B Detail: Piping Isometric Building

You might also like

You are on page 1of 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

NPD Weight
CONN TO Description Qty
[DN] [Kg]
N 22LDH10BB001-N2b
350, RF, CL150, unset
A +X=-57/11-20ULA 1 PIPE-WELDED, S-10S, A312-TP304LW, ASME-B36.19M 350 15.1 M 620.8 A
+Y=+3713/A-20ULA 127 2 TEMPERATURE NOZZLE, OD40 x 45L, A182-F304L, DWG 350X25 2 0.6
+Z=+26595 NO. : ZTO004-4711-MTB030-479750
3 ELBOW 45 DEG LONG RADIUS (45.0 DEG), S-10S, 350 1 18.1
A403-WP304L, ASME-B16.9
4 ELBOW 90 DEG LONG RADIUS (90.0 DEG), S-10S, 350 2 72.1
3
71 14 A403-WP304L, ASME-B16.9
5 WELD NECK FLANGE, CL150 WNRF(S-10S), A182-F304L, 350 1 47.2
ASME-B16.5

F5.1 G6.1 B7.1


B B

25
1.4

44
35
0N
PD
31
27
533

13

C 4.2 C
12
+X=-770/11-20ULA
534
+Y=+586/A-20ULA
+Z=+26595

6 FLAT GASKET, CL150, GRAPHITE/REINFORCING RING 350 1 -


7 STUD BOLT, A193-B8M/A194-8M, STAINLESS STEEL, 25 12 -
ASME-B18.2.1, WITH 2 NUTS, 2 WASHERS PER BOLT,

1.3
DETAIL B 150MM BOLT LENGTH
8 THERMOWELL, 200-65, A182-F304L, DIN 25 2 1.0
43772-4-7-M18x1.5
D 9 AXIAL STOP+GUIDE HORIZONTAL (AF+GH) 350 1 -
D
10 RIGID HANGER (RH) 350 1 -
11 SLIDING BASE (SB) 350 1 -

3222
12 LUG PLATE, A240-304, PL10x40x100 25 8 2.4
13 SHEAR LUG PLATE, A240-304, PL6x12x80 25 1 0.1
14 PLUG SCREW, EN STANDARD, A105, MTE M18x1.5 25 2 0.2
15 GASKET RING, EN STANDARD, COPPER, 18x22 25 2 0.2

SEE
3.1 SHEET 1

+X=-200/12-20ULA
E +Y=+3080/A-20ULA E
PD
+Z=+19742 0N
24/25/26/27 35
28/29/30/31 55 22LDH05BR003-SPL-4
223 8.2/14.2/15.2 13
2.2 SEE DETAIL C 762.6
22LDH05CT401 08
350X25NPD 39
PENGERANG POWER SDN BHD
ORIENT 22LDH05BQ011 (Company No. 1089490-K)
DETAIL C EAST S9.1/12.1
(LOOKING DOWN) 22LDH05BQ003 Level 51, Tower 2, PETRONAS Twin Towers
+Z=+22840 AF+GH
Kuala Lumpur City Centre
19 00 50088 Kuala Lumpur, Malaysia
18 15 SEE DETAIL A
F F
PETRONAS PETRONAS TECHNICAL SERVICES SDN BHD
1.1 TECHNICAL (Company No. 347848-X)
8.1/14.1/15.1 223 S10.1/13.1 SERVICES
300

SEE DETAIL C RH (Z=0) Tower 1, PETRONAS Twin Towers


22LDH05CT001 8A Kuala Lumpur City Centre
SEE DETAIL B 50088 Kuala Lumpur, Malaysia
222
8

17
9 24
2.1 95
350X25NPD
G ORIENT
223 G
EAST

+Z=+22540
16
72

72

S11.1
27

25

22LDH05BR003-SPL-6 22LDH05BQ004
SB
2265

22LDH05BR003-SPL-5
AG Malaysia Sdn Bhd MMC
H Siemens AG Siemens Malaysia Sdn. Bhd. MMC Engineering Services Sdn Bhd
H
Level 1, Reception, CP Tower unit 702, Level 7, Wisma Zelan
95 PG ES PM No. 11, Jalan 16/11 No. 1, Jalan Tasik Permaisuri 2
+X=-770/11-20ULA 24 Pusat Dagang Seksyen 16 Bandar Tun Abdul Razak
+Y=+586/A-20ULA
DETAIL A 63067 Offenbach, Germany 46350 Petaling Jaya, Malaysia 56000 Kuala Lumpur
1.2

Malaysia
+Z=+19742 11

533 SEONGHWA
Industrial Co., Ltd
534 10
PCP-SAG-PIP-ISO-LDH-480396
Ursprung/Original Ursprung-Nr./Original-No. REV Urspr.-PKZ-Nr.
J 4.1 Orig.-PC J
MY1008-22LDH05-&MTB020-112314 00/03

PENGERANG COGENERATION PLANT MY1008


22LDH05BR003-SPL-4
22LDH05BR003-SPL-5 446547961 &MTC030
INCH-DIA
22LDH05BR003-SPL-6 22LDH05BR003
K SHOP 128.5 480396 K
FIELD 81 SPISO PLMS-P
R0 2018-08-10 S.W.Kim J.W.Han AS BUILT
THK THK THK FIELD SHOP
(mm) (mm) (mm) in% BW SW RFN FIL in% BW SW RFN FIL Definition
24 25 F FIL - - No 8A 25 F FIL - - No 19 25 F FIL 33.4 3.38 No R 10 0 0 0 R 10 0 0 0 Radiographic Examination
25 25 F FIL - - No 8 350 S BW 355.6 4.78 No 12 350 S BW 355.6 4.78 No U 0 0 0 0 U 0 0 0 0 Ultasonic Examination.

80
26 25 F FIL - - No 9 350 F BW 355.6 4.78 No 13 350 S BW 355.6 4.78 No P P Liquid Penetration Examination
10 0 10 0 10 0 10 0
27 25 F FIL - - No 10 350 S BW 355.6 4.78 No 14 350 S BW 355.6 4.78 No - -
S 0 0 0 0 S 0 0 0 0 Magnetic Examination
28 25 F FIL - - No 11 350 F BW 355.6 4.78 No
L 29 25 F FIL - - No 16 25 S O-LET 33.4 3.38 No H 0 0 0 0 H 0 0 0 0 Hardness Testing
30 25 F FIL - - No 17 25 F FIL 33.4 3.38 No M 10 0 10 10 M 10 0 10 10 Metascope or ferritic check 2015-10-30 M.J.Shin Piping
31 25 F FIL - - No 18 25 S O-LET 33.4 3.38 No V V Visual Examination 2015-10-30 S.W.Kim
Exportkennzeichnung AL: ECCN:
Remarks
100 100 100 100 100 100 100
The extent of NDE is mandatory for shop and field welds of the
100
2015-10-30 J.W.Han
Isometric 22LDH05BR003
respective piping system as a designated lot.
Bearbeitung dieses Dokumentes, Verwertung und Mitteilung
- Final dimensions of valves and in- line components to be
checked by erection contractor before installation. General Weld type Addition for extent of NDE below 100%: All materials, all nominal pipe sizes Building: 20ULA
gestattet. Zuwiderhandlungen verpflichten zu Schadenersatz. BW : Butt weld and all welders shall be considered for a random spot examination of welds
- Pipe routing NPS < 3" (DN80) should be Position number acc. partlist SW : Socket weld
bzw bei Kennzeichen "AL:N" oder "ECCN:N", kann sich eine Genehmigungspflicht, unter anderem
checked by erection contractor at site Shop weld number O-LET : Weldolet, sockolet Set of Rules for
oder Geschmacks-mustereintragung vorbehalten. RFN : Reinforce Nozzle Construction
Insulation 80 mm
- All pipes without fit-up allowance Field weld number
Transmittal, reproduction, dissemination and/or editing of this FIL : Fillet
Export classification AL: ECCN: - Fit-up allowance of pipe = 150mm, Support type SF : Socket Fusion Pipe Material Class A15S2AA0120 max. allow. work. Temperature 159 C R0
M document as well as utilization of its contents and Goods labeled with "AL not equal to N" are subject to European or German export authorization which is additional marked with "+150" KKS-support number BF : Butt Fusion

20
communication thereof to others without express authorization - For Part No. only figure before dot to be Slope BL : Butt Lamination
are prohibited. Offenders will be held liable for payment of
when being exported out of the EU. Goods labeled with "ECCN not equal to N" are subject to US
matched with BOM Part No.
NL : Nozzle Lamination Internal Coating max. allow. work. Pressure 7 bar MY1008-22LDH05-&MTC030-480396
reexport authorization. Even without a label, or with label "AL:N" or"ECCN:N", authorization may be Flow direction SC : Solvent Cement
damages. All rights created by patent grant or registration of a - For shop pre-fabrication Referance
utility model or design patent are reserved.
required due to the final whereabouts and purpose for which the goods are to be used.
drawing no.
F
S
: Field weld
: Shop weld External Coating MY1008-61810-&MDC080-484504 Test Pressure 10.5 bar 2 /2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

You might also like