NX-EC0/ECS/PG0 CSM_NX-EC0_ECS_PG0_DS_E_3_4
NX-PG0242-5 NX-PG0342-5
General Specifications
Item Specification
Enclosure Mounted in a panel
Grounding method Ground to less than 100 Ω
Ambient operating temperature 0 to 55°C
Ambient operating humidity 10% to 95% (with no condensation or icing)
Atmosphere Must be free from corrosive gases.
Ambient storage temperature -25 to 70°C (with no condensation or icing)
Altitude 2,000 m max.
Pollution degree Pollution degree 2 or less: Meets IEC 61010-2-201.
Operating
environment Noise immunity Conforms to IEC61000-4-4, 2 kV (power supply line)
Overvoltage category Category II: Meets IEC 61010-2-201.
EMC immunity level Zone B
Conforms to IEC 60068-2-6.
Vibration resistance 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X,
Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistance Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions
cULus: Listed (UL508) or Listed (UL 61010-2-201), ANSI/ISA 12.12.01,
Applicable standards *
EU: EN 61131-2, C-Tick or RCM, KC Registration, NK, LR
* Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent applicable standards for each model.
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products.
EtherCAT is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
EtherNet/IPTM is a trademark of ODVA.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
1
NX-EC0/ECS/PG0
System Configurations
Connected to a CPU Unit
The following figure shows a system configuration when NX Units are connected to an NX-series CPU Unit.
Support software
(Sysmac Studio) CPU Rack
Connection to built-in
EtherNet/IPTM port
NX Units
EtherCAT Coupler Unit
.xml
ESI files
Built-in EtherCAT® port
*1. The connection method for the Sysmac Studio depends on the model of the CPU Unit or Industrial PC.
*2. An EtherCAT Slave Terminal cannot be connected to any of the OMRON CJ1W-NC@81/@82 Position Control Units even though they can
operate as EtherCAT masters.
Note: To check whether NX Units can be connected to your CPU Unit or Communications Coupler Unit, refer to the version information.
2
NX-EC0/ECS/PG0
Model Number Structure
NX-@@@@@@-@
(1) (2) (3) (4) (5)
3
NX-EC0/ECS/PG0
Ordering Information
Applicable standards
Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent applicable standards for each model.
* Refer to the I/O Refreshing Methods in the USER'S MANUAL (Cat. No. W524) for the communications cycles for each model.
4
NX-EC0/ECS/PG0
Cables and Connectors for Line Driver Output Units with MIL Connectors
Product name Specification Model
Optional Products
Product name Specification Model
Unit/Terminal Block For 10 Units
NX-AUX02
Coding Pins (Terminal Block: 30 pins, Unit: 30 pins)
Specification
Product name Terminal number Terminal current Model
No. of terminals Ground terminal mark
indications capacity
12 A/B NX-TBA122
Terminal Block 16 A/B None 10 A NX-TBA162
12 C/D NX-TBB122
Accessories
Not included.
5
NX-EC0/ECS/PG0
Version Information
Connected to a CPU Unit
Refer to the user's manual for the CPU Unit details on the CPU Units to which NX Units can be connected.
NX Units Corresponding unit versions/versions
Model Unit version CPU Unit Sysmac Studio
Ver. 1.1
NX-EC0112 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.0
NX-EC0122 Ver. 1.1 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.1
NX-EC0132 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.0
NX-EC0142 Ver. 1.1 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.1
NX-EC0212 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.0
NX-EC0222 Ver. 1.1 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.0
NX-ECS112 Ver. 1.1 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.0
NX-ECS212 Ver. 1.1 Ver. 1.13 Ver. 1.17
Ver. 1.2
Ver. 1.1
Ver. 1.17
NX-PG0112 Ver. 1.2 Ver. 1.13
Ver. 1.3 Ver. 1.19
Ver. 1.0
Ver. 1.1 Ver. 1.17
NX-PG0122 Ver. 1.13
Ver. 1.2
Ver. 1.3 Ver. 1.19
Ver. 1.2 Ver. 1.17
NX-PG0232-5 Ver. 1.13
Ver. 1.3 Ver. 1.19
Ver. 1.2 Ver. 1.17
NX-PG0242-5 Ver. 1.13
Ver. 1.3 Ver. 1.19
Ver. 1.2 Ver. 1.17
NX-PG0332-5 Ver. 1.13
Ver. 1.3 Ver. 1.19
Ver. 1.2 Ver. 1.17
NX-PG0342-5 Ver. 1.13
Ver. 1.3 Ver. 1.19
Note: Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the
oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and
versions.
6
NX-EC0/ECS/PG0
7
NX-EC0/ECS/PG0
8
NX-EC0/ECS/PG0
(B)
(C)
(A)
24 mm Width
(B)
(C)
(A)
9
NX-EC0/ECS/PG0
Terminal Blocks
(A)
A B A B A B C D
(B)
A1 B1 A1 B1 A1 D1
(C)
A2 B2 A2 B2 A2 D2
A3 B3 A3 B3 A3 D3
A4 B4 A4 B4 A4 D4
A5 B5 A5 B5 A5 D5
A6 B6 A6 B6 A6 D6
A7 B7 A7 B7 A7 D7
A8 B8 A8 B8 A8 D8
C D
10
NX-EC0/ECS/PG0
Applicable Wires
Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching ferrules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tool are given in the following table.
Applicable wire
Terminal type Manufacturer Ferrule model Crimping tool
(mm2 (AWG))
Terminals other Phoenix AI0,34-8 0.34 (#22) Phoenix Contact (The figure in parentheses is the applicable wire
than ground Contact AI0,5-8 0.5 (#20) size.)
terminals CRIMPFOX 6 (0.25 to 6 mm2, AWG 24 to 10)
AI0,5-10
AI0,75-8 0.75 (#18)
AI0,75-10
AI1,0-8 1.0 (#18)
AI1,0-10
AI1,5-8 1.5 (#16)
AI1,5-10
Ground AI2,5-10 2.0 *1
terminals
Terminals other Weidmuller H0.14/12 0.14 (#26) Weidmueller (The figure in parentheses is the applicable wire size.)
than ground H0.25/12 0.25 (#24) PZ6 Roto (0.14 to 6 mm2, AWG 26 to 10)
terminals
H0.34/12 0.34 (#22)
H0.5/14 0.5 (#20)
H0.5/16
H0.75/14 0.75 (#18)
H0.75/16
H1.0/14 1.0 (#18)
H1.0/16
H1.5/14 1.5 (#16)
H1.5/16
*1. Some AWG 14 wires exceed 2.0 mm2 and cannot be used in the screwless clamping terminal block.
When you use any ferrules other than those in the above table, crimp them to the twisted wires so that the following processed dimensions are
achieved.
8 to 10 mm
1.6 mm max.
(Terminals other than ground terminals)
2.0 mm max. 2.4 mm max.
(Ground terminals) (Terminals other than ground terminals)
2.7 mm max.
(Ground terminals)
<Additional Information> If more than 2 A will flow on the wires, use plated wires or use ferrules.
11
NX-EC0/ECS/PG0
(B)
(C)
(A)
(B)
(C)
(A)
12
NX-EC0/ECS/PG0
34 terminals
34 terminals 34 terminals
Connecting Cable
The table below shows applicable connecting cables.
Model Manufacturer
XW2Z-EE OMRON Corporation
The cable length from the Unit to an external device connected through the Connector-Terminal Block Conversion Units should not be longer than
the specified cable length for the Unit.
Refer to the Specification for each units.
13
NX-EC0/ECS/PG0
Dimensions (Unit: mm)
14.1
12.0 0.55
1.5
104.5
100
1.5
65.2
71
80
24 mm Width
26.1
24.0 0.55
1.5
C D
104.5
100
C D
1.5
65.2
71
80
14
NX-EC0/ECS/PG0
100 104.5
76.9
34.2
8.9
1.5
65.2
30
71
32.1
89.8
100 104.5
76.9
34.2
8.9 1.5
65.2
21.9 71
30 89.8
32.1
Related Manual
Man. No Model Manual Application Description
W524 NX-EC0@@@ NX-series Position Learning how to use NX-series The hardware, setup methods, and
NX-ECS@@@ Interface Units User’s Position Interface Units functions of the NX-series Incremental
NX-PG0@@@ Manual Encoder Input Units, SSI Input Units, and
Pulse Output Unit are described.
15
NX-series Incremental Encoder Input Unit
NX-EC0@@@
More precise timing control by
synchronizing the position data with the
EtherCAT Distributed Clock
• Process encoder input data using the MC Function Modules of the
NJ/NX/NY5 Controllers
• Time-stamp inputs enables high-precision timing control in
combination with time-stamp outputs
Features
• Open collector output type and line driver output type Incremental Encoders can be connected
• High-speed remote I/O control with communications cycle as fast as 125 μs*1
• Free-run refreshing, synchronous I/O refreshing, or task period prioritized refreshing*2 with the NX1P2 CPU Unit or
EtherCAT Coupler Unit
• The MC Function Modules of the NJ/NX/NY5 Controllers allows the encoder to be used as a motion axis
• Latching (1 internal signal and 2 input signals from external devices)
• Pulse Period Measurement
• 32 bit counters (80000000 to 7FFFFFFF HEX)
• Maximum counting rate: 4 MHz (Line receiver: 4 MHz, Open collector: 500 kHz)
• Time Stamping
• Maximum and minimum counter value setting
• Connect to the CJ PLC using the EtherNet/IPTM bus coupler
*1. When using the NX-EC01@@ together with the NX701-@@@@ and NX-ECC203.
*2. Task Period Prioritized refreshing is available when the NX-ECC203 is used together.
16
NX-EC0@@@
System Configuration
The following figure shows a system configuration when an Incremental Encoder Input Unit is connected to an NJ/NX-series CPU Unit via an
EtherCAT Coupler Unit.
I/O power *1
supply External input
(latch input 1, latch input 2, gate input, or reset input)
Incremental encoder
*1. You can specify functions for up to two external inputs to a One-input Incremental Encoder Input Unit. You cannot use external inputs for a
Two-input Unit.
17
NX-EC0@@@
Incremental Encoder Input Unit Specifications
Incremental Encoder Input Unit
NX-EC0112
Unit name Incremental Encoder Input Unit Model NX-EC0112
Type of external Screwless clamping terminal block
Number of channels 1 channel
connections (16 terminals)
I/O refreshing method Free-Run refreshing, synchronous I/O refreshing or task period prioritized refreshing *
IOG
Left-side I/O power supply + I/O power supply + Right-side
NX bus NX bus
connector I/O power supply − I/O power supply − connector
Installation orientation:
Installation orientation and • Connected to a CPU Unit: Possible in upright installation.
restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
* The I/O refreshing method is automatically set according to the connected Communications Coupler Unit and CPU Unit.
18
NX-EC0@@@
Encoder
A B
Z NC
IOV IOV
I0 I1
I2 NC
19
NX-EC0@@@
NX-EC0122
Unit name Incremental Encoder Input Unit Model NX-EC0122
Type of external Screwless push-in terminal block
Number of channels 1 channel
connections (16 terminals)
I/O refreshing method Free-Run refreshing, synchronous I/O refreshing or task period prioritized refreshing *
IOV
A, B, Z
Terminal block Current limiter Inter-
I0 to I2
nal
Circuit layout cir-
IOG cuits
Installation orientation:
Installation orientation • Connected to a CPU Unit: Possible in upright installation.
and restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
* The I/O refreshing method is automatically set according to the connected Communications Coupler Unit and CPU Unit.
20
NX-EC0@@@
Encoder
A B
Z NC
IOV IOV
Terminal connection Sensor 1 IOG IOG
diagram
I0 I1
I2 NC
21
NX-EC0@@@
NX-EC0132
Unit name Incremental Encoder Input Unit Model NX-EC0132
Type of external Screwless clamping terminal block
Number of channels 1 channel
connections (12 terminals × 2)
I/O refreshing method Free-Run refreshing, synchronous I/O refreshing or task period prioritized refreshing *
22
NX-EC0@@@
Encoder Input
No isolation: 5 V
External Inputs
IOV Power
supply
Installation orientation:
Installation orientation and • Connected to a CPU Unit: Possible in upright installation.
restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
I0 I1 A+ B+ Encoder
IOG IOG Z+ 5V
Sensor 2
I2 NC Z- 0V
Terminal connection diagram
Sensor 3 IOV NC NC NC
IOG NC NC NC
23
NX-EC0@@@
NX-EC0142
Unit name Incremental Encoder Input Unit Model NX-EC0142
Type of external Screwless push-in terminal block
Number of channels 1 channel
connections (12 terminals × 2)
I/O refreshing method Free-Run refreshing, synchronous I/O refreshing or task period prioritized refreshing *
24
NX-EC0@@@
Encoder Input
No isolation: 5 V
No isolation: 5 V GND
Non-
isolated No isolation: 5 V
power
supply No isolation: 5 V GND
Left-side I/O power supply + I/O power supply + Right-side
NX bus NX bus
connector I/O power supply − I/O power supply − connector
Circuit layout
External Inputs
IOV Power
A, B, Z Isola- Inter-
Terminal block Current limiter
I0 to I2 tion nal
cir- cir-
IOG cuit cuits
Installation orientation:
Installation orientation and • Connected to a CPU Unit: Possible in upright installation.
restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
I0 I1 A+ B+ Encoder
IOG IOG Z+ 5V
Sensor 2
Terminal connection I2 NC Z- 0V
diagram Sensor 3 IOV NC NC NC
IOG NC NC NC
25
NX-EC0@@@
NX-EC0212
Unit name Incremental Encoder Input Unit Model NX-EC0212
Type of external Screwless clamping terminal block
Number of channels 2 channels
connections (12 terminals)
I/O refreshing method Free-Run refreshing, synchronous I/O refreshing or task period prioritized refreshing *
IOG
Installation orientation:
Installation orientation and • Connected to a CPU Unit: Possible in upright installation.
restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
* The I/O refreshing method is automatically set according to the connected Communications Coupler Unit and CPU Unit.
26
NX-EC0@@@
Encoder 1
A1 B1
Z1 NC
IOV IOV
IOG IOG
Terminal connection diagram
Encoder 2 A2 B2
Z2 NC
27
NX-EC0@@@
NX-EC0222
Unit name Incremental Encoder Input Unit Model NX-EC0222
Type of external Screwless push-in terminal block
Number of channels 2 channels
connections (12 terminals)
I/O refreshing method Free-Run refreshing, synchronous I/O refreshing or task period prioritized refreshing *
IOV
A1, B1, Z1
Terminal block Current limiter Inter-
A2, B2, Z2
nal
Circuit layout cir-
IOG cuits
Installation orientation:
Installation orientation and • Connected to a CPU Unit: Possible in upright installation.
restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
* The I/O refreshing method is automatically set according to the connected Communications Coupler Unit and CPU Unit.
28
NX-EC0@@@
Encoder 1
A1 B1
Z1 NC
IOV IOV
Terminal connection IOG IOG
diagram
Encoder 2 A2 B2
Z2 NC
29
NX-series SSI Input Unit
NX-ECS@@@
Synchronous Serial Interface (SSI) to
connect external axes to the Sysmac
system
• Process SSI encoder input data using the MC Function Modules
of the NJ/NX/NY5 Controllers
• SSI to connect an absolute encoder or linear encoder
Features
• SSI clock frequency up to 2 MHz
• High-speed remote I/O control with communications cycle as fast as 125 μs*1
• Free-run refreshing, synchronous I/O refreshing, or task period prioritized refreshing*2 with the NX1P2 CPU Unit or
EtherCAT Coupler Unit
• The MC Function Modules of the NJ/NX/NY5 Controllers allows the encoder to be used as a motion axis
• Choice of SSI Coding Methods (No conversion, binary code, or gray code)
• Time Stamping
• Multi-turn and single-turn encoders supported
• Data Refresh Status (Data refreshing can be checked on the host controller.)
• Maximum connecting SSI cable length: 400 m
• Connect to the CJ PLC using the EtherNet/IPTM bus coupler
*1. When using the NX-EC01@@ together with the NX701-@@@@ and NX-ECC203.
*2. Task Period Prioritized refreshing is available when the NX-ECC203 is used together.
System Configuration
The following figure shows a system configuration when an SSI Input Unit is connected to an NJ/NX-series CPU Unit via an EtherCAT Coupler Unit.
Support software (Sysmac Studio)
EtherCAT master (NJ/NX-series CPU Unit)
I/O power
supply
*
SSI encoder
* The SSI encoder is supplied with 24-VDC power from the SSI Input Unit.
30
NX-ECS@@@
SSI Input Unit Specifications
SSI Input Unit 1 channel NX-ECS112
Unit name SSI Input Unit Model NX-ECS112
Type of external Screwless push-in terminal block
Number of channels 1 channel
connections (12 terminals)
I/O refreshing method Free-Run refreshing, synchronous I/O refreshing or task period prioritized refreshing *1
D+
120 Ω
Circuit layout D-
No isolation: 5 V GND
Non-
isolated No isolation: 5 V
power
supply No isolation: 5 V GND
Left-side I/O power supply + I/O power supply + Right-side
NX bus NX bus
connector I/O power supply − I/O power supply − connector
Installation orientation:
Installation orientation • Connected to a CPU Unit: Possible in upright installation.
and restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
C+ D+ Encoder
C- D-
IOV IOV
Terminal connection IOG IOG
diagram NC NC
NC NC
31
NX-ECS@@@
D1+, D2+
120 Ω
Circuit layout D1-, D2-
No isolation: 5 V GND
Non-
isolated No isolation: 5 V
power No isolation: 5 V GND
supply
Left-side I/O power supply + I/O power supply + Right-side
NX bus NX bus
connector I/O power supply − I/O power supply − connector
Installation orientation:
Installation orientation • Connected to a CPU Unit: Possible in upright installation.
and restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
32
NX-series Pulse Output Unit
NX-PG0@@@
Positioning control with pulse outputs
to command stepper motor drives and
other pulse input motor drives
• The MC Function Modules of the NJ/NX/NY5 Controllers
enable pulse outputs for motor control
• The same motion control instructions as those for Servomotor
control can be used to program single-axis PTP control and
interpolation
• Non-networked motors, such as DD motors, stepper motors,
and DC motors, can be connected
Features
• The MC Function Modules of the NJ/NX/NY5 Controller allows you to connect with as many axes as the NJ/NX/
NY5 Controller can control
• High-speed remote I/O control with communications cycle as fast as 125 μs*1
• Free-run refreshing or task period prioritized refreshing*2 with the EtherCAT Coupler Unit
• Latching (2 external latch inputs)
• Open collector pulse outputs up to 500 kHz or line driver pulse outputs up to 4 MHz
• Line driver output models with two or four channels
*1. When using the NX-EC01@@ together with the NX701-@@@@ and NX-ECC203.
*2. Task Period Prioritized refreshing is available when the NX-ECC203 is used together.
33
NX-PG0@@@
System Configurations
NX-PG0112/-PG0122
The following figure shows a system configuration when the NX-PG0112/-PG0122 Pulse Output Unit is connected to an NJ/NX-series CPU Unit
via an EtherCAT Coupler Unit.
*1. When the Unit is connected to an NJ-series CPU, you can use these inputs by adding a Digital Input Unit and assigning MC Function Module functions.
*2. The pulse output from a Pulse Output Unit is a 24-VDC PNP open collector output. Connect an external current-limiting resistor according to
the input specifications of the connected motor drive.
Example: For a G5-series Servo Drive, connect a 2-kΩ (1/2-W) resistor in series.
34
NX-PG0@@@
NX-PG0232-5/-PG0242-5/-PG0332-5/-PG0342-5
The following figure shows a system configuration when the NX-PG0232-5/-PG0242-5/-PG0332-5/-PG0342-5 Pulse Output Unit is connected to
an NJ/NX-series CPU Unit via an EtherCAT Coupler Unit.
Motor
Drive with pulse train input
*1. When the Unit is connected to an NJ/NX-series CPU, you can use these inputs by assigning MC Function Module functions to external inputs inside
a Pulse Output Unit or to inputs of a Digital Input Unit that is added. For information on Digital Input Units, refer to the NX-series Digital I/O Units User’s
Manual (Cat. No. W521). For NX-PG0232-5, NX-PG0242-5, NX-PG0332-5, and NX-PG0342-5 Pulse Output Units, the number of available external
inputs that can be used in always ON status is restricted by ambient operating temperature and installation orientation.
*2. The pulse output from a Pulse Output Unit is a 24-VDC open collector output. When it is used as a control output for a motor drive such as an
error counter reset output, connect an external current-limiting resistor according to the input specifications of the connected motor drive. A
line drive output does not need a current limiting resistor.
35
NX-PG0@@@
Pulse Output Unit Specifications
Pulse Output Unit (Open collector output, NPN type) NX-PG0112
Unit name Pulse Output Unit Model NX-PG0112
Type of external Screwless clamping terminal block
Number of axes 1
connections (16 terminals)
I/O refreshing method *1 Synchronous I/O refreshing or task period prioritized refreshing
36
NX-PG0@@@
IOV
Terminal block
A, B, O0
Inter- Isola- Drive
nal tion circuit
cir- cir-
cuits cuit
Non-
isolated
power Short-circuit protection
supply
Left-side I/O power supply + I/O power supply + Right-side
NX bus NX bus
connector I/O power supply − I/O power supply − connector
Circuit layout
External Inputs
IOG
Installation orientation:
Installation orientation and • Connected to a CPU Unit: Possible in upright installation.
restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
A B Driver
IOV IOV
O0 NC
IOV IOV
Terminal connection diagram
NC NC
I0 I1
37
NX-PG0@@@
38
NX-PG0@@@
A, B, O0
Inter- Isola- Drive
nal tion circuit
cir- cir-
cuits Terminal block
cuit
Non- Short-circuit protection
isolated
power
supply IOG
IOV
Installation orientation:
Installation orientation and • Connected to a CPU Unit: Possible in upright installation.
restrictions • Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: There are no restrictions.
A B Driver
IOG IOG
O0 NC
I0 I1
39
NX-PG0@@@
Pulse Output Unit (Line driver output, NPN type) 2 channels NX-PG0232-5
Unit name Pulse Output Unit Model NX-PG0232-5
Type of external
Number of channels 2 channels MIL connector (34 terminals ×1)
connections
*1
I/O refreshing method Synchronous I/O refreshing or task period prioritized refreshing
40
NX-PG0@@@
A+ and B+
Internal Isolation MIL connector
circuits circuit
A− and B−
No isolation: 5 V GND
External Output
O0 to O2
Internal Isolation Drive
circuits circuit circuit
MIL connector
OG
POV Non-isolated
MIL connector power
POG supply
I0−
120 Ω Isolation Internal
circuit circuits
I0+
MIL connector
No isolation: 5 V GND
IV
MIL connector Internal
circuits
I0 to I4 Power supply limiter
41
NX-PG0@@@
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: The number of external inputs that can be always ON is restricted as shown below.
• For upright installation
(points)
25
20
15
Number of input
points that are 10 points at 49.375°C
always ON 10
5 4 points at 55°C
0
Installation orientation and
0 10 20 30 40 50 60
restrictions
Ambient temperature (°C)
• For any installation other than upright
(points)
25
20
15
Number of input
points that are 10 points at 42.5°C
always ON 10
0 point at 55°C
0
0 10 20 30 40 50 60
Ambient temperature (°C)
42
NX-PG0@@@
43
NX-PG0@@@
Pulse Output Unit (Line driver output, PNP type) 2 channels NX-PG0242-5
Unit name Pulse Output Unit Model NX-PG0242-5
Type of external
Number of channels 2 channels MIL connector (34 terminals ×1)
connections
*1
I/O refreshing method Synchronous I/O refreshing or task period prioritized refreshing
44
NX-PG0@@@
A+ and B+
Internal Isolation MIL connector
circuits circuit
A− and B−
No isolation: 5 V GND
External Output
O0 to O2
Internal Isolation Drive
circuits circuit circuit
MIL connector
Short-circuit
OV
POV Non-isolated protection
MIL connector power
POG supply
Circuit layout
External Inputs (Line Receiver)
No isolation: 5 V
I0−
120 Ω Isolation Internal
circuit circuits
I0+
MIL connector
No isolation: 5 V GND
45
NX-PG0@@@
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: The number of external inputs that can be always ON is restricted as shown below.
• For upright installation
(points)
25
20
15
Number of input
points that are 10 points at 49.375°C
always ON 10
5 4 points at 55°C
0
Installation orientation and
restrictions 0 10 20 30 40 50 60
Ambient temperature (°C)
• For any installation other than upright
(points)
25
20
15
Number of input
points that are 10 points at 42.5°C
always ON 10
0 point at 55°C
0
0 10 20 30 40 50 60
Ambient temperature (°C)
46
NX-PG0@@@
47
NX-PG0@@@
Pulse Output Unit (Line driver output, NPN type) 4 channels NX-PG0332-5
Unit name Pulse Output Unit Model NX-PG0332-5
Type of external
Number of channels 4 channels MIL connector (34 terminals ×2)
connections
*1
I/O refreshing method Synchronous I/O refreshing or task period prioritized refreshing
48
NX-PG0@@@
A+ and B+
Internal Isolation MIL connector
circuits circuit
A− and B−
No isolation: 5 V GND
External Output
O0 to O2
Internal Isolation Drive
circuits circuit circuit
MIL connector
OG
POV Non-isolated
MIL connector power
POG supply
Circuit layout
External Inputs (Line Receiver)
No isolation: 5 V
I0−
120 Ω Isolation Internal
circuit circuits
I0+
MIL connector
No isolation: 5 V GND
IV
MIL connector Internal
circuits
I0 to I4 Power supply limiter
49
NX-PG0@@@
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: The number of external inputs that can be always ON is restricted as shown below.
• For upright installation
(points)
25
20 points at 40°C
20
15
Number of input
points that are
always ON 10
5 4 points at 55°C
0
Installation orientation and 0 10 20 30 40 50 60
restrictions Ambient temperature (°C)
• For any installation other than upright
(points)
25
20 points at 30°C
20
Number of input 15
points that are
always ON
10
0 point at 55°C
0
0 10 20 30 40 50 60
Ambient temperature (°C)
50
NX-PG0@@@
51
NX-PG0@@@
Pulse Output Unit (Line driver output, PNP type) 4 channels NX-PG0342-5
Unit name Pulse Output Unit Model NX-PG0342-5
External connection
Number of channels 4 channels MIL connector (34 terminals ×2)
terminals
*1
I/O refreshing method Synchronous I/O refreshing or task period prioritized refreshing
52
NX-PG0@@@
A+ and B+
Internal Isolation MIL connector
circuits circuit
A− and B−
No isolation: 5 V GND
External Output
O0 to O2
Internal Isolation Drive
circuits circuit circuit
MIL connector
Short-circuit
OV
POV Non-isolated protection
MIL connector power
POG supply
Circuit layout
External Inputs (Line Receiver)
No isolation: 5 V
I0−
120 Ω Isolation Internal
circuit circuits
I0+
MIL connector
No isolation: 5 V GND
53
NX-PG0@@@
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: The number of external inputs that can be always ON is restricted as shown below.
• For upright installation
(points)
25
20 points at 40°C
20
15
Number of input
points that are
always ON 10
5 4 points at 55°C
0
Installation orientation and 0 10 20 30 40 50 60
restrictions
Ambient temperature (°C)
• For any installation other than upright
(points)
25
20 points at 30°C
20
Number of input 15
points that are
always ON
10
0 point at 55°C
0
0 10 20 30 40 50 60
Ambient temperature (°C)
54
NX-PG0@@@
• The connection diagram for CN2 is the same as the one for CN1.
Failure detection None Protection None
55
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.