I have come across many problems with new Delta PSU which has
been swapped out and not done properly by the external
contractors. Tonight just called out to site with similar looking issues
which I like to share with you.
. !ll the ones I managed to "x are due to the controller not been
commissioned properly or not commissioned at all# $ou need to
load the correct con"guration "les depending on the number o%
battery strings installed& I have the "les and procedure which I will
send out later. This will clear many o% the alarms.
+. ,any o% you have come across this one whereby i% you leave the
controller plugged in and %ully commissioned the D) power is cut-o
completely too all the e/uipment connected. 0hen you disconnect
the controller the power kicks in 1a clunk is heard %rom the solenoid
which turns on the power2. The reason %or this is because the
solenoid wires are crossed %rom %actory# $es hard to believe in %act
true( come across + sites with this problem. Simply reverse these
two black wires on the solenoid and problem solved 1see pics2
Page 1 28/5/2010
DELTA PSC3 CONFIGURATION
Username con"guration
Password psc+
Page 2 28/5/2010
There are currently two S0 Eersions used in the Eoda%one UF
network( '.+: and '.3'. The version can be seen in the screen shot
above. It has been agreed that we upgrade all the sites we have to
S0 Eersion '.3'.
I%( as shown above( the version is '.+: you need to upgrade to '.3'.
6rowse to the screen shown below using the menu on the le%t hand
side o% the screen.
Page 3 28/5/2010
4nter the EXACT "le name in the ;ilename box. )lick Start( then <F
in the message box.
Page 4 28/5/2010
)lose the browser. )heck on the unit that the IP address is correct
and that the D>)P is set to server.
$ou now need to load the correct con"guration "le %or the site.
These "les are loaded to the PS) + %rom your P) as described below.
The T;TP server is built into this S0 version but you still need to set
the Symantec "rewall to <G, as in 4ricsson +H commissioning.
Page 5 28/5/2010
There are "ve con"guration "les available %or S0 Eersion '.3'. The
%ormat is shown below
n6'+DPS':::399E;HlobalUF.xml
;rom the PS) + select the screen below using the menu on the le%t
hand side o% the screen.
In ?;ile TypeA select ?SetupA in the dropdown box. Then click ?Joad
;ile ;rom P)A.
Page 6 28/5/2010
)lick 6rowse and search %or the .xml "le you re/uire.
Page 7 28/5/2010
Alar# C$%&
Page 8 28/5/2010
This alarm is showing S 5on Urgent *;! 1recti"er ;ail !larm2.
This shows that there are 3 recti"ers in situ but the S0 is only
expecting +.
)lick !cknowledge and the S0 recognises all 3 recti"ers.
Page 9 28/5/2010
)lick Save 1Top le%t2 where modi"ed is displayed.
Page 10 28/5/2010
)heck by going back to the alarm status screen.
Page 11 28/5/2010