As per table-2 of IEC 60099-4, next higher rating of available surge arrester is 96 KV
• Based on above selected Rated voltage of 96KV, value of continuous operating voltage is
calculated again as Uc = 0.8 x Ur
Uc = 0.8 x 96 = 76.8 ̴ 77 KV
IEC 60099-4: Cl 8.3.3: One lightning current impulse shall be applied to each of the three samples
for each of the following three peak values of approximately 0,5, 1 and 2 times the nominal
discharge current of the arrester.
IEC 60099-4: Cl 8.3.4: One switching current impulse shall be applied to each of the three samples
with peak values according to Table 1 with a tolerance of ±5 %. The residual voltages are
determined in accordance with 6.3.
• Temporary Over voltages: Temporary over voltages shall be calculated for 1 s & 10 s as per IEC
60099-4, clause no: 6.2.3.5. Further the value of Temporary over voltage at 10 s shall be equal to
the rated voltage as per Clause no. 3.54 of IEC 60099-4.
Temporary Over voltage for 10 s = Rated voltage = 96 KV
• Energy discharge capabilities are experimental values.
• Power frequency withstand voltage:
Lightning Impulse withstand voltage (1,2/50 Lightning Impulse withstand voltage (1,2/50
µs) = 550 kV µs) = 650 kV
• Siemens Surge Arresters are designed as separate gas compartment with dedicated pressure
relief device (rupture discs) as per Design-A (Clause No. 8.10.1 of IEC 60099-4).