You are on page 1of 2

Fuel Analysis Operational Report Report date

ASIAN-ALLIANCE OFFSHORE PTE LTD 04-Jan-2023

ANAHITA (9737917)
Offshore Soyo Block 17, 11-Dec-2022

Operational
Based on this sample, operational difficulties may be experienced. Please refer to the
comments on Pour Point

Sample Number FUJ22F013338


Bunker Port Offshore Soyo Block 17
Bunker Date 11-Dec-2022
Supplier TOTAL ENERGIES
Loaded From BORINGIA SWAN
Quantity per C.Eng. Not Stated

Product Type MGO


Fuel Usage Not Stated
Sampling Point Not Stated
Sampling Method Not Stated
Seal Data 7598727 (VPS, Intact)
Marpol Seal 7598028

Source Of Data B.D.N.


Density @ 15°C 847.5 kg/m³
Viscosity @ 40°C 3.6 mm²/s
Sulfur 0.107 % m/m
Volume @ 15°C 699.997 m³
Quantity 593.247 MT

Sent From Luanda


Date Sent 27-Dec-2022
Arrived at Lab 31-Dec-2022

Indicates that comments are given. Page 1 of 2


FUJ22F013338
ANAHITA (9737917)

Test Results
Unit Test Results DMA Test Method
Density @ 15°C kg/m³ 847.5 890.0 ISO 12185
Viscosity @ 40°C mm²/s 3.314 2.000\6.000 ISO 3104
Micro Carbon Residue 10% % m/m < 0.10 0.30 ISO 10370
Sulfur % m/m 0.16 1.50 ISO 8754
Ash % m/m < 0.01 0.01 LP 1001
Pour Point °C -3 -6\0 ISO 3016
Flash Point °C 69.0 60.0 ISO 2719-A
Visual Appearance - Pass Bright&Clear LP 1902
Calculated Cetane Index¹ - 51 40 ISO 4264
Acid Number mg KOH/g < 0.1 0.5 LP 2003
FAME content % V/V < 0.1 0.1 EN 14078
Water % V/V < 0.01 ASTM D6304-C
Vanadium mg/kg <1 IP 501
Sodium mg/kg <1 IP 501
Aluminium mg/kg <1 IP 501
Silicon mg/kg <1 IP 501
Iron mg/kg <1 IP 501
Nickel mg/kg <1 IP 501
Calcium mg/kg <1 IP 501
Magnesium mg/kg <1 LP 1101
Zinc mg/kg <1 IP 501
Phosphorus mg/kg <1 IP 501
Potassium mg/kg <1 LP 1101
Net Specific Energy¹ MJ/kg 42.74 ISO 8217
Aluminium + Silicon mg/kg <2
Temp.@ 10% recovery °C 210 ISO 3405
Temp.@ 50% recovery °C 288 ISO 3405
Temp.@ 90% recovery °C 353 ISO 3405
FTIR Screening - Pass LP 2403
¹ Calculated value

Operational Advice
Pour Point Although pour point exceeds the -6°C winter limit, the summer limit
of 0°C is met. Transfer may be difficult if the fuel temperature drops
below 10°C. Maintaining a fuel temperature about 10°C above the
pour point is recommended for satisfactory storage and transfer.

Best Regards,
On behalf of Veritas Petroleum Services BV
Jubinraj K.P
Technical Support Engineer
Best wishes for the Holiday Season and a prosperous New Year
For assistance or further information on this report please contact your nearest VPS office or contact us
directly at Tel : +65 67792475, Email : Singapore@vpsveritas.com

Reference to part(s) of this report which may lead to misinterpretation is prohibited.

Page 2 of 2 FUJ22F013338