjacent spans.
There should be at least one restrained edge.
4 There are three standard fire exposure conditions that need to be satisfied:
The top reinforcement should be placed in the upper half of the flange.
R Mechanical resistance for load bearing
E Integrity of separation f l x and l y are the spans of a two-way slab (two directions at right angles) where
I Insulation l y is the longer span.
5 The ribs in a one-way spanning ribbed slab can be treated as beams and reference can g Normally the requirements of BS EN 1992–1–1 will determine the cover.
be made to Chapter 4, Beams. The topping can be treated as a two-way slab where
1.5 < ly / lx ≤ 2.
2
18
3. Slabs
Figure 1
Procedure for determining flexural reinforcement dimension, so the designer should ensure that
a ≥ cnom + f link + f bar /2.
START The requirements for various types of slab are given in Table 2.
Table 4
Determine K’ from Table 4 or
Values for K ’
K’ = 0.60d – 0.18 d 2 – 0.21 where d ≤ 1.0
% redistribution d (redistribution ratio) K’
0 1.00 0.208a
Compression
reinforcement
10 0.90 0.182a
No
Is K ≤ K ’ ? required – not 15 0.85 0.168
recommended for
typical slabs 20 0.80 0.153
Yes
25 0.75 0.137
30 0.70 0.120
No compression reinforcement required Key
a It is often recomended in the UK that K´ should be limited to 0.168 to ensure ductile failure.
K z/d K z/d
Calculate tension reinforcement required from ≤0.05 0.950a 0.13 0.868
M
As = 0.06 0.944 0.14 0.856
fyd z
0.07 0.934 0.15 0.843
0.08 0.924 0.16 0.830
Check minimum reinforcement requirements (see Table 6) 0.09 0.913 0.17 0.816
0.26 fctm bt d 0.10 0.902 0.18 0.802
As,min = where fck ≥ 25
fyk 0.11 0.891 0.19 0.787
0.12 0.880 0.20 0.771
Key
Check maximum reinforcement requirements
a Limiting z to 0.95d is not a requirement of Eurocode 2, but is considered to be good practice.
As,max = 0.04 Ac for tension or compression
reinforcement outside lap locations
Table 6
Minimum percentage of reinforcement required
Table 3
Bending moment and shear coefficients for slabs fck fctm Minimum % (0.26 fctm /fyka )
25 2.6 0.13%
End support /slab connection First Interior Interior
interior spans supports 28 2.8 0.14%
Pinned Continuous
support 30 2.9 0.15%
End End End End
support span support span 32 3.0 0.16%
Moment 0 0.086Fl – 0.04Fl 0.075Fl –0.086Fl 0.063Fl –0.063Fl 35 3.2 0.17%
Shear 0.40F 0.46F 0.6F 0.5F 40 3.5 0.18%
Notes 45 3.8 0.20%
1 Applicable to one-way spanning slabs where the area of each bay exceeds 30 m2,
Qk ≤ 1.25 Gk and qk ≤ 5 kN/m2 50 4.1 0.21%
2 F is the total design ultimate load, l is the span Key
3 Minimum span > 0.85 longest span, minimum 3 spans
4 Based on 20% redistribution at supports and no decrease in span moments a Where fyk = 500 MPa.
3
19
How to design concrete structures using Eurocode 2
Figure 2
Simplified rectangular stress block for concrete up to class C50/60 from Eurocode 2
Figure 3 Figure 4
Procedure for assessing deflection Determination of steel stress
START
4
20
3. Slabs
It is not usual for a slab to contain shear reinforcement, therefore it is rI = Effective depth, d (mm)
As /(bd)
only necessary to ensure that the concrete shear stress capacity ≤200 225 250 275 300 350 400 450 500 600 750
without shear reinforcement (vRd,c – see Table 7) is more than applied
0.25% 0.54 0.52 0.50 0.48 0.47 0.45 0.43 0.41 0.40 0.38 0.36
shear stress (vEd = VEd /( bd )). Where shear reinforcement is required,
e.g. for ribs in a ribbed slab, refer to Chapter 4, originally published as 0.50% 0.59 0.57 0.56 0.55 0.54 0.52 0.51 0.49 0.48 0.47 0.45
Beams 8. 0.75% 0.68 0.66 0.64 0.63 0.62 0.59 0.58 0.56 0.55 0.53 0.51
1.00% 0.75 0.72 0.71 0.69 0.68 0.65 0.64 0.62 0.61 0.59 0.57
Two-way slabs 1.25% 0.80 0.78 0.76 0.74 0.73 0.71 0.69 0.67 0.66 0.63 0.61
1.50% 0.85 0.83 0.81 0.79 0.78 0.75 0.73 0.71 0.70 0.67 0.65
Unlike BS 8110 there is no specific guidance given in Eurocode 2 on
how to determine the bending moments for a two-way slab. The 1.75% 0.90 0.87 0.85 0.83 0.82 0.79 0.77 0.75 0.73 0.71 0.68
assessment of the bending moment can be carried out using any ≥2.00% 0.94 0.91 0.89 0.87 0.85 0.82 0.80 0.78 0.77 0.74 0.71
suitable method from Section 5 of the Code. However, co-efficients
k 2.000 1.943 1.894 1.853 1.816 1.756 1.707 1.667 1.632 1.577 1.516
may be obtained from Table 8 (taken from the Manual for the design of
building structures to Eurocode 29) to determine bending moments per Table derived from: v Rd,c = 0.12 k (100r I fck)1/3 ≥ 0.035 k1.5 fck 0.5
unit width (Msx and Msy) where: where k = 1 + R(200/d) ≤ 2 and r I = As /(bd) ≤ 0.02
Note
Msx = bsx w lx2 1 This table has been prepared for fck = 30.
2 Where r I exceeds 0.40% the following factors may be used:
Msy = b sy w lx2
fck 25 28 32 35 40 45 50
Where bsx and bsy are coefficients, lx is the shorter span and w (load
Factor 0.94 0.98 1.02 1.05 1.10 1.14 1.19
per unit area) is the STR ultimate limit state combination. For more
information on combinations refer toChapter 1, originally published as
Introduction to Eurocodes3.
Figure 5
Basic span-to-effective-depth ratios
Notes
1 For two-way spanning slabs, the check should be
carried out on the basis of the shorter span.
2 This graph assumes simply supported span
condition (K = 1.0).
K = 1.5 for interior span condition
K = 1.3 for end span condition
K = 0.4 for cantilevers
3 Compression reinforcement, r’, has been taken as 0.
4 Curves based on the following expressions:
[ ( )]
1.5
l 1.5 fck r 0 fck
r0
= K 11 + + 3.2 –1
d r r
where r ≤ r 0
and
l
d
= K 11 +[1.5 fck r 0
( r – r ’)
+
fck
12
r’
r0 ]
where r > r 0 .
5
21
How to design concrete structures using Eurocode 2
Current practices for determining forces in ribbed and waffle slabs may also
START
be used for designs to Eurocode 2. Where a waffle slab is treated as a
two-way slab refer to previous section, but note that their torsional stiffness
is significantly less than for a two-way slab and the bending moment co-
efficients may not be applicable. Where it is treated as a flat slab reference No Outside scope
Concrete class of this
may be made to Chapter 7, originally published as Flat slabs4 ≤ C50/60? publication
The position of the neutral axis in the rib should be determined, and Yes
then the area of reinforcement can be calculated depending on Determine l0 (see Figure 7) and beff from:
whether it lies in the flange or web (see flow chart in Figure 6). The beff = (bw + beff1 + beff2) where
beff1 = (0.2b1 + 0.1 l0) ≤ 0.2 l0 ≤ b1
main differences compared with BS 8110 are that the assessment of
beff2 = (0.2b2 + 0.1 l0) ≤ 0.2 l0 ≤ b2
the flange width is more sophisticated (see Figures 7 and 8). Note: The flange width at the support will be
different from that at mid-span.
For symbols refer to Figures 7 and 8
Where a slab is formed with permanent blocks or a with a topping
thickness less than 50 mm and one-tenth of the clear distance
between ribs it is recommended that a longitudinal shear check is
M
carried out to determine whether additional transverse reinforcement is Determine K from: K =
bd 2 fck
required (see BS EN 1992–1–1, Cl 6.2.4).
Negative moment 0.047 0.066 0.078 0.087 0.093 0.045 Calculate area of reinforcement required from
at continuous edge MR,f M – MR,f
As = +
fywd (d – 0.5 hf ) fywd z
Positive moment 0.036 0.049 0.059 0.065 0.070 0.034
at midspan
6
22
3. Slabs
Figure 7 Figure 8
Definition of l0 , for calculation of effective flange width Effective flange width parameters
quantity of reinforcement Ac
As
Cross sectional area of concrete
Area of tension steel
bh
Minimum spacing of reinforcement leff Effective span of member See Section 5.3.2.2 (1)
The minimum clear distance between bars should be the greater of: l0 Distance between points of zero moment
moment where the following applies: gm Partial factor for material properties 1.15 for reinforcement (gs )
1.5 for concrete (gc )
� For the principal reinforcement: 2h but not more than 250 mm
r0 Reference reinforcement ratio Rfck /1000
� For the secondary reinforcement: 3h but not more than 400 mm
r Required tension reinforcement at mid-span As/bd
Where h is the depth of the slab.
to resist the moment due to the design
loads (or at support for cantilevers)
For slabs 200 mm thick or greater the bar size and spacing should be r’ Required compression reinforcement at As2/bd
limited to control the crack width and reference should be made to mid-span to resist the moment due to the
design loads (or at support for cantilevers)
section 7.3.3 of the Code or Chapter 2, originally published as Getting
started 5.
7
23
3. Slabs
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–1: Eurocode 2: Design of concrete structures – Part 1–1 General rules and rules for buildings. BSI, 2004.
2 BRITISH STANDARDS INSTITUTION. BS 8110–1: The structural use of concrete – Part 1, Code of practice for design and construction. BSI, 1997.
3 NARAYANAN, R S & BROOKER, O. How to design concrete structures using Eurocode 2: Introduction to Eurocodes. The Concrete Centre, 2005.
4 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Flat slabs. The Concrete Centre, 2006.
5 BROOKER, O. How to design concrete structures using Eurocode 2: Getting started. The Concrete Centre, 2005.
6 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–2, Eurocode 2: Design of concrete structures. General rules – structural fire design, BSI 2004.
7 WEBSTER, R & BROOKER, O. How to design concrete structures using Eurocode 2: Deflection calculations. The Concrete Centre, 2006.
8 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Beams. The Concrete Centre, 2006.
9 THE INSTITUTION OF STRUCTURAL ENGINEERS/THE INSTITUTION OF CIVIL ENGINEERS. Manual for the design of concrete building structures to
Eurocode 2. IStructE/ICE, 2006.
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/18 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-28-5 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
24 published January 2006, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ and British Cement Association views expressed are not necessarily those of the DTI.
How to design concrete structures using Eurocode 2
5. Columns
R Moss BSc, PhD, DIC, CEng, MICE, MIStructE O Brooker BEng, CEng, MICE, MIStructE
Designing to Eurocode 2
This chapter is intended to assist engineers with the design of columns and
walls to Eurocode 21. It sets out a design procedure to follow and gives useful
commentary on the provisions within the Eurocode. The layout and content
of Eurocode 2 may appear unusual to designers familiar with BS 81102.
Eurocode 2 does not contain the derived formulae; this is because it has been
European practice to give principles and general application rules in the codes
and for detailed application rules to be presented in other sources such as
textbooks or guidance documents.
It should also be noted that values from the UK National Annex (NA) have
been used throughout this publication, including values that are embedded in
derived formulae. (Derivations can be found at www.eurocode2.info.) A full list
of symbols related to column design is given at the end of this chapter.
Design procedure
A procedure for carrying out the detailed design of braced columns (i.e.
columns that do not contribute to resistance of horizontal actions) is shown
in Table 1. This assumes that the column dimensions have previously been
determined during conceptual design or by using quick design methods, for
example those presented in Economic concrete frame elements 4. Column sizes
should not be significantly different from those obtained using BS 8110. Steps
1 to 4 of Table 1 are covered by earlier chapters and the next step is therefore
to consider fire resistance.
fastest method for determining the minimum dimensions and cover for columns.
O Brooker ;>g`<>g`FB<>FBLmkn\m> R M Moss;L\Ia==B<<>g`FB<>FBLmkn\m> R Webster<>g`?BLmkn\m>
A J Harris ;L\FL\=B<FB<><>g`?@L
(Ref. CCIP–006)
There are, however, some restrictions and if these apply further guidance can
be obtained from specialist literature.6 The simplified method may give more
economic columns, especially for small columns and/or high fire resistance periods.
Rather than giving a minimum cover, the tabular method is based on nominal
axis distance, a (see Figure 1). This is the distance from the centre of the main
Continues page 35
How to design concrete structures using Eurocode 2
Table 1
Column design procedure
2 Assess actions on the column 2: Getting started BS EN 1991 (10 parts) and UK National Annexes
3 Determine which combinations of actions apply 1: Introduction to Eurocodes UK NA to BS EN 1990 Tables NA.A1.1 and NA.A1.2 (B)
4 Assess durability requirements and determine concrete strength 2: Getting started BS 8500: 2002
5 Check cover requirements for appropriate fire resistance period 2: Getting started and Table 2 Approved Document B. BS EN 1992–1–2
6 Calculate min. cover for durability, fire and bond requirements 2: Getting started BS EN 1992–1–1 Cl. 4.4.1
7 Analyse structure to obtain critical moments and axial 2: Getting started and ‘Structural BS EN 1992–1–1 section 5
forces analysis’ section
9 Determine area of reinforcement required See Figures 2 and 3 BS EN 1992–1–1 section 6.1
10 Check spacing of bars ‘Rules for spacing’ section BS EN 1992–1–1 sections 8 and 9
Note
NA = National Annex.
Table 2 Figure 1
Minimum column dimensions and axis distances for fire resistance Section through structural member, showing nominal axis distance a
b Method B may be used which indicates 600/70 for R 240 and µfi = 0.7. Key
See BS EN 1992–1–2 Table 5.2b
a Normally the requirements of BS EN 1992–1–1 will determine the cover.
34
5. Columns
reinforcing bar to the surface of the member. It is a nominal (not present methods A and B. Both are equally applicable, although
minimum) dimension, and the designer should ensure that: method A has smaller limits on eccentricity than method B. Method A
a ≥ cnom + f link + f bar/2. is slightly simpler and is presented in Table 2; limits of applicability
are given in the notes. Similar data for load-bearing walls is given in
For columns there are two tables given in Eurocode 2 Part 1–2 that Table 3.
Figure 2 For columns supporting the uppermost storey, the eccentricity will
Flow chart for braced column design often exceed the limits for both methods A and B. In this situation
Annex C of Eurocode 2, Part 1–2 may be used. Alternatively,
START
consideration can be given to treating the column as a beam for
determining the design fire resistance.
Design moments
Determine slenderness limit, λlim, from: The design bending moment is illustrated in Figure 4 and defined as:
l 15.4C
lim =
√n MEd = Max {M02, M0e + M2, M01 + 0.5 M2}
(See ‘Slenderness’ section on page 5 for explanation.)
where
M01 = Min {|Mtop|, |Mbottom|} + ei NEd
Yes M02 = Max {|Mtop|, |Mbottom|} + ei NEd
Column is slender
Is l ≥ l lim? (refer to Figure 3).
ei = Max {lo/400, h/30, 20} (units to be in millimetres).
Mtop, Mbottom = Moments at the top and bottom of the column
No M0e = 0.6 M02 + 0.4 M01 ≥ 0.4 M02
Column is not slender. MEd = M02
M2 = NEd e2 where NEd is the design axial load and e2
is deflection due to second order effects
M01 and M02 should be positive if they give tension on the same side.
Use column chart (see Figure 9) to find As required for NEd
and MEd. Alternatively, solve by iteration or by using RC
Spreadsheet TCC53 from Spreadsheets for concrete design to A non-slender column can be designed ignoring second order effects
BS 8110 and Eurocode 2 7
and therefore the ultimate design moment, MEd = M02.
35
How to design concrete structures using Eurocode 2
Yes Figure 4
Design bending moments
Check detailing requirements
M02
M ei NEd M02
Figure 5
Effective lengths for isolated members
M0e M0e + M2
M2 = NEd e2
+ =
y
y
l
y
M M01 0.5 M2 M01 + 0.5 M2
First order Additional second Total moment
moments for order moments for diagram for
a) l0 = l b) l0 = 2l c) l0 = 0.7l d) l0 = l /2 e) l0 = l f) l/2 < l0 < l g) l0 > 2l ‘stocky’ columns ‘slender’ columns ‘slender’ columns
Figure 4
Figure 5 Design moments
Effective lengths for isolated members
36
File How t o Columns Figure 4
File How to Columns Fig 5 25.01.06
25.01.06 Job No.
Job No.
5. Columns
Table 4 Slenderness
Effective length factor, F, for braced columns
Eurocode 2 states that second order effects may be ignored if they
k2 k1 are less than 10% of the first order effects. As an alternative, if the
0.10 0.20 0.30 0.40 0.50 0.70 1.00 2.00 5.00 9.00 Pinned slenderness (l) is less than the slenderness limit (l lim), then second
order effects may be ignored.
0.10 0.59 0.62 0.64 0.66 0.67 0.69 0.71 0.73 0.75 0.76 0.77
0.20 0.62 0.65 0.68 0.69 0.71 0.73 0.74 0.77 0.79 0.80 0.81 Slenderness, l = lo/i where i = radius of gyration and slenderness limit.
0.30 0.64 0.68 0.70 0.72 0.73 0.75 0.77 0.80 0.82 0.83 0.84
20ABC 15.4C
0.40 0.66 0.69 0.72 0.74 0.75 0.77 0.79 0.82 0.84 0.85 0.86 l lim = ≤
n n
0.50 0.67 0.71 0.73 0.75 0.76 0.78 0.80 0.83 0.86 0.86 0.87
where
0.70 0.69 0.73 0.75 0.77 0.78 0.80 0.82 0.85 0.88 0.89 0.90
A = 1/(1+0.2 hef) (if hef is not known, A = 0.7 may be used)
1.00 0.71 0.74 0.77 0.79 0.80 0.82 0.84 0.88 0.90 0.91 0.92 B= (if ω, reinforcement ratio, is not known,
2.00 0.73 0.77 0.80 0.82 0.83 0.85 0.88 0.91 0.93 0.94 0.95 B = 1.1 may be used)
5.00 0.75 0.79 0.82 0.84 0.86 0.88 0.90 0.93 0.96 0.97 0.98 C = 1.7 – rm (if rm is not known, C = 0.7 may be used – see below)
9.00 0.76 0.80 0.83 0.85 0.86 0.89 0.91 0.94 0.97 0.98 0.99 n = NEd / (Ac fcd)
Pinned 0.77 0.81 0.84 0.86 0.87 0.90 0.92 0.95 0.98 0.99 1.00 rm = M01/M02
M01, M02 are the first order end moments, |M02| ≥ |M01|
Figure 6
Calculating factor C If the end moments M01 and M02 give tension on the same side,
rm should be taken positive.
105 kNm 105 kNm 105 kNm
Of the three factors A, B and C, C will have the largest impact on
l lim and is the simplest to calculate. An initial assessment of l lim can
therefore be made using the default values for A and B, but including
a calculation for C (see Figure 6). Care should be taken in determining
105 kNm 0 105 kNm
C because the sign of the moments makes a significant difference. For
rm = 1.0 rm = 0 rm = -1.0
unbraced members C should always be taken as 0.7.
a) C = 1.7 - 1 = 0.7 b) C = 1.7 - 0 = 1.7 c) C = 1.7 + 1.0 = 2.7
Column design resistance
Note For practical purposes the rectangular stress block used for the design
Figure 7 columns, C = 0.7
For unbraced
Stress block diagram for columns of beams (see Chapter 4, originally published as Beams 9) may also be
Figure 6
Calculating Factor C used for the design of columns (see Figure 7). However, the maximum
f cd d2 compressive strain for concrete classes up to and including C50/60,
ecu 2 s sc
File How t o Columns Figure 6 esc As2 when the whole section is in pure compression, is 0.00175 (see Figure
25.01.06
Job No. dc
x 8a). When the neutral axis falls outside the section (Figure 8b), the
h maximum allowable strain is assumed to lie between 0.00175 and
n. axis
d2 0.0035, and may be obtained by drawing a line from the point of zero
ey As
s st strain through the ‘hinge point’ of 0.00175 strain at mid-depth of the
section. When the neutral axis lies within the section depth then the
a) Strain diagram b) Stress diagram
maximum compressive strain is 0.0035 (see Figure 8c).
Figure 8
Figure 8 diagram for columns
Stress block
Strain diagrams for columns
Figure 7
Strain diagrams for columns
37
The general relationship is shown in Figure 8d). For concrete classes Creep
above C50/60 the principles are the same but the maximum strain Depending on the assumptions used in the design, it may be necessary
values vary. to determine the effective creep ratio hef (ref. Cl. 3.1.4 & 5.8.4). A
nomogram is provided in the Eurocode (Figure 3.1) for which the
Two expressions can be derived for the area of steel required, (based on cement strength class is required; however, at the design stage it often
a rectangular stress block, see Figure 7) one for the axial loads and the not certain which class applies. Generally, Class R should be assumed.
other for the moments: Where the ground granulated blastfurnace slag (ggbs) exceeds 35%
AsN /2 = (NEd – fcd b dc) / (σsc – σst) of the cement combination or where pulverized fuel ash (pfa) exceeds
where 20% of the cement combination, Class N may be assumed. Where
AsN = Area of reinforcement required to resist axial load ggbs exceeds 65% or where pfa exceeds 35%, Class S may be assumed.
NEd = Axial load
fcd = Design value of concrete compressive strength
σsc (σst) = Stress in compression (and tension) reinforcement Biaxial bending
b = Breadth of section
dc = Effective depth of concrete in compression = lx ≤ h The effects of biaxial bending may be checked using Expression (5.39),
l = 0.8 for ≤ C50/60 which was first developed by Breslaer.
x = Depth to neutral axis a a
Figure 9a
Column design chart for rectangular columns d2 /h = 0.05
1.3
Kr = 0.2
1.2 d2/h = 0.05
0.3 Asfyk/bhfck
1.1
1.0 0.4
1.0 0.9
0.8
0.9
0.7 0.5
0.6
0.8
0.5 0.6
0.7 0.4
N/bhfck
0.3
0.7
0.6 0.2
0.1
0.5
0 0.8
0.4
0.9
0.3
1.0
0.2
0.1
0
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
2
M/bh fck
38
5. Columns
Figure 9b
Column design chart for rectangular columns d2 /h = 0.10
1.3
0.2
1.2 d2/h = 0.10
0.3 Asfyk/bhfck
1.1
1.0 0.4
1.0
0.9
0.8
0.9
0.7 0.5
0.8 0.6
0.5
0.6
0.7 0.4
N/bhfck
0.3
0.7
0.6 0.2
0.1
0.5
0 0.8
0.4
0.9
0.3
Kr =1
0.2
0.1
0
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
2
M/bh fck
Figure 9c
Column design chart for rectangular columns d2 /h = 0.15
1.3
0.2
1.2 d2/h = 0.15
0.3
1.1
Asfyk/bhfck
1.0
1.0 0.9 0.4
0.8
0.9
0.7 0.5
0.8 0.6
0.5 0.6
0.7 0.4
N/bhfck
0.3
0.6 0.2 0.7
0.1
0.5 0 0.8
0.4
0.9
0.3
Kr =1
0.2
0.1
0
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40
2
M/bh fck
39
How to design concrete structures using Eurocode 2
Figure 9d
Column design chart for rectangular columns d2 /h = 0.20
1.3
0.2
1.2 d2/h = 0.20
0.3 Asfyk/bhfck
1.1
1.0
1.0
0.9 0.4
0.9 0.8
0.7 0.5
0.8 0.6
0.5
0.6
N/bhfck
0.7 0.4
0.3
0.6 0.2 0.7
0.1
0.5
0
0.8
0.4
0.3 0.9
0.2
Kr = 1
0.1
0
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35
2
M/bh f ck
Figure 9e
Column design chart for rectangular columns d2 /h = 0.25
1.3
0.2
1.2 d2/h = 0.25
1.1 0.3
Asfyk/bhfck
1.0 1.0
0.9 0.4
0.9
0.8
0.7
0.8
0.6 0.5
0.5
0.7
N/bhfck
0.4
0.3 0.6
0.6
0.2
0.5 0.1
0 0.7
0.4
0.8
0.3
0.9
0.2
0.1
Kr = 1
0
0 0.05 0.10 0.15 0.20 0.25 0.30
2
M/bh fck
40
5. Columns
Unbraced columns
As Area of total column reinforcement
used in Expression (5.13N). The design moments should be assessed e2 Second order eccentricity (1/r)lo/c
including second order effects. The tabular method for fire resistance ei Eccentricity due to geometric imperfections
design (Part 1–2) does not explicitly cover unbraced columns; however Es Elastic modulus of reinforcing steel 200 GPa
reference can be made to the Handbook to EN 1992–1–2 6. fcd Design value of concrete compressive strength αcc fck/γc
lo Effective length
When the section length of a vertical element is four times greater
Kr Correction factor depending on axial load
than its thickness it is defined as a wall. The design of walls does not
Kh Factor taking into account creep
differ significantly from that for columns except for the following:
M01,M02 First order moments including the effect of
■ The requirements for fire resistance (see Table 3). geometric imperfections |M02| ≥ |M01|
■ Bending will be critical about the weak axis.
M2 Nominal second order moment NEd e2
■ There are different rules for spacing and quantity of reinforcement
M0e Equivalent first order moment 0.6 M02 + 0.4 M01 ≥ 0.4 M02
(see below).
MEd Ultimate design moment
There is no specific guidance given for bending about the strong axis MEqp First order bending moment under
quasi-permanent loading
for stability. However, the principles of CIRIA Report 10810 may be
n Relative axial force NEd/(Acfcd)
followed. Alternatively the strut and tie method may be used (section
6.5 of the Eurocode). nbal Value of n at maximum moment of resistance 0.4
rm
Ultimate axial load
quantity of reinforcement x
z
Depth to neutral axis
Lever arm
(d – z)/0.4
αcc Coefficient taking account of long term effects 0.85 for flexure and axial
Maximum areas of reinforcement on compressive strength and of unfavourable loads. 1.0 for other
In Eurocode 2 the maximum nominal reinforcement area for columns effects resulting from the way load is applied phenomena (From UK NA)
and walls outside laps is 4% compared with 6% in BS 8110. However, β Factor 0.35 + fck/200 – λ/150
this area can be increased provided that the concrete can be placed εyd Design value of strain in reinforcement fyd/Es
and compacted sufficiently. If required self-compacting concrete may γm Partial factor for material properties 1.15 for reinforcement (γs)
be used for particularly congested situations, where the reinforcing bars 1.5 for concrete (γc)
should be spaced to ensure that the concrete can flow around them. l Slenderness lo/i
Further guidance can be found in Self-compacting concrete.11 l lim Slenderness limit
41
5. Columns
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–1, Eurocode 2: Design of concrete structures. General rules and rules for buildings. BSI, 2004.
2 BRITISH STANDARDS INSTITUTION. BS 8110–1, Structural use of concrete – Part 1, Code of practice for design and construction. BSI, 2004.
3 NARAYANAN, R S & BROOKER, O. How to design concrete structures using Eurocode 2: Introduction. The Concrete Centre, 2005.
4 GOODCHILD, C H. Economic concrete frame elements. BCA 1997.
5 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–2. Eurocode 2: Design of concrete structures. General rules – structural fire design. BSI, 2004.
6 DEPARTMENT OF COMMUNITIES AND LOCAL GOVERNMENT. Handbook to EN 1992–1–2. DCLG, due 2006.
7 GOODCHILD, C H WEBSTER, R M. Spreadsheets for concrete design to BS 8110 and Eurocode 2, version 3. The Concrete Centre, 2006.
8 BRITISH STANDARDS INSTITUTION. Background paper to the UK National Annex to BS EN 1992–1–1 and BS EN 1992–1–2. BSI, due 2006.
9 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Beams. The Concrete Centre, 2006.
10 CIRIA. Report 102: Design of shear wall buildings. CIRIA, 1984.
11 THE CONCRETE SOCIETY. Technical Report No 62: Self-compacting concrete. A review. The Society, 2005.
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/20 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-30-7 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
42 published March 2006, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ and British Cement Association views expressed are not necessarily those of the DTI.
Eurocode 2 Column Design Charts
How to design concrete structures using Eurocode 2
6. Foundations
R Webster CEng, FIStructE O Brooker BEng, CEng, MICE, MIStructE
Limit states
The following ultimate limit states (ULS) should be satisfied for geotechnical
design; they each have their own combinations of actions. (For an explanation
of Eurocode terminology please refer to Chapter 1, originally published as
Introduction to Eurocodes5.)
EQU Loss of equilibrium of the structure.
STR Internal failure or excessive deformation of the structure or structural
member.
GEO Failure due to excessive deformation of the ground.
:cementZg]concretebg]nlmkrin[eb\Zmbhg This chapter is taken UPL Loss of equilibrium due to uplift by water pressure.
from The Concrete
Centre’s publication,
HYD Failure caused by hydraulic gradients.
Ahpmh=^lb`g<hg\k^m^ How to design
Lmkn\mnk^lnlbg`>nkh\h]^+
concrete structures In addition, the serviceability limit states (SLS) should be satisfied. It will
using Eurocode 2
A J Bond F:FL\=B<Ia=FB<><>g` T Harrison ;L\Ia=<>g`FB<>?B<M R S Narayanan?K>g`
usually be clear that one of the limit states will govern the design and
O Brooker ;>g`<>g`FB<>FBLmkn\m> R M Moss;L\Ia==B<<>g`FB<>FBLmkn\m> R Webster<>g`?BLmkn\m>
A J Harris ;L\FL\=B<FB<><>g`?@L
(Ref. CCIP–006)
therefore it will not be necessary to carry out checks for all of them, although
it is considered good practice to record that they have all been considered.
Geotechnical Categories
Eurocode 7 recommends three Geotechnical Categories to assist in establishing
the geotechnical design requirements for a structure (see Table 1).
How to design concrete structures using Eurocode 2
It is anticipated that structural engineers will take responsibility for the to be applied to the actions for these combinations of partial factors
geotechnical design of category 1 structures, and that geotechnical are given in Table 2 and the partial factors for the geotechnical
engineers will take responsibility for category 3 structures. The material properties are given in Table 3. Combination 1 will generally
geotechnical design of category 2 structures may be undertaken by govern the structural resistance, and Combination 2 will generally
members of either profession. This decision will very much depend on govern the sizing of the foundations.
individual circumstances.
The partial factors for soil resistance to sliding and bearing should be
Methods of design and combinations taken as 1.0 for both combinations.
There has not been a consensus amongst geotechnical engineers
over the application of limit state principles to geotechnical design. The partial factors to be applied to the actions at the EQU limit state
Therefore, to allow for these differences of opinion, Eurocode 7 are given in Table 4; the geotechnical material partial factors being the
provides for three Design Approaches to be used for the ULS. The same as for Combination 2 in Table 3.
decision on which approach to use for a particular country is given
in its National Annex. In the UK Design Approach 1 will be specified For the SLS, Eurocode 7 does not give any advice on whether the
in the National Annex. For this Design Approach (excluding pile and characteristic, frequent or quasi-permanent combination should be
anchorage design) there are two sets of combinations to use for the used. Where the prescriptive method is used for spread foundations
STR and GEO ultimate limit states. The values for the partial factors (see page 3) then the characteristic values should be adopted. For
Table 1
Geotechnical categories of structures
Table 2
Design values of actions derived for UK design, STR/GEO ultimate limit state – persistent and transient design situations
Exp. (6.10) 1.35 Gka 1.0 Gka 1.5b Qk – 1.5b co,ic Qk,i
Exp. (6.10a) 1.35 Gka 1.0 Gka – 1.5 co,1c Qk 1.5b co,ic Qk,i
Exp. (6.10b) 0.925d x 1.35 Gka 1.0 Gka 1.5b Qk – 1.5b co,ic Qk,i
Exp. (6.10) 1.0 Gka 1.0 Gka 1.3b Qk,1 – 1.3b co,i b Qk,i
Key
a Where the variation in permanent action is not considered significant Gk,j,sup and Gk,j,inf may be taken as Gk
b Where the action is favourable, gQ,i = 0 and the variable actions should be ignored
c The value of c o can be obtained from Table NA.A1.1 of the UK NA to BS EN 1990 (or see Table 3 of Chapter 1)
d The value of j in the UK NA to BS EN 1990 is 0.925
Table 3
Partial factors for geotechnical material properties
Angle of shearing Effective cohesion Undrained shear Unconfined strength Bulk density
resistance strength
(apply to tan h)
Symbol gh gc’ gcu gqu gg
Combination 1 1.0 1.0 1.0 1.0 1.0
Combination 2 1.25 1.25 1.4 1.4 1.0
44
6. Foundations
Table 5
Presumed allowable bearing values under static loading (from BS 8004)
Category Type of soil Presumed allowable bearing value (kN/m2) Remarks
Non- Dense gravel, or dense sand and gravel > 600 Width of foundation not less than 1 m.
cohesive Groundwater level assumed to be below the base
soils Medium dense gravel, or medium < 200 to 600 of the foundation.
dense sand and gravel
Loose gravel, or loose sand and gravel < 200
Compact sand > 300
Medium dense sand 100 to 300
Loose sand < 100
Cohesive Very stiff boulder clay and hard clay 300 to 600 Susceptible to long-term consolidation settlement
soils
Stiff clay 150 to 300
Firm clay 75 to 150
Soft clay and silt <75
Very soft clay and silt Not applicable
Note
These values are for preliminary design purposes only.
45
How to design concrete structures using Eurocode 2
A flow chart showing the design process for shallow foundations is Partial factors for the soil parameters used to determine the resistances
given in Figure 1. can be obtained from Table 3 above (Combination 2).
Where there is a moment applied to the foundation, the EQU limit The pressure distribution under the base should be assessed to ensure
state should also be checked. Assuming the potential overturning of that the maximum pressure does not exceed the bearing resistances
the base is due to the variable action from the wind, the following obtained from the geotechnical design report at both EQU and GEO
combination should be used (the variable imposed action is not ultimate limit states (see Figure 2). If the eccentricity is greater than
considered to contribute to the stability of the structure): L/6 at SLS, then the pressure distribution used to determine the
settlement should be modified because tension cannot occur between
0.9 Gk + 1.5 Qk,w EQU combination the base and the soil. In this case the designer should satisfy himself
where: that there will be no adverse consequences (e.g. excessive rotation of
Gk is the stabilising characteristic permanent action the base). It should also be noted that the ULS pressure distribution
(Use 1.1 Gk for a destabilising permanent action) diagram will be rectangular and not trapezoidal.
Qk,w is the destabilising characteristic variable wind action
Reinforced concrete pads
Figure 1
Procedures for depth of spread foundations Where the pad foundations require reinforcement the following checks
should be carried out to ensure:
■ Sufficient reinforcement to resist bending moments.
START
■ Punching shear strength.
■ Beam shear strength.
Obtain soil parameters from Ground Investigation report
The moments and shear forces should be assessed using the STR
combination:
1.35 Gk + 1.5 Qk STR combination 1 (Exp. (6.10))
Design using
Yes No
direct method?
However, there may be economies to made from using Expressions
(6.10a) or (6.10b) from the Eurocode.
Size foundation
Use prescriptive method.
(geotechnical design) using
Size foundation The critical bending moments for design of bottom reinforcement
the worst of Combinations
(geotechnical design) are located at the column faces. Both beam shear and punching
1 or 2 (ULS) for actions
using SLS for actions
and geotechnical material shear should then be checked at the locations shown in Figure 3. For
and presumed
properties. Combination 2
bearing resistance
will usually govern. punching shear the ground reaction within the perimeter may be
deducted from the column load (Expression (6.48), Eurocode 2–1–16).
It is not usual for a pad foundation to contain shear reinforcement,
therefore it is only necessary to ensure that the concrete shear stress
Check overturning using EQU
Is there an limit state for actions and capacity without shear reinforcement (vRd,c – see Table 6) is greater than
overturning moment? GEO Combination 2
Yes applied shear stress (vEd = VEd/(bd)).
for material properties.
No If the basic shear stress is exceeded, the designer may increase the
depth of the base. Alternatively, the amount of main reinforcement
Design foundation (structural design) using the worst of
Combinations 1 and 2 (ULS) for actions and geotechnical could be increased or, less desirably, shear links could be provided. (See
material properties.
Chapter 4, originally published as Beams8 for an explanation of how to
design shear reinforcement.)
Figure 2
Pressure distributions for pad foundations
M M M
P 6e
1
L L
P or P P
2P P
1.5 L 3 e L 2e
e e
P P
e = M/ P e
P 6e L = width of base P
1+
L L
SLS pressure distributions ULS pressure distribution
Figure 2
Pressure Distribution for Pa d Foundations
46
How to Foundations
Fi g 2 16.02.06
6. Foundations
design to BS 8110 and Eurocode 2 7). The procedure for determining the
punching shear requirements is shown in Figure 4.
Determine value of vEd,max
(design shear stress at face of column) from:
Table 6 vEd,max = β(VEd – DVEd) (from Exp. (6.38))
vRd,c resistance of members without shear reinforcement, MPa (u0deff)
rl Effective depth, d (mm) where u0 is perimeter of column
(see Clause 6.4.5 for columns at base edges)
300 400 500 600 700 800 900 1000a deff = (dy + dz)/2 where dy and dz
are the effective depths in orthogonal directions
0.25% 0.47 0.43 0.40 0.38 0.36 0.35 0.35 0.34
0.50% 0.54 0.51 0.48 0.47 0.45 0.44 0.44 0.43
Determine value of vRd,max (refer to Table 7)
0.75% 0.62 0.58 0.55 0.53 0.52 0.51 0.50 0.49
1.00% 0.68 0.64 0.61 0.59 0.57 0.56 0.55 0.54
1.25% 0.73 0.69 0.66 0.63 0.62 0.60 0.59 0.58 No
Is vEd,max < vRd,max? Redesign foundation
1.50% 0.78 0.73 0.70 0.67 0.65 0.64 0.63 0.62
1.75% 0.82 0.77 0.73 0.71 0.69 0.67 0.66 0.65 Yes
≥2.00% 0.85 0.80 0.77 0.74 0.72 0.70 0.69 0.68
Determine value of vEd, (design shear stress) from:
k 1.816 1.707 1.632 1.577 1.535 1.500 1.471 1.447 vEd = (VEd – DVEd)
Key (u1deff)
where u1 is length of control perimeter (refer to Figure 5). For
a For depths greater than 1000 calculate vRd,c directly. eccentrically loaded bases, refer to Exp. (6.51).
Notes The control perimeter will have to be found through iteration;
it will usually be between d and 2d
1 T able derived from: vRd,c = 0.12 k (100r I fck)(1/3) ≥ 0.035 k1.5 fck0.5
where k = 1 + √(200/d) ≤ 2 and r I = √(rIy +r Iz) ≤ 0.02,
r Iy = Asy/(bd) and r Iz = Asz/(bd)
2 T his table has been prepared for fck = 30; Determine concrete punching shear capacity vRd (without
where r l exceed 0.40% the following factors may be used: shear reinforcement) from 2dvRd,c/a (Refer to Table 6 for vRd,c)
fck 25 28 32 35 40 45 50
Factor 0.94 0.98 1.02 1.05 1.10 1.14 1.19 Either increase main
steel, or provide
Is vEd < vRd at No punching shear
critical perimeter? reinforcement required.
(Not recommended
Figure 3 for foundations.)
Yes
Shear checks for pad foundations
No shear reinforcement required. Check complete.
Figure 5
Typical basic control perimeters around loaded areas
2d
u1
u1 2d
2d
bz
Bends may be
d required
h d
by
Figure 3
Figure 5
Shear checks for pad foundations
Typical basic control perimeters around loaded areas.
How to Foundations 47
Fi g 3 20.02.06 How to Foundations
Job No. Fi g 5 20.02.06
Job No.
How to design concrete structures using Eurocode 2
The basic design processes for rafts are similar to those for isolated Alternatively, a truss analogy may be used; this is covered in Sections 5.6.4
pad foundations or pilecaps. The only difference in approach lies in the and 6.5 of Eurocode 2–1–1. The strut angle y should be at least 21.8° to
selection of an appropriate method for analysing the interaction between the horizontal; note that y should be measured in the plane of the column
the raft and the ground so as to achieve a reasonable representation of and pile.
their behaviour. For stiffer rafts (i.e. span-to-thickness greater than 10) with
a fairly regular layout, simplified approaches such as yield line or the flat Both beam shear and punching shear should then be checked as shown in
slab equivalent frame method may be employed, once an estimation of Figure 6. For beam shear, the design resistances in Table 6 may be used. If the
the variations in bearing pressure has been obtained from a geotechnical basic shear stress is exceeded, the designer should increase the depth of the
specialist. Whatever simplifications are made, individual elastic raft base. Alternatively, the amount of main reinforcement could be increased or,
reactions should equate to the applied column loads. less desirably, shear links could be provided. Care should be taken that main
bars are fully anchored. As a minimum, a full anchorage should be provided
Thinner, more flexible rafts or those with a complex layout may require from the inner face of piles. Large radius bends may be required.
the application of a finite element or grillage analysis. For rafts bearing
on granular sub-grades or when contiguous-piled walls or diaphragm When assessing the shear capacity in a pile cap, only the tension steel
perimeter walls are present, the ground may be modelled as a series placed within the stress zone should be considered as contributing to the
of Winkler springs. However, for cohesive sub-grades, this approach is shear capacity (see Figure 7).
unlikely to be valid, and specialist software will be required.
Figure 6
Critical shear perimeters for piles
For the purpose of this chapter it is assumed that the pile design will be
carried out by a specialist piling contractor. The actions on the piles must f /5
be clearly conveyed to the pile designer, and these should be broken down
into the unfactored permanent actions and each of the applicable variable
Punching shear 5 2d from column face
actions (e.g. imposed and wind actions). The pile designer can then carry
out the structural and geotechnical design of the piles. f
Table 7
Values for vRd, max
25 4.50
How to Foundations
28 4.97 Fi g 7 20.02.06
Job No. a a
30 5.28
32 5.58
hF
35 6.02
40 6.72
bF
45 7.38
50 8.00
Figure 8
Dimensions for plain foundations
48 How to Foundations
Fi g 8 20.02.06
Job No.
6. Foundations
Strip and pad footings may be constructed from plain concrete fck fctm Minimum % (0.26 fctm /fyka )
provided the following rules are adhered to. 25 2.6 0.13%
■ In compression, the value of acc, the coefficient taking account of 28 2.8 0.14%
long-term effects applied to design compressive strength 30 2.9 0.15%
(see Cl. 3.1.6), should be taken as 0.6 as opposed to 0.85 for 32 3.0 0.16%
reinforced concrete. 35 3.2 0.17%
■ The minimum foundation depth, hF, (see Figure 8) may be 40 3.5 0.18%
calculated from: 45 3.8 0.20%
50 4.1 0.21%
Key
a Where fyk = 500 MPa.
where:
sgd = the design value of the ground bearing pressure
fctd = the design concrete tensile strength from Exp. (3.16) Selected symbols
Symbol Definition Value
For many situations this is unlikely to offer any savings over the current Ac Cross sectional area of concrete bh
practice of designing for hf ≥ a. As Area of tension steel
As, prov Area of tension steel provided
The possibility of splitting forces, as advised in Clause 9.8.4 of Eurocode
As, req’d Area of tension steel required
2–1–1, may need to be considered.
d Effective depth
Eurocode 2 allows plain concrete foundations to contain reinforcement deff Average effective depth (dy + dz) /2
for control of cracking. fcd Design value of concrete compressive strength acc fck /gc
fck Characteristic cylinder strength of concrete
fctm Mean value of axial tensile strength 0.30 fck2/3 for fck ≤ C50/60
quantity of reinforcement
h Overall depth of the section
leff Effective span of member See Section 5.3.2.2 (1)
M Design moment at the ULS
Crack control Qk Characteristic value of a variable action
Refer to Chapter 2, originally published as Getting started 9. Qk,w Characteristic value of a variable wind action
VEd Design value of applied shear force
Minimum area of principal reinforcement vEd Design value of applied shear stress
VRd,c Design value of the punching shear
The minimum area of reinforcement is As,min = 0.26 fctm bt d/fyk but not
resistance without punching shear reinforcement
less than 0.0013bt d (see Table 8). vRd,c Design value of the punching shear stress
resistance without punching shear reinforcement
Maximum area of reinforcement vRd,max Design value of the maximum punching shear
resistance along the control section considered
Except at lap locations, the maximum area of tension or compression
x Depth to neutral axis (d – z)/0.4
reinforcement, should not exceed As,max = 0.04 Ac
xmax Limiting value for depth to neutral axis (d – 0.4)d where d ≤1.0
z Lever arm
Minimum spacing of reinforcement acc Coefficient taking account of long term 0.85 for flexure and
The minimum spacing of bars should be the greater of: effects on compressive strength and of axial loads, 1.0 for
■ Bar diameter, unfavourable effects resulting from the way other phenomena
load is applied (From UK National Annex)
■ Aggregate size plus 5 mm, or
b Factor for determining punching shear stress
■ 20 mm. d Ratio of the redistributed moment to the elastic
bending moment
Deep elements gm Partial factor for material properties
For deep elements the advice in Eurocode 2 for the side faces of deep r0 Reference reinforcement ratio fck/1000
beams may be followed. The UK National Annex recommends that 0.2% r l Required tension reinforcement at mid-span As l bd
to resist the moment due to the design
is provided in each face. The distance between bars should not exceed loads (or at support for cantilevers)
the lesser of twice the beam depth or 300 mm. For pile caps the side c0 Factor for combination value of a variable action
face may be unreinforced if there is no risk of tension developing. c1 Factor for frequent value of a variable action
c2 Factor for quasi-permanent value of a variable action
49
6. Foundations
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1997: Eurocode 7: Geotechnical design. BSI (2 parts).
2 BRITISH STANDARDS INSTITUTION. BS 5930: Code of practice for site investigation. BSI, 1999.
3 BRITISH STANDARDS INSTITUTION. BS 8002: Code of practice for earth retaining structures. BSI, 1994.
4 BRITISH STANDARDS INSTITUTION. BS 8004: Code of practice for foundations. BSI, 1986.
5 NARAYANAN, R S & BROOKER, O. How to design concrete structures using Eurocode 2: Introduction to Eurocodes. The Concrete Centre, 2005.
6 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–1, Eurocode 2: Design of concrete structures. General rules and rules for buildings. BSI, 2004.
7 GOODCHILD, C H & WEBSTER R M. Spreadsheets for concrete design to BS 8110 and Eurocode 2, version 3. The Concrete Centre, 2006.
8 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Beams. The Concrete Centre, 2006.
9 BROOKER, O. How to design concrete structures using Eurocode 2: Getting started. The Concrete Centre, 2005.
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/21 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-31-5 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
50 published April 2006, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ and British Cement Association views expressed are not necessarily those of the DTI.
How to design concrete structures using Eurocode 2
7. Flat slabs
R Moss BSc, PhD, DIC, CEng, MICE, MIStructE O Brooker BEng, CEng, MICE, MIStructE
Designing to Eurocode 2
This chapter covers the analysis and design of concrete flat slabs to Eurocode
21, a process which is essentially the same as when using BS 81102. However,
the layout and content of Eurocode 2 may appear unusual to designers
familiar with BS 8110. Eurocode 2 does not contain the derived formulae or
specific guidance on determining moments and shear forces. This has arisen
because it has been European practice to give principles in the codes and for
the detailed application to be presented in other sources such as textbooks.
It should be noted that values from the UK National Annex (NA) have been
used throughout this publication, including values that are embedded in
derived formulae (derivations can be found at www.eurocode2.info). A list of
symbols related to flat slab design is given at the end of this chapter.
Analysis
Using Eurocode 2 for the analysis of flat slabs is similar to using BS 8110. The
following methods may be used:
■ Equivalent frame method
■ Finite element analysis
■ Yield line analysis
■ Grillage analogy
Fire resistance (not minimum) dimension, so the designer should ensure that
a ≥ cnom + f link + f bar /2
Eurocode 2, Part 1–2: Structural fire design5, gives a choice of advanced, The requirements for flat slabs are given in Table 2.
simplified or tabular methods for determining the fire resistance. Using
tables is the fastest method for determining the minimum dimensions
and cover for flat slabs. There are, however, some restrictions and if these Flexure
apply further guidance can be obtained from specialist literature6.
The design procedure for flexural design is given in Figure 1; this
Rather than giving a minimum cover, the tabular method is based includes derived formulae based on the simplified rectangular stress
on nominal axis distance, a. This is the distance from the centre of block from Eurocode 2. Where appropriate Table 3 may be used to
the reinforcing bar to the surface of the member. It is a nominal determine bending moments for flat slabs.
Table 1
Flat slab design procedure
Table 2
Minimum dimensions and axis distances for reinforced concrete slabs
52
7. Flat slabs
Figure 1 Whichever method of analysis is used, Cl. 9.4.1 requires the designer
Procedure for determining flexural reinforcement to concentrate the reinforcement over the columns. Annex I of the
Eurocode gives recommendations for the equivalent frame method on
START how to apportion the total bending moment across a bay width into
column and middle strips to comply with Cl. 9.4.1. Designers using
Carry out analysis of slab to determine design moments grillage, finite element or yield line methods may also choose to follow
(M) (Where appropriate use coefficients from Table 3).
the advice in Annex I to meet this requirement.
K z/d K z/d
Check minimum reinforcement requirements (see Table 6) ≤ 0.05 0.950a 0.13 0.868
0.26 fctm bt d 0.06 0.944 0.14 0.856
As,min = where fyk ≥ 25
fyk
0.07 0.934 0.15 0.843
0.08 0.924 0.16 0.830
0.09 0.913 0.17 0.816
Check maximum reinforcement requirements.
As,max = 0.04 Ac for tension or compression 0.10 0.902 0.18 0.802
reinforcement outside lap locations 0.11 0.891 0.19 0.787
0.12 0.880 0.20 0.771
Key
a Limiting z to 0.95d is not a requirement of Eurocode 2, but is considered to be good practice
Table 3
Bending moment coefficients for flat slabs
Table 6
End support/slab connection First Interior Interior Minimum percentage of reinforcement required
interior spans supports
Pinned Continuous support fck fctm Minimum % (0.26 fctm /fyka )
End End End End 25 2.6 0.13%
support span support span 28 2.8 0.14%
Moment 0 0.086Fl – 0.04Fl 0.075Fl –0.086Fl 0.063Fl – 0.063Fl 30 2.9 0.15%
32 3.0 0.16%
Notes
35 3.2 0.17%
1 Applicable to slabs where the area of each bay exceeds 30 m2, 40 3.5 0.18%
Qk, ≤ 1.25 Gk and qk ≤ 5 kN/m2
45 3.8 0.20%
2 F is the total design ultimate load, l is the effective span
3 Minimum span > 0.85 longest span, minimum 3 spans
50 4.1 0.21%
4 Based on 20% redistribution at supports and no decrease in span moments Key
a Where fyk = 500 MPa
53
How to design concrete structures using Eurocode 2
Deflection depth ratios are appropriate where the structure remains propped
during construction or until the concrete attains sufficient strength to
support the construction loads. It can generally be assumed that early
Eurocode 2 has two alternative methods of designing for deflection; striking of formwork will not significantly affect the deflection after
either by limiting span-to-depth ratio or by assessing the theoretical installing the cladding and/or partitions9.
deflection using the Expressions given in the Eurocode. The latter is
dealt with in detail in Chapter 8, originally published as Deflection
calculations 7. Punching shear
The span-to-depth ratios should ensure that deflection is limited The design value of the punching shear force, VEd, will usually be the
to span/250 and this is the procedure presented in Figure 3. The support reaction at the ultimate limit state. In principle the design
Background paper to the UK National Annex 8 notes that the span-to- for punching shear in Eurocode 2 and BS 8110 is similar. The main
differences are as follows.
Figure 2 ■ Standard factors for edge and corner columns that allow for
Simplified rectangular stress block for concrete up to class C50/60 moment transfer (b) are greater in Eurocode 2. However, b can
from Eurocode 2
be calculated directly from Expressions (6.38) to (6.46) of the
Eurocode to give more efficient designs.
Figure 4
Basic span-to-effective-depth ratios for flat slabs
39
37 fck = 50
Figure 3 fck = 45
Procedure for assessing deflection 35 fck = 40
fck = 35
33 fck = 32
Span-to-effective-depth ratio (l/d)
START fck = 30
31 fck = 28
fck = 25
Determine basic l/d from Figure 4 29 fck = 20
27
Determine Factor 1 (F1)
For ribbed or waffle slabs 25
F1 = 1 – 0.1 ((bf/bw) – 1) ≥ 0.8†
(bf is flange breadth and bw is rib breadth)
Otherwise F1 = 1.0 23
21
Determine Factor 2 (F2)
Where the slab span exceeds 8.5 m and it supports 19
brittle partitions, F2 = 8.5/leff
Otherwise F2 = 1.0 17
15
Determine Factor 3 (F3) 0.40% 0.60% 0.80% 1.00% 1.20% 1.40% 1.60% 1.80% 2.00%
F3 = 310/ss Percentage of tension reinforcement (A s /bd)
Where ss = Stress in reinforcement at serviceability
limit state (see Figure 5)
ss may be assumed to be 310 MPa (i.e. F3 = 1.0)
Notes
Note: As,prov ≤ 1.5 As,req’d (UK National Annex) Figure 4
Increase Basic span-to-depth ratios for flat slabs flat slab (K = 1.2).
1 This graph assumes a simply supported
As,prov
2 Compression reinforcement, r’, has been taken as 0.
[ ( ) ]
l fck r 0 r0 1.5
Job No. = K 11 + 1.5
Yes + 3.2 fck –1 where r ≤ r 0 and
d r r
Check complete
† The Eurocode is ambiguous regarding linear interpolation. It is understood that this
was the intention of the drafting committee and is in line with current UK practice.
l
d
= K 11 +
1.5 fck r 0
( r – r ’)
+
[ fck
12 ]
r’
r0
where r > r 0 .
54
7. Flat slabs
■ In Eurocode 2 the maximum value of shear at the column face is As an alternative to using shear links, proprietary shear stud rails
not limited to 5 MPa, and depends on the concrete strength used. may be used. Eurocode 2 (Figure 6.22) allows them to be laid out
■ With Eurocode 2 the permissible shear resistance when using shear
in a radial or cruciform pattern and gives spacing requirements for
links is higher, although such designs may not be economic or both. Other techniques are available for increasing punching shear
desirable. resistance and these are covered in a best practice guide10.
Figure 5
Determination of steel stress Determine value of vRd,max from Table 7
No
320 Is vEd,max ≤ vRd,max? Redesign slab
300
Yes
Unmodified steel stress, ssu
240
Determine concrete punching shear capacity
(without shear reinforcement), vRD,c from Table 8
220 where r l = (r ly r lz)0.5
(r ly, r lz are the reinforcement ratios in two orthogonal
200 directions for fully bonded tension steel, taken over a
width equal to column width plus 3d each side.)
180
1.0 2.0 3.0 4.0
No Punching shear
Ratio Gk/Qk Is vEd > vRd,c? reinforcement not
required
c2 = 0.8, gG = 1.35 c2 = 0.6, gG = 1.25 Yes
c2 = 0.6, gG = 1.35 c2 = 0.3, gG = 1.25
Determine area of punching shear reinforcement per perimeter
c2 = 0.3, gG = 1.35 c2 = 0.2, gG = 1.25 from:
Asw = (vEd – 0.75vRd,c)sr u1/(1.5 fywd,ef)
c2 = 0.2, gG = 1.35 where
sr is the radial spacing of shear reinforcement (see Figure 9)
fywd,ef = 250 + 0.25 deff ≤ fywd (see Table 9)
To determine stress in the reinforcement (ss), calculate the ratio Gk/Qk , read
up the graph to the appropriate curve and read across to determine ssu .
Determine the length of the outer perimeter where shear
reinforcement not required from:
ss can be calculated from the expression: ss = ssu
( As,req
As,prov )( )
d
1
uout,ef = b VEd/(vRd,c d)
55
How to design concrete structures using Eurocode 2
Figure 7
Table 8 Recommended standard values for b
vRd,c resistance of members without shear reinforcement, MPa Rules for spacing and
rI Effective depth, d (mm)
≤200 225 250 275 300 350 400 450 500 600 750 quantity of reinforcement
File How to Flat Slabs Figure 7
v1 14.03.06
0.25% 0.54 0.52 0.50 0.48 0.47 0.45 0.43 0.41 0.40 0.38 0.36 Job No.
0.50% 0.59 0.57 0.56 0.55 0.54 0.52 0.51 0.49 0.48 0.47 0.45 Minimum area of reinforcement
0.75% 0.68 0.66 0.64 0.63 0.62 0.59 0.58 0.56 0.55 0.53 0.51 The minimum area of longitudinal reinforcement in the main direction
1.00% 0.75 0.72 0.71 0.69 0.68 0.65 0.64 0.62 0.61 0.59 0.57 is As,min = 0.26 fctm bt d/fyk but not less than 0.0013b d (see Table 6).
1.25% 0.80 0.78 0.76 0.74 0.73 0.71 0.69 0.67 0.66 0.63 0.61
The minimum area of a link leg for vertical punching shear
1.50% 0.85 0.83 0.81 0.79 0.78 0.75 0.73 0.71 0.70 0.67 0.65
reinforcement is
1.75% 0.90 0.87 0.85 0.83 0.82 0.79 0.77 0.75 0.73 0.71 0.68
1.5Asw,min /(sr.st) ≥ 0.08fck½/fyk
≥ 2.00% 0.94 0.91 0.89 0.87 0.85 0.82 0.80 0.78 0.77 0.74 0.71
which can be rearranged as
k 2.000 1.943 1.894 1.853 1.816 1.756 1.707 1.667 1.632 1.577 1.516
Asw,min ≥ (sr.st)/F
Notes
1 Table derived from: v Rd,c = 0.12 k (100r I fck)1/3 ≥ 0.035 k1.5 fck 0.5 where where
k = 1 + R(200/d) ≤ 2 and r I = R(r ly + r lz) ≤ 0.02, r ly = Asy/(bd) and r lz = Asz/(bd)
sr = the spacing of the links in the radial direction
2 This table has been prepared for fck = 30;
Where r I exceeds 0.40% the following factors may be used: st = the spacing of the links in the tangential direction
fck 25 28 32 35 40 45 50 F can be obtained from Table 10
Factor 0.94 0.98 1.02 1.05 1.10 1.14 1.19
Maximum area of reinforcement
Outside lap locations, the maximum area of tension or compression
reinforcement should not exceed As,max = 0.4 Ac
Figure 8
Typical basic control perimeters around loaded areas
Minimum spacing of reinforcement
The minimum spacing of bars should be the greater of:
■ Bar diameter
u1
■ Aggregate size plus 5 mm
2d
2d u1 ■ 20 mm
Figure 5
Typical basic control perimeters around loaded areas.
56
How to Foundations
Fi g 5 20.02.06
Job No.
7. Flat slabs
■ For the secondary reinforcement: 3h but not more than 400 mm fck Factor, F
Where h is the depth of the slab. 25 1875
28 1772
For slabs 200 mm thick or greater, the bar size and spacing should be
30 1712
limited to control the crack width and reference should be made to
32 1657
Section 7.3.3 of the Eurocode or Chapter 2, originally published as
35 1585
Getting started.4
40 1482
45 1398
Spacing of punching shear reinforcement
50 1326
Where punching shear reinforcement is required the following rules
Note
should be observed.
fck has been taken as 500 MPa
■ It should be provided between the face of the column and kd
inside the outer perimeter where shear reinforcement is no longer
required. k is 1.5, unless the perimeter at which reinforcement is no Selected symbols
longer required is less than 3d from the face of the column. In this Symbol Definition Value
case the reinforcement should be placed in the zone 0.3d to 1.5d Ac Cross sectional area of concrete bh
from the face of the column.
As Area of tension steel
■ There should be at least two perimeters of shear links.
As2 Area of compression steel
■ The radial spacing of the links should not exceed 0.75d
As, prov Area of tension steel provided
(see Figure 9).
■ The tangential spacing of the links should not exceed 1.5d within As, req’d Area of tension steel required
Figure 9 fctm Mean value of axial tensile strength 0.30 fck2/3 for fck ≤ C50/60
Punching shear layout (from Table 3.1, Eurocode 2)
hs Slab thickness
Outer perimeter of shear K Factor to take account of the different See Table N 7.4 in
Outer control
reinforcement perimeter structural systems UK National Annex
u out
leff Effective span of member See Section 5.3.2.2 (1)
Figure 9
Punching shear layout
57
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–1, Eurocode 2: Design of concrete structures – General rules and rules for buildings. BSI, 2004.
2 BRITISH STANDARDS INSTITUTION. BS 8110–1: The structural use of concrete – Part 1, Code of practice for design and construction. BSI, 1997.
3 NARAYANAN, R S & BROOKER, O. How to design concrete structures using Eurocode 2: Introduction to Eurocodes. The Concrete Centre, 2005.
4 BROOKER, O. How to design concrete structures using Eurocode 2: Getting started. The Concrete Centre, 2005.
5 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–2, Eurocode 2: Design of concrete structures. General rules – structural fire design. BSI, 2004.
6 DEPARTMENT OF COMMUNITIES AND LOCAL GOVERNMENT. Handbook to BS EN 1992–1–2. DCLG, due 2006.
7 WEBSTER, R & BROOKER, O. How to design concrete structures using Eurocode 2: Deflection calculations. The Concrete Centre, 2006.
8 BRITISH STANDARDS INSTITUTION. Background paper to the UK National Annex to BS EN 1992–1–1 and BS EN 1992–1–2. BSI, 2006.
9 PALLETT, P. Guide to flat slab formwork and falsework. Construct, 2003.
10 BRITISH CEMENT ASSOCIATION. Prefabricated punching shear reinforcement for reinforced concrete flat slabs. BCA, 2001.
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/22 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-32-3 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
58 published May 2006, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ and British Cement Association views expressed are not necessarily those of the DTI.
How to design concrete structures using Eurocode 2
8. Deflection calculations
R Webster CEng, FIStructE O Brooker BEng, CEng, MICE, MIStructE
Overview
In the past structures tended to be stiff with relatively short spans. As
technology and practice have advanced, more flexible structures have resulted.
There are a number of reasons for this, including:
■ The increase in reinforcement strength leading to less reinforcement being
required for the ultimate limit state (ULS) and resulting in higher service
stresses in the reinforcement.
■ Increases in concrete strength resulting from the need to improve both
durability and construction time, and leading to concrete that is more stiff
and with higher service stresses.
■ A greater understanding of structural behaviour and the ability to It is often recommended that the design value of the concrete
analyse that behaviour quickly by computer. tensile strength for a low restraint layout is taken as the average
■ The requirement to produce economic designs for slabs whose of fctm,fl and fctm, to allow for unintentional restraint. For high restraint
thicknesses are typically determined by the serviceability limit state fctm should be used.
(SLS) and which constitute 80% to 90% of the superstructure costs.
■ Client requirements for longer spans and greater operational Creep
flexibility from their structures. Creep is the time-dependant increase in compressive strain in a
concrete element under constant compressive stress. Creep is usually
considered in the design by modifying the elastic modulus using a
Factors affecting deflection creep coefficient, h, which depends on the age at loading, size of
the member and ambient conditions, in particular relative humidity.
An accurate assessment of deflection can only be achieved if Eurocode 2 gives advice on the calculation of creep coefficients in
consideration is given to the factors that affect it. The more important detail in Annex B. It also advises on the appropriate relative humidity
factors are discussed in detail below. to use in Figure 3.1.
Tensile strength The cement strength class is required in the assessment of creep,
The tensile strength of concrete is an important property because however, at the design stage it is often not clear which class should
the slab will crack when the tensile stress in the extreme fibre is be used. Generally, Class R should be assumed. Where the ground
exceeded. In Eurocode 2 the concrete tensile strength, fctm, is a mean granulated blastfurnace slag (ggbs) content exceeds 35% of the
value (which is appropriate for deflection calculations) and increases cement combination or where fly ash (pfa) exceeds 20% of the
as the compressive strength increases. This is an advancement when cement combination, Class N may be assumed. Where ggbs exceeds
compared with BS 8110 where the tensile strength is fixed for all 65% or where pfa exceeds 35% Class S may be assumed.
concrete strengths.
Elastic modulus
The degree of restraint to shrinkage movements will influence the The elastic modulus of concrete is influenced by aggregate type,
effective tensile strength of the concrete. A layout of walls with high workmanship and curing conditions. The effective elastic modulus
restraint will decrease the effective tensile strength. Typical examples under sustained loading will be reduced over time due to the effect
of wall layouts are given in Figure 1. For a low restraint layout the of creep. These factors mean that some judgement is required
following expression may be used for the concrete tensile strength: to determine an appropriate elastic modulus. Eurocode 2 gives
fctm,fl = (1.6 – h/1000)fctm > fctm recommended values for the 28-day secant modulus, Ecm, (in Table 3.1)
where and makes recommendations for adjustments to these values to
fctm,fl = Mean flexural tensile strength of reinforced concrete account for different types of aggregate. The long-term elastic modulus
fctm = Mean tensile strength of concrete should be taken as:
Figure 1
Typical floor layouts
Figure 1
60
Typical floor layouts
8. Deflection calculations
Ec,LT = Ec28/(1 + h) Commercial pressures often lead to a requirement to strike the formwork
where as soon as possible and move on to subsequent floors, with the minimum
Ec28 = 28-day tangent modulus = 1.05 Ecm of propping. Tests on flat slabs have demonstrated that as much as 70%
h = Creep factor. (Note that with Eurocode 2, h relates to a 28-day of the loads from a newly cast floor (formwork, wet concrete, construction
short-term elastic modulus, whereas a ‘true’ creep factor would loads) may be carried by the suspended floor below7. It can generally
be associated with the modulus at the age of loading.) be assumed that early striking of formwork will not greatly affect the
deflection after installing the cladding and/or partitions. This is because the
The assessment of the long-term E-value can be carried out more deflection affecting partitions will be smaller if the slab becomes ‘cracked’
accurately after the contractor has been appointed because they should be before, rather than after, the installation of the cladding and/or partitions.
able to identify the concrete supplier (and hence the type of aggregates)
and also the construction sequence (and hence the age at first loading). Cracking
Deflection of concrete sections is closely linked to the extent of
Loading sequence cracking and the degree to which cracking capacity is exceeded. The
The loading sequence and timing may be critical in determining point at which cracking occurs is determined by the moments induced
the deflection of a suspended slab because it will influence the point in the slab and the tensile strength of the concrete, which increases
at which the slab will crack (if at all) and is used to calculate the creep with age. Often the critical situation is when the slab is struck, or when
factors for the slab. A loading sequence is shown in Figure 2, which the load of the slab above is applied. Once the slab has cracked its
shows that in the early stages relatively high loads are imposed while stiffness is permanently reduced.
casting the slab above. The loading sequence may vary, depending on
the construction method. It is therefore necessary to find the critical loading stage at which
cracking first occurs. This critical loading stage corresponds with the
Smaller loads are imposed when further slabs are cast above. The loads minimum value of K, where:
are then increased permanently by the application of the floor finishes
K = fctm ^W 0.5h
and erection of the partitions. Finally, the variable actions are applied
to the structure and, for the purpose of deflection calculation, the
quasi-permanent combination should be used. (See Chapter 1, where
originally published as Introduction to Eurocodes5 for further W = The serviceability loading applied up to that stage
information on combinations of actions.) However, it is likely that the fctm = The concrete tensile strength at that stage
quasi-permanent combination will be exceeded during the lifetime Where the frequent combination is the critical load stage, then
of the building and, for the purpose of determining whether the slab the degree of cracking (z) calculated for the frequent combination
might have cracked, the frequent combination may be critical. should also be used for the quasi-permanent combination, but not for
Figure 2
Loading history for a slab – an example
14
h
12
b g
10 f
c
e
8 d
a
Load (kN/m)
6 Loading sequence
a Slab struck e Floor finishes applied
4 b 1st slab above cast f Partitions erected
c 2nd slab above cast g Quasi-permanent variable actions
2 d 3rd slab above cast h Frequent variable actions
0
0 50 100 150 200 250 300
Duration (days)
61
How to design concrete structures using Eurocode 2
any of the earlier load stages. If, however, an earlier stage Figure 3
proves critical, the z value at that stage should be carried Outline of rigorous method for calculating deflection
forward to all subsequent stages.
Collate input data
Further information can be found in the best practice ■ Element dimensions and reinforcement details and arrangements from the
guide Early striking and improved backpropping6. ultimate limit state design
■ Loading sequence e.g.
• Striking the formwork
Shrinkage curvature • Casting the floor above
Shrinkage depends on the water/cement ratio, relative • Erection of the partitions and/or cladding
• Application of finishes
humidity and the size and shape of the member. The effect The sequence will vary from project to project
of shrinkage in an asymmetrically reinforced section is to ■ Concrete properties (see Table 1)
induce a curvature that can lead to significant deflection in • Mean compressive strength (fcm)
shallow members. This effect should be considered in the • Mean tensile strength (fctm or fctm,fl)
• Elastic modulus (Ec28) = 1.05 Ecm
deflection calculations.
■ Critical arrangement of actions
(or repeat the calculations for each arrangement to determine the critical case)
Methods for
Assess whether the element has flexural cracking
calculating deflections ■ Determine the critical load stage at which cracking first occurs.
(See ‘Cracking’ on page 3)
Two methods for calculating deflection are presented ■ Calculate the following properties:
• Creep coefficients, h (Annex B of Eurocode 2 or Figure 4)
below, and these are based on the advice in TR58 • Long term elastic modulus, ELT (see Panel 1)
Deflections in concrete slabs and beams8. • Effective modulus ratio, ae from: ae = Es /ELT
• Neutral axis depth for uncracked condition, xu (see Panel 2)
• Second moment of area for uncracked condition, Iu (see Panel 2)
Rigorous method • Calculate cracking moment, Mcr from:
Mcr = fctm Iu/(h – xu), using appropriate value for fctm.
The rigorous method for calculating deflections is the
■ Does the moment at the critical load stage exceed the cracking moment?
most appropriate method for determining a realistic
• If yes, the element is cracked at all subsequent stages.
estimate of deflection. However, it is only suitable for z = 1 – 0.5(Mcr/M)2 [z = 0 for uncracked situation]
Repeat at 1/20 points for all three loading stages
use with computer software. The Concrete Centre has Use these critical values of fctm and z for subsequent stages.
• If no, the element will not crack at any stage.
produced a number of spreadsheets that use this method
to carry out deflection calculations for a variety of slabs
and beams9. These offer a cost-effective way to carry
Determine the curvature of the slab
out detailed deflection calculations, and they include the
■ When the slab is cracked calculate the following properties at the load stage
ability to consider the effect of early age loading of the being considered, using appropriate values for fctm, z and ELT:
concrete. Figure 3 illustrates the principles of the method • Neutral axis depth for cracked section, xc (see Panel 2)
and shows how the factors affecting deflection are • Second moment of area for cracked condition, Ic (see Panel 2)
considered in the rigorous deflection calculations. ■ Calculate the flexural curvature:
1 MQP MQP
rfl = g E e Ic + ]1 – g g E e Iu
Finite element analysis may also be used to obtain
■ Calculate the curvature due to shrinkage strain 1/rcs (see Panel 2)
estimates of deflection. In this case the principles
■ Calculate the total curvature, 1/rt = 1/rfl + 1/rcs
in Figure 3 should be applied if credible results are to
be obtained.
Repeat the calculations at frequent intervals (say at 1/20 points) and integrate
Panel 1 twice to obtain the overall deflection.
Determining long term elastic modulus of elasticity
Calculate long-term elastic modulus, ELT from: If deflection affecting cladding and/or partitions is required, repeat calculations
for frequent combination and for loading at time of installation of partitions
W1 W2 W3 W4 W5
E LT = RW c + + + + m and/or cladding.
Eeff,1 Eeff, 2 Eeff, 3 Eeff, 4 Eeff, 5
where
Eeff = Ec28/(1+h) Estimate deflections:
■ Overall deflection (quasi-permanent combination)
Wn = Serviceability load at stage n
■ Deflection affecting partitions/cladding (Frequent combination deflection
h = Creep coefficient at relevant loading time
less deflection at time of installation)
and duration
62
8. Deflection calculations
Table 1
Concrete properties
fck MPa 320 325 328 330 332 335 340 350
fcm = (fck + 8) MPa 328 333 336 338 340 343 348 358
fctm = (0.3 fck(2/3) ≤ C50/60 or 2.12 ln(1 + (fcm/10)) > C50/60) MPa 332.21 332.56 332.77 332.90 333.02 333.21 333.51 334.07
fctm* = (0.3 fcm(2/3) ≤ C50/60 or 1.08 ln(fcm) + 0.1 > C50/60)a MPa 332.77 333.09 333.27 333.39 333.51 333.68 333.96 334.50
Ecm = (22 [(fcm)/10]0.3 GPa 330.0 331.5 332.3 332.8 333.3 334.1 335.2 337.3
Ec28 = (1.05 Ecm) GPa 331.5 333.0 333.9 334.5 335.0 335.8 337.0 339.1
ecd,0 CEM class R, RH = 50% microstrain 746 706 683 668 653 632 598 536
ecd,0 CEM class R, RH = 80% microstrain 416 394 381 372 364 353 334 299
ecd,0 CEM class N, RH = 50% microstrain 544 512 494 482 471 454 428 379
ecd,0 CEM class N, RH = 80% microstrain 303 286 275 269 263 253 239 212
ecd,0 CEM class S, RH = 50% microstrain 441 413 397 387 377 363 340 298
ecd,0 CEM class S, RH = 80% microstrain 246 230 221 216 210 202 189 166
eca(∞) microstrain 325 338 345 350 355 363 375 100
Key
2
2 + ] ae - 1 g ] Asd + As2 d2 g
bh be used when striking at less than 7 days or where construction overload is taken into account.
a fctm* may
bh2 + ] ae - 1 g ] As + As2 g
xu =
2 2 + ] ae - 1 g ] Asd + As2 d2 g
bh
xu =
Panel
Useful
2 bh ] - a1 grectangular
2bh + aefor ] Assd++AAs2s2gdsection
2g
x u =Expressions
bh 2
]] aaeea-h 11 gg ]] A
Akssd+
g 2g
]As2as2ed- 1 g 6 As ]d - xu g + As2 ] x u - d 2 g @
3 2 +
bhbh + + bh - +A 2 2
I u = 12 2 + 2 - xu
bh + ] a - 1 g ] As2 + As2 g
xu = 2
where
bh23 + ] aeea- h 1 g ] Aksd + As2 d2 g
bh
= 12 3 + bh 2 - xu 2 + ] ae - 1 g 6 As ]d - xu g + As2 ] x u - d 2 g @
2 2
Ixuu = As = a
rea of tension reinforcement
] g ] g
I u = 12 + bh a 2 - xuk + ] ae - 1 g 6 As ]d - xu g + As2 ] x u - d 2 g @
bhbh + ae - h 1 As + As2 2 2
As2 = area of compression reinforcement
xc = #bh7 ^ As ae + Ahs2 ] ae - 1 g h + 2 b ^ As d ae + A s2d22 ] ae - 1 g h A - 2^ As ae + As2 ] ae - 1 g h -
2 0.5
I u = 12 + bh a 2 - xuk + ] ae - 1 g 6 As ]d - xu g + As2 ] x u - d 2 g @
3 2 b = breadth of section
b
d = e ffective depth to tension
Ixuc =
#bh7 ^3 s aebh+aAhs2 -
= 12 A+ ] aexu- k 1+g h] +
2 2
ae - 2 b 1^ Ags 6dAase]d+-Axs2udg22 ]+
ae A- 1 g h A - 2^ A a + As2 ] ae - 1 g h -
s2 ] x u - d 2 g @ s e
0.5
b reinforcement
2
xc = #bx7 c^3 As ae + A s2 ] ae -2 1 g h + 2 b ^ As d ae + A s2d22] ae - 1 g h A - ^ As ae + As2 ] ae - 1 g h -
2 0.5 d2 = d
epth to compression reinforcement
I c = 3 + ae As ^ d - x c g + ^ ae - 1 g As2 ^ d2 - x c g
b
h = overall depth of section
xc = #bx7 ^3 As ae + A s2 ] ae - 1 g h + 2 b ^ As d ae + A s2d2 ] ae - 1 g h A - ^ As ae + As2 ] ae - 1 g h -
2 0.5
b
g g g
ae = modular ratio
c
^
I c = 3 + ae As d - x c + a2 e - 1 As2 d2 - x c
2
^ ^ 2
1 S S
= gbxfc3cs a e +^1 - g h 2fcs ae
u c
t 0 10 t 0 10
20 20
30 30
50 50
100 100
7.0 6.0 5.0 4.0 3.0 2.0 1.0 0 100 300 500 700 900 1100 1300 7.0 6.0 5.0 4.0 3.0 2.0 1.0 0 100 300 500 700 900 1100 1300
h (?, t 0 ) h 0 (mm) h (?, t 0) h o (mm)
a) Inside conditions - RH = 50% b) Outside conditions - RH = 80%
How to use Nonogram
Ke y Notes
C20/25 C40/50 1 t0 = age of concrete at time of loading
A D
C25/30 C45/55 2 h0 = 2A c /u
C30/37 C50/60 3 Intersection point between lines D & E can also be above point A E C
B
C35/45 4 For t0 > 100 it is sufficiently accurate to assume t = 100
Figure 4
63
q 0.104 Calculate total shrinkage strain e1cs from e1cs = ecd1+ eca where: 1
= r + 0.9
ecd = kh ecd,0 = Drying shrinkagert,strain
0.9 f I
fctm I u ctm u from r
QP n Mrcr cs = t,QP
ql 2 kh = Coefficient based on notional size, = Table 2 h – xu
Mcr see
h – xu
8 ecd,0 = Nominal unrestrained drying shrinkage, see Table 1
1
eca = bas(t) eca(∞) = eca(∞) for long-term
dQP = KL 2deflection, see Table 1
rt,QP
1M MQP MQP
q 0.102 1
= gr n
=
QPg + ^1M–QPg h E I
Eeff^1Ic – g h
+
Calculate curvature due to shrinkager n strain 1/r
Eeff Ic Panel 2) Eeff Iu eff u
cs (see
ql 2
15.6 1 1 1
1 1 = 1 +
r +
=rt,QP
Calculate total curvature r r rcs from
t,QP n rcsn
b
q MA MC MB K = 0.104 (1 )
10 1
MA + MB Calculate quasi-permanent deflection from dQP2 = 1KL 2 rt,QP
b= dQP = KL rt,QP
MC where K can be obtained from Figure 6 and L is the span.
al W End deflection
Wal
a (3 a ) Do you need No
= to calculate deflection
6 Finish
load at end K = 0.333 due to cladding and
partitions?
Yes
2 2
al qa l a (4 a )
q 2 12 Calculate the deflection that will occur at the time of application of
the load due to partitions and/or cladding.
if a = l , K = 0.25
1 Calculate the creep coefficient h(t,t0), where t is the age when
partition/cladding loads are applied and t0 is the age of striking.
b h(t,t0) ≈ h(∞,t0) bc(t,t0). For bc(t,t0) refer to Figure 7, alternatively
MA MB K = 0.083 (1 ) refer to Annex B of Eurocode 2.
4
MA + MB 2 Calculate the moment due to self-weight, partitions/cladding and any
MC b= other loads which have been applied prior to the installation of the
MC
cladding/partition, Mpar and use in place of MQP
al al 3 Recalculate the section properties, curvature and hence deflection,
1 (5 4a 2 )
2 dpar, using h(t,t0) or equivalent instead of h(∞,t0)
2
Wl (3 4a 2) 80 3 4a 4 The approximate deflection affecting cladding and partitions is
24 d = dQP – dpar
64
8. Deflection calculations
Table 2
Values for Kh
Precamber
h0 kh A slab or beam can be precambered to reduce the effect of deflection
>100 1.0 below the horizontal (see Figure 8). However, in practice too much
precamber is generally used and the slab remains permanently
>200 0.85
cambered. This is because of the difficulty in accurately calculating
>300 0.75
deflection. A precamber of up to half the quasi-permanent
>500 0.70
combination deflection could be used, but a lower figure is
Notes
recommended. Precamber does not reduce the deflections affecting
h0 is the notional size (mm) of the cross-section = 2Ac/u
where partitions or cladding.
Ac = Concrete cross-sectional area
Flat slabs
u = Perimeter of that part of the cross section which is exposed to drying
Figure 7
Coefficient for development of creep with time after loading Flat slabs are very popular and efficient floor systems. However,
because they span in two directions, it can be difficult to calculate their
deflection. TR58 8 gives several suitable methods for assessing flat slab
0.60
deflection. Of these, a popular method is to take the average deflection
of two parallel column strips and to add the deflection of the middle
0.55 strip spanning orthogonally to get an approximation of the maximum
deflection in the centre of the slab.
0.50
The recommended acceptance criteria for a flat slab are shown in Figure 9.
Coefficient, bc (t, t0)
0.45
Accuracy
0.40 The calculation of deflection in Eurocode 2 using the rigorous method
presented here is more advanced than that in BS 811010. It can be
0.35 used to take account of early-age construction loading by considering
reduced early concrete tensile strengths.
Figure 8
Figure 9
Deflection limits for
65
File How to Deflections Figure 8
29.03.06
Job No. File How to Deflections Figure 9
8. Deflection calculations
Cladding tolerances ■ Manufacturers may say that their glazed systems can only
accommodate deflection as low as 5 mm.
Deflection may affect cladding or glazing in the following ways: There should be open discussions between the designers for the various
■ When a slab deflects, the load on the central fixings will be relieved elements to determine the most cost-effective way of dealing with the
and shed to outer fixings. interaction of the structure and cladding.
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1992–1–1, Eurocode 2: Design of concrete structures. General rules and rules for building. BSI, 2004.
2 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Beams. The Concrete Centre, 2006.
3 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Slabs. The Concrete Centre, 2006.
4 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Flat slabs. The Concrete Centre, 2006.
5 NARAYANAN, R S & BROOKER, O. How to design concrete structures using Eurocode 2: Introduction to Eurocodes. The Concrete Centre, 2005
6 BRITISH CEMENT ASSOCIATION. Early striking and improved backpropping. BCA, 2001. (Available from www.concretecentre.com)
7 PALLETT, P. Guide to flat slab formwork and falsework. Construct, 2003
8 THE CONCRETE SOCIETY. Technical report No. 58 Deflections in concrete slabs and beams. The Concrete Society, 2005.
9 GOODCHILD, C H & WEBSTER, R M. Spreadsheets for concrete design to BS 8110 and EC2, version 3. The Concrete Centre, 2006.
10 BRITISH STANDARDS INSTITUTION. BS 8110–1. Structural use of concrete – Code of practice for design and construction. BSI, 1997.
Acknowledgements
The content of this publication was produced as part of the project ‘Eurocode 2: transition from UK to European concrete design standards’. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates • Arup • British Cement Association • British Precast • Building Research Establishment • Clark Smith Partnership •
Concrete Innovation and Design • Construct • Department for Trade and Industry • Office of the Deputy Prime Minister • The Concrete Centre •
The Concrete Society • Quarry Products Association.
Ref: TCC/03/23 All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
ISBN 1-904818-33-1 information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
First
66 published May 2006, revised December 2006
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
© The Concrete Centre™ and British Cement Association views expressed are not necessarily those of the DTI.
How to design concrete structures using Eurocode 2
Errata
Introduction to Eurocodes
Location Original Amendment
Table 5, rows 3,5,7 & 9 1.5 Qk 1.5c Qk
Page 6, Item 13 in left The punching shear checks are carried at The punching shear checks are carried out at 2d
hand column 2d from the face of the column… from the face of the column…
Getting started
Location Original Amendment
Table 6, row 3 0.900 Gl + 0.100 Ql 0.090 Gl + 0.100 Ql
Table 10, notes - Note 2 added:
a is the axis distance (see Figure 4)
Note 3 added:
hs is the slab thickness, including non-
combustible flooring
Table 8, row 9 Car park elements subject to airborne Elements subject to airborne chlorides only
chlorides only
Slabs
Location Original Amendment
Table 3, note 2 F is the total design ultimate load, l, is F is the total design ultimate load, l, is the span
the effective span
Table 3, new note 4 - Based on 20% redistribution at support and no
decrease in span moments
Table 4, values for K’
% redistribution K’ % redistribution K’
0 0.205 0 0.208a
5 0.193 10 0.182a
10 0.180 15 0.168
15 0.166 20 0.153
20 0.151 25 0.137
25 0.136 30 0.120
Table 4, new key - a It is often recommended in the UK that
K’should be limited to 0.168 to ensure ductile
failure
Table 5, 6 0.954 0.950a
Figure 3, box 5 from top σs may assumed to be 310 MPa σs may be assumed to be 310 MPa
of diagram
Figure 5, heading Basic span-to-depth ratios Basic span-to-effective-depth ratios
Figure 5, Note 2 - K = 0.4 for cantilevers
Figure 5, Note 4 ⎡
l 1.5 fck ρ 0 fck ρ' ⎤ l ⎡ 1.5 fck ρ 0 fck ρ' ⎤
= K ⎢11 + + ⎥ = K ⎢11 + + ⎥
d ⎢⎣ (ρ − ρ') 12 ρ0 ⎥
⎦
d ⎢⎣ (ρ − ρ' ) 12 ρ0 ⎥⎦
Page 5 ‘Design for shear’ It is not usual for a slab to contain shear It is not usual for a slab to contain shear
reinforcement, therefore it is only reinforcement, therefore it is only necessary to
necessary to ensure that the concrete ensure that the concrete shear stress capacity
shear stress capacity without shear without shear reinforcement (vRd,c – see Table
reinforcement (vRd,c – see Table 7) is less 7) is more than applied shear stress (vEd = VEd
than applied shear stress (vEd = VEd /(bd /(bd )).
)).
Page 6 ‘Ribbed or waffle Current practices for determining forces Current practices for determining forces in
slabs’ in ribbed and waffle slabs may also be ribbed and waffle slabs may also be used for
used for designs to Eurocode 2. Where a designs to Eurocode 2. Where a waffle slab is
waffle slab is treated as a two-way slab treated as a two-way slab refer to previous
refer to previous section. Where it is section, but note that their torsional stiffness is
treated as a flat slab reference may be significantly less than for a two-way slab and
made to How to design concrete the bending moment coefficients may not be
structures to Eurocode 2: Flat slabs4 applicable. Where it is treated as a flat slab
reference may be made to How to design
concrete structures to Eurocode 2: Flat slabs4
Page 7 ‘Maximum For slabs 200 mm thick or greater For slabs 200 mm thick or greater the bar size
spacing of reference should be made to section and spacing should be limited to control the
reinforcement’ 7.3.3 of the Code or Chapter 2, crack width and reference should be made to
originally published as Getting started5. section 7.3.3 of the Code or Chapter 2,
originally published as Getting started5.
Beams
Location Original Amendment
Table 2, row 5 bmin in column C = 300 bmin in column C = 200
Table 3, row 3 0.900 Gl + 0.100 Ql 0.090 Gl + 0.100 Ql
Table 4, values for K’
% redistribution K’ % redistribution K’
0 0.205 0 0.208a
5 0.193 10 0.182a
10 0.180 15 0.168
15 0.166 20 0.153
20 0.151 25 0.137
25 0.136 30 0.120
Table 4, new key - a It is often recommended in the UK that
K’should be limited to 0.168 to ensure ductile
failure
Figure 5, box 2 vEd = shear stress at d from face of vEd = design shear stress
support
Figure 5 ⎛ ⎞
v Ed ⎛ v Ed ⎞
θ = 0.5 sin −1⎜⎜ ⎟
⎟ θ = 0.5 sin−1⎜⎜ ⎟
⎝ 0.18fck (1 − fck / 250) ⎠ . f ( − f / ) ⎟
⎝ 0 20 ck 1 ck 250 ⎠
Figure 5 A sw v Ed b w A sw v Ed b w
= =
s 0.9 d fywd cot θ s fywd cot θ
Figure 7, Note 4 ⎡
l 1.5 fck ρ 0 fck ρ' ⎤ l ⎡ 1.5 fck ρ 0 fck ρ' ⎤
= K ⎢11 + + ⎥ = K ⎢11 + + ⎥
d ⎢⎣ (ρ − ρ') 12 ρ0 ⎥
⎦
d ⎢⎣ (ρ − ρ' ) 12 ρ 0 ⎦⎥
Columns
Location Original Amendment
Table 3, heading - Delete:
, using method A
Figure 4 MoE Moe
Page 6 ASN/2 = (NEd - fcd b dc)/[(σsc - σst)γc] ASN/2 = (NEd - fcd b dc)/(σsc - σst)
Page 6 ASN/2 = Area of reinforcement required to ASN = Area of reinforcement required
resist axial load to resist axial load
Page 6 ASM/2 = [M - fcd b dc (h/2 - dc/2)] ASM/2 = [M - fcd b dc (h/2 - dc/2)]
[(h/2 - dc/2)(σsc - σst)γc] [(h/2 - dc/2)(σsc - σst)]
Page 6 ASM/2 = Area of reinforcement required to ASM = Area of reinforcement required
resist axial load to resist axial load
Page 8 ‘spacing requirements for - Add to final paragraph:
columns’ No bar should be further than
150 mm from transverse
reinforcement (links) in the
compression zone
Foundations
Location Original Amendment
Table 4, row 3 1.0 Gk 1.1 Gk
Flat slabs
Location Original Amendment
Table 3, Note 4 Based on 15% redistribution at supports Based on 20% redistribution at
and no decrease in span moments supports and no decrease in span
moments
Table 4, values for K’
% redistribution K’ % redistribution K’
0 0.205 0 0.208a
5 0.193 10 0.182a
10 0.180 15 0.168
15 0.166 20 0.153
20 0.151 25 0.137
25 0.136 30 0.120
Table 4, new key - a It is often recommended in the UK
that K’should be limited to 0.168 to
ensure ductile failure
Figure 3, box 4 from top of Determine Factor 2 (F2) Determine Factor 2 (F2)
diagram Where the slab span exceeds 7 m and it Where the slab span exceeds 8.5 m
supports brittle partitions, F2 = 7/leff and it supports brittle partitions, F2
Otherwise F2 = 1.0 = 8.5/leff
Otherwise F2 = 1.0
Figure 4, Note 3 ⎡
l 1.5 fck ρ 0 fck ρ' ⎤ l ⎡ 1.5 fck ρ 0 fck ρ' ⎤
= K ⎢11 + + ⎥ = K ⎢11 + + ⎥
d ⎢⎣ (ρ − ρ') 12 ρ0 ⎥
⎦
d ⎢⎣ (ρ − ρ' ) 12 ρ0 ⎥⎦
Page 6, ‘Minimum areas of 1.5 Asw,min / (sr st) ≥ 0.08 fck1/2 fyk 1.5 Asw,min / (sr st) ≥ 0.08 fck1/2 /fyk
reinforcement’
Table 7
fck vrd,max fck vrd,max
20 3.31 20 3.68
25 4.05 25 4.50
28 4.48 28 4.97
30 4.75 30 5.28
32 5.02 32 5.58
35 5.42 35 6.02
40 6.05 40 6.72
45 6.64 45 7.38
50 7.20 50 8.00
Deflection calculations
Location Original Amendment
Figure 5, box 5, item 2 (200 MPa) (200 GPa)
Introduction
BS 8500 Concrete – Complementary British Standard to BS EN 206–11 was revised
in December 2006 principally to reflect changes to Special Digest 12 and bring it
into line with other standards.
The guidelines given in BS 8500 for durability are based on the latest research
and recommends strength, cover, cement content and water/cement ratios for
various exposure conditions.
Compressive strength
BS 8500 uses ‘compressive strength class’ to define concrete strengths; the
notation used gives the cylinder strength as well as the cube strength (see
:cementZg]concretebg]nlmkrin[eb\Zmbhg This chapter is taken
from The Concrete Table 3). It is important to quote the compressive strength class in full to
Centre’s publication, avoid confusion.
Ahpmh=^lb`g<hg\k^m^ How to design
Lmkn\mnk^lnlbg`>nkh\h]^+
concrete structures
A J Bond F:FL\=B<Ia=FB<><>g`
O Brooker ;>g`<>g`FB<>FBLmkn\m>
A J Harris ;L\FL\=B<FB<><>g`?@L
T Harrison ;L\Ia=<>g`FB<>?B<M
R M Moss;L\Ia==B<<>g`FB<>FBLmkn\m>
R S Narayanan?K>g`
R Webster<>g`?BLmkn\m>
using Eurocode 2 Cover to reinforcement
(Ref. CCIP–006) The durability guidance given in BS 8500 is based on the assumption that the
minimum cover for durability is achieved. An allowance should be made in the
design for deviations from the minimum cover (∆cdev). This should be added to
the minimum cover to obtain the nominal cover.
Continues page 4
1
How to design concrete structures using Eurocode 2
Table 1
Exposure Classes
XC1 Dry or permanently wet. Reinforced and prestressed concrete surfaces inside enclosed structures except areas of structures
with high humidity. Reinforced and prestressed concrete surfaces permanently submerged in
non-aggressive water.
XC2 Wet, rarely dry. Reinforced and prestressed concrete completely buried in soil classed as AC-1 and with a hydraulic
gradient not greater than 5. For other situations see ‘chemical attack’ section below.
XC3 & Moderate humidity or cyclic wet and dry. External reinforced and prestressed concrete surfaces sheltered from, or exposed to, direct rain.
XC4 Reinforced and prestressed concrete surfaces inside structures with high humidity (e.g. poorly
ventilated, bathrooms, kitchens). Reinforced and prestressed concrete surfaces exposed to alternate
wetting and drying.
Corrosion induced by chlorides other than from sea water (XD classes) a
(Where concrete containing reinforcement or other embedded metal is subject to contact with water containing chlorides, including de-icing salts,
from sources other than from sea water.)
XD1 Moderate humidity. Concrete surfaces exposed to airborne chlorides. Parts of structures exposed to occasional or slight
chloride conditions.
XD2 Wet, rarely dry. Reinforced and prestressed concrete surfaces totally immersed in water containing chlorides b.
XD3 Cyclic wet and dry. Reinforced and prestressed concrete surfaces directly affected by de-icing salts or spray containing
de-icing salts (e.g. walls; abutments and columns within 10 m of the carriageway; parapet edge
beams and buried structures less than 1 m below carriageway level, pavements and car park slabs).
Corrosion induced by chlorides from sea water (XS classes) a
(Where concrete containing reinforcement or other embedded metal is subject to contact with chlorides from sea water or air carrying salt originating from sea water.)
XS1 Exposed to airborne salt but not in direct External reinforced and prestressed concrete surfaces in coastal areas.
contact with sea water.
XS2 Permanently submerged. Reinforced and prestressed concrete completely submerged and remaining saturated,
e.g. concrete below mid-tide level b.
XS3 Tidal, splash and spray zones. Reinforced and prestressed concrete surfaces in the upper tidal zones and the splash and
spray zones c.
Freeze/thaw attack (XF classes)
(Where concrete is exposed to significant attack from freeze/thaw cycles whilst wet.)
XF1 Moderate water saturation without Vertical concrete surfaces such as facades and columns exposed to rain and freezing. Non-vertical
de-icing agent. concrete surfaces not highly saturated, but exposed to freezing and to rain or water.
XF2 Moderate water saturation with de-icing agent. Elements such as parts of bridges, which would otherwise be classified as XF1 but which are
exposed to de-icing salts either directly or as spray or run-off.
XF3 High water saturation without de-icing agent. Horizontal concrete surfaces, such as parts of buildings, where water accumulates and which are
exposed to freezing. Elements subjected to frequent splashing with water and exposed to freezing.
XF4 High water saturation with de-icing agent Horizontal concrete surfaces, such as roads and pavements, exposed to freezing and to de-icing
or sea water d. salts either directly or as spray or run-off. Elements subjected to frequent splashing with water
containing de-icing agents and exposed to freezing.
Chemical attack (ACEC classes)
(Where concrete is exposed to chemical attack.) Note: BS 8500-1 refers to ACEC classes rather than XA classes used in BS EN 206-1
Key
a The moisture condition relates to that in the concrete cover to reinforcement or other embedded develop a specification that is appropriate to the actual conditions likely to be encountered.
metal but, in many cases, conditions in the concrete cover can be taken as being that of the
c Exposure XS3 covers a range of conditions. The most extreme conditions are in the spray zone. The
surrounding environment. This might not be the case if there is a barrier between the concrete and
least extreme is in the tidal zone where conditions can be similar to those in XS2. The
its environment.
recommendations given take into account the most extreme UK conditions within this class.
b Reinforced and prestressed concrete elements, where one surface is immersed in water containing
d It is not normally necessary to classify in the XF4 exposure class those parts of structures located in
chlorides and another is exposed to air, are potentially a more severe condition, especially where the
the United Kingdom which are in frequent contact with the sea.
dry side is at a high ambient temperature. Specialist advice should be sought where necessary, to
2
11. BS 8500 for building structures
Table 2
Selected a recommendations for normal-weight reinforced concrete quality for combined exposure classes and cover to reinforcement for at least a
50-year intended working life and 20 mm maximum aggregate size
Exposure conditions Cement/ Strength classc, maximum w/c ratio, minimum cement or combination
combination content (kg/m3), and equivalent designated concrete (where applicable)
designationsb
Typical example Primary Secondary Nominal cover to reinforcementd
15 + D c dev 20 + D c dev 25 + D c dev 30 + D c dev 35 + D c dev 40 + D c dev 45 + D c dev 50 + D c dev
Internal mass
X0
___ All Recommended that this exposure is not applied to reinforced concrete
concrete
Internal elements C20/25,
(except humid XC1
___ All 0.70, 240 or <<< <<< <<< <<< <<< <<< <<<
locations) RC20/25
Buried concrete C25/30,
in AC-1 ground XC2 AC-1 All ___ ___ 0.65, 260 or <<< <<< <<< <<< <<<
conditions e RC25/30
Vertical surface C40/50, C30/37, C28/35, C25/30,
protected from ___ All except ___ 0.45, 340 or 0.55, 300 0.60, 280 or 0.65, 260 or <<< <<< <<<
IVB-V
direct rainfall RC40/50 or RC30/37 RC28/35 RC25/30
C40/50, C30/37, C28/35,
Exposed vertical
XF1
All except ___ 0.45, 340 or 0.55, 300 0.60, 280 or <<< <<< <<< <<<
surfaces IVB-V
XC3 RC40/50 or RC30/37 RC28/35
& C40/50,0.45,
XC4 XF3
All except ___ 340 g or <<< <<< <<< <<< <<< <<<
IVB-V
RC40/50XFg
Exposed horizontal
surfaces C30/37, C28/35, C25/30,
XF3 (air All except ___ ___ 0.55, 300 0.60, 280 0.60, 280
<<< <<< <<<
entrained) IVB-V plus air g,h plus air g,h plus air g, h, j
or PAV2 or PAV1
Elements subject
to airborne XD1f
___ All ___ ___ C40/50, C32/40, C28/35,
<<< <<< <<<
0.45, 360 0.55, 320 0.60, 300
chlorides
IIB-V, IIIA ___ ___ ___ ___ ___ C35/45, C32/40, C28/35,
0.40, 380 0.45, 360 0.50, 340
Car park decks and
areas subject to ___ CEM I, IIA, ___ ___ ___ ___ ___ See C40/50, C35/45,
IIB-S, SRPC BS 8500 0.40, 380 0.45, 360
de-icing spray
IIIB, IVB-V ___ ___ ___ ___ ___ C32/40, C28/35, C25/30,
0.40, 380 0.45, 360 0.50, 340
IIB-V, IIIA ___ ___ ___ ___ ___ C35/45, C32/40, C32/40,
0.40, 380 0.45, 360 0.50, 340
Vertical elements XD3f
subject to de-icing XF2
CEM I, IIA, ___ ___ ___ ___ ___ See C40/50, C35/45,
IIB-S, SRPC BS 8500 0.40, 380 0.45, 360
spray and freezing
IIIB, IVB-V ___ ___ ___ ___ ___ C32/40, C32/40 C32/40,
0.40, 380 0.45, 360 0.50, 340
3
How to design concrete structures using Eurocode 2
Table 3
Eurocode 24 recommends that ∆c dev is taken as 10 mm, unless the Compressive strength class for normal and heavyweight concrete
fabrication is subjected to a quality assurance system where it is
Example Compressive Designated Previous Grade
permitted to reduce ∆c dev to 5 mm, or 0 mm if the element can be strength classes concrete of concrete
rejected if it is out of tolerance (e.g. precast elements). (BS 8500) (BS 8500) (BS 53283 & BS 81105)
C20/25 RC20/25 C25
Cement types and minimum cement content C25/30 RC25/30 C30
Table 4 may be used to understand the cement/combination
C28/35 RC28/35 C35
designations. It should be noted from Table 2 that the strength,
water/cement ratio and minimum cement content may vary depending C30/37 RC30/37 –
on the cement type used. In the UK, all cement/combinations are C32/40 RC32/40 C40
available (except SRPC), although in most concrete production plants C35/45 RC35/45 C45
either ground granulated blastfurnace slag or flyash (pfa) is available; not C40/50 RC40/50 C50
both. When using a designated concrete (see section below), it is not
C45/55 – –
necessary to specify the types of cement/combinations.
C50/60 – C60
Explanation of the compressive strength class notation NOTE: Refer to BS 8500-1: 2006, Table A.20 for full list of Compressive strength classes.
C 40 /50
A Includes heavyweight concrete
Table 4
B Minimum characteristic 150 mm Cement and combination typea
diameter by 300 mm cylinder
‘C’ for normal Cylinder Cube
weight strengthB strengthC strength, N/mm2 Broad Composition Cement/combination
concrete A C Minimum characteristic cube
designationb types (BS 8500)
‘LC’ for strength, N/mm2
lightweight
CEM I Portland cement CEM I
concrete
SRPC Sulfate-resisting Portland cement SRPC
IIA Portland cement with 6–20% of fly CEM II/A-L, CEM II/A-LL,
Air content ash, ground granulated blastfurnace CIIA-L, CIIA-LL,
Where air entrainment is required for exposure classes XF3 and XF4 slag, limestone, or 6–10% silica CEM II/A-S, CIIA-S
fumec CEM II/A-V, CIIA-V
the minimum air content by volume of 3.0%, 3.5% or 5.5% should CEM II/A–D
be specified for 40 mm, 20 mm and 10 mm maximum aggregate size
IIB-S Portland cement with 21–35% CEM II/B-S, CIIB-S
respectively. ground granulated blastfurnace slag
IIB-V Portland cement with 25–35% fly ash CEM II/B-V, CIIB-V
Freeze/thaw aggregates
IIB+SR Portland cement with 25–35% fly ash CEM II/B-V+SR,
For exposure conditions XF3 and XF4 freeze/thaw resisting
CIIB-V+SR
aggregates should be specified. The producer is then obliged to
IIIAd, e Portland cement with 36–65% CEM III/A,, CIIIA
conform to the requirements given in BS 8500–2: 2006, Cl.4.3.
ground granulated blastfurnace slag
IIIA+SRe Portland cement with 36–65% CEM III/A+SRf,
Aggressive ground ground granulated blastfurnace slag CIII/A+SRf
Where plain or reinforced concrete is in contact with the ground with additional requirements that
further checks are required to ensure durability. An aggressive enhance sulfate resistance
chemical environment for concrete class (ACEC class) should be IIIBe, g Portland cement with 66–80% CEM III/B, CIIIB
assessed for the site. BRE Special Digest 12 gives guidance on the ground granulated blastfurnace slag
assessment of the ACEC class and this is normally carried out as part IIIB+SRe Portland cement with 66–80% CEM III/B+SRf , CIIIB+SRf
of the interpretive reporting for a ground investigation. Knowing the ground granulated blastfurnace slag
with additional requirements that
ACEC class, a design chemical class (DC class) can be obtained from
enhance sulfate resistance
Table 5.
IVB-V Portland cement with 36–55% fly ash CEM IV/B(V), CIVB
Key
For designated concretes, an appropriate foundation concrete (FND a There are a number of cements and combinations not listed in this table that may be specified for
designation) can be selected using Table 6; the cover should be certain specialist applications. See BRE Special Digest 12. for the sulfate-resisting characteristics of other
cements and combinations.
determined from Table 2 for the applicable exposure classes. A FND b The use of these broad designations is sufficient for most applications. Where a more limited range of
cement or combinations types is required, select from the notations given in BS 8500-2:2006, Table 1.
concrete has the strength class of C25/30, therefore, where a higher c When IIA or IIA-D is specified, CEM I and silica fume may be combined in the concrete mixer using the
strength is required a designed concrete should be specified. For k-value concept; see BS EN 206-1:200, 5.2.5.2.3.
d Where IIIA is specified, IIIA+SR may be used.
designed concretes, the concrete producer should be advised of the e Inclusive of low early strength option (see BS EN 197-4 and the “L” classes in BS 8500-2:2006, Table A.1.).
f “+SR” indicates additional restrictions related to sulfate resistance. See BS 8500-2:2006, Table 1,
DC-class (see section on specification). footnote D.
g Where IIIB is specified, IIIB+SR may be used.
4
11. BS 8500 for building structures
Table 5
Selection of the DC-class and the number of Addition Protection Fire design
Measures (APMs) where the hydrostatic head of groundwater is not more Having selected concrete cover and strength to meet the durability
than five times the section width a, b, c, d, e recommendations of BS 8500, the nominal cover should be checked
ACEC-class DC-class in accordance with Eurocode 24, for fire cover.
(Aggressive
Chemical Intended working life
Environment for
Concrete cast against uneven surfaces
At least 50 years At least 100 years The nominal cover (i.e. minimum cover plus fixing tolerance) should
Concrete class)
AC-1s, AC-1 DC-1 DC-1 be a minimum of 75 mm for concrete cast directly against the earth
and 50 mm for concrete cast against blinding.
AC-2s, AC-Z DC-2 DC-2
AC-4s
AC-4z
DC-4
DC-4z
DC-4
DC-4z
Specification
AC-4 DC-4 Refer to BS 8500 Method of specifying
There are various methods of specifying concrete to BS 8500
AC-4ms DC-4m DC4m
(see Table 8). The most popular are designated and designed.
AC-4m DC-4m Refer to BS 8500 BS 8500 also introduces a new method ‘proprietary concrete’.
AC-5 DC-4f DC-4f
The specifier
AC-5z DC-4zf DC-4z/1 f
Figures 1 and 2 show standard specification forms produced by the
AC-5m DC-4mf DC-4mf Quarry Products Association for designated and designed concretes8.
Key Similar tables are included in the National Structural Concrete
a Where the hydrostatic head of groundwater is greater than five times the section width, refer to BS 8500. Specification 9 (NSCS). In BS 8500 the ‘specifier’ is the person or body
b For guidance on precast products see Special Digest 12.
responsible for the final compilation of the technical requirements,
c For structural performance outside these values refer to BS 8500.
called the specification, which is passed to the concrete producer.
d For section widths < 140 mm refer to BS 8500.
This will generally be the contractor, however, the designer will want
e Where any surface attack is not acceptable e.g. with friction piles, refer to BS 8500.
f This should include APM3 (surface protection), where practicable, as one of the APMs; refer to BS 8500.
to ensure their requirements are incorporated and this will normally
be through their own specification for the works (e.g. with the
NSCS). Figures 1 and 2 have been annotated to indicate which
Table 6 information is typically provided by the designer and contractor. The
Guidance on selecting designated concrete for reinforced concrete
foundations designer should require that any reported non-conformities are
passed to them for assessment.
DC-Class Appropriate Designated Concrete
Continues page 8
5
How to design concrete structures using Eurocode 2
Table 7
Factors affecting the abrasion resistance of concrete floors
Factor Effect
Power floating Power finishing and, in particular, repeated power trowelling is a significant factor in creating abrasion
resistance, however, excessive repetitions of the process do not necessarily further enhance performance.
Curing Prompt and efficient curing is essential in order to retain sufficient water in the surface zone to complete
hydration and the development of concrete strength at and close to the surface.
Cement content Cement content should not be less than 325 kg/m3. Cement contents above 360 kg/m3 are unlikely to
enhance abrasion resistance and excessive cement content can impair the power finishing process.
Water/cement ratio Water/cement ratio is of great importance. It should not exceed 0.55. Reducing to 0.50 is likely to increase
abrasion resistance but lowering further is unlikely to give further enhancement.
Aggregates Coarse aggregate usually has no direct effect on abrasion resistance, except in floors in very aggressive
environments where the surface is expected to be worn away. Coarse and fine aggregates should not contain
soft or friable materials.
Dry shake finishes Dry shake finishes can be used to enhance the surface properties in high abrasion locations.
Figure 1
Example specification of Designated Concrete
Schedule for the specification requirements of designated concretes for use on contract
Contract Title: New Office
Contract period: June - Dec ‘04
4.2.2d) Consistence S1, S2, S3, S4 S1, S2, S3, S4 S1, S2, S3, S4 S1, S2, S3, S4
(Ring the class required when other than F2, F3, F4, F5 F2, F3, F4, F5 F2, F3, F4, F5 F2, F3, F4, F5
the default classes of S3 for the GEN, FND
and RC series and S2 for the PAV series. Use
a separate column for different consistence
with the same designated concrete)
C Other (specify) C
4.2.3 C D Additional requirements –– –– –– C D
Exchange of information
BS EN 206-1, 7.1 Total volume required 48 m 3 12003 m3 72 m3 3
Anticipated peak delivery rate 6 m /day 18 m /hr 6 m /day
3
C Any access limitations C
KEY
5.1a) Intended method of placing, Skip + Pumping Skip + Designer specifies
e.g. pumping, and finishing, e.g. power tamped + float tamped D
concrete designation,
C floating, the concrete C maximum aggregate
5.1b) Where identity testing is routine: N/A N/A N/A size and any
additional
Type of test requirements
Volume of concrete in assessment
Number of tests on this volume Contractor specifies
C consistence, any
Whether a non-accredited laboratory
additional
C will be used C requirements and
5.1 & BS EN 206-1, 7.1 Other information from the specifier –– –– –– completes exchange
C to the producer C of information
section
5.2 & BS EN 206-1, 7.2 Information required from –– –– ––
C the producer C Red text
Example
A There is no need to cite BS EN 206-1 as BS 8500-2 has a clause that requires conformity to BS EN 206-1. specification
6
11. BS 8500 for building structures
Table 8
Methods of specifying concrete
Figure 2
Example specification of Designed Concrete
Schedule for the specification requirements of designed concretes for use on contract
Contract Title: New Office
Contract period: June - Dec ‘04
BS 8500-1 Requirement Schedule
reference
4.3.2a) The concretes below shall be supplied as designed concretes in accordance with this specification
and the relevant clauses of BS 8500-2A
D Concrete reference, if any Pads Slab Cols D
4.3.2b) D Compressive strength class C28/35 C25/30 C32/40 D
4.3.2c) For sulfate resisting concrete, design chemical class DC-2z DC- DC- DC-
D D
For other concretes, limiting values of composition: 0.70 0.55
Maximum w/c ratio
D Minimum cement/combination content, kg/m3 240 300 D
4.3.2d) & Cement or combination types CEM 1, SRPC, CEM 1, SRPC, CEM 1, SRPC, CEM 1, SRPC,
xx xx
4.3.3a) (delete those not permitted) IIA, IIB IIA, IIB IIA, IIB IIA, IIB
Other special property, e.g. white, low heat, +SR IIIA, IIIB, IVB IIIA, IIIB, IVB IIIA, IIIB, IVB IIIA, IIIB, IVB
D (specify) D
4.3.2e) D Maximum aggregate size, mm 20 20 10 D KEY
4.3.2f) Chloride class (ring the one required) Cl 0,10 Cl 0,10 Cl 0,10 Cl 0,10 D Designer specifies
O
O
O
content, cement or
4.3.2i) Consistence (Ring the class required. S1, S2, S3, S4 S1, S2, S3, S4 S1, S2, S3, S4 S1, S2, S3, S4
F2, F3, F4, F5 F2, F3, F4, F5 F2, F3, F4, F5 combination types
Use separate columns for the same basic F2, F3, F4, F5
(unless design
concretes with different consistence)
C D C D chemical class is
Other (specify)
specified), maximum
4.3.2 UKAS or equivalent accredited third party product Yes Yes Yes Yes aggregate size,
Note 2 D conformity certification (delete if not required) D chloride class, target
4.3.3b) Additional requirements density (excluding
to n) C D C D normal weight
Exchange of information concrete),
requirement for
BS EN Volume required 48 m 3 1200 m3 72 m3
6 m3/day 18 m3/hr 6 m3/day
third party product
206-1, 7.1 Anticipated peak delivery rate
C C conformity
Any access limitations
certification
5.1a) Intended method of placing, e.g. pumping, and Skip + Pumping Skip + (recommended)
C finishing, e.g. power floating, the concrete tamped + float tamped C and any additional
5.1b) Where identity testing is routine:
Type of test
N/A N/A N/A requirements
Contractor specifies
Volume of concrete in assessment C
Number of tests on this volume consistence,
C Whether a non-accredited laboratory will be used C any additional
requirements and
5.1 & BS EN Other information from the specifier to the –– –– –– completes exchange
206-1,7.1 C producer C of information
5.2 & BS EN Information required from the producer –– –– –– section
206-1, 7.2 C C
A There is no need to cite BS EN 206-1 as BS 8500-2 has a clause that requires conformity to BS EN 206-1.
Red text
Example
B Where RC is ringed, the chloride class shall be Cl 0.40 except where SRPC is used. In this case the chloride class shall be Cl 0,20. Specification
7
11.11.
BSBS 8500
8500 forfor building
building structures
structures
Table 9a
Consistence slump classes and likely target values Conformity
Under BS 8500, the concrete producer is now required to follow a
Slump class Target slump (mm) formal procedure called ‘conformity’ to verify that the concrete is in
S1 20 accordance with the specification. It is, therefore, recommended
S2 70 that the concrete supplier should have third party certification.
S3 130
Where this is not adopted, the specifier is advised to adopt
adequate identity testing to ensure the concrete is as specified.
S4 190
Identity testing
The specifier is responsible for organising any identity testing, which
Table 9b is in all but in name acceptance testing. Identity testing can include
Consistence flow classes and likely target values strength, consistence and air content. There are a number of
Flow class Target flow (mm) situations where it is recommended:
� where the producer does not hold third party certification
F2 380
� in cases of doubt
F3 450
� for critical elements, e.g. high strength columns
F4 520 � for spot checks on the producer.
F5 590
Exchange of information
To enable the concrete producer to design and produce a suitable
concrete, certain information must be provided in addition to the
specification, e.g. where the concrete needs to be pumped or a high
quality finish is required.
References
1 BRITISH STANDARDS INSTITUTION. BS 8500: Concrete – Complementary British Standard to BS EN 206–1. BS1, 2006.
2 BUILDING RESEARCH ESTABLISHMENT. BRE Special Digest 1 – Concrete in aggressive ground (3rd edition). BRE, 2005.
3 BRITISH STANDARDS INSTITUTION. BS 5328: Concrete, BSI. (Withdrawn by BSI on 1 December 2003).
4 BRITISH STANDARDS INSTITUTION. BS EN 1992, Eurocode 2: Design of concrete structures. BSI (4 parts).
5 BRITISH STANDARDS INSTITUTION. BS 8110-1: The structural use of concrete – Part 1: Code of practice for design and construction. BSI, 1997.
6 BRITISH STANDARDS INSTITUTION. BS 8204-2: Screeds, bases and in-situ floorings, Part 2: Concrete wearing surfaces – Code of practice. BSI, 1999.
7 THE CONCRETE SOCIETY. Technical report 34: Concrete industrial ground floors. The Concrete Society, 2003.
8 QUARRY PRODUCTS ASSOCIATION. Visit the Webpage www.qpa.org/pro_rea.
9 CONSTRUCT. National structural concrete specification for building construction. Construct, 2004.
10 BRITISH STANDARDS INSTITUTION. BS 4027: Specification for sulfate–resisting Portland cement. BSI, 1996.
Ref: TCC/03/30 All advice or information from The Concrete Centre is intended for use in the UK only by those who will evaluate the significance and
limitations of its contents and take responsibility for its use and application. No liability (including that for negligence) for any loss
ISBN 1-904818-50-1 resulting from such advice or information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should
note that publications from The Concrete Centre are subject to revision from time to time and they should therefore ensure that they
Published April 2007. Reprinted December 2007
are in possession of the latest version. This publication has been produced following a contract placed by the Department for Trade
First published as How to use BS 8500 with BS 8110, and Industry (DTI); the views expressed are not necessarily those of the DTI.
March 2005
© The Concrete Centre™
Worked Examples for Eurocode 2
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
1 Introduction
1.1 Aim
The aim of this publication is to illustrate through worked examples how Eurocode 2[1–4] may
be used in practice to design in-situ building structures. It is intended that these worked
examples will explain how calculations to BS EN 1992–1–1[1] may be performed. This will be
carried out within the environment of other relevant publications:
Eurocode 2.
Other Eurocodes.
Material and execution standards.
Publications by The Concrete Centre and others.
There are, therefore, many references to other documents and while it is intended that this
publication, referred to as Worked examples, can stand alone it is anticipated that users
may require several of the other references to hand, in particular, Concise Eurocode 2 [5],
which summarises the rules and principles that will be commonly used it the design of
reinforced concrete framed buildings to Eurocode 2.
Figure 1.1
Worked examples in context
The worked examples relate to in-situ concrete building structures. The designs are in
accordance with Eurocode 2 Part 1–1[1], as modified by the UK National Annex[1a] and explained
in PD 6687[5]. The design of other forms of concrete are covered in other publications[6–9].
Generally, the calculations are cross-referenced to the relevant clauses in Eurocode 2[1–4]
and, where appropriate, to other documents. See Table 1.1 for a guide to presentation and
Section 11 for references. All references in the margins are to Eurocode 2 Part 1–1[1] unless
indicated otherwise. References to BS 8110[10]refer to Part 1 unless otherwise stated.
Table 1.1
Guide to presentation
<6.4.4> Relevant clauses or figure numbers from Eurocode 2 Part
1–1 (if the reference is to other parts, other Eurocodes or
6.4.4 other documents this will be indicated)
<NA>
From the relevant UK National Annex (generally to
NA Eurocode 2 Part 1–1)
<6.4.4 &NA>
From both Eurocode 2 Part 1–1 and UK National Annex
6.4.4 & NA
<Fig. 2.1>
Relevant parts of this publication
Section 5.2
<SMDSC[22] >
Relevant parts of Standard method of detailing structural
SMDSC[22] concrete – a manual for best practice.
<Concise EC2>
Concise Eurocode 2
Concise EC2
As some of the detailing rules in Eurocode 2 are generally more involved than those to BS
8110, some of the designs presented in this publication have been extended into areas that
have traditionally been the responsibility of detailers. These extended calculations are not
necessarily part of ‘normal’ design but are included at the end of some calculations. It is
assumed that the designer will discuss and agree with the detailer areas of responsibility and
the degree of rationalisation, the extent of designing details, assessment of curtailment and
other aspects, that the detailer should undertake. It is recognised that in the vast majority of
cases, the rules given in detailing manuals[12,13] will be used. However, the examples are
intended to help when curtailment, anchorage and lap lengths need to be determined.
Figure 1.2
The Eurocode hierachy
BS EN 1990 provides the necessary information for the analysis of structures including
partial and other factors to be applied to the actions from BS EN 1991. It establishes the
principles and requirements for the safety, serviceability and durability of structures. It <BS EN 1990:
describes the basis for design as follows: 2.1>
A structure shall be designed and executed (constructed) in such a way that it will, during its
intended life, with appropriate degrees of reliability and in an economical way:
■ Sustain all actions and influences likely to occur during execution and use.
■ Remain fit for the use for which it is required.
In other words, it shall be designed using limit states principles to have adequate stability,
structural resistance (including structural resistance in fire), serviceability and durability.
For building structures, a design working life of 50 years is implied.
BS EN 1990 states that limit states should be verified in all relevant design situations,
persistent, transient or accidental. No relevant limit state shall be exceeded when design
values for actions and resistances are used in design. The limit states are:
■ Ultimate limit states (ULS), which are associated with collapse or other forms of
structural failure.
■ Serviceability limit states (SLS), which correspond to conditions beyond which specified
service requirements are no longer met.
All actions are assumed to vary in time and space. Statistical principles are applied to arrive
at the magnitude of the partial load factors to be used in design to achieve the required
reliability index (level of safety). There is an underlying assumption that the actions
themselves are described in statistical terms.
This publication is mainly concerned with designing for the actions defined by Part––1
Densities, self-weight, imposed loads for buildings.
Note
National Annexes and
explanatory documents
(e.g. PD 6687, and Non-
Contradictory
Complementary
Information – NCCI) are
not shown.
Figure 1.3
Eurocode 2 in context
Concise Eurocode 2 for the design of in-situ concrete framed buildings to BS EN 1992–1–
1: 2004 and its UK National Annex: 2005[11].
Generally each calculation is rounded and it is the rounded value that is used in any further
calculation.
The values of γc and γs, partial factors for materials, are indicated in Table 1.2.
Table 1.2
Partial factors for materials <Table 2.1 & NA>
Design situation γc – concrete γs – reinforcing steel
ULS – persistent and transient 1.50 1.15
Accidental – non-fire 1.20 1.00
Accidental – fire 1.00 1.00
SLS 1.00 1.00
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
2 Analysis, actions and load arrangements
2.1 Methods of analysis
At the ultimate limit state (ULS) the type of analysis should be appropriate to <5.1.1(7)>
the problem being considered. The following are commonly used:
Linear elastic analysis.
Linear elastic analysis with limited redistribution.
Plastic analysis.
At the serviceability limit state (SLS) linear elastic analysis may be used.
Within the limits set, coefficients for moment and shear derived from elastic
analysis may be used to determine forces in regular structures (see Appendix B).
The design of columns should be based on elastic moments without redistribution. <5.2.7>
Plastic analysis may be used for design at ULS provided that the required ductility <5.6.2>
can be assured, for example, by:
Limiting xu / d (to ≤ 0.25 for concrete strength classes ≤ C50/60).
Using Class B or C reinforcement.
Ensuring the ratio of moments at intermediate supports to moments in spans is
between 0.5 and 2.0.
2.2 Actions
Actions refer to loads applied to the structure as defined below:
Permanent actions refer to actions for which the variation in magnitude with
time is negligible.
Variable actions are actions for which the variation in magnitude with time is
not negligible.
Accidental actions are actions of short duration but of significant magnitude
that are unlikely to occur on a given structure during the design working life.
Imposed deformations are not considered in this publication.
2.4.3.1 General
Roofs do not qualify for load reductions. The method given below complies with the < BS EN 1991-1-1,
UK National Annex but differs from that given the Eurocode. 6.3.1.2 (10),
6.3.1.2 (10) & NA>
2.4.3.2 Area
A reduction factor for imposed loads for area αA may be used and should be
determined using
2.4.3.4 Use
According to the UK NA, αA and αn may not be used together. < BS EN 1991-1-1
6.3.1.2 (11) & NA>
s = μi Ce Cts k
where
μi = snow load shape factor
μ1 = undrifted snow shape factor
μ2 = drifted snow shape factor
For flat roofs, 0° = α (with no higher structures close or abutting),
μ1 = μ2 = 0.8
For shallow monopitch roofs, 0°< α < 30° (with no higher <BS EN 1991-1-3 5.3.1 ,
structures close or abutting), μ1 = 0.8, μ2 = 0.8 (1 + α/ 30) 5.3.2 & NA>
For other forms of roof and local effects refer to BS EN 1991–1–3
Sections 5.3 and 6
Ce = exposure coefficient <BS EN 1991-1-3 5.2(7),
For windswept topography Ce = 0.8 Table 5.1>
For normal topography Ce = 1.0
For sheltered topography Ce = 1.2
Ct = thermal coefficient, Ct = 1.0 other than for some glass-covered <BS EN 1991-1-3 5.2(8)>
roofs, or similar
sk = characteristic ground snow load kN/m2
= 0.15(0.1Z + 0.05) + (A+100) / 525 <BS EN 1991-1-3 NA 2.8>
where
Z = zone number obtained from the map in BS EN 1991–1–3 NA
Figure NA.1
A = site altitude, m
Figure NA.1 of the NA to BS EN 1991–1–3 also gives figures for sk at
100 m a.m.s.l. associated with the zones. For the majority of the
South East, the Midlands, Northern Ireland and the north of England
apart from high ground, sk = 0.50 kN/m2. For the West Country, West
Wales and Ireland the figure is less. For most of Scotland and parts of
the east coast of England, the figure is more. See Figure 2.1
Snow load is classified as a variable fixed action. Exceptional circumstances <BS EN 1991-1-3 2(1)
may be treated as accidental actions in which case reference should be made 5.2(3)>
to BS EN 1991–1–3
Figure 2.1
Characteristic ground snow load map
(Ground snow load at 100 m a.m.s.l. (kN/m2)
Figure 2.2 Map of fundamental Figure 2.3 Exposure factor Figure 2.4 Multiplier for
basic wind velocity, vb,map, (m/s) ce,flat(z) for sites in country or exposure correction for sites in
town terrain town terrain
Note
Subject to altitude correction.
<BS EN 1991-1-4 4.2(1) Note 2, <BS EN 1991-1-4 4.5(1) Note 1, NA <BS EN 1991-1-4 4.5(1) Note 1,
NA 2.4 (Fig. NA.1)> 2.17 (Fig. NA.7)> NA 2.17 (Fig. NA.8)>
Table 2.5 b) Typical area loads for concrete slabs and sheet materials
Typical area loads kN/m3 Typical area loads kN/m
Concrete slabs Plasterboard (12.5 mm) 0.09
P. C. solid units (100 mm) 2.50 Plasterboard (19 mm) 0.15
P. C. hollowcore unitsa (150 mm) 2.40 Plywood (12.5 mm) 0.08
P. C. hollowcore unitsa (200 mm) 2.87 Plywood (19 mm) 0.12
P. C. hollowcore unitsa (300 mm) 4.07 Quarry tiles including mortar bedding 0.32
P. C. hollowcore unitsa (400 mm) 4.84 Raised floor – heavy duty 0.50
Ribbed slabb (250 mm) 4.00 Raised floor – medium weight 0.40
Ribbed slabb (300 mm) 4.30 Raised floor – lightweight 0.30
Ribbed slabb (350 mm) 4.70 Render (13 mm) 0.30
Waffle slabc – standard moulds (325 mm) 6.00 Screed – 50 mm 1.15
Waffle slabc – standard moulds (425 mm) 7.30 Screed – lightweight (25 mm) 0.45
Waffle slabc – standard moulds (525 mm) 8.60 Stainless steel roofing (0.4 mm) 0.05
Sheet materials Suspended ceiling – steel 0.10
Asphalt (20 mm) 0.46 Suspended fibreboard tiles 0.05
Carpet and underlay 0.05 T&G boards (15.5 mm) 0.09
Chipboard (18 mm) 0.12 T&G boards (22 mm) 0.12
Dry lining on stud (20 mm) 0.15 Tiles – ceramic floor on bed 1.00
False ceiling – steel framing 0.10 Battens for slating and tiling 0.03
Felt (3 layer) and chippings 0.35 Tiles – clay roof (max) 0.67
Glass – double glazing 0.52 Tiles – natural slate (thick) 0.65
Glass – single glazing 0.30 Tiles – interlocking concrete 0.55
Insulation – glass fibre (150 mm) 0.03 Tiles – plain concrete 0.75
Linoleum (3.2 mm) 0.05 Key
Paving stones (50 mm) 1.20 a Hollowcore figures assume no topping
b Ribbed slabs: 150 web @ 750 centres with 100 mm thick
Plaster – two coat gypsum (12 mm) 0.21 flange/slab. Web slope 1:10
Plaster skim coat 0.05 c Waffle slabs: 150 ribs @ 900 centres with 100 mm thick
flange/slab. Web slope 1:10
where
γF = partial factor for the action according to the limit state under
consideration. Table 2.6 indicates the partial factors to be used in the
UK for the combinations of representative actions in building structures.
ψFk may be considered as the representative action, Frep, appropriate to the
limit state being considered
where
ψ = a factor that converts the characteristic value of an action into a
representative value. It adjusts the value of the action to account
for the nature of the limit state under consideration and the joint
probability of the actions occurring simultaneously. It can assume
the value of 1.0 for a permanent action or ψ0 or ψ1 or ψ2 for a
variable action. Table 2.7 shows how characteristic values of
variable actions are converted into representative values. This
table is derived from BS EN 1990[13] and its National Annex[13a].
Fk = characteristic value of an action as defined in Sections 2.2 and 2.3.
Either
Exp. 6.10 1.35 Gk + 1.5 Qk,1
Action ψ0 ψ1 ψ2
Imposed loads in buildings
Category A: domestic, 0.7 0.5 0.3
residential areas
Category B: office areas 0.7 0.5 0.3
Category C: congregation areas 0.7 0.7 0.6
Category D: shopping areas 0.7 0.7 0.6
Category E: storage areas 1.0 0.9 0.8
Category F: traffic (area vehicle 0.7 0.7 0.6
weight ≤ 30 kN)
Category G: traffic area (30 kN < 0.7 0.5 0.3
vehicle weight ≤ 160 kN)
Category H: roofsa 0.7 0.0 0.0
Snow loads where altitude ≤ 0.5 0.2 0.0
1000 m a.m.s.l.a
Wind loadsa 0.5 0.2 0.0
Temperature effects (non-fire)a 0.6 0.5 0.0
Notes
1 The numerical values given above are in accordance with BS EN 1990 and its UK National
Annex.
2 Categories K and L are assumed to be as for Category H
Key
a On roofs, imposed loads, snow loads and wind loads should not be applied together. < BS
EN 1991–1–1–1 3.3.2>
Expression (6.10) leads to the use of γF = γG = 1.35 for permanent actions and γF =
γQ = 1.50 for variable actions (γG for permanent actions is intended to be constant
across all spans).
Expression (6.10) is always equal to or more conservative than the less favourable
of Expressions (6.10a) and (6.10b). Expression (6.10b) will normally apply when
the permanent actions are not greater than 4.5 times the variable actions (except
for storage loads, category E in Table 2.7, where Exp. (6.10a) always applies).
Note
Assuming ψ 0 = 0.7 i.e. applicable to all areas except storage.
Figure 2.5
When to use Exp. (6.10a) or Exp. (6.10b)
Compared with the use of Exp. (6.10), the use of either Exp. (6.10a) or (6.10b)
leads to a more consistent reliability index across lightweight and heavyweight
materials.
Again the designer may choose between using Exp. (6.10) or the less favourable of Exp. < BS EN 1990
(6.10a) or (6.10b). 6.4.3.2(3) >
Either:
Exp. (6.10) 1.35 Gk + 1.5 Qk,1 + Σψ0,i 1.5 Qk,i
or the worst case of:
Exp. (6.10a) 1.35 Gk + ψ0,I 1.5 Qk,1 + ψ0,i 1.5 Qk,i
and
Exp. (6.10b) 1.25 Gk – 1.5 Qk,1 + Σψ0,I 1.5 Qk,i
In the above, Qk,1 refers to the leading variable action and Qk,i refers to accompanying
independent variable actions. In general the distinction between the two types of
actions will be obvious (see Figure 2.6); where it is not, each load should in turn be
treated as the leading action. Also the numerical values for partial factors given in the
UK National Annex[13a] are used in the equations above. The value of ψ0 depends on the <BS EN 1990
use of the building and should be obtained from the UK National Annex for BS EN 1990 A1.2.2, A1.3.1
(see Table 2.7). & NA>
The expressions take into account the probability of joint occurrence of loads by
applying the ψ0,i factor to the accompanying variable action. The probability that
these combined actions will be exceeded is deemed to be similar to the
probability of a single action being exceeded.
If the two independent variable actions Qk,1 and Qk,2 are associated with different
spans and the use of Exp. (6.10b) is appropriate, then in one set of analyses
1.25Gk + 1.5Qk,1 should be applied to the ‘Qk,1’ spans with 1.25Gk + ψ0,i 1.5Qk,2
applied to the ‘Qk,2’ spans. In associated analyses, 1.25Gk + ψ0,i 1.5Qk,1 should be
applied to the ‘Qk,1’ spans and 1.25Gk + 1.5Qk,2 to the ‘Qk,2’ spans. See Example
2.11.2 (2 variable actions).
There are three combinations of actions at SLS (or Load combination at SLS).
These are given in Table 2.8. The combination and value to be used depends on
the nature of the limit state being checked. Quasi-permanent combinations are <BS EN 1990 6.5, Table
associated with deformation, crack widths and crack control. Frequent A1.4>
combinations may be used to determine whether a section is cracked or not.
The numeric values of ψ 0, ψ 1 and ψ 2 are given in Table 2.7.
Table 2.8
Partial factors to be applied in the verification of the SLS
Combination Permanent actions Gk Variable actions Qk
Unfavourablea Favourablea Leadingb Othersb
Characteristic Gk,sup Gk,inf Qk,1 ψ0,iQk,i
Frequent Gk,sup Gk,inf ψ1,1Qk,1 ψ2,iQk,i
Quasi-permanent Gk,sup Gk,inf ψ2,1Qk,1 ψ2,iQk,i
Key
a Generally Gk,sup and Gk,inf may be taken as Gk. See Section 2.4
b ψ factors are given in Table 2.7
When the variation of a permanent action is not small then the upper (Gkj,sup)
and the (Gkj,inf) characteristic values (the 95 and 5 percentile values <BS EN 1990 4.1.2>
respectively) should be established. This procedure is only necessary when the <BS EN 1990 4.1.2 (3)>
coefficient of variation (= 100 × standard deviation/mean) is greater than 10. In
terms of permanent actions, variations in the self-weight of concrete in
concrete frames are considered small.
At ULS where the variation is not small, γGk,sup should be used with Gkj,sup and
γGk,inf with Gkj,inf. Similarly, where the variation is not small, at SLS Gkj,sup should
be used where actions are unfavourable and Gkj,inf used where favourable.
Where checks, notably checks on static equilibrium (EQU), are very sensitive to <BS EN 1990 6.4.3 (4)>
variation of the magnitude of a permanent action from one place to another the
favourable and unfavourable parts of this action should be considered as
individual actions. γG,sup and γG,inf should be used in such ‘very sensitive’
verifications.
For building structures, design concentrates mainly on the ULS, the ultimate
limit state of strength (STR), and SLS, the serviceability limit state. However, it <BS EN 1990 3.3, 3.4,
is essential that all limit states are considered. The limit states of equilibrium 6.5>.
(EQU), strength at ULS with geotechnical actions (STR/GEO) and accidental <BS EN 1990 6.4>.
situations must be taken into account as appropriate.
Note
Whilst the use of Exp. (6.10) is indicated, these arrangements may equally be used with Exp. (6.10a) or
(6.10b).
Figure 2.7
Load arrangements for beams and slabs according to UK NA
Figure 2.8
Continuous beam in a domestic structure
Actions: kN/m
Permanent action, gk
Self weight, 175 mm thick slabs = 26.3
E/o self weight downstand 800 × 225 = 4.5
50 mm screed @ 22 kN/m3 = 6.6
Finishes and services = 3.0
Dividing wall 2.40 × 4.42 (200 mm dense blockwork with plaster = 10.6
both sides) = 51.0
Total
Variable action, qk
Imposed, dwelling @ 1.5 kN/m2 = 9.0
Ultimate load, n
Assuming use of Exp. 6.10, n = 1.35 × 51 + 1.5 × 9.0 = = 82.4
Assuming use of worst case of Exp. (6.10a) or Exp. (6.10b)
Exp. (6.10a): n = 1.35 × 51 + 0.7 × 1.5 × 9.0 = = 78.3
Exp. (6.10b): n = 1.25 × 51 + 1.5 × 9.0 = = 77.3
In this case Exp. (6.10a) would be critical1 and ∴n = 78.3
Determine the various arrangements of actions and magnitude of actions for ULS
verification of a continuous beam supporting a 175 mm slab @ 6 m centres. Note <BS EN 1991-1-1
that the variable actions are from two sources: 6.3.1.1 & NA>
Office use: 2.5 kN/m2, ψ0 = 0.7;shopping use: 4.0 kN/m2, ψ0 = 0.7 < BS EN 1990
A.1.2.2. & NA>
1
This could also be determined from Figure 2.1 or by determining that gk > 4.5qk
a) Load combination
Load combination Exp. (6.10a) or Exp. (6.10b) will be used, as either will produce a smaller
total load than Exp. (6.10). It is necessary to decide which expression governs.
Actions: kN/m
Permanent action
As before, Example 2.8.1 = 51.0
Variable action
Office @ 2.5 kN/m2 = 15.0
Shopping @ 4.0 kN/m2 = 24.0
Ultimate load, n
For office use:
Exp. (6.10a): n = 1.35 × 51 + 0.7 × 1.5 × 15.0 = 84.6
Exp. (6.10b): n = 1.25 × 51 + 1.5 × 15.0 = 86.3
For shopping use:
Exp. (6.10a): n = 1.35 × 51 + 1.5 × 0.7 × 24.0 = 94.1
Exp. (6.10b): n = 1.25 × 51 + 1.5 × 24.0 = 99.8
b) Arrangement of actions
i) Actions
As the variable actions arise from different sources, one is a leading variable action and
the other is an accompanying variable action. The unit loads to be used in the various
arrangements are:
Actions: kN/m
Permanent
1.25 × 51.0 = 63.8
Variable
Office use
as leading action, γQQk = 1.5 × 15 = = 22.5
as accompanying action, ψ0γQQk = 0.7 × 1.5 × 15 = = 15.75
♣
This could also be determined from Figure 2.1 or by determining that gk < 4.5qk
Figure 2.10
For maximum bending moment in span AB
Figure 2.11
For maximum bending moment in span CD
The arrangement of loads is shown in Figure 2.12. As both spans AB and BC receive load < BS EN 1991 6.3.1.1 (10)
from the same source, no reduction is possible (other than that for large area2). & NA>
Figure 2.12
For maximum bending moment at support B
2
Variable actions may be subjected to reduction factors: αA, according to A area
supported (m2), αA = 1.0 – A / 1000 ≥ 0.75. < BS EN 1991-1-1 6.3.1.2 (10) & NA>
Figure 2.13
For maximum bending moment at support D
Figure 2.14
For curtailment and hogging in span CD
Eurocode 2 requires that all spans should be loaded with either γG,supp or γG,inf (as per Table <2.4.3(2)>
2.6). As illustrated in Figure 2.14, using γG,inf, = 1.0 might be critical for curtailment and
hogging in spans.
Figure 2.15
Propped cantilever beam and loading
Figure 2.16
EQU: maximum uplift at A
Note
γGk,inf gk = 1.0 gk may be critical in terms of curtailment of top bars BA.
Figure 2.17
ULS: maximum moment at B
Notes
1 Depending on the magnitude of gk, qk length AB and BC, γGkinf gk (= 1.0 gk) may be more critical
for span moment.
2 The magnitude of the load combination indicated are those for Exp. (6.10) of BS EN 1990. The
worse case of Exp (6.10a) and Exp (6.10b) may also have been used.
3: Presuming supports A and B were columns then the critical load combination for Column A
would be as Figure 2.18. For column B the critical load combination might be either as
Figure 2.17 or 2.18.
Figure 2.18
ULS: maximum span moment AB
Figure 2.19
SLS: maximum deformation at C
Note
Quasi-permanent load combinations may also be used for calculations of crack widths
or controlling cracking, i.e. the same load combinations as shown in Figures 2.19 and
2.20 may be used to determine SLS moment to determine stress in reinforcement. The
characteristic and/or frequent combinations may be appropriate for other SLS limit
states: for example, it is recommended that the frequent combination is used to
determine whether a member has cracked or not.
Figure 2.20
SLS maximum deformation AB
Figure 2.21
Frame configuration
Figure 2.23
Frame with roof variable action as leading variable action
Figure 2.24
Frame with wind as lead variable action
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
3 Slabs
3.1 General
The calculations in this section are presented in the following Sections:
3.2 A simply supported slab showing what might be deemed typical hand calculations.
3.3 A detailed version of the same simply supported slab but designed, and curtailment
lengths determined, strictly in accordance with the provisions of BS EN 1992–1–1.
3.4 A continuous ribbed slab designed, and curtailment lengths determined, strictly in
accordance with the provisions of BS EN 1992–1–1.
3.5 A bay of a flat slab.
They are intended to be illustrative of the Code and not necessarily best practice.
A 175 mm thick slab is required to support screed, finishes, an office variable action of 2.5
kN / m2 and demountable partitions (@ 2 kN / m). The slab is supported on load-bearing
block walls. fck = 30, fyk = 500. Assume a 50-year design life and a requirement for 1 hour
resistance to fire.
3.2.1 Actions
kN / m2
Permanent
Self-weight 0.175 × 25 = 4.4 <BS EN 1991-1-1 Table A1>
50 mm screed = 1.0
Finishes, services = 0.5
gk = 5.9
Variable
Offices, general use B1 = 2.5
Movable partitions @ 2.0 kN / m = 0.8 <BS EN 1991-1-1 Tables 6.1, 6.2
& NA>
qk = 3.3 <BS EN 1991-1-1, 6.3.1.2 (8)>
3.2.2 Cover
Nominal cover, cnom
3.2.4 Analysis
Design moment
MEd = 12.3 × 4.82 / 8 = 35.4 kNm
Shear force
V = 12.3 × 4.8 / 2 = 29.5 kN / m
3.2.6 Deflection
Check span-to-effective-depth ratio
Basic span-to-effective-depth ratio for ρ = 0.41% = 20 <Table 7.4N & NA>
As,prov / As,req = 645 / 599 = 1.08 <Exp. (7.17)>
Max. span = 20 × 1.08 × 144 = 3110 mm i.e. < 4800 mm ∴ no good
3.2.7 Shear
By inspection, OK
However, if considered critical
V = 29.5 kN / m as before
VEd= 29.5 ‒ 0.14 × 12.3 = 27.8 kN / m <6.2.1(8)>
vEd = 27.8 × 103 / 144 × 103 = 0.19 MPa
vRd,c =0.53 MPa <6.2.2(1), Concise Table 15.6>
∴ No shear reinforcement required
Figure 3.2
Simply supported slab: summary
Note
It is presumed that the detailer would take this design and detail the slab to normal best
practice, e.g. to SMDSC[21]. This would usually include dimensioning and detailing
curtailment, laps, U-bars and also undertaking the other checks detailed in Section 3.2.9.
( 0.15%)
∴ H12 @ 175 B1 OK
Crack control
OK by inspection <Table 7.2N & NA>
Curtailment main bars
Curtail main bars 50 mm from or at face of support. <SMDSC[21] Fig. 6.4; How to,
Detailing>
At supports
50% of As to be anchored from face of support <9.3.1.2.(1)>
Use H12 @ 350 B1 T1 U-bars
In accordance with SMDSC[21] detail MS3 lap U-bars 500 mm
with main steel, curtail T1 leg of U-bar 0.1l (= say 500 mm) from
face of support.
A 175 mm thick continuous slab is required to support screed, finishes, an office variable
action of 2.5 kN / m2 and demountable partitions (@ 2 kN / m). The slab is supported on
200 mm wide load-bearing block walls at 6000 mm centres. fck = 30, fyk = 500 and the design
life is 50 years. A fire resistance of 1 hour is required.
Figure 3.3
Continuous solid slab
3.3.1 Actions
kN / m2
Permanent
As Section 3.2 gk = 5.9
Variable
As Section 3.2 qk = 3.3 <BS EN 1991-1-1
6.3.1.2(8)>
3.3.2 Cover
Nominal cover, cnom
‡
A free unsupported edge is required to use ‘longitudinal and transverse reinforcement’ <9.3.1.4(1)>
generally using U-bars with legs at least 2h long. For slabs 150 mm deep or greater, SMDSC [21]
standard detail recommends U-bars lapping 500 mm with bottom steel and extending 0.1l top into
span.
3.3.4 Analysis
Clear span, lk = 5800
a1 = min[h / 2; t / 2] = min[175 / 2; 200 / 2] = 87.5 <5.3.2.2(1)>
a2 = min[h / 2; t / 2] = min[175 / 2; 200 / 2] = 87.5
leff = 5975
Bending moment
End span MEd = 0.086 × 12.3 × 5.9752 = 37.8 kNm / m <5.1.1(7), Concise Table 15.2>
1st internal support MEd = 0.086 × 12.3 × 5.9752 = 37.8 kNm / m <5.1.1(7), Concise Table 15.2>
Internal spans and supports
MEd = 0.063 × 12.3 × 5.9752 = 27.7 kNm / m <5.1.1(7), Concise Table 15.2>
Shear
End support VEd = 0.40 × 12.3 × 5.975 = 29.4 kN / m <5.1.1(7), Concise Table 15.2>
1st interior support VEd = 0.60 × 12.3 × 5.975 = 44.1 kN / m <5.1.1(7), Concise Table 15.2>
§
The use of Concise Table 15.2 implies certain amounts of redistribution which are defined in Concise
table 15.14.
3.3.8 Shear
Design shear force, VEd
At d from face of end support
VEd = 29.4 ‒ (0.144 + 0.0875) × 12.3 = 26.6 kN / m <6.2.1(8)>
At d from face of 1st interior support
VEd = 44.1 ‒ (0.144 + 0.0875) × 12.3 = 41.3 kN / m
Figure 3.4
Continuous solid slab: design summary
Note
It is presumed that the detailer would take this design and detail the slab to normal best practice. This would usually include rationalising,
dimensioning and detailing curtailment, laps, U-bars and also undertaking the other checks detailed in 3.3.10 to 3.3.14. The determination
of curtailment lengths, anchorages and laps is shown in detail using the principles in Eurocode 2. In practice these would be determined
from published tables of data or by using reference texts [12, 21].
d) Crack control
As slab < 200 mm, measures to control cracking are <7.3.3(1)>
unnecessary.
3.3.11 Curtailment
a) End span, bottom reinforcement
Assuming end support to be simply supported, 50% of As
should extend into the support. <9.3.1.2(1) >
50% × 639 = 320 mm2 / m
Try H12 @ 300 (376 mm2 / m) at supports
In theory, 50% curtailment of reinforcement may take place al <9.3.1.2(1) Note, 9.2.1.3 (2)>
from where the moment of resistance of the section with the
remaining 50% would be adequate to resist the applied
bending moment. In practice, it is usual to determine the
curtailment distance as being al from where MEd = MEd,max / 2.
Thus: for a single simply supported span supporting a UDL of n,
MEd,max = 0.086nl 2 ; RA = 0.4nl
At distance, X, from end support, moment,
MEd@X = RAX – nX 2 / 2
∴ when M@X = MEd,max / 2:
0.086nl 2 / 2 = 0.4nlX – nX 2 / 2
Assuming X = xl
0.043nl 2 = 0.4nlxl – nx 2 l 2 / 2
0.043 = 0.4x – x2 / 2
0 = 0.043 − 0.4x + x2 / 2
**
Detail MS2 of SMDSC[21], suggests 50% of T1 legs of U-bars should extend 0.3l (= say 1800 mm)
from face of support by placing U-bars alternately reversed.
††
Detail MS2 of SMDSC[21], suggests 50% of T1 legs of U-bars should extend 0.3l (= say 1800 mm)
from face of support by placing U-bars alternately reversed.
Figure 3.5
Curtailment of bottom reinforcement: actions, bending moments, forces in reinforcement and
curtailment
‡‡
Maximum z = 0.947 at mid span and greater towards support.
3.3.13 Laps
Lap H12 @ 300 U-bars with H12 @ 150 straights
Tension lap, l0 = α1 α2 α3 α5 α6 lb,rqd α l0min <Exp. (8.10)>
where
α1 = 1.0 (straight bars) <Table 8.2>
α2 = 1 − 0.15 (cd − φ) / φ
where
cd = min(pitch, side cover or cover) <Fig. 8.4>
= 25 mm
φ = bar diameter
= 12 mm
α2 = 0.84 <Table 8.2>
α3 = 1.0 (no confinement by reinforcement)
α5 = 1.0 (no confinement by pressure)
α6 = 1.5 <Table 8.3>
<Exp. (8.3)>
lb,rqd = (φ / 4) σsd / fbd
where
Figure 3.6
Continuous solid slab: reinforcement details
Figure 3.8
Continuous ribbed slab example
This 300 mm deep ribbed slab is required for an office to support a variable action of 5 kN / m2.
It is supported on wide beams that are the same depth as the slab, as shown in Figure 3.9.
Figure 3.9
Long section through slab
One hour fire resistance required: internal environment. Ribs are 150 mm wide @ 900 mm
cc. Links are required in span to facilitate prefabrication of reinforcement. Assume that
Using UDLs simplifies the analysis and remains popular. One method is to ignore the
weight of the solid part of the slab in the analysis of the ribbed slab (and the weight of
the solid area added to the supporting beam actions). This ignores the effect the solid
areas have on bending in the ribbed slab.
Alternatively the weight of the solid part of the slab is spread as a UDL over the whole
span. This is conservative both in terms of moment and shears at solid/shear interfaces
but underestimates hogging in internal spans.
The advent of computer analysis has made analysis using patch loads more viable and
the resulting analysis more accurate.
The ribbed part of the slab may be designed to span between solid areas. (The ribs span
d / 2 into the solid areas which are assumed to act as beams in the orthogonal
direction.) However, having to accommodate torsions induced in supporting beams and
columns usually makes it simpler to design from centreline of support to centreline of
support.
Analysis programs can cope with the change of section and therefore change of stiffness
along the length of the slab. Moments would be attracted to the stiffer, solid parts at
supports. However, the difference in stiffnesses between the ribbed and the solid parts
is generally ignored.
In line with good practice analysis, this example is carried out using centreline of support to
centreline of support and patch loads§§. Constant stiffness along the length of the slab has
been assumed.
3.4.1 Actions
Permanent: UDL kN / m2
Self-weight:
Rib 0.15 × 0.2 × 25 / 0.9 = 0.833
Slope 2 × (1 / 2) × 0.2 / 10 × 0.2 × 25 / 0.9 = 0.112
Slab 0.1 × 2.5 = 2.500
Cross rib 0.19 × 0.71 × 0.2 × 25 / (0.9 × 7.5) = 0.100
Total self-weight = 3.545 3.55
Ceiling 0.15
Services 0.30
Raised floor 0.30
Total permanent actions = 4.30
§§
In this case, assuming the patch load analysis is accurate, assuming the weight of solid area is
spread over the whole span would overestimate span and support moments by 6 – 8% and shears at
the solid/rib interface by 8 – 9%. Ignoring the weight of the solid area in the analysis of this ribbed slab
would lead to underestimates of span moments by 1%, support moments by 3% and no difference in
the estimation of shear at the solid shear interface. This may have been the preferred option!
3.4.2 Cover
Nominal cover, cnom
Figure 3.10
Section AA: section through ribbed slab
Arrangement
Choose to use all-and-alternate-spans-loaded <5.1.3(1) & NA option b>
3.4.4 Analysis
Analysis by computer, includes 15% redistribution at support and <BS EN 1990 A1.2.2
none in the span.*** & NA, 5.3.1 (6)>
Figure 3.11
Bending moment diagrams
Figure 3.12
Redistributed shears, kN / m
At solid/rib interface
AB @ 550 mm from A
MEd (sagging) = 20.4 kNm / m ≡ 18.3 kNm / rib
VEd = 32.5 kN / m ≡ 29.3 kN / rib
***
Note 1: A ribbed slab need not be treated as discrete elements provided rib spacing ≤ 1500 mm, depth of
the rib ≤ 4 × its width, the flange is > 0.1 × distance between ribs and transverse ribs are provided at
a clear spacing not exceeding 10 × overall depth of the slab.
Note 2: As 7.5 m < 85% of 9.0 m, coefficients presented in Concise Eurocode 2[10] are not applicable.
K = MEd / bd2fck
where
b = 900 mm
d = 300 − 25 – 8 – 20 / 2 = 257
assuming 8 mm link at H20 in span
fck = 35
= 55.5 × 106 / (900 × 2572 × 35) = 0.027
K′ = 0.207 <Appendix A1>
or restricting x / d to 0.45
K′ = 0.168
K ≤ K′ ∴ section under-reinforced and no compression
reinforcement required.
z = (d / 2) [1 + (1 − 3.53K)0.5] ≤ 0.95d <Appendix A1>
= (257 / 2) (1 + 0.951) ≤ 0.95 × 257
= 251 ≤ 244 ∴ z = 244 mm
But z = d – 0.4x <Appendix A1>
∴ x = 2.5(d − z) = 2.5(257 − 244) = 33 mm
∴ By inspection, neutral axis is in flange
As = MEd / fydz
where
fyd = 500 / 1.15 = 434.8 MPa
= 55.5 × 106 / (434.8 × 244) = 523 mm2 / rib
Try 2 no.H20 / rib (628 mm2 / rib)
Span AB - Deflection
Allowable l / d = N × K × F1 × F2 × F3 <Concise Sec. 15.7>
where
N = Basic l / d: check whether ρ > ρ0 and whether to <7.4.2(2)>
use Exp. (7.16a) or Exp. (7.16b)
ρ0 = fck0.5 / 1000 = 350.5 / 1000 = 0.59%
ρ = As / Ac††† = As,req / [bwd + (beff − bw)hf] <PD 6687>
where
bw = min. width between tension and compression
chords. At bottom assuming 1 / 10 slope to rib:
= 150 + 2 × (25 + 8 + 20 / 2) / 10
= 159 mm
Section 2.18 of PD 6687 [5] suggests that ρ in T-beams should be based on the area of concrete
†††
‡‡‡
In analysis, 15% redistribution of support moments led to redistribution of span moments:
δ = 61.7 / 65.3 = 0.94
§§§
Both As,prov / As,req and any adjustment to N obtained from Exp. (7.16a) or Exp. (7.16b) is restricted
to 1.5 by Note 5 to Table NA.5 in the UK NA. Therefore, 310 / σs is restricted to 1.5.
****
An alternative method would have been to calculate the reinforcement required to resist MEd at the
shift distance, al, from the interface
Figure 3.14
Section through rib
††††
Both As,prov / As,req and any adjustment to N obtained from Exp. (7.16a) or Exp. (7.16b) is restricted
to 1.5 by Note 5 to Table NA.5 in the UK NA.
Figure 3.15
Summary of design
(0.17%)
∴ Use A142 in flange (say OK) <BS 8666[28]>
b) Secondary reinforcement
Not applicable
d) Crack control
Loading is the main cause of cracking ∴ use Table 7.2N or <7.3.3(2)
Table 7.3N for wmax = 0.3 mm and max. σs = 200 MPa (see 7.3.1.5>
deflection check)
Max. bar size = 25 mm <Table 7.2N>
or max. spacing = 250 mm <Table 7.3N>
OK by inspection.
e) Effects of partial fixity
Assuming partial fixity exists at end supports, 15% of As is <9.3.1.2(2)>
required to extend 0.2 × the length of the adjacent span.
As,req = 15% × 525 = 79 mm2 / rib
For the rib in tension:
As,min = 0.26 × 0.30 × 300.666 × 159 × 257 / 500 = 55 mm2 / rib
3.4.11 Curtailment
Wherever possible simplified methods of curtailing reinforcement would be followed. The
following is intended to show how a rigorous assessment of curtailment of
reinforcement might be undertaken.
End support A: bottom steel at support
Check anchorage
As simply supported, 25% of As should be anchored in support. <9.3.1.1(4), 9.3.1.2(1) & Note,
25% × 595 = 148 mm2 9.2.1.4(1) & NA>
Use 1 no.H20 / rib (314 mm2 / rib)
Check anchorage length
Envelope of tensile force:
To resist envelope of tensile force, provide reinforcement to al <9.3.1.1(4), 9.2.1.3(1), 9.2.1.3(2),
or lbd beyond centreline of support. 9.2.1.3(3) Fig. 9.2>
For members without shear reinforcement, al = d = 232 <9.2.1.3>
By inspection, σsd = 0, lbd = lbd,min = max(10φ, 100 mm)
Indirect support:
As anchorage may be measured from face of indirect support, <9.3.1.1(4), 9.2.1.4(2), 9.2.1.4(3),
check, force to be resisted at solid/rib interface: Fig. 9.3b>
Fs = MEd / z + FE
Anchorage length
lbd = αlb,rqd ≥ lb,min <8.4.4, Exp. (8.4)>
where:
α = conservatively 1.0
lb,rqd = (ϕ / 4) (σsd / fbd) <Exp. (8.3)>
where
ϕ = 20
σsd = design stress in the bar at the ULS
= 121.1 × 1000 / 314 = 385 MPa
fbd = ultimate bond stress
= 2.25 η1 η2 fct,d <8.4.2 (2)>
where
η1 = 1.0 for good bond conditions
η2 = 1.0 for bar diameter ≤ 32 mm
<3.1.6 (2),Tables 3.1 and 2.1 and
fct,d = αct fct,k / γc
NA>
= 1.0 × 2.2 / 1.5
= 1.47 MPa
fbd = 2.25 × 1.47 = 3.31 MPa
∴ lb,rqd = (20 / 4) (385 / 3.31) = 581 mm <Fig. 9.3>
lb,min = max[10ϕ; 100 mm] = 200 mm
∴ lbd= 581 mm measured from solid/rib intersection.
i.e. 31 mm beyond centreline of support‡‡‡‡.
End support A: top steel
Assuming partial fixity exists at end supports, 15% of As is required <9.3.1.2(2)>
to extend at least 0.2 × the length of the adjacent span§§§§.
As,req = 15% × 525 = 79 mm2 / rib
As,min = 0.26 × 0.30 × 350.666 × 159 × 257 / 500 = 68 mm2 / rib <9.3.1.1
9.2.1.1(1), Exp. (9.1N)>
Use 2 no. H12 T1 / rib in rib and 2 H10 T1 / rib between ribs
(383 mm2 / rib)
Support B (and C): top steel
At the centreline of support (2 H16 T + 3 H12 T) / rib are
required. The intention is to curtail in two stages, firstly to 2
H16 T / rib then to 2 H12 T / rib.
Curtailment of 2 H16 T / rib at support (capacity of 2 H12 T / rib + shift rule)
‡‡‡‡
Whilst this would comply with the requirements of Eurocode 2, it is common practice to take
bottom bars 0.5 × a tension lap beyond the centreline of support (= 250 mm beyond the centreline of
support; see MS1 in SMDSC[21]).
§§§§
It is usual to curtail 50% of the required reinforcement at 0.2l and to curtail the remaining 50%
at 0.3l or line of zero moment (see MS2 in SMDSC[21]).
Figure 3.16
Curtailment of top reinforcement at B per rib
3.4.12 Laps
At AB, check lap 1 no.H20 B to 2 no.H20 B in rib full tension lap
l0 = α1 α6 lb,rqd > l0,min <Exp. (8.10)>
where
α1 = 1.0 (cd = 45 mm, i.e. < 3ϕ) <Table 8.2>
α6 = 1.5 (as > 50% being lapped)
lb,rqd = (ϕ / 4) (σsd / fbd)
where
ϕ = 20
σsd = 434.8
fbd = 3.0 MPa as before
l0,min = max. 10ϕ or 100 = 200 Exp. (8.6)
l0 = 1.0 × 1.5 × (20 / 4) × 434.8 / 3.0
= 1087 mm, say = 1200 mm <SMDSC[21]>
At BA and BC, check lap 2 no. H12 T to 2 no. H16 T in rib – full tension lap
l0 = α1 α6 lb,rqd > l0,min <Exp. (8.10)>
where
α1 = 0.7 (cd = 45 mm, i.e. > 3ϕ) <Table 8.2>
α6 = 1.5 (as > 50% being lapped)
lb,rqd = (ϕ / 4) (σsd / fbd)
where
ϕ = 12
σsd = 434.8
fbd = 2.1 (3.0 MPa as before but η1 = 0.7 for not <8.4.2 (2)>
good bond conditions)
l0,min = max. 10ϕ or 100 = 120 Exp. (8.6)
Figure 3.17
Curtailment of flexural reinforcement in ribbed slab
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
3.5 Flat slabs
This example is for the design of a reinforced concrete flat slab without column heads. The slab is part of
a larger floor plate and is taken from Guide to the design and construction of reinforced concrete flat
slabs[29], where finite element analysis and design to Eurocode 2 is illustrated. As with the Guide, grid line
C will be designed but, for the sake of illustration, coefficients will be used to establish design moments
and shears in this critical area of the slab.
The slab is for an office where the specified load is 1.0 kN / m2 for finishes and 4.0 kN / m2 imposed (no
partitions). Perimeter load is assumed to be 10 kN / m. Concrete is C30 / 37. The slab is 300 mm thick
and columns are 400 mm square and extend 4.5 m above and below. A 2 hour fire rating is required.
Figure 3.18
Part plan of flat slab
3.5.1 Actions
kN / m2
Permanent
Self-weight 0.30 × 25 7.5 <BS EN 1991-1-1 Table A1>
Finishes 1.0 <specified>
gk = 8.5
Variable
Offices
qk = 4.0 <specified & BS EN 1991-1-1 6.3.1.2(8)>
Figure 3.19
Panel centred on grid C
Ultimate load, n
By inspection, Exp. (6.10b) is critical. <Fig. 2.5>
n = 1.25 × 8.50 + 1.5 × 4.0 = 16.6 kN / m2 <BS EN 1990 Exp. (6.10b)>
Arrangement
Choose to use all-and-alternate-spans-loaded load cases and coefficients ‡‡. <5.1.3(1) & NA option b>
‡‡
The all-spans-loaded case with 20% redistribution of support moments would also have <5.3.1 & NA> been
acceptable but would have involved some analysis. The use of Table 5.9 in BS EN 1992–1–2 (Fire resistance of solid
flat slabs) is restricted to where redistribution does not exceed 15%: The coefficients presume 15% redistribution at
supports. <Concise Table 15.3>
Figure 3.20
Column and middle strips
Percentages
Column strip Middle strip
-ve (hogging) Long span = 70%§§ Long span = 30% <Table I.1, CS Flat slab
Short span = 75% Short span = 25% guide[29]>
+ve (sagging) 50% 50% <Table I.1>
Parallel to grid C, column strip is ly / 2 = 3 m wide. The middle strip is also 3 m wide. <NA.3[1a], Fig. I.1>
MEd
Column strip, 3 m wide Middle strip, 3 m wide
-ve (hogging) 0.70 × 952.8 / 3.0 = 222.3 kNm / m 0.30 × 952.8 / 3.0 = 95.3 kNm / m
+ve (sagging) 0.50 × 842.7 / 3.0 = 140.5 kNm / m 0. 50 × 842.7 / 3.0 = 140.5 kNm / m
§§
The Concrete Society Guide[29] recommends a percentage, k1, based on Lx / Ly Assuming Lx / Ly = 1.5 the distribution
of moments in the long span between column strips and middle strips is given as 70% and 30%.
♣
As punching shear force (rather than a beam shear force) ‘effective’ span is not appropriate.
***
Cladding and strip of slab beyond centre of support.
†††
Otherwise for flat slabs 8.5 / 9.5 = 0.89 as span > 8.5 m. <7.4.2(2)>
‡‡‡
In line with Note 5 to Table NA.5, 1.50 is considered to be a maximum for 310 / σs.
§§§
Note: Continuity into columns will reduce sagging moments and criticality of deflection check (see Section 3.5.14).
****
Note requirement for at least 2 bars in bottom layer to carry through column <9.4.1(3)>
††††
The hogging moment could have been considered at face of support to reduce the amount of reinforcement
required.
Figure 3.21
Edge panel on grid 1 (grid 3 similar)
Actions
Permanent from slab gk = 5 × 8.5 kN / m2 = 42.5 kN / m
Variable from slab qk = 5 × 4.0 kN / m2 = 20.0 kN / m
Percentages
Column strip, 1.7 m wide Middle strip <Table I.1, CS Flat slab guide [29]>
-ve (hogging) Short span = 75% Short span = 25%
+ve (sagging) 50% 50%
Short span moments:
MEd
Column strip, 1.7 m wide Middle strip, 3.3 m wide
-ve (hogging) (0.75 × 248.5 + 37.4) / 1.70 0.25 × 248.5 / 3.3
= 131.6 kNm / m = 18.8 kNm / m
+ve (sagging) (0.50 × 248.5 + 37.4) / 1.70 0.50 × 248.5 / 3.3
= 95.1 kNm / m = 37.6 kNm / m
(ρ = 0.15%)
Use H12 @ 300 T2 (376 mm2 / m)
‡‡‡‡
The hogging moment could have been considered at face of support to reduce the amount of reinforcement required. This
should be balanced against the effect of the presence of a 200 × 200 hole at some supports which would have the effect of
increasing K but not unduly increasing the total amount of reinforcement required in the column strip (a 1.5% increase in
total area would been required).
Figure 3.22
Internal panel on grid 2
Ultimate load, n
By inspection, Exp. (6.10b) is critical. <Fig. 2.5>
n = 1.25 × 77.4 + 1.5 × 36.4 = 151.4 kN / m <BS EN 1990 Exp. (6.10b)>
MEd
Column strip, 3.0 m wide Middle strip, 6.1 m wide
-ve (hogging) 0.75 × 453.2 / 3.0 0.25 × 453.2 / 6.1
= 113.3 kNm / m = 18.5 kNm / m
+ve (sagging) 0.50 × 453.2 / 3.0 0.50 × 453.2 / 6.1
= 75.5 kNm / m = 37.1 kNm / m
Punching shear force, VEd, as before
§§§§
The hogging moment could have been considered at face of support to reduce the amount of reinforcement
required.
*****
Column C2 is taken to be an internal column. In the case of a penultimate column, an additional elastic reaction factor
should have been considered.
†††††
At the perimeter of the column, vRd,max assumes the strut angle is 45°, i.e, that cot θ = 1.0.
Where cot θ = < 1.0, vRd,max is available from Concise EC2[10] Table 15.7.
Perimeter required such that punching shear links are no longer required: <Exp. (6.54)>
uout = VEd × β / (d × vRd,c)
uout = 1204.8 × 1.15 × 103 / (250 × 0.61) = 9085 mm
The values used here for ρlx, ρly ignore the fact that the reinforcement is concentrated over the support.
‡‡‡‡‡
Considering the concentration would have given a higher value of VRdc at the expense of further calculation to
determine ρlx, ρly at 3d from the side of the column.
§§§§§
vRd,c for various values of d and ρl is available from Concise EC2[10] Table 15.6.
******
Clause 6.4.5 provides Expression (6.52), which by substituting vEd for vRd,c, allows calculation of the area of required shear
reinforcement, Asw, for the basic control perimeter, u1. This should be considered as the required density of shear reinforcement. The
Check shear stress at basic perimeter u1 (2.0d from face of column) <6.4.2>
vEd = βVEd / u1d < vRd,c
where
β, VEd and d as before
u1 = control perimeter under consideration. <Fig. 6.15>
For punching shear at 2d from edge column
columns u1 = c2 + 2c1+ π × 2d = 2771 mm
vEd = 1.4 × 609.5 × 103 / 2771 × 250 = 1.23 MPa
vRd,c = 0.18 / γc × k × (100 ρlfck)0.333 <Exp. (6.47) & NA>
where
γc = 1.5
k = as before = 1 +(200 / 250)0.5 = 1.89
ρl = (ρlxρly)0.5
where <6.4.4.1(1)
ρlx, ρly = areas of bonded steel in a width of the column
plus 3d each side of column.
ρlx = (perpendicular to edge) 10 no.H20 T2 + 6 no. H12
T2 in 2 × 750 + 400, i.e. 3818 mm2 in 1900 mm.
ρlx = 3818 / (250 × 1900) = 0.0080
ρly = (parallel to edge) 6 no. H20 T1 + 1 no. T12 T1 in
400 + 750 i.e. 1997 mm2 in 1150 mm. ρlY = 1997 /
(250 × 1150) = 0.0069
ρl = (0.0080 × 0.0069)0.5 = 0.0074
area of shear reinforcement required for any other perimeter should be based on this value, Asw / u1 together with the
requirements for minimum reinforcement and spacing of shear reinforcement (see Clause 9.4.3).
Figure 3.23
Flexural tensile reinforcement adjacent to columns C1 (and C3)
††††††
vRd,c for various values of d and ρl is available from Concise EC2[10] Table 15.6.
Check shear stress at basic perimeter u1 (2.0d from face of column) <6.4.2>
vEd = βVEd / u1d < vRdc
where
β, VEd and d as before
u1 = control perimeter under consideration. For <Fig. 6.15>
punching shear at 2d from edge column columns u1
= c2 + 2c1+ π × 2d = 2771 mm
Allowing for hole
200 / (c1 / 2): x / ( c1 / 2 + 2d) <Fig. 6.14>
200 / 200: x / ( 200 + 500)
∴ x = 700 mm
u1 = 2771 – 700 = 2071 mm
vEd = 1.4 × 516.5 × 103 / 2071 × 250 = 1.40 MPa
vRd,c = 0.18 / γc × k × (100 ρlfck)0.333 <Exp. (6.47) & NA>
where
γc = 1.5
k = as before = 1 + (200 / 250)0.5 = 1.89
ρl = (ρlxρly)0.5
where
ρlx, ρly = areas of bonded steel in a width of the column plus 3d <6.4.4.1(1)
each side of column.
ρlx = (perpendicular to edge) 8 no.H20 T2 + 6 no.H12 T2 in
2 × 720 + 400 − 200, i.e. 3190 mm2 in 1640 mm.
ρlx = 3190 / (240 × 1640) = 0.0081
ρly = (parallel to edge) 6 no.H20 T1 (5 no. are effective)
+ 1 no. T12 T1 in 400 + 750 – 200, i.e. 1683 mm2 in 950 mm.
ρlY = 1683 / (260 × 950) = 0.0068
ρl = (0.0081 × 0.0068)0.5 = 0.0074
fck = 30
vRd,c = 0.18 / 1.5 × 1.89 × (100 × 0.0074 × 30)0.333 = 0.64 MPa <Concise EC2 Table 15.6‡‡‡‡‡‡>
‡‡‡‡‡‡
vRd,c for various values of d and ρl is available from Concise EC2 [10] Table 15.6
Figure 3.24
Flexural tensile reinforcement adjacent to columns D1 and D3
Perimeter required where punching shear links no longer required <Exp. (6.54)>
uout = 516.5 × 1.4 × 10 / (250 × 0.64) = 4519 mm
3
Shear reinforcement:
As before, sr max. = 175 mm; st max. = 350 mm and fywd,ef = 312 MPa <9.4.3(1) 9.4.3(2)>
For perimeter u1
Asw ≥ (vEd – 0.75vRd,c) sr u1 / 1.5fywd,ef) per perimeter <Exp. (6.52)>
= (1.40 – 0.75 × 0.64) × 175 × 2071 / (1.5 × 312) = 712 mm2 per perimeter
Asw,min ≥ 0.08 × 300.5 (175 × 350) / (1.5 × 500) = 36 mm2
Asw / u1 ≥ 712 / 2071 = 0.34 mm2 / mm
Using H8 (50 mm2) max. spacing = min[50 / 0.3; 1.5d]
= min[147; 375] = 147 mm cc No good
Try using H10, max. spacing = 78.5 / 0.34 = 231 mm cc, say 175 cc
∴ Use min. H10 (78.5 mm2) legs of links at 175 mm cc around perimeters
perimeters at 175 mm centres
Check min. 9 H10 legs of links (750 mm2) in perimeter u1, 2d from column face.
Note: As the requirement for these columns is for H10 links
change ALL links to H10 to avoid potential problems on site
Interior support:
Column strip centre: H20 @ 200 T2* H16
Column strip outer: @ 250 T2
Middle strip: H12 @ 300 T2
Punching shear
Internal (e.g. at C2):
Use H10 legs of links in perimeters at max. 175 mm centres.
Max. tangential spacing of legs of links, st max. = 270 mm
Last perimeter, from column face, min. 767 mm
Edge (e.g. at C1, C3 assuming no holes):
Use H10 legs of links in perimeters at max. 175 mm centres.
Max. tangential spacing of legs of links, st max. = 175 mm
Last perimeter, from column face, min. 940 mm
Edge (e.g. at D1, D3 assuming 200 × 200 hole on face of column):
Use H10 legs of links in perimeters at max. 175 mm centres.
Max. tangential spacing of legs of links, st max. = 175 mm
Last perimeter, from column face, min. 1123 mm
Note
* rationalise centre of bars in column strips T2 and B2 to 175 mm centres to suit punching shear links.
Figure 3.26
Punching shear links at column C2 (102 no links) (column D2 similar)
Method of analysis
The use of coefficients in the analysis would not usually be advocated in the design of such a
slab. Nonetheless, coefficients may be used and unsurprisingly, their use leads to higher
design moments and shears, as shown below.
These higher moments and shears result in rather more reinforcement than when using other
more refined methods. For instance, the finite element analysis used in Guide to the design
and construction of reinforced concrete flat slabs[29] for this bay, leads to:
H16 @ 200 B1 in spans 1-2 (cf. H20 @ 200 B1 using coefficients),
H20 @ 125 T1 at support 2 (cf. H20 @ 100 T1 using coefficients) and
3 perimeters of shear links at C2 for VEd = 1065 kN (cf. 5 perimeters using coefficients)
2 perimeters of shear links at C3 (cf. 7 perimeters using coefficients)
Shear reinforcement
H10 punching shear links are required for columns D1 and D3. Whilst the other columns were
found to require only H8s, H10s have been adopted throughout to avoid confusion in
detailing or on site. The cost differential would have been marginal.
With added area, the numbers of links could have been reduced on the other columns. A
rectangular arrangement (300 × 175 grid) of H10 links would have been possible. However,
as the grid would need to change orientation around the columns and as the reinforcement
in B2 and T2 is essentially at 175 centres, it is considered better to leave the regular square
grid arrangement.
Use of shear reinforcement in a radial arrangement, e.g. using stud rails, would have
simplified the shear reinforcement requirements.
Curtailment of reinforcement
In this design, the reinforcement would be curtailed and this would be done either in line
with previous examples or more practically in line with other guidance [20, 21].
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
6 Walls
6.1 General
Walls are defined as being vertical elements whose lengths are four times greater than
their thicknesses. Their design does not differ significantly from the design of columns in
that axial loads and moments about each axis are assessed and designed for.
Generally, the method of designing walls is as follows:
1. Determine design life. <BS EN 1990 & NA Table NA 2.1>
2. Assess actions on the column. <BS EN 1991 (10 parts) & UK
NAs>
3. Determine which combinations of actions <BS EN 1990 & NA Tables NA
apply. A1.1 & NA A1.2(B)>
4. Assess durability requirements and determine <BS 8500–1>
concrete strength.
5. Check cover requirements for appropriate fire <Approved Document B
resistance period. BS 1992–1–2>
6. Determine cover for fire, durability and bond. <BS EN 1992–1–1 Cl. 4.4.1>
7. Analyse structure for critical combination <BS EN 1992–1–1 Section 5>
moments and axial forces.
8. Check slenderness and determine design <BS EN 1992–1–1 Section 5.8>
moments.
9. Determine area of reinforcement required. <BS EN 1992–1–1 Section 6.1>
10. Check spacing of bars <BS EN 1992–1–1 Sections 8 & 9>
Example 6.2 shows the design of a simple linear shear wall as typically used in medium rise
buildings. Similar principals may be applied to walls that are shaped as C, L, T, Z and rectangles
in-plan but issues of limiting flange dimensions and shear at corners need be addressed. The
example shows only ULS design as, apart from minimum areas of steel to control cracking, SLS
issues are generally non-critical in medium-rise structures. For shear walls in high-rise
structures, reference should be made to specialist literature (ref to CIRIA R102 Design of shear
wall buildings).
Figure 6.1
Typical floor plan
Qk = αn × 196.1
where
αn = 1.1 – n / 10
where
n =no. of storeys qualifying for reduction* <BS EN 1991-1-1 6.3.1.2(11) & NA>
=3
= 1.1 – 3 / 10 = 0.8
∴Qk = 0.8 × 196.1 = 156.9 kN Qk /m = 156.9 / 4.4 = 35.7 kN /m
Check relative stiffness of lift shaft and wall A to determine share of load on wall A.
Lift shaft: ILS = 2.44 / 12 – 2.04 / 12 – 0.2 × 1.63 / 12
= 1.36 m4
Wall A: IWallA = 0.2 × 4.43 / 12
= 1.41 m4
∴ Wall A takes = 1.41 / (1.41 + 1.36) = 51% of wind load.
Check shear centre to resolve the effects of torsion.
Determine centre of reaction of lift shaft
Area x Ax
2.4 × 2.4 = 5.76 1.2 6.912
–2.0 × 2.0 = –4.00 1.2 –4.800
–1.6 × 0.2 = –0.32 2.3 –0.732
1.44 1.38
*
Includes storeys supporting Categories A (residential & domestic), B (office), C (areas of
congregation) and D (shopping) but excludes E (storage and industrial), F (traffic), G (traffic) and H
(roofs).
†
Assuming centreline of wall A is 50 mm to right hand side of grid.
‡
For medium rise shear walls there are a number of methods of design. Cl. 9.6.1 suggests strut-and-
tie (see Section xx). Another method [ref to Concrete Buildings Design manual] is to determine elastic
tensile and compression stresses from NEd/bL +/– 6MEd/bL2 and determine reinforcement
requirements based on those maxima. The method used here assumes a couple, consisting of 1.0 m of
wall either end of the wall. The reinforcement in tension is assumed to act at the centre of one end and
the concrete in compression (with a rectangular stress distribution) acts at the centre of the other
end. The forces generated by the couple add or subtract from the axial load in the 1 m ends of the
walls. The method is useful for typical straight shear walls of say 2.5 to 5.0 m in length.
§
As Hi derives mainly from permanent actions its resulting effects are considered as being a
permanent action too.
Figure 6.8 Plan of wall A and location of sections Figure 6.9 Section A – A
A – A and B – B
Section A – A @ 1st floor.
The slab frames into the wall. For the purposes of assessing fixed end moments, the width of slab
contributing to the moments in the wall is assumed to be the length of the wall plus distances half
way to adjacent supports either end. Therefore, consider the fixed end moment for 1.50/2 + 4.40 +
1.30/ 2 = 5.8 m width of adjoining slab framing into the 4.4 m long shear wall (see Figure 6.8).
**
FEM Fixed End Moment for 1 m width of adjoining slab.
FEM
Assuming variable action is a leading action:
= 302.8 / 2 = 151.4 kNm
kw =I/l
= 2200 × 2003 / (12 × 1650) = 8.88 × 105
††
Ignoring effect of landing.
‡‡
Assuming wind load is lead variable action.
§§
Strictly incompatible with Qk = 0. However, allow Qk= 0.
Figure 6.12 Stresses and strains in wall subject to tension and out of plane moment
Restoring moment
Mk = (1021.0 + 5.0 x 1.2 x 0.9 x 25 + 0 x 225.1 ) x (0.3 + 2.2)
= 2890 kNm
At ULS of EQU,
Overturning moment
= fn(γQ,1Qk1 + γG,supGk) <BS EN 1990 Table
= 1.5 x 1057.5 + 1.1 x 211.0 = 1818.4 kNm A1.2(A) & NA>
Restoring moment
= fn(γG,infGk) <BS EN 1990 Table
= 0.9 x 2890 = 2601 kNm i.e. > 1818.4 kNm A1.2(A) & NA>
∴ OK
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
5 Columns
5.1 General
The calculations in this section illustrate:
5.2 Design of a non-slender column using design charts.
5.3 Design of a perimeter column using iteration of equations to determine reinforcement
requirements.
5.4 Design of an internal column with high axial load.
5.5 Design of a slender column requiring a two hour fire resistance.
In general axial loads and first order moments are assumed to be available. The designs
consider slenderness in order to determine design moments, MEd. The columns are designed
and checked for biaxial bending. The effects of allowing for imperfections are illustrated.
A general method of designing columns is as follows:
Figure 5.1
Forces in edge column
*
Effective lengths are covered in Eurocode 2 Section 5.8.3.2 and Exp (5.15). The effective length of most columns
will be l/2< l0 < l < Figure 5.7f)>. PD 6686[ref to] Cl 2.10 suggests that using the procedure outlined in
Eurocode 2 and <5.8.3.2(3) 5.8.3.2(5)> leads to similar effective lengths to those tabulated in BS 8110[ref
to] and reproduced in Table 5.1 of Concise EC2. For simplicity tabular values are used in this example. However,
experience suggests that these tabulated values are conservative.
a = 1.48 by interpolating between values given for NEd / NRd= 0.1 ,(1.0) and NEd / <5.8.9(4), Notes to
NRd = 0.7, (1.5) Exp. (5.39)>
(MEdz / MRdz)a + (MEdy / MRdy)a = (38.5 / 76.1)1.48 + (32.4 / 76.1)1.48 <Exp. (5.39)>
= 0.36 + 0.28
= 0.64 ∴ OK.
∴ 4 no. H25 OK.
Figure 5.2
Design summary: edge column
5.3.1 Cover
cnom = cmin + Δcdev <Exp. (4.1)>
where
cmin = max[cmin,b, cmin,dur]
where
cmin,b = diameter of bar. Assume 32 mm bars and 8 mm links <4.4.1.2(3)>
= 32 mm to main bars, 32 − 8 = 24 mm to links
= say 25 mm
cmin,dur = minimum cover due to environmental conditions. Assume XC1.
cmin,dur = 15 mm
cmin = 25 mm
Δcdev = 10 mm <4.4.1.3(3)>
Therefore cnom = 25 + 10 = 35 mm to links cnom= 35 mm to links
Check validity of using Method B and Table 5.2b: <BS EN 1992–1–2: 5.3.3>
emax = 0.25b = 75 mm ∴ no good.
Use BS EN 1992–1–2 Annex C Tables C1 – C9. <BS EN 1992–1–2: Annex C>
2 †
Assume min. 4 no. H25 = 1964 mm (≡ 2.2%)
ω = Asfyd / Acfcd = 0.022 × (500 / 1.15) / (0.85 × 30 / 1.5) <BS EN 1992–1–2: 5.3.3(2)>
= 0.56
e ≈ 0.25b and ≤ 100 mm
λ = l0 / i <BS EN 1992–1–2: 5.3.3(2),
where 5.3.3(3)>
l0 = 0.7 × 3.325 = 2327 mm
i = radius of gyration = (I / A)0.5 = h / 120.5
= 300 / 120.5 = 87 mm
λ = 2327 / 87 = 276
n = N0Ed,fi / 0.7(Acfcd + Asfyd) <BS EN 1992–1–2: 5.3.3(2)>
= 0.7 × 1129.6 / 0.7(3002 × 0.85 × 30 / 1.5 + 1964 × 500 / 1.15)
= 1129.6 / 2383.9
= 0.47
∴ interpolate for λ = 30 and n = 0.47 between
Table C5 (ω = 0.5, e = 0.25b) ⇒ bmin = 235, a = 35 mm
†
Using 4 no. H20 gives ω = 0.34, n = 0.54 and bmin = 310 mm ∴ no good!
‡
See Section 5.2.1
§
The effects of imperfections need only be taken into account in the most unfavourable direction.
<5.8.9(2)>
Figure 5.4
Section in axial compression and bending <Fig. 6.1>
Figure 5.5
Design summary: perimeter column
The suspended slabs (including the ground floor slab) are 300 mm thick flat slabs at 4500
mm vertical centres. Between ground and 5th floors the columns at C2 are 500 mm square;
above 5th floor they are 465 mm circular. Assume an internal environment, 1 hour fire
resistance and fck = 50 MPa.
Axial load to Exp. (6.10b) <BS EN 1990 Exp. (6.10) & NA>
NEd = ξγGGk + γQQk1 + ψ0,1γQQki
assuming the variable action of the roof is an independent variable action:
= 0.925 × 1.35 × 5553.6 + 1.5 × (2279.5 − 42.0) × 0.6 + 0.7 × 1.5 × 42.0
= 1.25 × 5553.6 + 1.5 × 2237.5 × 0.6 + 0.7 × 1.5 × 42.0
= 6942.1 + 2013.8+ 44.1
= 9000.0 kN
To Exp. (6.10b), NEd= 9000.0 kN
Modified
diagram
3 2 1 required
Figure 5.7
Subframe on column C2 along grid C
**
According to BS EN 1991–1–1 6.3.1.2(11) the imposed load on the roof is category H and therefore
does not qualify for reduction factor αn.
where
b = breadth d = depth L = length
lc = lower column uc = upper column
23 = beam 23 21 = beam 21
0.54 / 4.5
=
2 × 0.5 / 4.5 + 0.75 × 6.1 × 0.33 / 8.6 + 0.75 × 6.1 × 0.33 / 9.6
4
Modified
diagram
required
B C D
6200
Figure 5.8
Subframe on column C2 along grid 2
††
FEM 23 = Fixed end moment in span 23 at 2
‡‡
Using design actions to Exp (6.10) would have resulted in a requirement for 8500 mm2.
5.4.13 Links
Minimum diameter of links: = φ / 4 = 32 / 4 <9.5.3 & NA>
= 8 mm
Spacing: either
a) 0.6 × 20 × φ = 12 × 32 = 384 mm <9.5.3(3), 9.5.3(4)>
b) 0.6 × h = 0.6 × 500 = 300 mm or
c) 0.6 × 400 = 240 mm
∴ use H8 links at 225 mm cc.
Number of legs:
Bars at 127 mm cc i.e. < 150 mm ∴ no need to restrain bars in face but good <9.5.3(6)
practice suggests alternate bars should be restrained SMDSC 6.4.2>
∴ use single leg on face bars both ways @ 225 mm centres.
§§
Gk = 562.1; Qk = 755.6 × αn = 755.6 × 0.9; NEd = 562.1 × 1.25 + 755.6 × 0.9 × 1.5 = 1722.7 kN
5.5.1 Cover
Nominal cover, cnom
cnom = cmin + Δcdev <Exp. (4.1)>
where
cmin = max[cmin,b, cmin,dur]
where
cmin,b = diameter of bar. Assume 32 mm main bars and 10 mm links <4.4.1.2(3)>
cmin,dur = minimum cover due to environmental conditions. Assuming <BS 8500–1 Table
primarily XC3 / XC4, secondarily XF1, cmin,dur = 25 mm A4>
Δcdev = allowance in design for deviation
= 10 mm
∴ try cnom = 32 + 10 = 42 mm to main bars
or = 25 + 10 = 35 mm to 8 mm links
Try cnom = 35 mm to 8 mm links
c) As additional check, check adequacy of section to Annex B3 and Annex C. <BS EN 1992–1–2:
Using BS EN 1992–1–2 Table C.8 5.3.3(1), Annex C &
NA>
For ω = 1.0, e = 0.25b, R120, λ = 30 <BS EN 1992–1–2:
and interpolating between n = 0.3 and n = 0.5, Annex C(2)>
bmin = 350 mm, amin = 48 mm.
∴ Axis distance = 43 mm + φ / 2 is OK
∴ 4 no. H32 + 4 no. H25 with 35 mm cover to 8 mm links
(a = 55 mm min.) OK.
Figure 5.13
First order moments
***
With reference to Exp. (5.13N), ϕef may be taken as equal to 2.0. However, for the purpose of
illustration the full derivation is shown here.
†††
Imperfections need to be taken into account in one direction only. <5.8.9(2)>
Figure 5.14
Design summary: small perimeter column
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
4 Beams
4.1 General
The calculations in this Section are presented in the following parts:
4.2 A simply supported continuous beam showing what might be deemed typical hand
calculations.
4.3 A heavily loaded L-beam.
4.4 A wide T-beam. This example is analysed and designed strictly in accordance with the
provisions of BS EN 1992–1–1.
They are intended to be illustrative of the Code and not necessarily best practice.
A 450 mm deep × 300 mm wide rectangular beam is required to support office loads of gk =
30.2 kN / m and qk = 11.5 kN / m over 2 no. 6 m spans. fck = 30 MPa, fyk = 500 MPa. Assume
300 mm wide supports, a 50-year design life and a requirement for a 2-hour resistance to
fire in an external but sheltered environment.
Figure 4.2
Section through beam
4.2.1 Actions
kN / m
Permanent
gk = 30.2
Variable
qk = 11.5
4.2.2 Cover
Nominal cover, cnom
cnom = cmin + Δcdev <Exp. 4.1>
where
cmin = max[cmin,b; cmin,dur]
where
<4.4.1.2(3)>
cmin,b = minimum cover due to bond
= diameter of bar.
Assume 25 mm main bars
cmin,dur = minimum cover due to environmental conditions.
Assuming XC3 (moderate humidity or cyclic wet and <Table 4.1 BS 8500-1
dry) and secondarily XF1 (moderate water saturation Table A4, How to xxxx[20]>
without de-icing salt) using C30/37 concrete ,
cmin,dur = 25 mm
Δcdev= allowance in design for deviation. Assuming no
measurement of cover Δcdev= 10 mm <4.4.1.2(3)>
∴ cnom = 25 + 10 = 35 mm
Fire:
Check adequacy of section for 2 hours fire resistance (i.e. R = 120)
For bmin = 300 mm, minimum axis distance, a = 35 mm ∴ OK <BS EN 1992-1-2, 5.6.3(1),
Table 5.6>
cnom = 35 mm
4.2.4 Analysis
Design moments
Spans
MEd = (1.25 × 30.2 × 0.090 + 1.5 × 11.5 × 0.100) × 6.02 <Concise EC2 Table 15.3>
= 122.3 + 62.1 = 184.4 kNm
Support <Concise EC2 Table 15.3>
MEd = 50.8 × 0.106 × 6.02 = 193.8 kNm
Shear force
VAB = 0.45 × 6.0 × 50.8 = 137.2 kN
VAB = 0.63 × 6.0 × 50.8 = 192.0 kN
Table 4.1
Coefficients for use with beams (See Concise EC2 Table 15.3)
Coefficient Location
Outer Near middle At 1st At middle At interior
support of end span interior of interior supports
support spans
Moment gk and qk 25% spana — 0.094 — 0.075
Moment gk — 0.090 — 0.066 —
Moment qk — 0.100 — 0.086 —
Shear 0.45 — 0.63:0.55 — 0.50:0.50b
Conditions
For beams and slabs, 3 or more spans. (They may also be used for 2 span beams but support moment coefficient =
0.106 and internal shear coefficient = 0.63 both sides.)
Key
a At outer support ‘25% span’ relates to the UK Nationally Determined Parameter for BS EN 1992-1-1 9.2.1.2(1)
for minimum percentage of span bending moment to be assumed at supports in beams in monolithic
construction. 15% may be appropriate for slabs (see BS EN 1992-1-1 Cl 9.3.1.2).
b For beams of five spans, 0.55 applies to centre span.
4.2.6 Shear
Support B (critical)
Shear at central support = 192.0 kN
At face of support
VEd = 192.0 − (0.300 / 2 + 0.392) × 50.8 = 164.50 kN <6.2.1(8)>
vEd = VEd / bd
= 164.5 × 103 / (392 × 300) = 1.40 MPa
Maximum shear capacity
‡
K′ is limited to 0.208. However, if, as is usual practice in the UK, x / d is limited to 0.45, z / d is as a
consequence limited to 0.82 and K′ to 0.168.
Shear reinforcement
Assuming z = 0.9 d <6.2.3(1)>
Asw / s ≥ VEd / (0.9 d × fywd × cot θ) <6.2.3(3), Exp. (6.8)>
≥ 164.5 × 103 / (0.9 × 392 × (500 / 1.15) × 2.5) = 0.429
More accurately, <6.2.3(3), Exp. (6.8)>
Asw / s ≥ VEd / (z × fywd × cot θ)
≥ 164.5 × 103 / (333 × 1087) = 0.454
Minimum shear links, <9.2.2(5)>
Asw,min / s = 0.08bwfck0.5 / fyk
= 0.08 × 300 × 300.5 / 500 = 0.263 Not critical
Max. spacing = 0.75d = 0.75 × 392 = 294 mm <9.2.2(6)>
Use H8 @ 200 (Asw / s = 0.50)
Support A (and C)
Shear at end support = 137.2 kN
At face of support
VEd = 137.2 − (0.150 + 0.392) × 50.8 = 109.7 kN <6.2.1(8)>
By inspection,shear reinforcement required and cot θ = 2.5 <Concise EC2 Fig. 15.1a>
Asw / s ≥ VEd / (z × fywd × cot θ) <Concise EC2 15.5.3>
≥ 109.7 × 103 / [353 × (500 / 1.15) × 2.5] = 0.285
Use H8 @ 200 (Asw / s = 0.50) throughout††
Figure 4.3
Continuous rectangular beam: Summary of design
Note
It is presumed that the detailer would take this design and detail the slab to normal best practice, e.g.
to Standard method of detailing structural concrete[21]. This would usually include dimensioning and
detailing curtailment, laps, U-bars and also undertaking the other checks detailed in Section 4.2.8.
§
The absolute maximum for vRd,max (and therefore the maximum value of vEd) would be 5.28 MPa when
cot θ would equal 1.0 and the variable strut angle would be at a maximum of 45°.
**
For determination of VRd,max see Section 4.3.10.
††
As maximum spacing of links is 294 mm, changing spacing of links would appear to be of limited
benefit.
Figure 4.4
Continuous rectangular beam: RC details
Figure 4.5
Heavily loaded L-beam
This edge beam supports heavy loads from storage loads. The variable point load is
independent of the variable uniformly distributed load. The beam is supported on 350 mm
square columns 4000 mm long. fck = 30 MPa; fyk = 500 MPa. The underside surface is subject
to an external environment and a 2 hour fire resistance requirement. The top surface is
internal subject to a 2 hour fire resistance requirement. Assume that any partitions are
liable to be damaged by excessive deflections.
Figure 4.6
Section through L-beam
4.3.1 Actions
Permanent:
UDL from slab and cladding gk = 46.0 kN / m
Fire:
Check adequacy of section for 2 hours fire resistance R120 <BS EN 1992-1-2 5.6.3>
By inspection, BS EN 1992–1–2 Table 5.6 web thickness OK <BS EN 1992-1-2, Table 5.6>
Axis distance, a, required = 35 mm OK by inspection <BS EN 1992-1-2, Table 5.6>
∴ Try 35 mm nominal cover bottom and sides to 10 mm link
4.3.4 Analysis
Analysis by computer, assuming simple supports and including 15% redistribution at <BS EN 1990 A1.2.2 & NA,
supports (with, in this instance, consequent redistribution in span moments). 5.3.1 (6)>
Table 4.2
Elastic and redistributed moments kNm
Span number 1 2
Elastic M 1168 745
Redistributed M 1148 684
δ 0.98 0.92
Figure 4.7
Redistributed envelope, kNm
‡‡
Note: 350 × 350 is a minimum for columns requiring a fire resistance of 120 minutes
<BS EN 13670
Table 5.2a>
§§
The distance l0 is described as the distance between points of zero moment, ‘which may <5.3.2.1(2)>
be obtained from Figure 5.2’. In this case l0 = 0. (see figure 4.11) <Figure 5.2>.
Figure 4.9
Distance ‘A’
where
ϕ = 32
σsd = design stress in the bar at the ULS
= 434.8 × 1012 / 1608 = 274 MPa
fbd = ultimate bond stress <8.4.2 (2)>
= 2.25 η1 η2 fct,d
where
η1 = 1.0 for good bond conditions
η 2 = 1.0 for bar diameter ≤ 32 mm <3.1.6 (2),Tables 3.1 & 2.1, &
fct,d = αct fctk / γc NA>
= 1.0 × 2.0 / 1.5
= 1.33 MPa
fbd = 2.25 × 1.33 = 3.0 MPa
lb,rqd = (32 / 4) (274 / 3.0) = 731 mm***
lb,min =max[10ϕ; 100 mm] = 250 mm
∴ lbd = 731 mm i.e. < 1006 mm ∴ OK
Use 2 no. H32 U-bars
***
Anchorage lengths may be obtained from published tables. In this instance, a figure of 900 mm may
be obtained from Table 13 of the How to on Detailing. <How to: Detailing [12]>
Figure 4.10
<Fig. 5.3>
Effective flange width beff
Figure 4.11
<Fig. 5.2>
Elevation showing definition of lo for calculation of flange width
†††
The distance l0 is described as the distance between points of zero shear, ‘which may <5.3.2.1(2)>
be obtained from Figure 5.2’. From the analysis, l0 could have been taken as 7200 mm. <Figure 5.2>
Figure 4.12
Span AB bottom reinforcement
= 11 + 7.2 + 0 = 18.2
K = (end span) = 1.3 <Table 7.4N & NA>
F1 = (beff / bw = 1780 / 350 = 5.1) = 0.80 <7.4.2(2), Concise EC2 10.5.2>
F2 = 7.0 / leff (span > 7.0 m) <7.4.2(2)>
where
leff = 9000 mm <5.3.2.2(1)>
F2 = 7.0 / 9.0 = 0.77
F3 = 310 / σs
where
σs in simple situations = (fyk / γs) (As,req / As,prov) (SLS loads / ULS loads)
(1 / δ). However in this case separate analysis at SLS would be
required to determine σs. Therefore as a simplification use the
conservative assumption:
310 / σs = (500 / fyk) (As,req / As,prov) <Exp. (7.17)>
= (500 / 500) × (4824 / 4158) = 1.16
∴ Permissible l / d = 18.2 × 1.3 × 0.80 × 0.77 × 1.16 = 16.9
Actual l / d = 9000 / 668 = 13.5
As permissible less than actual
∴ OK
∴ 4 no. H32 B1 + 2 no. H32 B3 (4824 mm2) OK
2.18 of PD 6687[5] suggests that ρ in T sections should be based on the area of concrete above the
‡‡‡
Figure 4.13
Support B reinforcement
where
b = beff = beff1 + bw + beff2 <5.3.2.1, Fig. 5.3>
where
beff1 = (0.2b1 + 0.1l0) ≤ 0.2 l0 ≤ b1
where
b1 = distance between webs / 2.
Assuming beams at 7000 mm cc <Fig. 5.2>
= (7000 – 350) / 2 = 3325 mm
l0 = 0.85 × l1 = 0.85 × 8000 = 6800 mm
beff1 = 0.2 × 3325 + 0.1 × 6800 ≤ 0.2 × 6800 ≤ 3325
= 1345 ≤ 1360 ≤ 3325
= 1360 mm
bw = 350 mm
beff2 = (0.2b2 + 0.1l0) ≤ 0.2 l0 ≤ b2
where
b2 = 0 mm
beff2 = 0 mm
∴ b = 1360 + 350 + 0 = 1710 mm
Figure 4.14
Summary of L-beam design
Figure 4.16
Continuous wide T-beam
This central spine beam supports the ribbed slab in Example 3.4. The 300 mm deep ribbed
slab is required for an office to support a variable action of 5 KN/m2. The beam is the same
depth as the slab and is supported on 400 mm square columns, see Figure 4.17. fck = 35 MPa;
fyk = 500 MPa. 1 hour fire resistance required, internal environment. Assume that partitions
are liable to be damaged by excessive deflections.
Figure 4.17
Section through T-beam
4.4.2 Cover
Nominal cover, cnom
∴ cnom = 15 + 10 = 25 mm to links
or = 25 + 10 = 35 mm to main bars
Use 10 mm diameter links to give cnom = 35 mm to main bars
and 25 mm to links (as per ribbed slab design)
Fire:
Check adequacy of section for REI 60 <BS EN 1992-1-2 5.6.3>
<BS EN 1992-1-2
Table 5.6>
Axis distance required
Minimum width bmin = 120 mm with a = 25mm <BS EN 1992-1-2
or bmin = 200 mm with a = 12 mm Table 5.6>
∴ at 2000 mm wide (min.) a < 12 mm
By inspection, not critical
Use 25 mm nominal cover to links
§§§
The actions may also have been estimated assuming an elastic reaction factor of 1.1 for the slab
viz:
Permanent: UDL kN / m
Loads from ribbed slab (7.50 + 9.0) / 2 × 4.30 × 1.1 = 39.0
Self-weight/patch load extra over solid 2.0 × 4.17 = 8.3
47.3
Variable
Imposed (7.50 + 9.0) / 2 × 5.00 × 1.1 = 45.4
4.4.4 Analysis
Analysis by computer, assuming simple supports and including 15% redistribution <BS EN 1990 A1.2.2 &
at supports (with in this instance consequent redistribution in span moments). NA, 5.3.1 (6) >
Table 4.3
Elastic and redistributed moments, kNm
Span number 1 2 3 4
Elastic M 641.7 433.0 433.0 641.7
Redistributed M 606.4 393.2 393.2 606.4
δ 0.945 0.908 0.908 0.945
Figure 4.18
Redistributed envelope, kNm
****
cf. 126.7 kN / m from analysis of slab
= 11 + 6.8 + 0 =17.8
K = (end span) = 1.3 <Table 7.4N & NA>
F1 = (beff / bw = 4057 / 2000 = 2.03) = 0.90 <7.4.2(2), Concise EC2 10.5.2>
F2 = 7.0 / leff (span > 7.0 m) <7.4.2(2)>
where <5.3.2.2(1)>
leff = 7100 + 2 × 300 / 2 = 7400 mm
F2 = 7.0 / 7.4 = 0.95
F3 = 310 / σs
where
σs = (fyk / γs) (As,req / As,prov) (SLS loads / ULS loads) (1 / δ)
= 434.8 × (5835 / 5892) [(47.8 + 0.3 × 45.8) / (1.25 ×
47.8 + 1.5 × 45.8)] × (1 / 0.945)
= 434.8 × 0.99 × 0.48 × 1.06
= 219 MPa
F3 = 310 / σs <Exp. (7.17)>
= 310 / 219 = 1.41
∴ Permissible l / d = 17.8 × 1.3 × 0.90 × 0.95 × 1.41 = 27.9
2.18 of PD 6687[5] suggests that ρ in T sections should be based on the area of concrete above
††††
‡‡‡‡
Both As,prov / As,req and any adjustment to N obtained from Exp. (7.16a) or Exp. (7.16b) is restricted
to 1.5 by Note 5 to Table NA.5 in the UK NA.
where
b = beff = beff1 + bw + beff2 <5.3.2.1, Fig. 5.3>
where
beff1 = (0.2b1 + 0.1l0) ≤ 0.2 l0 ≤ b1
where
b1 referring to Figure 3.9
= (7500 – 1000 – 550) / 2 = 2975 mm
l0 = 0.70 × l2 = 0.7 × 7500 = 5250 mm <Fig. 5.2>
beff1 = (0.2 × 2975 + 0.1 × 5250 ≤ 0.2 × 5250 ≤ 2975
= 1120 ≤ 1050 ≤ 2975
= 1050 mm
bw = 2000 mm
beff2 = (0.2b2 + 0.1l0) ≤ 0.2 l0 ≤ b2
where
b2 = distance between webs / 2
Referring to Figure 3.9
= (9000 – 1000 – 550) / 2 = 3725 mm
l0 = 5250 mm as before
beff2 = 0.2 × 3725 + 0.1 × 5250 ≤ 0.2 × 5250 ≤ 3725
= 1270 ≤ 1050 ≤ 3725
= 1270 mm
b = 1050 + 2000 + 1270 = 4320 mm
§§§§
2.18 of PD 6687[5] suggests that r in T sections should be based on the area of concrete above
the centroid of the tension steel.
*****
12 no. H20 B (3768 mm2) used to suit final link arrangements.
†††††
12 no. H25 used to suit final arrangement of links.
‡‡‡‡‡
(2000 mm – 2 × 25 mm cover − 10 mm diameter) / 175 = 11 spaces, ∴ 12 legs
Check shear stress at basic perimeter u1 (2.0d from face of column) <6.4.2>
vEd = βVEd / u1d < vRdc
where
β, VEd, d as before <Fig. 6.13>
u1 = control perimeter under consideration. For
punching shear at 2d from interior columns
= 2(cx + cy) + 2π × 2d
= 1600 + 2π × 2 × 235 = 4553 mm
vEd = 1.15 × 1087.0 × 103 / 4553 × 235 = 1.17 MPa
vRdc = 0.18 / γc × k × (100 ρlfck)0.333 <Exp. (6.47) & NA>
where
γc = 1.5
k = 1 + (200/d)0.5 ≤ 2
k = 1 +(200 / 235)0.5 = 1.92
ρl = (ρlx ρly)0.5 <6.4.4.1(1)
where
ρlx = areas of bonded steel in a width of the column
§§§§§
In this case, at the perimeter of the column, it is assumed that the strut angle is 45°, i.e. that
cot θ = 1.0. In other cases, where cot θ < 1.0, vRd,max is available from Concise EC2[10] Table 15.7.
Figure 4.21
Shear links and punching shear perimeter u1
******
vRd,c for various values of d and ρl is available from Concise EC2[10] Table 15.6
Figure 4.22
Summary of design
Figure 4.23
Section X–X