Professional Documents
Culture Documents
INDEX
(-31.#4"3(.-
(12$/ 1 3(.-
#(132$/ 1 3(.-
".,!(-$# (1#(132$/ 1 3(.-
/1(-"(/+$2.%'8#1 4+("2$/ 1 3(.-
,.#$1-,$3'.#2.%'8#1 4+("2$/ 1 3(.-
/1.#4"326(3'(-3$&1 3$#'8#1 4+("2$/ 1 3(.-
$7 ,/+$2823$,2
24,, 18
//$-#(7 /(/(-&28,!.++$&$-#
Disclaimer: Caleffi makes no warranty that the information presented in idronics meets the mechanical, electrical or other code requirements applicable within a Mixed Sources
given jurisdiction. The diagrams presented in idronics are conceptual, and do not represent complete schematics for any specific installation. Local codes may Products from well-managed
forests, controlled sources and
require differences in design, or safety devices relative to those shown in idronics. It is the responsibility of those adapting any information presented in idronics to
recycled wood or fiber.
verify that such adaptations meet or exceed local code requirements.
Separation in Hydronic Systems
(-31.#4"3(.- little dirt. What dirt the system does contain should
be captured and removed. The state-of-the-art dirt
To “separate” means to disconnect or segregate. The separators discussed in this issue of idronics can remove
word separate has several meanings in the context particles as small as 5 microns in diameter.
of hydronic heating or cooling systems. This issue of
idronics examines three distinctly different forms of '8#1 4+("2$/ 1 3(.-
separation within such systems. They are: Many hydronic systems contain multiple circulators,
some of which need to operate at the same time. Ideally,
1. Air separation the operation of any one of these circulators will not
2. Dirt separation create any change in the flow or head produced by any
3. Hydraulic separation other circulator in the system that also happens to be
operating. When this is achieved, the circulators are said
All of these are desirable characteristics that exist in well- to be hydraulically separated from each other.
planned hydronic systems.
There are several methods by which hydraulic separation
(12$/ 1 3(.- can be achieved. This issue of idronics discusses each of
The ideal fluid in a hydronic heating or cooling system them, along with their strengths and limitations.
is water without any impurities, air bubbles or dissolved
gases such as oxygen and nitrogen. However, every For many applications, it makes sense to combine the
hydronic system starts out with air in all of its components. three fundamental forms of separation into a single
A well-planned system will quickly enable this air to be device. In other applications, or for retrofit situations, this
gathered and removed from the system. It will also reduce may not be possible or practical.
the dissolved air gases in the water to levels where they
are of no concern. The system should then maintain the A thorough understanding of the principles involved in
water at a very low level of dissolved air content over each type of separation equips designers to select the
its entire life. Any small amounts of air that may enter best products and installation locations for the system
the system during component maintenance should be at hand. This issue of idronics was written to provide this
quickly captured and ejected. understanding.
#(132$/ 1 3(.-
A newly assembled hydronic system usually contains (12$/ 1 3(.-
dirt or remnants of oils used during manufacturing,
transportation or installation. It may also contain pieces Air control within hydronic systems has always presented
of joint sealing tape, rubber particles or ferrous metal challenges. It began with the earliest hydronic systems
particles. The latter is common when cast iron or steel that did not have circulators. Water flow was created by
components such as circulators, panel radiators or cast the buoyancy difference between hot water in the boiler
iron sectional boilers are used in the system. and cooler water returning from the heat emitters. These
systems used large-diameter piping and operated at very
Dirt or metal particles are undesirable in hydronic systems. low flow velocities. Air removal was mostly a matter of
Fine particles of dirt can interfere with the operation of waiting for air pockets to form and then releasing this air
moving parts within valves or circulators. They can also through manually operated valves located at high points
coat the internal surfaces of both heat sources and heat in the system where the air accumulated.
emitters, decreasing rates of heat transfer. Metal particles
such as iron oxides can collect in circulators due to the Most of these early systems were “open-loop” rather
magnetic fields they create. All well-planned and properly than closed-loop systems. An expansion tank vented
commissioned hydronic systems should contain very to the atmosphere was located at the high point of the
3
system—usually in the attic or upper floor, as seen in
Figure 2-1 Figure 2-1, which appeared in a heating design manual
"open" expansion tank at top of system
published in 1906.
To!
expansion!
tank
boiler!
Þtting
water to system
from!
boiler
air bubbles
dip tube
4
Air bubbles rising from the boiler were captured by a Figure 2-3
special “boiler fitting,” and directed through a pipe to the
expansion tank. Another special “tank fitting” was used
to minimize the absorption of air within the expansion
tank into the system water. The overall process is best
described as air control rather than air elimination.
Although some of these systems are still in operation,
they do not represent modern technology. Very few
systems are now installed using this approach.
r/PJTFTJOUIFQJQJOHBOEIFBUFNJUUFSTUIBUBOOPZ
occupants
r*OBEFRVBUFGMPXTEVFUPBNJYUVSFPGXBUFSBOEBJSJO
circulators
r1PPSIFBUUSBOTGFSCZIFBUFNJUUFSTXIFOBMMIFBU
transfer surfaces are not wetted
5
Entrapped air sounds often become noticeable as flow hydronic systems that experience chronic air problems
begins to disturb stationary air pockets. Air-filled cavities are constantly allowing air to enter the system. This
within piping and radiators act as acoustic amplifying resupplies oxygen that furthers the corrosion reaction.
chambers, especially if water enters a component which Poorly deaerated hydronic systems can fail prematurely
has trapped a large pocket of air. Noise is also generated due to such corrosion. Corrosion of internal surfaces
when dissolved gases within water are released due can lead to leakage in thin steel components such as
to a sudden drop in pressure. This is called gaseous panel radiators or expansion tank shells. Corrosion on
cavitation, and it often occurs at the orifice of valves or other surfaces can eventually break off as ferrous oxide
the inlet of circulators. particles that can be carried throughout the system
and possibly become trapped in components such as
(M@CDPT@SD %KNV Circulator impellers are designed to circulators or heat exchangers.
transfer mechanical energy called “head” to incompressible
liquids. A mixture of water and air is not an incompressible The following chemical reactions can occur in hydronic
liquid. Although most circulators can maintain flow when systems containing ferrous (iron-containing) components.
the liquid passing through contains some entrained air,
mechanical energy transfer is not as efficient as when
the liquid is fully deaerated. This decreases circulator O2 + Fe + 2H 2O Fe(OH )2 + H 2
efficiency and reduces the rate of heat conveyance by the FERROUS
OXYGEN IRON IONS WATER HYDROGEN
HYDROXIDE
system. Noise is also present as a mixture of liquid and air
bubbles pass through a circulator.
3Fe(OH )2 Fe
Fe3O4 + H 2 + H 2O
/NNQ 'D@S 3Q@MREDQ Air has much lower heat transfer FERROUS
HYDROXIDE MAGNETITE
MA
MAGNETIT
TE HYDROGEN WATER
Figure 2-6
BBDKDQ@SDC "NQQNRHNM Air is about 23% oxygen, and If oxygen continues to be present in the system, magnetite
oxygen in contact with ferrous metals such as steel and will be converted to hematite (Fe2O3), which can cause
cast iron causes corrosion. Many improperly deaerated pitting corrosion throughout the system.
6
Figure 2-7 shows a pipe and circulator with accumulated
iron oxide sludge. Consider the effect such accumulation Figure 2-8
would have on flow rate.
Figure 2-7a
spring-loaded
internal check
valve traps
rising air
in volute
Figure 2-7b
Figure 2-9
Courtesy of Heatboy
Circulators installed in vertical piping with upward dissolved gases released from solution
flow and having spring-loaded check valves near their create gaseous cavitation within circulator
discharge are especially susceptible to large pockets
7
of air. If a sufficient volume of air enters the volute and
displaces water in the impeller, the circulator may be Figure 2-10 air pocket
unable to clear itself and will quickly be running without
lubrication. Failure is almost certain.
Every hydronic system is completely filled with air at the The ability of a fluid to entrain air can be judged by its
start of its commissioning. As water enters the lower ability to move bubbles vertically downward, against their
portions of the system, air rises upward. However, some natural tendency to rise. If the fluid moves downward
components or improper piping configurations may not faster than a bubble can rise, it will pull the bubble along.
allow all the air initially contained in the system to rise A minimum flow velocity of 2 feet per second is needed
to the top where an air venting device may be present. to entrain air bubbles within downward-flowing pipes.
This results in trapped air pockets. These pockets
8
,("1.!4!!+$2 #(22.+5$# (1
Air can also exist in hydronic systems as microbubbles. Molecules of the gases that make up air (nitrogen,
Individually, most microbubbles are too small to be oxygen, carbon dioxide and some other compounds) can
seen by the human eye. However, dense collections of exist “in solution” with water molecules. Since molecules
microbubbles can make otherwise clear water appear are too small to be seen, water that appears perfectly
cloudy. A common place to see temporary clouds of clear and free of bubbles can still contain a significant
microbubbles is in a drinking glass just filled with water amount of dissolved gases that ultimately need to be
from a faucet having an aerator device. Figure 2-11 shows removed from the system.
a visually enhanced microscopic view of microbubbles.
The amount of dissolved gases that water can hold
Figure 2-11 depends on the water’s temperature and pressure. At
higher temperatures, the ability of water to contain
dissolved gases decreases, and vice versa. As the
pressure of the water increases, so does its ability to
hold dissolved gases in solution.
Source: www.urmc.rochester.edu
In hydronic systems, microbubbles form when water with Figure 2-12
dissolved gases such as oxygen and nitrogen is heated
in a boiler or other heat source. In chilled-water cooling Gauge pressure
Max amount in gallons of dissolved air per 100 gallons of water
9
As the pressure of the water is lowered, so is its ability For example, the ability of water to absorb air as it
to hold dissolved gases in solution. Figure 2-12 shows cools helps reduce the volume of stationary pockets in
that reducing the pressure of 170ºF water from 15 to 0 areas of the system where flow is slow. This absorbed
psi gauge pressure reduces the amount of dissolved air can be carried back to a high-efficiency separating
gas it can contain from 1.8% to about 0.6% of its device where it is then captured and ejected from the
volume. This explains why air bubbles are more likely system. The ability of water to absorb air can also cause
to form in the upper portions of a multi-story hydronic an undesirable condition called “water logging” in older
system. Lower static pressure in the upper portions of style expansion tanks without diaphragms or bladders.
the building makes it easier for dissolved air to come
out of solution. Higher static pressure near the bottom It’s always desirable to minimize the dissolved air
of the system tends to keep gases in solution. content of the system’s water. This is accomplished by
establishing conditions that encourage dissolved gases
Temperature also affects the solubility of dissolved gases to come out of solution (e.g., high temperatures and low
in water. Figure 2-13 shows a simple piping system with pressures), and placing an effective air separating device
representative temperatures and gauge pressures at four at a location where such conditions occur.
locations.
(11$,.5 +#$5("$2
The graph to the right of the piping schematic shows Most air removal devices used in hydronic systems can
the combination of temperature and gauge pressures be classified as either:
at these four locations. Notice that point A is the lowest
of the four points, and thus represents the lowest 1. High-point vents
solubility of air in water of the four locations. The lower 2. Central air separators
the solubility, the more likely microbubbles are present;
thus point A is the preferred location for the Caleffi High-point vents release air from one or more high points
Discal air separator. in the system where it tends to accumulate. Typical
locations for high-point vents are the top of each heat
Water can repeatedly absorb and release gases as its emitter, the top of distribution risers, the top of tanks or
temperature and/or pressure changes. This can affect hydraulic separators, or wherever piping turns downward
hydronic systems in several ways—some good and following an upward or horizontal run. Figure 2-14 shows
some not so good. some examples.
5.5
30 psi 45 psi 60 psi 75 psi 90 psi 105 psi
B C 18 psi 5.0
32 psi 169.9ºF
4.5
NOTE: pressures shown on
piping are gauge pressures 4.0
15 psi
ON
Discal air 3.5
separator
B
170ºF 3.0 D
2.5 C
20 psi 135ºF
2.0
0 psi
A
A
1.5
19.8 psi
D
VENT
1.0
0.5
low head loss boiler
0
32 65 100 135 170 205 240 275 310 345
10
Figure 2-14
air vent
manual air vent
air vent air vent
TRV
y
ra
ar
hydraulic
or
ct
separator
lle
co
r
la
manual air vent
so
TRV
manual
air vent air vent
manifold
buffer station
tank
Figure 2-15a
A central air separator is used to remove entrained air from a
flowing fluid, as well as to maintain the system at the lowest
possible air content.
, -4 + (15$-32
The simplest type of high-point venting device is a manual air vent.
These components are essentially small valves that thread into 1/8-
inch or 1/4-inch FPT tappings, and are operated with a screwdriver or
square head key. When opened, air moves through the valve seat and
exits through a small side opening.
Manual air vents are commonly installed at the top of each heat
emitter. An example of a manual air vent installed at the top of a panel
radiator is shown in Figure 2-15. Such vents are opened to release Figure 2-15b
air that rises to the high point as fluid enters lower in the system.
When the fluid level reaches the manual air vent, a small stream of
water will flow out the side of the vent. A small piece of flexible tubing
can be used to guide this stream into a can or pail. It’s important
to capture this water and not allow it to stain carpets or otherwise
damage surrounding materials. When a steady stream of water has
been flowing from the vent for several seconds, it should be closed.
After air has been removed from the system, be sure to check that the
system has adequate static water pressure.
11
fittings resemble a 90º elbow, but with
Figure 2-16a Figure 2-16b an extra port having either 1/8” or 1/4”
air vent FPT threads. They are typically installed
at high points where piping changes
baseboard tee
from vertical to horizontal. Their name
comes from a common application in
which they are mounted on the outlet of
a fin-tube element within a baseboard
convector, as seen in Figure 2-16b.
Minerals or sediment in the system water can interfere with the operation
of the internal hygroscopic disc. It is generally recommended that these
discs be replaced every three years. Caleffi hygroscopic air vents
contain an internal spring-loaded check valve that closes whenever the
upper portion of the vent body is removed, such as when changing the
fiber discs. This is illustrated in Figure 2-19c.
internal
disc
(WET)
Although hygroscopic air vents are automatic, they can be manually
opened and are therefore not recommended in locations where
tampering is possible. A float-type air vent is a preferred choice in such
locations.
12
Figure 2-19a Figure 2-19b Figure 2-19c
%+. 3 38/$ (15$-32 that this cap is loosened when the vent is put into
A float-type air vent provides fully automatic air release operation. If the cap is fully closed, the vent cannot
and instantaneous response to the presence of water. An operate. Caleffi vents can be equipped with Caleffi-
example of such a device is shown in Figure 2-20. specific “anti-siphon” caps that prevent airflow into the
vent if the pressure at the vent location drops below
atmospheric pressure.
Figure 2-20a Figure 2-20b
cap, (sealed when closed)
Float-type air vents are available in different sizes and
air outlet ports
shapes. Compact designs allow mounting within the
spring-loaded stem
valve seat & O-ring
enclosures of heat emitters, such as fin-tube convectors
linkage or fan-coils. Larger “high-capacity” vents are available for
air use at the top of central air separators, storage tanks, or
other locations where high-volume air venting is needed.
It’s important to remember that some float-type air vents can
also allow air to enter the system if the system pressure at
their installed location drops below atmospheric pressure.
This can happen as a result of improper placement of the
expansion tank relative to the circulator. It can also be
caused by low static pressure in the system. Caleffi anti-
water
siphon vent caps are designed to prevent this intake of air.
inlet
It’s good practice to design and commission all closed-
loop hydronic systems so there is at least 5 psi of
It contains an air chamber, a float assembly and an air positive static pressure at the top of the system. This
valve. As air accumulates within the chamber, the float ensures that float-type vents will always be able to expel
descends. A linkage attached to the float eventually any air that accumulates.
opens the valve mechanism at the top of the unit. As air is
released, water flows into the chamber and lifts the float to It’s also important to verify that the pressure rating of
close the valve. Some Caleffi float-type vents are equipped float-type air vents is suitable for the conditions and
with hygroscopic caps that seal the vent from water locations where they will be located in the system.
leakage, and thus provide secondary leak protection if the Hydronic systems that have piping installed over several
vent’s internal valve mechanism does not operate properly. building stories can generate high static pressure in the
lower portions of the system, where such vents may be
Most float-type air vents are equipped with a cap that located at the top of tanks, heat exchangers, hydraulic
protects the valve mechanism from debris. It’s important separators, boilers or other devices.
13
Figure 2-21a Figure 2-21b
"$-31 + (12$/ 1 3.12 the air removal efficiency of these devices, albeit at the cost
The ability to maintain very low air levels within a closed- of larger and more expensive hardware. Air purgers are not
loop hydronic system is vital to quiet, efficient and reliable designed to capture microbubbles, and as such, cannot
operation. The key component in providing this function is lower the dissolved air content of the system as well as
a central air separator. Such devices can be categorized separators specifically designed for this purpose. A cutaway
as either air purgers or microbubble air separators. illustration of a typical air purger is shown in Figure 2-21b.
Figure 2-21a shows an example of a cast iron air purger. ,("1.!4!!+$ (12$/ 1 3.12
These relatively simple devices encourage well-formed air Due to their small size and low buoyancy, microbubbles
bubbles to rise into a collection chamber and then pass are more difficult to capture relative to well-formed
out through a float-type air vent at the top of that chamber. bubbles or large air pockets. Doing so requires surfaces
They rely heavily on the buoyancy of well-formed bubbles upon which microbubbles can cling and eventually merge
as the means of separation. To achieve proper operation, into larger bubbles. This process is called coalescence
the velocity of the flow stream entering the separator must and is critically important to attaining and maintaining
be kept below 4 feet per second. Lower velocities increase minimum air levels in hydronic systems.
cap
air discharge valve
14
The surface on which microbubbles coalesce
Figure 2-23 is called the “coalescing media.” Some
microbubble air separators use metal meshes
for this media, while others use special
polymers. In either case, the coalescing media
must provide high surface contact area,
chiller enhancement of vertical bubble movement
and a relatively low pressure drop.
microbubble /+ "$,$-3.%"$-31 + (1
air separator
microbubble (vertical)
2$/ 1 3.12
air separator Central air separators work best when
(horizontal)
located where the solubility of dissolved
gases within the system water is lowest. In
heating systems, they should be mounted
near the outlet of the heat source (see Figure
VENT VENT
circulator
heating
DHW
15
(1, - &$,$-3
There are some situations in which it is not desirable to eject Air management maintains the internal air volume in its
air from a closed-loop hydronic system. Instead, the air in proper location within the system. In the system shown in
the system needs to be maintained in part of the system. Figure 2-25, any air that is captured by the microbubble
air separator is returned to the air-filled portion of the
A closed-loop solar thermal system using drainback system rather than being ejected from the system. This
freeze protection is one such situation. Consider the allows the pressurized closed-loop system to maintain
closed-loop, drainback protection solar combisystem its initial pressurization, since air is not being expelled
shown in Figure 2-25. from it. Likewise, when the collector circulator turns off,
air from the top of the tank moves back through the air
For drainback freeze protection to work, there must be return tube, and then up into the collector array. At the
air in the collectors and any exposed piping whenever same time, water within the collector array and exposed
the collector circulator is off. Total air elimination, as piping flows back down to the tank. No air is ejected
previously discussed, would defeat the purpose of from the system.
drainback freeze protection. However, the air in the
collectors and upper portion of the storage tank should Notice that there is no automatic makeup water assembly
not be allowed to find its way into the distribution system on this system. Such an assembly, if present, would
where it could potentially cause problems such as noise, eventually allow the system to fill with water should there
poor circulator performance or trapped air pockets. be an air leak at any point.
Thus, the air in the system must be “managed.”
Also note that there is no expansion
tank in this system. The captive air
Figure 2-25 volume at the top of the storage
Starmax V
tank, if properly sized, provides the
collectors volume needed to accommodate
the expansion volume of the
system’s water and serve as the
drainback space.
auxiliary boiler
air
pressure
adjust
air space
to / from
sightglass
distribution
ThermoCon tank
16
Figure 3-1 #(132$/ 1 3(.-
17
Similar fouling can occur with chillers and heat exchangers Figure 3-7
in chilled-water cooling systems.
Figure 3-9
18
DIRT SepARATION meTHODS: Figure 3-11
There are three common methods for capturing and
expelling dirt from hydronic systems:
Figure 3-10
19
Figure 3-13 Figure 3-15
6
5 1" Y-strainer
(70% plugged)
pressure drop (psi)
1" Y-strainer
2 (clean basket)
0
0 2 4 6 8 10 12 14 16
4
indication that the strainer should be cleaned. Ball valves
are installed to isolate the strainer so its basket can be 3
removed without significant fluid loss, as shown in Figure
1" Y-strainer
3-14. Flow through the system must be stopped during 2 (clean basket)
this cleaning procedure.
1 1" Dirtcal
+.6 5$+."(38 9.-$#(132$/ 1 3.12
0
Low-velocity-zone dirt separators allow gravity and 0 2 4 6 8 10 12 14 16
deflection to separate dirt particles from the flow stream.
The velocity of the flow stream entering such a separator
20
as the same Y-strainer with a basket that
is 70% plugged. Figure 3-17
Efficiency (%)
Lower head loss and pressure drop
Efficiency Efficiency
reduces the circulator power required
( Separated quantity
Initial quantity
.100%) 50 passages ( 2 f/s) 50 passages ( 4 f/s)
for a given flow rate. This reduces long-
100
term system operating cost.
0
through a low-velocity-zone dirt
Micro
(μm)
1000
105
150
210
250
500
16
35
63
10
20
50
separator affects performance. The 5
0
21
Figure 3-19 rotor can, preventing the powerful rare-earth magnets on or within the separator.
circulator from operating. Iron oxide particles are attracted to these magnets,
improving the capture efficiency of the separator. When
The high-efficiency wet- the magnetic portion of the separator is removed, the iron
rotor circulators that oxide particles along with other debris can be flushed out
are increasingly used in from the lower bowl of the separator.
hydronic systems contain
very strong rare earth Figures 3-20 and 3-21 show external and internal views
magnets within their of a Caleffi DirtMag magnetic dirt separator. Notice the
rotors, as demonstrated black collar near the bottom of the separator’s bowl. This
in Figure 3-18. They may collar contains powerful rare earth magnets that attract
also use closer spacing ferrous metal particles and hold them against the side of
between the rotor can and the brass body, which is nonmagnetic.
rotor to improve magnetic
coupling between the The permanent magnets used in this collar maintain
rotor and stator, which their full strength over time, allowing the separator to
improves motor efficiency. constantly attract and capture ferrous particles as they
form in the system.
Evidence suggests that
the long-term wire-to- Figure 3-22 Figure 3-23
water efficiency of these circulators can decrease by
20% or more due to accumulation of iron-based particles
within the circulator, as seen in Figure 3-19. Although
the circulator may still operate, it does so at reduced
flow and head relative to when first installed. In other
cases, the circulator can be completely stalled by the
accumulation of such particles.
22
Figure 3-24 Figure 3-26
distribution
piping
system
dirt
separator
VENT
Figure 3-27
Figure 3-25
air! system!
separator circulator
purge!
valve
magnetic!
dirt!
separator
23
Notice that purging valves have been located just
Figure 3-29
upstream of the dirt separator. This allows some of the
dirt in the system to be flushed out during initial filling brazed
and purging. This, in turn, decreases the amount of dirt -plate
the separator will eventually have to capture. heat dirt
exchanger separator
When possible, it’s also desirable to place the dirt
separator upstream of circulators. This helps extract dirt
before flow passes through the circulator. When doing so,
allow at least 12 pipe diameters of straight pipe between dirt
the outlet of the air separator and inlet of the circulator. separator
Some systems use multiple circulators to push flow
from different circuits into the boiler. In this case, the
compromise is to place the dirt separator upstream of the
boiler, as shown in Figure 3-28.
In systems with a main mixing valve, it’s best to place dirt
Figure 3-28 boiler separators in the return line from the distribution system
ahead of the valve. This increases flow through the
separator and better protects the mixing valve from dirt.
DHW DHW
heating heating
24
Figure 4-1 Figure 4-2 Figure 4-3
combined
air & dirt VENT
separator
chilled-water
Figure 4-4 air handlers
air vent
Combined air &
dirt separator variable-speed
pressure-regulated
circulator
balancing
valves
chiller
25
/+ "$,$-3.%".,!(-$# 2(9(-& (1#(132$/ 1 3.12
(1#(132$/ 1 3.12 The ability of an air separator, dirt separator or a
The preferred placement of a combination air & dirt separator combined air & dirt separator to remove the undesired
depends on the application and system piping. In heating materials from a stream of water depends on the flow
systems, preference should be given to air separation. The velocity of that stream. Slower flow velocities improve
preferred placement of the combined air & dirt separator is separation efficiency. For optimum performance, the
near the outlet of the heat source, as shown in Figure 4-3. pipe size for any of these separators should limit flow
This creates conditions favorable to air separation (e.g., velocity to 4 feet per second. Higher flow velocities of
higher fluid temperature and lower pressure). up to 10 feet per second are possible but will decrease
the efficiency of air and dirt separation. Separation will
In cooling systems, the preferred placement of the air still occur, but over a longer time. Figure 4-5 lists the
& dirt separator is near the return to the chiller plant, as nominal pipe size of separators along with the flow rates
shown in Figure 4-4. Water at this location has a slightly corresponding to flow velocities of 4 feet per second and
higher temperature compared to water leaving the chiller. 10 feet per second.
This improves the conditions under which microbubbles
can form. It also places the dirt separating function on the
inlet to the chiller plant, which reduces the potential of dirt
accumulation within the chiller.
Figure 4-5
BRASS STEEL
size 3/4" 1" 1.25" 2" 2.5" 3" 4" 5" 6" 8" 10" 12"
$"!
4 ft/sec 8.0 9.3 10.0 37.3 63 95 149 259 380 625 980 1410
GPM
$"!
10 ft/sec GPM 19.0 22.1 25.0 88.8 150 227 355 616 904 1570 2450 3530
26
/1(-"(/+$2.%'8#1 4+("2$/ 1 3(.-
Figure 5-2
circulator 1
Figure 5-3
common piping
head (gain or loss) (feet of head)
applies to this situation. The point where the blue circuit $" $"
" "#
head loss curve crosses the orange pump curve for are operating circuit operating
circulator 1 establishes the flow rate in circuit 1.
27
Figure 5-4 circulator 2
circuit 2
common piping
circuit 1
circulator 1
common piping
circulator 1
common piping circuit 1
The operating point of circuit 1 has moved very slightly + "*.%'8#1 4+("2$/ 1 3(.-
to the left and slightly upward. This implies that the flow Having stressed that hydraulic separation is desirable, it
rate through circuit 1 has decreased very slightly. This very is worthwhile to consider a situation in which hydraulic
small change in flow rate is indicated in Figure 5-3. Such separation is NOT present and observe the consequences.
a small change in circuit flow rate will have virtually no
effect on the ability of circuit 1 to deliver heat. Thus, the Consider the horizontal piping system shown in Figure 5-5.
interference created when circulator 2 was turned on is of no The larger circulator is sized to move sufficient flow through
consequence. Therefore, this situation provides acceptable the higher flow-resistance circuit including the high-flow-
hydraulic separation between the two circulators. resistance heat source. When operating, the flow created by
the large circulator creates a pressure drop of 5 psi between
One could imagine a hypothetical situation in which the head the supply and return headers connected to the heat source.
loss across the common piping was zero, even with both
circuits operating. Because no head loss occurs across the
Figure 5-5
common piping, it would be impossible for either circulator
small circulator
to have any effect on the other circulator. Such a condition
P=22 psi
would represent “perfect” hydraulic separation and would large circulator
be ideal. Fortunately, perfect hydraulic separation is not P=17psi
required to ensure that the flow rates through independently heat source
operated circuits, each with their own circulator, and each with high backseated
sharing the same low-head-loss common piping, remain check valve
P= 10 psi
ON OFF
reasonably stable, and thus capable of delivering consistent
heat transfer. In animated terms, the two simultaneously
P = 5 psi
operating circulators cannot “sense” each other’s presence
within the system, and thus operate as if they were each in
an independent circuit. P=12 psi
P=13 psi
One can think of (and design) circuits that are known to P=16 psi
have a high degree of hydraulic separation, as if they
were completely independent of each other, as illustrated
in Figure 5-4.
P=17 psi
The required hydraulic performance of each circuit can be
28
Figure 5-6 Figure 5-6 shows the pump curve for the
smaller circulator. Notice that the maximum
15
6 head added (feet) possible differential pressure this circulator
4 psi can create is 4 psi.
D
144
4 10
P = ( Head )
29
whenever two or more of the
Figure 5-8 secondary circuits are operating
simultaneously. Although there
are situations in which this
temperature drop doesn’t
present a problem, it does add
complications that designers
must assess and compensate for.
vertical air separator
One way to overcome the
secondary circuits
series temperature drop effect
associated with series primary
loops is to create a parallel
primary loop, as shown in Figure
5-9.
boiler
circulator A parallel primary loop is divided
into two or more “crossover
bridges.” A pair of closely spaced
tees within each crossover bridge
VENT
provides hydraulic isolation
between each secondary circuit
closely closely closely closely and the parallel primary loop.
spaced primary spaced spaced spaced
tees circulator tees tees tees
Unlike a system with a series
series primary loop
primary loop, a system with a
parallel primary loop provides
magnetic essentially the same supply water
dirt separator temperature to each secondary
circuit, regardless of which
secondary circuits are operating.
This benefit is achieved through
the secondary circulator operates. Because the flow more complicated and costly
created by the primary circulator does not induce flow piping. Notice that each crossover bridge contains a
in the secondary circuit, nor does it have any significant flow-balancing valve. These valves are needed to set
effect on the flow in the secondary circuit when its the flow through each crossover bridge in proportion
secondary circulator is operating, these two circuits are to the thermal load served by the secondary circuit
hydraulically separated from each other. supplied from that bridge. If these valves are not present
and properly adjusted, there may be problems such as
This concept can be extended to multiple secondary inadequate flows through the crossover bridges located
circuits served by a common primary loop, as shown farther away from the primary circulator.
in Figure 5-8. Each secondary circuit, including the
secondary circuit through the boiler, is joined to the Another important consideration is that both series and
primary circuit using a pair of closely spaced tees to parallel primary/secondary systems require a primary
provide hydraulic separation. circulator. This circulator adds to the installed cost of
the system. More importantly, it adds to the system’s
The configuration shown in Figure 5-8 is more precisely operating cost over its entire life. Even one small primary
called a series primary/secondary system. With this loop circulator in a system can have operating costs that
approach, all secondary circuits are arranged in a total more than $1,000 over a typical 20-year design
sequence around the common primary loop. life. Larger primary loop circulators can have life-cycle
operating costs of several thousand dollars.
Although hydraulic separation exists between all circuits,
so does an often-undesirable effect—a drop in supply For example: Consider a primary loop circulator that must
water temperature from one secondary circuit to the next produce a flow rate of 50 gpm, with a corresponding
30
head of 15 feet (which is evidenced by a pressure gain Furthermore, if the cost of electricity were to inflate at 4%
of 6.35 psi across the circulator). Assume the circulator each year, the total operating cost of this circulator over a
is a typical wet-rotor design and has a wire-to-water 20-year period would be:
efficiency of 25% at these operating conditions. The
estimated input power to operate this circulator is:
boiler
circulator
primary
circulator
VENT
closely
spaced closely
tees spaced
tees
balancing
valves
magnetic
dirt separator
31
,.#$1-,$3'.#2.% Nearly all cast iron sectional boilers have large chambers
'8#1 4+("2$/ 1 3(.- through which water moves very slowly as it passes
from the boiler’s inlet to its outlet. These slow internal
Any component or combination of components with very velocities create very low head loss through the boiler,
low head loss, and common to two or more hydronic even when all the zone circulators are operating. If this
circuits, can provide hydraulic separation between those type of boiler is combined with low-head-loss header
circuits. piping, as discussed in the previous section, the resulting
combination creates low-head-loss common piping for
One way to create low head loss is to keep the flow path the zone circuits. This, along with a very simple piping
through the common piping very short. Another way to arrangement, provides the necessary conditions for
create low head loss is to significantly reduce the flow hydraulic separation.
velocity through the common piping.
When modulating/condensing boilers were first introduced
Examples of devices that use these principles include: to North America, many of them used compact internal
heat exchangers that created much higher head loss in
1. A heat source that has very low head loss comparison to traditional cast iron boilers. Some of these
2. A pair of closely spaced tees boilers were installed using the same piping arrangement
3. A buffer tank with specific piping arrangement that was common practice with cast iron boilers, as
4. A hydraulic separator shown in Figure 6-2.
5. Specialty components such as a Caleffi HydroLink
Figure 6-2
Each of these methods can provide hydraulic separation
high-head-loss boiler
between simultaneously operating circulators, as well as
equal supply water temperature to each load circuit.
Figure 6-1
VENT
low-head-loss
common piping
low-head-loss
headers
The high head loss of the mod/con boiler significantly
increased the overall head loss of the common piping and
largely negated the hydraulic separating characteristic
attained in systems using the older style, low-head-
VENT
32
their compact heat exchangers.
Figure 6-3 Piping methods were modified
to correct this problem. These
methods will be discussed shortly.
tees
boiler low-head-loss separation between any two or
circulator common piping more of the circulators connected
to the headers.
33
Figure 6-5 flow velocity creates minimum head loss, while also allowing
Tube/pipe size Flow rate at Flow rate at for air bubble entrainment. The latter is useful when air bubbles
2 ft/sec 4 ft/sec need to be forced downward in a vertical header during
system commissioning.
1” M copper 5.5 gpm 10.9 gpm
Figure 6-5 lists the flow rates corresponding to flow velocities
1.25” M copper 8.2 gpm 16.3 gpm of 2 feet per second and 4 feet per second for type M copper
tubing in sizes from 1-inch to 5-inch, and in schedule 40
1.5” M copper 11.4 gpm 22.9 gpm steel for larger pipe sizes. For other piping materials or sizes,
the flow rate corresponding to a given flow velocity can be
2” M copper 19.8 gpm 39.6 gpm calculated using Formula 6-1.
2.5” M copper 30.5 gpm 61.1 gpm Formula 6-1:
3” M copper 43.6 gpm 87.1 gpm d2
f = v i
0.408
4” M copper 75.9 gpm 152 gpm
Where:
5” M copper 118 gpm 236 gpm v = average flow velocity (ft/sec)
f = flow rate (gpm)
6” schd. 40 steel 180 gpm 361 gpm di = exact inside diameter of pipe (inches)
8” schd. 40 steel 312 gpm 624 gpm With proper hydraulic separation, such as shown in Figure 6-4,
it is possible to combine circulators with significantly different
10” schd. 40 steel 492 gpm 984 gpm pump curves on the same header system. It is also possible
to combine fixed-speed and variable-speed circulators on the
12” schd. 40 steel 699 gpm 1397 gpm
same low-head-loss headers.
34
Figure 6-7
Figure 6-9 shows the external appearance of several
Caleffi hydraulic separators. The front portion of the
insulation shell has been removed from the two smaller
separators. The large, self-supporting hydraulic separator
is awaiting site-installed insulation.
Figure 6-8
boiler with high-
head-loss
characteristic
boiler
circulator
VENT
hydraulic
separator
35
sufficient air collects at the top of the
Figure 6-10 body, the float-type air vent allows it to be
ejected from the system. Thus, a hydraulic
separator can provide air separation.
diameter = 2"
" Second, the reduced flow velocity
area = A inside the hydraulic separator allows dirt
particles to drop into a collection chamber
at the bottom of the body. A valve at the
bottom can be periodically opened to
diameter = 6" flush out any accumulated dirt. Thus, the
"
area = 9A
" hydraulic separator also serves as a dirt
!
removal device.
"
"
The efficiency of both air and dirt separation
is enhanced through use of a coalescing
media in the active flow zones, which are
in line with the side ports of the separator.
These are shown in Figure 6-11.
36
Figure 6-12
HydroCal
distribution
boiler circuit heating
system
load(s)
air
separator
distribution
system
boiler
closely
circuit heating
spaced
load(s)
tees
dirt
separator
37
Figure 6-16
Figure 6-14
existing cast iron radiators
mod/con boiler (converted from steam)
w/ compact heat exchanger
vent
ECM
pressure- thermostatic
regulated radiator
circulator valve
(each rad.)
Courtesy of Tweet / Garot Mechanical, Inc.,
supply temperature Greenbay, Wisconsin
sensor (in well)
existing piping Given the surface area of their bodies,
hydraulic separators should always
be insulated to minimize heat loss to
VENT
Hydraulic separators
are available in pipe
sizes from 1-inch to
over 12-inch. The
“size” of a hydraulic
Courtesy of Osborne Company Courtesy of Dan Schlicher
38
Figure 6-18
1" 1.25" 1.5" 2" 2.5" 3" 4" 5" 6" 8" 10" 12"
37(union)
11 18 26 80 124 247 300 484 792 1330 1850
The temperatures at the two outlet ports of a hydraulic In this case only:
separator (e.g., ports 2 and 3 in Figure 6-19) depend on
the temperatures at the two inlet ports (e.g., ports 1 and 4
T1 = T2
in Figure 6-19), as well as the flow rates in both the boiler T3 = T4
circuit and distribution system.
39
There are three possible cases: returning to the heat source from port 3 equals the
temperature returning from the distribution system into
1. Flow in the distribution system is equal to flow in the port 4. Again, very little mixing takes place within the
boiler circuit separator. Dirt particles carried into the separator at port
2. Flow in the distribution system is greater than flow in 4 will settle to the bottom of its body, where they can be
the boiler circuit periodically flushed out through the drain valve.
3. Flow in the distribution system is less than flow in the
boiler circuit If a conventional boiler (e.g., one that is not intended to
operate with sustained flue gas condensation) is used, the
"@RD ū #HRSQHATSHNM EKNV DPT@KR ANHKDQ EKNV This designer should verify that the water temperature on the
situation tends to be the exception rather than the norm. return side of the distribution system is high enough to
It is illustrated in Figure 6-20. prevent sustained flue gas condensation within the boiler.
The use of a hydraulic separator in itself does not guarantee
The flow and temperature leaving port 2 of the hydraulic that the water temperature entering the boiler will be high
separator is the same as the temperature of the hot water enough to prevent sustained flue gas condensation.
entering port 1. Very little internal mixing occurs because
the flows are balanced. Because of its buoyancy, the "@RD ū #HRSQHATSHNM RXRSDL EKNV HR FQD@SDQ SG@M
hot water entering port 1 remains near the top of the ANHKDQ EKNV Since the flow rates in the boiler circuit and
hydraulic separator. Most of the air bubbles carried into distribution system are not the same, mixing occurs within
port 1, or that form within the hydraulic separator, rise to the hydraulic separator. In this case, a portion of the cooler
the top of the unit and are ejected through the air vent. water returning from the distribution system moves upward
through the separator and mixes with the hot water
A similar situation exists at the lower ports of the separator. entering from the boiler, as shown in Figure 6-21.
Since the flows are balanced, the outlet temperature
This mixing reduces the water temperature supplied to
the distribution system. This is not necessarily a bad
Figure 6-21 thing, but the designer needs to realize it can occur and
plan accordingly.
40
same time, the boiler flow rate is 10 gallons per minute, "@RD ū #HRSQHATSHNM RXRSDL EKNV HR KDRR SG@M ANHKDQ
and the water temperature supplied to port 1 is 160ºF. EKNV Again, since the flow rates on opposite sides of the
Determine the mixed water temperature leaving port 3. hydraulic separator are not equal, mixing will occur inside
Also, what is the water temperature returning to the boiler? the separator. In this case, a portion of the hot water
entering from the boiler circuit moves downward through
The mixed water temperature is found using Formula 6-2: the separator and mixes with cool water entering from the
distribution system, as shown in Figure 6-23.
( f f ) T + ( f1 ) T1 ( 25 10 )120 + (10 )160
T2 = 4 1 4 = = 136º F
f4 25
Figure 6-23
Notice that the water temperature supplied to the
distribution system (136ºF) is substantially lower than the
water supplied from the boiler (160ºF). This is the result of
mixing within the hydraulic separator.
Figure 6-22
boiler
supply ( f f ) T + ( f4 ) T4
temperature T3 = 1 2 1
sensor in well f1
41
Where: If the system uses a conventional (non-condensing) boiler,
T3 = temperature of fluid returned to the boiler(s) (ºF) one might consider the boost in boiler return temperature
f1 = flow rate entering from boiler(s) (gpm) beneficial because it moves the boiler operating condition
f2, f4 = flow rate of the distribution system (gpm) away from potential flue gas condensation. However, this
T1 = temperature of fluid entering from boiler(s) (ºF) temperature boost effect can quickly diminish if flow through
T4 = temperature of fluid returning from distribution the distribution system increases (i.e., more load circuits
system (ºF) turn on), or if the return temperature of the distribution
system drops. Use of a hydraulic separator alone does not
Assume the boiler supply temperature is 170ºF, and that prevent flue gas condensation under all circumstances.
boiler flow rate into port 1 of the hydraulic separator is
15 gallons per minute. Water returns from the distribution $7/ -2(.-3 -*/+ "$,$-31$+ 3(5$
system and enters port 4 of the hydraulic separator at 3.3'$'8#1 4+("2$/ 1 3.1
100ºF and 10 gallons per minute flow rate. What is the Because there is very little head loss across a hydraulic
water temperature returned to the boiler? separator, vertically or horizontally, the system’s expansion
tank can be teed into the piping near any of the separator’s
Substituting these operating conditions into Formula 4 main ports. The lower ports are preferred because they
6-2 yields: expose the expansion tank to lower temperature fluids
compared to the upper ports. Figure 6-24 shows both of
( f f ) T + ( f4 ) T4 (15 10 )170 + (10 )100
T3 = 1 2 1 = = 123.3º F
these options.
f1 15
The system’s expansion tank should not be connected to
Notice that the boiler inlet temperature is about 23ºF the bottom of the hydraulic separator. This would allow
higher than the return temperature of the distribution dirt to migrate from the bottom of the separator into the
system. This is caused by mixing within the hydraulic expansion tank, where it will accumulate on top of the
separator. tank’s diaphragm.
Figure 6-24
makeup
makeup
VENT VENT
makeup VENT
water
water water subsystem
subsystem subsystem
expansion
expansion expansion
tank
tank tank
42
outdoor '8#1 4+("2$/ 1 3(.-6(3'
Figure 6-25 temperature ,4+3(/+$!.(+$12.1"'(++$12
sensor Hydraulic separators are ideal for use with multiple boiler
boiler systems. Figure 6-25 shows an example.
multiple
system
boiler
controller
system The headers supplying the boilers should be sized
for minimal head loss. A suggested sizing criteria is a
flow velocity of 2 to 4 feet per second when all boiler
circulators are operating.
to loads
The hydraulic separator allows the boiler side flow rate
to be significantly different from the distribution side flow
Figure 6-26
hydraulic
separator
VENT
Figure 6-27
rejected heat rejected heat
VFD
chiller #2 chiller #1
HydroCal with
insulation shell
FlowCal valve
motorized
to / from
ball valve purging chilled-water
valves cooling system
43
rate. It also allows for efficient air and dirt separation /1.#4"326(3'(-3$&1 3$#
within the system. Figure 6-26 shows an example of this '8#1 4+("2$/ 1 3(.-
type of system.
The principle of hydraulic separation combined with
Each boiler has its own circulator and check valve. This uniform supply water temperature to distribution circuits
makes it possible to stop flow through boilers that are not is desirable in both large and small hydronic systems.
operating, and thus stop unnecessary heat loss. It also
allows for partial heat delivery to the hydraulic separator Caleffi Hydro Separators are ideal for medium to large
if one of the boilers, or one of the boiler circulators, is not systems. Currently available models range from 1-inch to
responding. 12-inch pipe size connections.
This piping arrangement is also suitable for multiple For smaller systems, Caleffi offers products that integrate
chillers in chilled-water cooling systems, as shown in the principle of hydraulic separation with the functionality
Figure 6-27. of distribution headers. One example is the Caleffi
HydroLink, shown in Figure 7-1.
Notice that the chilled water from the chillers flows into
the lower side connection of the hydraulic separator. Figure 7-1
The somewhat warmer “chilled” water returning from the
distribution system flows into the upper side connection.
This arrangement creates more favorable conditions for
air separation at the top of the hydraulic separator and
minimizes the potential for dirt being carried into the
chillers.
44
Figure 7-2
opening
closely
opening spaced
tees
s
lace
rep
hydraulic
separation
chamber
THIS
vent
s
lace
rep
HYDROLINK
closely
spaced
tees
drain
A typical configuration for the HydroLink has the heat of the primary chamber for mounting an air vent and drain
source connected to the “primary” chamber piping valve/makeup water assembly, as shown in Figure 7-5.
on the left side of the unit, along with several load
circuits connected to the other “secondary” connections The HydroLink product is supplied with a form-fitting
that connect into the manifold chamber. Two additional insulation shell to minimize heat loss.
tapped connections are provided in the top and bottom
45
Figure 7-5 Figure 7-7
boiler
vent
circulators w/
check valves
HydroLink
purge
drain
VENT
valves
circulator
mixing
valve
Figure 7-6
46
Figure 7-8
distribution
manifold station distribution manifold station
variable-speed
pressure-regulated FloCal FloCal
circulator
zone valve zone valve
purging valve
station. The “crossover” tubes just above the isolation valve within each distribution manifold station allows the
ball valves on each manifold station allow hydraulic possibility of high-temperature supply water from the
separation between the built-in manifold station circulator header system. This, in combination with the relatively
and the variable-speed pressure-regulated circulator that low return water temperature that is typical of many
supplies flow in the headers. This arrangement also allows radiant panel systems, allows a low flow rate between the
the option of continuous flow through the distribution headers and manifold station, which minimizes pipe size
circuits connected to the manifold stations. The mixing and circulator power requirements.
47
the SEP4 separator and flowing onward to the space-
$7 ,/+$2823$,2
heating zones. This allows the boiler to respond to
any variations in the water temperature supplied to the
This section shows several examples of how air, dirt and
distribution system. The secondary circulator operates in
hydraulic separation can be applied in modern hydronic
a constant differential pressure mode and automatically
heating and cooling systems.
changes speed as required depending on the number
of active space-heating zones. Each zone circuit is
$7 ,/+$2823$,ū equipped with a Caleffi FlowCal balancing valve to assure
The system shown in Figure 8-1 uses a modulating/
properly proportioned flow.
condensing boiler to supply two zones of low-temperature
radiant panel heating, as well as an indirect domestic
Upon a call for domestic water heating, the ZVR103
water heater.
operates the boiler in setpoint mode to create a higher
supply water temperature, which allows for full boiler
The limited zoning in this system provides a good match
output to be transferred to the heat exchanger coil inside
between the modulating output of the boiler and the
the indirect water heater. The ZVR103 also turns off the
space-heating loads. Thus, the system is able to operate
system circulator, temporarily stopping any heat transfer
without a buffer tank.
to the space-heating zones.
Upon a demand for heating from either zone thermostat,
The SEP4 provides hydraulic separation between the
the Caleffi ZVR103 relay center powers on the associated
fixed-speed system circulator and the variable-speed
zone valve and turns on the variable-speed pressure-
secondary circulator. It also provides high-efficiency air
regulated secondary circulator, as well as the system
and dirt separation, including magnetically enhanced dirt
circulator. The boiler operates based on outdoor reset
separation. The latter is desirable because of the high-
control and monitors the temperature of the water exiting
efficiency circulator used in the system.
Figure 8-1
mod/con ZVR103
boiler
outdoor
temperature
sensor
Quicksetter
balancing
valves
DHW
CW
secondary
SEP4 circulator
system
circulator
priority
circulator
indirect water heater
48
$7 ,/+$2823$,ū
The system shown in Figure 8-2 uses a single modulating/ A DirtMag separator with an integral magnetic collar is
condensing boiler to supply space heating and domestic mounted on the piping leading into the boiler and boiler
hot water. circulator. Its use helps ensure that the high-efficiency
variable-speed circulator, as well as the small heat
Space heating is supplied by several panel radiators, exchanger passages inside the boiler, remain clear of
each of which is equipped with a thermostatic radiator ferrous metal particles and other debris.
valve allowing it to operate independently of the other
panels. Because of the extensive zoning, a small buffer Domestic hot water is heated by an indirect water heater
tank is used to prevent boiler short cycling. This buffer that is controlled as a priority load by the boiler’s internal
tank, when piped as shown, also provides hydraulic control circuitry.
separation between the boiler circulator and the variable-
speed pressure-regulated distribution circulator. $7 ,/+$2823$,ū
Hydraulic separators can be well-applied in modern
A vertical Discal air separator is mounted just below the geothermal heat pump systems. One example is shown
boiler’s outlet port, where the water is hottest and near it in Figure 8-3.
lowest pressure. This encourages microbubble formation,
capture and elimination from the system. The HydroCal separator shown in Figure 8-3 provides
hydraulic separation between the earth loop circulator
A float-type air separator is mounted at the top of the and the variable-speed pressure-regulated circulator
buffer tank to prevent air entrapment. that provides flow to the heat pumps. This allows for a
different flow rate in the earth loop compared to those
Manual air vents are located in the upper left corner of to the heat pump array. The flow rate to the heat pump
each panel radiator to expedite air removal at system array is controlled by the variable-speed pressure-
commissioning. regulated circulator, which responds to the opening and
Figure 8-2
TRV TRV
mod/con boiler
thermostatic
radiator valves
(TRV) on each
radiator
TRV TRV
Discal
DHW
DirtMag
temperature
sensor
(in well) variable-speed
pressure-regulated
distribution circulator
temperature
sensor TRV
(in well)
buffer tank
49
closing of zone valves or motorized
Figure 8-3 ball valves on each heat pump.
The earth loop circulator could
power required by the earth loop
circulator to be reduced as the
TXV number of operating heat pumps
decreases.
!
$7 ,/+$2823$,ū
The system shown in Figure 8-4
uses a Caleffi HydroLink as the
“hub” of a multi-temperature/multi-
load system.
50
Figure 8-4
to/from zones to/from zones
manifold valve
actuators on
each circuit
HydroMixers
vertical Discal
air separator future
load
HydroLink
3-way
thermostatic
mixing valve
VENT
air handler
the manifold station as the manifold valve actuators the domestic water heating mode to operate with a
open and close in response to zone thermostats. The single circulator.
supply water temperature from each HydroMixer can be
independently adjusted. The mixing can be done with To minimize thermal migration, spring-loaded check valves
either a thermostatic valve or motorized 3-way valve. are provided in the piping returning to the boiler from both
the indirect water heater and from the HydroLink.
The HydroLink also supplies hot water directly to the coil
of an air handler, which operates as a separate zone. A vertical Discal air separator provides high performance
air separation whenever heated water is flowing from the
The indirect water heater is operated as a priority load. boiler. Likewise, a vertical Dirtcal separator provides dirt
It is not connected through the HydroLink. This reduces separation for all flow about to pass into the boiler.
the amount of piping and water that must be heated
during a call for domestic water heating. It also allows
51
boiler #1 boiler #2
Figure 8-5
low-head-
loss headers
system
mixing mixing
circulator
VENT
52
Figure 8-5 shows how a larger Caleffi HydroCal separator Figure 8-7
can be used in combination with low-head-loss headers
to combine these boilers. The HydroCal unit provides
hydraulic separation between the boiler circulators and
the system circulator. It also provides high-efficiency air
and dirt separation for the system. The low-head-loss
headers in combination with the HydroCal separator
provide hydraulic separation between the individual boiler
circulators.
24,, 18
For optimal performance, modern hydronic systems
require several types of separating devices. These
include air separation, dirt separation, and in many
cases, hydraulic separation. The latter eliminates
undesirable interaction of simultaneously operating
Courtesy of GOES Heating Systems circulators. This issue of idronics has discussed the best
available technology for providing these functions. When
properly implemented, these functions allow the system
Figure 8-7 shows another example of a large (8” pipe size)
to operate without the detrimental effects of entrapped
Caleffi hydraulic separator that has been fully insulated.
air, accumulating debris and inconsistent flow.
Large hydraulic separators have several square feet of
surface area. Without insulation, this surface area would
create a high rate of heat loss and needlessly overheat
the mechanical room.
53
//$-#(7 /(/(-&28,!.++$&$-#
"#
circulator !
! "):-4
spring-loaded
VENT
preventer
gate valve check valve
pressure-
reducing distribution
globe valves purging valve valve station
cap metered
thermoelectric ThermoCon
balancing thermostatic
zone valve buffer
valve radiator valve
(2 way) tanks (4 sizes)
dual isolation
" valve for
brazed-
! panel radiators
plate
heat differential
exchanger pressure
bypass valve
DIRTCAL
dirt
separators
Comp.
DIRTMAG
dirt
separators Hydro
SEP4
Separator
heating mode
reversible HydroCal
water-to-water Separator
heat pump
DISCALDIRT DISCALDIRTMAG
reversing conventional boiler HydroCal
valve air & dirt air & dirt
Separator
separator separator
evaporator
condenser
FLOCAL DISCALDIRT
balancing air & dirt mixing units
TXV valve separator "-,9&2/ 1(-,0
QuickSetter
balancing solar
valve w/ circulation
:-4+$1$/ station
motorized
ball valve
(2 way)
Modulating / condensing boiler
high-temperature high-
solar air vent temperature
ThermoBloc™
solar
high-temperature expansion
shut-off valve for tank
4--#9/$#!-(*$/ solar air vent
indirect water heater (with trim)
54
FlowCal™ Y-strainer
Function
The FlowCal™ 120 series Y-strainers include a combination Y-strainer
with integral brass ball valve. Inspection, cleaning and replacing the
strainer cartridge can be done easily without removing the body from
the pipeline. All configurations are available with optional factory-
installed pressure and temperature test ports. Drain valves are also
available as an accessory for installing in the drain port connection.
Product range
120 series FlowCal™ Y-strainer with connections............... 1/2", 3/4", 1", 1-1/4" NPT female union x NPT female union; sweat union x sweat
538202 FD Drain valve for field installation in 1/2", 3/4" 120 series drain port...........................................................connection 1/4" NPT male
538402 FD Drain vlave for field installation in 1", 1-1/4" 120 series drain port...........................................................connection 1/2" NPT male
NA10233 Fast-plug pressure/temperature test port for 120 series Y-strainer, standard length 1-1/2".....................connection 1/4" NPT male
NA10235 Fast-plug pressure/temperature test port for 120 series Y-strainer, extended length 2-1/4".....................connection 1/4" NPT male
E
Connections - main: 1/2", 3/4", 1", 1-1/4" NPT female union x
NPT female
D
A
FFI
LE
CA
55
®
dirt separator
Product range
5462 series DIRTCAL® dirt separator for horizontal pipes, in brass.....................................connections 3⁄4" to 2" NPT female and 1" to 2" sweat
5465 series DIRTCAL® dirt separator for horizontal pipes, in steel..................................................................connections 2" to 4" ANSI flanged
NA5465 series DIRTCAL® dirt separator for horizontal pipes, in steel, ASME & CRN...........................................connections 2" to 6" ANSI flanged
Technical specifications
Brass DIRTCAL® Steel DIRTCAL®
,@SDQH@KR - body, dirt collection chamber and top plug: brass ,@SDQH@KR- body: epoxy resin painted steel
- internal element: glass reinforced nylon PA66G30 - internal element: stainless steel
- seal: EPDM - hydraulic seal: fiber
- drain valve: brass - drain valve: brass
/DQENQL@MBD
/DQENQL@MBD Suitable fluids: water, glycol solution
Suitable fluids: water, glycol solution Max. percentage of glycol: 50%
Max. percentage of glycol: 50% Max. working pressure: 150 psi (10 bar)
Max. working pressure: 150 psi Temperature range without insulation: 32—250°F (0—120°C)
Temperature range: 32–250°F Particle separation capacity: to 5 μm (0.2 mil)
Particle separation efficiency: to 5 μm "NMMDBSHNMR - flanged: 2"– 6" ANSI B16.5 150 CLASS RF
"NMMDBSHNMR - main: 3/4", 1", 1-1/4", 1-1/2" and 2" NPT female - top: 3/4" M (with plug)
1", 1-1/4", 1-1/2" and 2" sweat - drain: 1" NPT
- top: 1/2" F (with plug)
- drain: 3/4" garden hose connection FDMBX@OOQNU@K - NA5465 series designed and built in accordance
- vertical: hose connection with Section VIII, Division 1 of the AMSE Boiler and Pressure Vessel
Code and tagged and registered with the National Board of Boiler and
Pressure Vessel Inspectors, CRN Registered.
56
Operating principle Separation efficiency
The dirt separator operating principle The capacity for separating the dirt in the medium circulating in the
is based on the combined action of a closed circuits of the hydronic systems depends on three factors:
1
number of physical phenomena. The 1. It increases as the size and mass of the dirt particle increases.
internal element (1) is composed of a The larger and heavier dirt particles drop before the lighter ones.
set of concentric diamond pattern mesh
2. It increases as the fluid velocity decreases. If the velocity decreases,
surfaces. The dirt in the water strikes
there is a low-velocity-zone inside the dirt separator and the dirt
these surfaces, separates and drops
particles separate more easily.
into the bottom of the body (2) where
they collect. In addition, the large internal 2 3. It increases as the number of recirculations increases. The medium
volume of DIRTCAL® slows down the in the circuit, flowing through the dirt separator a number of times
velocity of the medium and with the 3 during operation, is subjected to a continuous separation, until the
help of gravity, separates the contained dirt particles are completely removed.
particles. 4 The special design of the internal mesh element in the Caleffi DIRTCAL®
The collected dirt can then be dirt separator, is able to completely separate the dirt particles in
discharged, even with the system the circuit down to a minimum particle size of 5 μm (0.2 mil). The
adjacent graph illustrates how DIRTCAL® quickly separates nearly all
running, by opening the drain valve (3)
with the handle (4). the dirt particles. After only 50 recirculations, approximately one day
of operation, up to 100% is effectively removed from the circuit for
particles of diameter greater than 100 μm (3.9 mil) and on average up
Dimensions to 80% taking account of the smallest particles. The continual passing
of the medium during normal operation of the system gradually leads to
complete dirt removal.
NPT B Sweat B
2”
A
A
Efficiency (%)
Efficiency Efficiency
( Separated quantity
Initial quantity
.100%) 50 passages (1.6 f/s) 50 passages (3.2 f/s)
C
100
80
1¼”
1¼”
60
40
"NCD ! C 6S KA
20
05A ⁄4" NPT
3
45⁄16" 5" 4.2
0
06A 1" NPT 45⁄16" 5" 4.2
particle
Micro
(Δm)
1000
105
150
210
250
500
16
35
63
10
20
50
5
0
B "@O
G "NCD ! C # $ % & ' J* * 6S KA
F@K
50A 2" 133⁄4" 1" 143⁄4" 247⁄16" 6 5⁄8" ⁄4"
3
6" 6 5⁄16" 12" 1.8 29
60A 2 ⁄2"
1
13 ⁄4"
3
1" 14 ⁄4" 24 ⁄16" 6 ⁄8"
3 7 5
⁄4"
3
7" 6 ⁄16"
5
12" 1.8 32
80A 3" 183⁄8" 1" 171⁄8" 291⁄8" 8 5⁄8" ⁄4"
3
71⁄2" 7 5⁄16" 13 3⁄8" 4.8 51
H
BI-DIRECTIONAL
57
®
DISCAL
air and dirt separator
m- RDQHDR CALEFFI
3DBGQDE
Function
Air and dirt separators are used to continuously remove the air and debris
contained in the hydronic circuits of heating and cooling systems. The air
discharge of these devices is very high. They are capable of automatically
removing all of the air present in the system down to the micro-bubble
®
level. The DISCALDIRT air and dirt separator also separates any solid
impurities in the system. The impurities collect at the bottom of the device
and can be removed through the drain pipe for the steel versions, to which
a separately sourced drain valve can be mounted, or drain shut-off valve
for the brass version. The circulation of fully de-aerated and cleaned water
enables the equipment to operate under optimum conditions, free from
noise, corrosion, localized or mechanical damage.
Insulation shells are available separately for field installation for the brass
®
DISCALDIRT air and dirt separators.
Product range
®
5460 series DISCALDIRT air and dirt separator in brass..........................................................connections 3/4", 1", 1-1/4" sweat & 1" NPT male
®
546 series DISCALDIRT air and dirt separator in steel with flanged connections..........................................................connections 2"–6" ANSI
®
NA546 series DISCALDIRT air and dirt separator in steel with flanged connections...................................................connections 2-1/2"–12" ANSI
*Prefix NA are designed and built in accordance with Section VIII, Division 1 of the ASME Boiler and Pressure Vessel Code and
tagged and registered with the National Board of Boiler and Pressure Vessel Inspector; CRN registered
Technical specifications
Brass DISCALDIRT® Steel DISCALDIRT®
,@SDQH@KR - body: brass ,@SDQH@KR - body: epoxy resin painted steel
- dirt separation chamber: brass - air vent body: brass
- air vent body: brass - internal element: 304 stainless steel
- internal element: glass reinforced nylon, PA66GF30 - air vent float: PP
- air vent float: PP - air vent float guide pin: stainless steel
- air vent float guide pin: stainless steel - air vent float linkages: stainless steel
- air vent float linkages: stainless steel - spring: stainless steel
- spring: stainless steel - seals: EPDM
- seals: EPDM - side drain shut-off valve: brass
- drain shut-off valve: brass /DQENQL@MBD
Suitable fluids: water, glycol solution
/DQENQL@MBD Max. percentage of glycol: 50%
Suitable fluids: water, glycol solution Max. working pressure: 150 psi
Max. percentage of glycol: 50% Temperature range: 32–250°F
Max. working pressure: 150 psi Particle separation efficiency: to 5 μm (0.2 mil)
Temperature range: 32–250°F "NMMDBSHNMR - flanged (ASME & CRN registered):
Particle separation efficiency: to 5 μm (0.2 mil) 2"–12" ANSI B16.5 150 CLASS RF
- flanged: 2"–6" ANSI B16.5 150 CLASS RF
"NMMDBSHNMR - main: 3/4", 1", 1-1/4" sweat; 1" NPT male - drain pipe: 2"–6": 1" NPT male
- drain shut-off valve: hose connection 8"–12": 2" NPT male
58
Dimensions
F
C
B
C 3 1/8”
D
E
38552
A
E
F
A
D
H
G
B
"@O 6S KA
"NCD ! C # $ % & ' F@K
050A 2" 13 ⁄4"
3
2 ⁄16"
3
14 ⁄16"
9
28 ⁄4"
1
6 ⁄8"
5
1" 13 ⁄16"
11
3.6 39.7
060A 2 1⁄2" 13 3⁄4" 2 3⁄16" 149⁄16" 281⁄4" 6 5⁄8" 1" 1311⁄16" 3.6 41.9
6S
"NCD "NMMDBSHNMR ! C # $ % 080A 3" 18 3⁄8" 2 3⁄16" 17" 341⁄2" 8 5⁄8" 1" 17 1⁄2" 7.6 72.7
KA
95A Sweat 3
⁄4" 7 3⁄8" 2 1⁄8" 5" 51⁄2" 12 3⁄4" 8.3 100A 4" 18 1⁄2" 2 3⁄16" 17" 341⁄2" 8 5⁄8" 1" 17 1⁄2" 7.8 77.1
16A NPT male 1" 7 3⁄8" 2 1⁄8" 5" 51⁄2" 12 3⁄4" 8.3 150A 6" 25" 2 3⁄16" 211⁄16" 4611⁄16" 12 3⁄4" 1" 25 5⁄8" 23.0 187.3
*Add prefix NA to flanged code number when ordering ASME tagged and registered with the
97A Sweat 11⁄4" 6 3⁄16" 2 1⁄8" 5" 51⁄2" 12 3⁄4" 8.3
National Board of Boiler and Pressure Vessel Inspector and CRN registered.
F Operating principle
3 1/8”
C ,HBQNATAAKD@HQRDO@Q@SHNM
3 1/8” The air and dirt separator uses the
combined action of several physical
principles. The active part is the
D
The bubbles, fusing with each other, increase in volume until the
hydrostatic thrust is such as to overcome the adhesion force to the
structure. They rise towards the top of the unit from which they are
released through a float-operated automatic air vent valve.
,HBQNO@QSHBKDCHQSRDO@Q@SHNM
®
G The DISCALDIRT dirt removing element
separates and collects any impurities present
B
in the system. Impurities in the fluid upon
striking the surfaces of the DISCALDIRT ® 1
National Board of Boiler and Pressure Vessel Inspector and CRN registered. gravity, to separate the particles it contains.
-.3$ Drawings may not reflect the actual size of the separators. The collected impurities are discharged, by 3
59
Automatic air vent
for heating systems and radiators
RDQHDR CALEFFI
3DBGQDE
Function
Automatic air vents are designed to remove trapped air that
accumulates in heating and air conditioning systems automatically.
Air removal enhances performance and life of a system by reducing
the affects of:
- corrosion due to the oxygen;
- pockets of air trapped in the heating emitters;
- cavitation in the circulation pumps.
- service check valve allows an easy replacement of air vent without
purging the system (except 5080).
Series 501
Extra high capacity float type automatic air vent designed for use on
large pipes where large quantity of air is required to be released from
the system.
Series 5022 - 5023
High capacity float type automatic air vent designed for use on
manifolds or pipes in sealed heating systems.
Series 5080
Radiator air vent valve designed to remove automaticall any air
trapped inside the heat emitters both during the filling of the system
and in normal operation.
Product range
501 series Extra high capacity automatic air vent..................................................................................................connections 3/4" NPT female
5020 series `MINICAL® automatic air vent..................................................................................................................connections 1/8" NPT male
5021 series MINICAL® automatic air vent with service check valve............................................................................connections 1/8" NPT male
5022 series High capacity automatic air vent............................................................................................................connections 1/2" NPT male
5023 series High capacity automatic air vent with service check valve.......................................................................connections 1/2" NPT male
5026 series Automatic air vent .......................................................................................................................connections 1/8" - 1/4" NPT male
5027 series Automatic air vent with service check valve...................................................................................connections 1/8" - 1/4" NPT male
5080 series Automatic hygroscopic air vent for radiators...........................................................................................connections 1/8" NPT male
60
C
C
F
A
E
B
E
B
C
E
D
A
B
B’
E’
A
B’
E’
D
D
A
A
D
Code A B C D E F
502015A 1/8” NPT 3 1/8” 17/8” 3/8” 2 3/4 ” A
B
C Code A B C D E’
Code A B C D E
D 502115A 1/8”NPT 3 11/16” 17/8” 3/8” 3 5/16”
502610A 1/8” 3 1/16 ” 1 9/16 ” 7/16 ” 2 5/8 ”
Code A B C D E 502620A 1/4” 3 1/16 ” 1 9/16 ” 1/2” 2 5/8 ”
502243A 1/2”NPT 4” 2 3/16” 1/2” 2 1/2 ”
Code A B’ C D E’
Code A B C D E F Code A B’ C D E’ 502710A 1/8” 4” 1 9/16 ” 1/2” 3 3/8 ” Code A B C D E F
501502A 3/8” 3/4” 1 9/16 ” 3 13/16” 6 1/4” 5 5/16 ” 502343A 1/2”NPT 4 3/4 ” 2 3/16 ” 1/2” 3 1/4” 502720A 1/4” 4” 1 9/16 ” 1/2” 3 3/8 ” 508013A 1/8” 1 1/4 ” 11/16 ” 7/16 ” 13/16 ” 9/16 ”
Operation
Air flow
The accumulation of air bubbles in the valve
body causes the float to drop so that the air
Flow rate
vent valve opens when the water pressure is
(Nl/s) 5020 - 5021 5022 - 5023 5026 - 5027 (SCFM) (Nl/s)
below the maximum venting pressure rating.
1.2 2.5 1.2
Construction details 1.1 1.1
2.25
1 1
2
,NCDKRVHSGRDQUHBDBGDBJU@KUD 0.9 0.9
The service check valve seals off the vent 0.8 1.75 0.8
body with an EPDM O-ring, allowing easy 0.7 1.5 0.7
maintenance by shutting off the water flow 0.6 1.25 0.6
when the vent is removed. This feature also 0.5 1 0.5
allows for easy inspection of the air vent. 0.4 0.4
,(-(" +® 0.3
0.75
0.3
RDQHDR 0.5
'XFQNRBNOHBB@ONOSHNM@K 0.2 0.2
All MINICAL® models can be equipped with the optional hygroscopic 0.1 0.25 0.1
safety cap, part number R59681. This special cap contains cellulose 0 0 0
fiber discs that form a seal by increasing their volume 50% when
(bar) (psi)
10
20
30
40
50
60
70
80
90
0
2.5
3.5
4.5
5.5
6.5
0.5
1.5
2.5
3.5
4.5
5.5
0
20
30
40
50
60
70
80
90
0
2.5
3.5
4.5
5.5
6.5
0.5
1.5
2.5
3.5
4.5
5.5
61
DISCAL® air separator
Function
Air separators are used to continuously remove the air contained
in the hydronic circuits of heating and cooling systems. The air
discharge capacity of these devices is very high. They are capable of
removing automatically all the air present in the system down to the
micro-bubble level.
The circulation of fully de-aerated water enables the equipment to
operate under optimum conditions, free from noise, corrosion, localized
or mechanical damage. Micro-bubbles, fusing with each other, increase
in volume (get larger) until they become large enough to rise to the top
where they are automatically released.
Product range
551 series DISCAL® air separator for horizontal pipes, in brass with drain.............................................connections 3/4", 1", 1-1/4", 1-1/2" and 2"
551 series DISCAL® air separator for horizontal pipes, in steel with flanged connections and drain......................................connections 2" to 6"
NA551 series DISCAL® air separator for horizontal pipes, in steel with flanged connections with drain, ASME and CRN..........connections 2" to 6"
NA5519 series DISCAL® air separator for vertical pipes, in brass......................................................................connections 3/4" and 1" integral sweat
Technical specifications
Brass air separator Max. working pressure: 150 psi
,@SDQH@KR - body: brass Temperature range: 32–250°F
- internal element "NMMDBSHNMR - flanged: 2"– 6" ANSI B16.5 150 CLASS RF
- drain pipe: 1" NPT male
(compact & vertical versions): 304 stainless steel
- internal element: glass reinforced nylon PA66GF30 FDMBX OOQNU@K - NA551 series is designed and built in accordance
- seal: EPDM with Section VIII, Division 1 of the ASME Boiler
- air vent float guide pin: stainless steel and Pressure Vessel Code and tagged and
registered with the National Board of Boiler and
/DQENQL@MBD
Pressure Vessel Inspector, and CRN registered.
Suitable fluids: water, glycol solution
Max. percentage of glycol: 50% Dimensions
Max. working pressure: 150 psi
Temperature range: 32–250°F
"NMMDBSHNMR C C C
A
D
D
D
- main:
E
A
B
62
Dimensions
D
**100A 4" 181⁄2" 1" 171⁄8" 23 7⁄16" 8 5⁄8" 213⁄16" 9" 75⁄16" 67
38466.01
WALL
BI-DIRECTIONAL
E
- 120A 5" 25" 1" 21 ⁄16"
7
30 ⁄2" 1
12 ⁄4"
3
2 ⁄16"
13
10" 9 ⁄8" 3
106
Tmax 250ϒF Tmax 220ϒF
Pmax 150 psi Pmax 150 psi
- 150A 6" 25" 1" 217⁄16" 301⁄2" 12 3⁄4" 213⁄16" 10" 9 3⁄8" 117
H
2HYD Ū aŪ Ū Ū Ū Ū
"@O &@K 1.8 1.8 4.8 4.8 13.7 13.7
C **Add prefix NA to flanged code number when ordering ASME tagged and registered with the
B F
National Board of boiler and Pressure Vessel Inspector and CRN registered.
†This dimension allows for a minimum of 3" wall clearance to accommodate insulation if used.
A
A
3 2
the whirling movement required
F F to facilitate the release of micro-
B B
bubbles and their adhesion to these 1
surfaces.
"NCD ! C # $ % 6SKA The bubbles, fusing with each other,
005A* ⁄4"
3
4 ⁄16"
5
2 ⁄16"
3
5 ⁄4"
3
7 ⁄2"
1
⁄2"
1
3.7 increase in size until the hydrostatic
thrust overcomes the adhesion force
006A* 1" 4 5⁄16" 2 3⁄16" 53⁄4" 71⁄2" ⁄2"
1
3.7
to the mesh. They rise towards the
007A* 1 ⁄4"
1
4 ⁄8"
7
2 ⁄16"
3
6 ⁄16"
9
8 ⁄4"
1
⁄2"
1
4.9 top of the unit from which they are
008A* 11⁄2" 47⁄8" 2 3⁄16" 6 9⁄16" 81⁄4" ⁄2"
1
4.9 released through a float-operated
automatic air vent, with stainless
009A* 2" 51⁄8" 2 3⁄16" 6 9⁄16" 81⁄4" ⁄2"
1
5.5 steel float guide pin (3). AQ@RRRDQHDR
028A* 1" SWT 5 ⁄16"
1
2 ⁄16"
3
5 ⁄4"
3
7 ⁄2"
1
⁄2"
1
3.7
Air separation efficiency
035A* 11⁄4" SWT 5 3⁄16" 2 3⁄16" 6 5⁄16" 81⁄4" ⁄2"
1
3.7
DISCAL® air separators continuously remove entrapped air in hydronic
041A* 11⁄2" SWT 5 3⁄4" 2 3⁄16" 6 9⁄16" 81⁄4" ⁄2"
1
4.9
systems with very high efficiency. The amount of air removed from a
054A* 2" SWT 61⁄8" 2 3⁄16" 6 9⁄16" 81⁄4" ⁄2"
1
5.5 system varies depending on fluid velocity and system pressures. As
*Add suffix C to sweat and NPT code number when ordering the brass illustrated on the graph, after just 25 recirculations at the 3.2 feet per
DISCAL® to ship with expansion tank service check valve, code 561402A. second fluid velocity, almost all the air artificially introduced into the
circuit is eliminated by the DISCAL® air separator, with percent removed
varying based on system pressure and fluid temperature.
The small amount which remains is then gradually eliminated during
normal system operation. In conditions where the fluid velocity is slower
Operating principles or the temperature of the medium is higher, the amount of air separated
The DISCAL® air separator is even greater.
is used to continuously Air introduced - Air removed - (%)
remove the air contained in 100
200
600
700
800
900
300
400
500
1000
1100
1200
(sec)
Tme
0
63
Hydro separator
Function
The Caleffi 548 and NA548 series hydraulic separator creates a zone
with a low pressure loss, which enables primary and secondary circuits
connected to it to be hydraulically independent of each other;SGDlNV
HMNMDBHQBTHSCNDRMNS@EEDBSSGDlNVHMSGDNSGDQ This device
consists of several different functional components, each of which
meets specific requirements, typical of the circuits used in heating and
air-conditioning systems.
p'XCQ@TKHBRDO@Q@SNQ - To keep connected hydronic circuits totally
independent from each other.
p #HQS QDLNUDQ - To permit the separation and collection of any
impurities present in the circuits. Provided with a valved connection
with discharge piping.
p TSNL@SHB @HQ UDMS U@KUD - For automatic venting of any air
contained in the circuits. Provided with a valved connection for
maintenance purposes.
Product range
548 series Hydro separator in steel with union connections, drain and insulation..........................................................connections 1" to 2"
548 series Hydro separator in steel with flanged connections, drain and insulation.............................................connections 2" to 4" ANSI
NA548 series Hydro separator in steel with flanged connections, drain and insulation ASME and CRN....................connections 2" to 4" ANSI
NA548 series Hydro separator in steel with flanged connections and drain, ASME and CRN...............................connections 5" to 12" ANSI*
*Larger sizes available, consult factory
Technical specifications
Threaded and sweat connections Flanged connections
"NMMDBSHNMR - main: 1", 1¼", 1½", 2" NPT female union "NMMDBSHNMR - main: 2"-12"ANSI B16.5 150 CLASS RF
1", 1¼", 1½", 2" sweat union - drain valve: 2 — 6": 1¼" NPT female
- drain valve: ¾" garden hose thread 8 — 12": 2" NPT female
- thermo well trap: ½" straight thread female - thermo well trap (8 — 12" only):
,@SDQH@KR - separator body: epoxy resin painted steel - front center: ¾" NPT female
- air vent body: brass - inlet/outlet flanges: ½" NPT female
- shut off and drain valve body: brass ,@SDQH@KR - separator body: epoxy resin painted steel
/DQENQL@MBD - air vent body: brass
Suitable fluids: water and non-hazardous glycol solution up to 50% - shut off and drain valve body: brass
Max. operating pressure: 150 psi - internal baffle: stainless steel
Working temperature range with insulation: 32–210°F /DQENQL@MBD
Working temperature range without insulation: 32–250°F Suitable fluids: water and non-hazardous glycol solution up to 50%
Max. operating pressure: 150 psi
3DBGMHB@KRODBHkB@SHNMRNEHMRTK@SHNM Working temperature range with insulation: 32–210°F
Materials: double density closed cell expanded PEX Working temperature range without insulation (vessel): 32–270°F
Thickness: 3/4"
Density: - internal part: 2 lb/ft 3DBGMHB@KRODBHkB@SHNMRNEHMRTK@SHNMENQl@MFDCUDQRHNMRTOSNŪ
- external part: 3 lb/ft (MSDQM@KHMRTK@SHNM
Thermal conductivity: 32°F: 9 BTU/in Materials: rigid closed cell expanded polyurethane foam
-40°F: 11 BTU/in Thickness: 2 3/8"
Coefficient of resistance to the diffusion of vapor: >1,300 Density: 3 lb/ft
Temperature range: 32–210°F Thermal conductivity: 6 BTU/in
Reaction to fire (DIN4102): class B 2 Temperature range: 32–220°F
.TSDQRJHM
Materials: embossed aluminum
Thickness: 7.0-mil
Reaction to fire (DIN 4102): class 1
'D@CBNUDQR
Heat formed materials: PS
64
Dimensions
E
E
A
A
A
HYDRO SEPARATOR
Serie 548
HYDRO SEPARATOR
Tmax 120¯C
Pmax 10 bar
Tmax 105¯C
Pmax 10 bar
HYDRO-SEPARATOR
Serie 548
38...
D
C
A
A
A
C
B
F
B
D
Code A B C D E E Weight (lb) Flow (gpm) Vol. (gal)
548052A 2” 1 1/4” 13” 13” 15” 14” 75 40 4.0
548062A 2 1/4” 1 1/4” 13” 13” 15” 14” 82 80 4.0
548082A 3” 1 1/4” 15” 18” 17” 18” 112 124 8.0
548102A 4” 1 1/4” 15” 18” 17” 18” 117 247 8.0 B
NA548120A* 5” 1 1/4” 15” 22” 19” 25” 220 300 22.5 F
Code A B C D D Weight (lb) Flow (gpm) Vol. (gal)
NA548150A* 6” 1 1/4” 15” 22” 19” 25” 231 484 23.2
548006A/96A 1” 8 3/4” 6 1/4” 8 5/8” 8” 13 11 0.5 * without insulation Code A B C D E D Weight (lb) Flow (gpm) Vol. (gal)
NA prefix indicates ASME tagged and registered with the National Board of Boiler NA548200A 8” 520 792 95
548007A/97A 1 1/4” 9 3/8” 7 3/8” 9 1/2” 8 3/8” 17 18 0.7 2” 39 3/8” 33 7/8” 27 1/2” 35 1/2”
and Pressure Vessel Inspectors.
548008A/98A 1 1/2” 10 7/8” 7 3/4” 10 1/4” 8 3/4” 25 26 1.3 NA548250A 10” 2” 43 5/16” 35 7/8” 30” 41 3/4” 725 1,330 175
Add NA prefix to 2” to 4” flanged connection for ASME approved.
548009A/99A 2” 12” 10 1/8” 11 7/8” 9 1/2” 27 34 3.5 NA548300A 12” 2” 47 1/4” 37 7/8” 31 1/2” 47 3/4” 1,100 1,850 255
For larger ASME sizes consult with factory.
Operating principle
When a single system contains a primary production circuit, with its When the secondary pump is off, there is no circulation in the secondary
own pump, and a secondary user circuit, with one or more distributions circuit; the whole flow rate produced by the primary pump is by-passed
pumps, operating conditions may arise in the system whereby the pumps through the separator.
interact, creating abnormal variations in circuit flow rates and pressures.
With the hydraulic separator, it is therefore possible to have a primary
The hydraulic separator creates a zone with a low pressure loss, which production circuit with a constant flow rate and a secondary distribution
enables the primary and secondary circuits connected to it to be circuit with a variable flow rate; these operating conditions are typical of
hydraulically independent of each other; VJGƀQYKPQPGEKTEWKVFQGU modern heating and cooling systems.
PQVCHHGEVVJGƀQYKPVJGQVJGT
Gp Gs
In this case, the flow rate in the respective circuits depends exclusively
on the flow rate characteristics of the pumps, preventing reciprocal
influence caused by connection in series.
Therefore, using a device with these characteristics means that the flow primary secondary
in the secondary circuit only circulates when the relevant pump is on,
permitting the system to meet the specific load requirements at that time.
3GQDDONRRHAKDGXCQ@TKHBA@K@MBDRHST@SHNMR@QDRGNVMADKNV
Gp Gs Gp Gs Gp Gs
65
HydroCal™ combination hydraulic,
air and dirt separator
549 and NA549 series CALEFFI
Tech ref: 01178
Function
The Caleffi HydroCal™ combination hydraulic, air and dirt separator
is a device that combines high performance air and dirt removal with
hydraulic separation. Primary and secondary circuits connected to it
become hydraulically decoupled thus eliminating pump conflict.
A proven, time tested stainless steel internal coalescing element
continuously and automatically eliminates all entrained air, including
microbubbles, in the system. Air discharge capacity is very high. Over
time, dirt particles as tiny as 5 microns are captured and collected
away from the flow stream.
The 3-in-1 high performance functionality of the HydroCal ™ saves
system installation and maintenance cost as there is no need to include
separate air and dirt separators. It can be used on either hot or chilled
water systems.
Product range
549 series HydroCal™ hydraulic, air and dirt separator in steel with flanged connections insulation.......................................connections 2–4" ANSI
NA549 series HydroCal™ hydraulic, air and dirt separator in steel with flanged connections, insulation, ASME and CRN......... connections 2–4" ANSI
NA549 series HydroCal™ hydraulic, air and dirt separator in steel with flanged connections ASME and CRN.........................connections 6–12" ANSI*
*Larger sizes are available, consult factory
Tmax 250ϒF
Pmax 150 psi
Tmax 220ϒF
Pmax 150 psi
/DQENQL@MBD
Suitable fluids: water and non-hazardous glycol solutions up to 50%
C
FDMBX@OOQNU@K 2–6”
Series NA549 is designed and built in accordance with Section VIII,
Division 1 of the ASME Boiler and Pressure Vessel Code and tagged
and registered with the National Board of Boiler and Pressure Vessel 8–12”
Inspector, and CRN registered.
6S %KNV 5NK
Technical specifications of insulation up to 4" "NCD A B C D E F KAR FOL F@K
(MMDQHMRTK@SHNM 549052A 2" 1 ⁄4" 1
13" 13" 15" 14" 73 37.3 4.0
Material: rigid closed cell expanded polyurethane foam 549062A 21⁄2" 11⁄4" 13" 13" 15" 14" 79 63 4.0
Thickness: 2-3/8" 549082A 3" 11⁄4" 15" 17 3⁄4" 17" 18" 108 95.5 8.0
Density: 3 lb/ft3 549102A 4" 11⁄4" 15" 17 3⁄4" 17" 18" 117 149 8.0
Conductivity (ISO 2581): 0.16 BTU·in/hr·ft2·°F (0.023 W/(m·K) NA549150A* 6" 11⁄4" 15" 22" 19" 25" 231 380 23.2
Temperature range: 32–220°F NA549200A* 8" 2" 33 7⁄8" 39 3⁄8" 271⁄2" 351⁄2" 520 625 95.0
.TSDQRJHM NA549250A* 10" 2" 33 7⁄8" 43 5⁄16" 30" 413⁄4" 725 1,030 175
Material: embossed aluminium NA549300A* 12" 2" 33 7⁄8" 47 1⁄4" 311⁄2" 47 3⁄4" 1100 1,650 255
Thickness: 7-mil (0.70 mm) *Without insulation
Fire resistance (DIN 4102): class 1 NA prefix indicates ASME tagged and registered with the National Board of Boiler and Pressure
'D@CBNUDQR Vessel Inspectors and CRN registered.
Heat formed material: PS Add NA prefix to 2" to 4" flanged connection for ASME approved, CRN registered.
66
Operating principle
'XCQ@TKHBRDO@Q@SHNM
When a single system contains a primary production circuit, with its through the separator. With the hydraulic separator, it is therefore
own pump, and a secondary user circuit, with one or more distribution possible to have a primary production circuit with a constant flow rate
pumps, operating conditions may arise in the system whereby the and a secondary distribution circuit with a variable flow rate; these
pumps interact, creating abnormal variations in circuit flow rates and operating conditions are typical of modern heating and cooling systems.
pressures. The hydraulic separator creates a zone with a low pressure
loss, which enables the primary and secondary circuits connected to it
to be hydraulically independent of each other; SGDlNVHMNMDBHQBTHS Three possible hydraulic balance situations are shown below.
CNDRMNS@EEDBSlNVHMSGDNSGDQ
In this case, the flow rate in the respective circuits depends exclusively Primary Secondary Primary Secondary Primary Secondary
on the flow rate characteristics of the circuit pumps, preventing
Gp Gs Gp Gs Gp Gs
reciprocal influence caused by connection in series. Therefore, using a
device with these characteristics means that the flow in the secondary
circuit only circulates when the relevant pump is on, permitting the
system to meet the specific load requirements at that time.
When the secondary pump is off, there is no circulation in the secondary
circuit; the whole flow rate produced by the primary pump is by-passed &Orimary = &Recondary &Orimary > &Recondary &Orimary < &Recondary
Construction details
,HBQNATAAKD@HQRDO@Q@SHNM
T h e H y d r o C a l ’s i n t e r n a l
element (1) creates the whirling
movement required to facilitate
the release of microbubbles and
their adhesion to the internal !
element surfaces. The bubbles,
fusing with each other, increase
in size until the hydrostatic thrust
overcomes the adhesion force
to the mesh. They rise towards
the top of the unit from which
they are released through a float-
operated automatic air vent.
,HBQNO@QSHBKDCHQSRDO@Q@SHNM
Impurities in the fluid upon
striking the surfaces of the
HydroCal’s internal element (1),
get separated and drop to the
bottom of the body (2) where
they collect.
C
In addition, the large internal
volume of HydroCal ™ slows
down the flow speed of the (RNK@SHMFSGD@HQUDMSU@KUD
fluid thus helping, by gravity, to
The air vent (A), replacement part number 501502A, is isolated
separate the particles it contains.
manually, using a shut-off ball valve (B), replacement part number
The collected impurities are NA39589.
discharged, by opening the drain
valve (3) with the handle (4), even 1 #HQSQDLNUHMFDKDLDMS
with the system operating. The HydroCal ™ dirt removing
element separates and collects
any impurities present in
the system.
These impurities are removed by
the drain valve (C) replacement
part number NA39588 for
2
connection sizes 2–6"; NA59600
for connection size 8–12", which
3
can be connected to a discharge
4 pipe, a t t h e b o t t o m o f t h e
separator.
67
SEP ™ combination hydraulic, air,
dirt and magnetic separator
5495 series CALEFFI
3DBGQDE
%TMBSHNM
The SEP4™ combination hydraulic, air, dirt and magnetic separator
is a device that, incorporates high performance air and magnetic and
non-magnetic dirt removal functionality into the hydraulic separation
function which makes the primary and secondary circuits connected
to it hydraulically independent, and can be used on hot or chilled water
systems.
The SEP4 ™ features an HDPE internal element that combines to
continuously and automatically eliminate air micro-bubbles with the
simultaneous removal of dirt particles as tiny as 5 microns. The air
discharge capacity is very high, with the capability of automatically
removing all the air present in the system down to the micro-bubble level.
The 4-in-1 high performance functionality of the SEP4™ saves system
installation and maintenance costs as there is no need to include separate
air and dirt separators. In addition to removing sand and rust impurities,
the added powerful removable external magnetic ring around the lower
body removes up to 95% of the ferrous oxide particles that can form in a
hydronic system.
Product range
Code ttA SEP4™ hydraulic, air, dirt and magnetic separator connections .............................................1", 1¼", 1½", 2" NPT female union
Code ttA SEP4™ hydraulic, air, dirt and magnetic separator connections .................................................... 1", 1¼", 1½", 2" sweat union
/DQENQL@MBD
Suitable fluids: water, glycol solution
Max. percentage of glycol: 50%
A
68
Operating principle
through the separator. With the hydraulic separator, it is therefore
'XCQ@TKHBRDO@Q@SHNM
possible to have a primary production circuit with a constant flow rate
When a single system contains a primary production circuit, with its and a secondary distribution circuit with a variable flow rate; these
own pump, and a secondary user circuit, with one or more distribution operating conditions are typical of modern heating and cooling systems.
pumps, operating conditions may arise in the system whereby the pumps
Three possible hydraulic balance situations are shown below.
interact, creating abnormal variations in circuit flow rates and pressures.
The hydraulic separator creates a flow path with a low pressure loss,
which enables the primary and secondary circuits connected to it to be
hydraulically independent of each other; SGDlNVHMNMDBHQBTHSCNDR Gp Gs
MNS@EEDBSlNVHMSGDNSGDQ In this case, the flow rate in the respective
circuits depends exclusively on the flow rate characteristics of the circuit
pumps, preventing reciprocal influence caused by connection in series.
Therefore, using a device with these characteristics means that the flow
in the secondary circuit only circulates when the relevant pump is on, primary secondary
permitting the system to meet the specific load requirements at that
time.
When the secondary pump is off, there is no circulation in the secondary
circuit; the whole flow rate produced by the primary pump is by-passed
Gp Gs Gp Gs Gp Gs
HM GHFGODQENQL@MBDETMBSHNM@KHSX
,HBQN O@QSHBKDCHQSRDO@Q@SHNM
Impurities in the fluid upon striking Hydraulic separation Air separation
the surfaces of the SEP4’s internal
dirt separation element (2), get
separated and drop to the bottom
of the body (3) where they collect.
In addition, the large internal
volume of SEP4™ slows down the
flow speed of the fluid thus helping,
by gravity, to separate the particles
it contains. Dirt separation Magnetic removal of ferrous particles
The collected impurities are
discharged, by opening the drain
valve (4) with the handle (5), even
with the system operating. 3
69
® ™
and DISCAL
magnetic dirt separator
- RDQHDR CALEFFI
3DBGQDE
Function
Air, dirt and magnetic separators are used to continuously remove the
air and debris contained in the hydronic circuits of heating and cooling
systems. Caleffi offers several versions of air, dirt and hydraulic separators
that also feature magnetic particle removal.
The DIRTMAG ® magnetic dirt separator and DISCALDIRTMAG ™
magnetic air and dirt separator removes both magnetic and non-
magnetic particles, featuring a powerful removable external magnet
around the body that removes up to 95% of the ferrous oxide particles
that can form in a hydronic system. The 5461 series and the 5463 series
brass versions are available with NPT threaded or sweat connections in
versions for horizontal pipes only. Insulation shells are available separately
for field installation.
The body of the patent pending NA5453 series separator is made
of glass reinforced nylon specifically designed for use in heating and
cooling systems. It also is especially versatile as it can be installed on
either horizontal or vertical piping with the rotating brass base mount. It
is available with conventional NPT and sweat union connections. Also
available for size ¾”, the Presscon™ copper tailpiece with union nut
makes installation and maintenance fast, easy and efficient. Special slots
in the EPDM O-ring allows fluid to leak during system testing if unpressed
and provide a perfect leak proof seal when completely pressed.
/QNCTBSQ@MFD
NA54530 series DIRTMAG® dirt separator with magnet for horizontal and vertical pipes...............................connections ¾” & 1” NPT male union
NA54539 series DIRTMAG® dirt separator with magnet for horizontal and vertical pipes.....................................connections ¾” & 1” sweat union
NA54536 series DIRTMAG® dirt separator with magnet for horizontal and vertical pipes.......................................................connections ¾” press
54611 series DISCALDIRTMAG™ air and dirt separator with magnet in brass...............................................................connections 1" NPT male
54619 series DISCALDIRTMAG™ air and dirt separator with magnet in brass..................................................connections 3/4", 1", 1-1/4" sweat
5463 series DIRTMAG® magnetic dirt separator for horizontal pipes, in brass..........................................................connections 1" to 2" sweat
Technical specifications
70
Dimensions
B 15/8"
NPT B Sweat B
31/2"
2”
2”
A
A
C
5½”
C
C
B
A
1¼”
1¼”
7"
C
"NCD ! C 6S KA
06A 1" NPT 4 5⁄16" 5" 4.2
2¼”
28A 1" SWT 51⁄16" 5" 4.2
07A 11⁄4" NPT 47⁄8" 6" 5.3 "NCD ! C 6S KA
35A 11⁄4" SWT 5 3⁄16" 6" 4.2 "NCD ! C 6S KA NA545305 ¾” NPT 6 7/8” 3 7/16” 4.5
08A 11⁄2" NPT 47⁄ 8" 6" 6.2 95A 3⁄4"SWT 7 3⁄8" 5" 8.5 NA545395 ¾” SWT 6 5/8” 3 5/16” 4.5
41A 11⁄2" SWT 5 3⁄4" 6" 4.9 96A 1" SWT 7 3⁄8" 5" 8.5 NA545365 ¾” press 7 1/4” 3 5/8” 4.5
09A 2" NPT 51⁄8" 6" 6.2 16A 1" NPT M 7 3⁄8" 5" 8.5 NA545306 1” NPT 7 1/2” 3 3/4” 4.5
54A 2" SWT 61⁄8" 6" 5.5 97A 1¼" SWT 7 3⁄8" 5" 8.5 NA545396 1” SWT 7 5/8” 3 7/8” 4.5
,HBQNATAAKD@HQRDO@Q@SHNM
1 Engineered
71
Magnetic Separation
Removes 95% of ferrous impurities
Ferrous oxide forms in hydronic systems when iron or steel corrodes.
This abrasive, extremely fine sediment is difficult to remove; it can
deposit onto heat exchanger surfaces and accumulate in pump
cavities causing reduced efficiency and premature wear. Caleffi
magnetic dirt separators accomplish 2½ times the ferrous oxide
removal performance of standard dirt separators, delivering up to
95% elimination efficiency.