Cooling water is used directly or indirectly to cool chemical products, air condenser, etc. To reduce the water
requirements for cooling systems, the changes have been made, such as changing from once through to
recirculating cooling systems and the reduction of blow down water quantity by higher cycle operation of open
recirculating cooling systems. Such application causes concentration of dissolved solid, resulting in frequent
problems from corrosion, scale and slime. Therefore, cooling water treatment chemicals are essential to prevent
these problems.
In cooling water system, circulating cooling water is usually saturated with dissolved oxygen. Dissolved solid
contents of cooling water are also higher than those in the make up water because of partial evaporation at the
cooling tower.
With high polymer degradation, Phosphonates and Phosphates, Kurita NT-2560 which create thin film on
the surface, is able to prevent corrosion and scale well.
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 3 of 17
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 4 of 17
II. OPERATION CONDITIONS
Water standard
Item Feed water 1 with Kurita NT-
Cooling 1
2560
pH - 7.62 8.12 8.0 - 9.0
Comment:
Cooling water #1 (factory 1): COC too high lead to strong tend of scale
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 5 of 17
Table 2: Water quality of Factoy #2
Water
Item Feed water
Cooling 3 Cooling 5 standard with
2
Kurita NT-2560
Comment:
Feed water (factory 2): The parameters do not exceed standard, quality of feed water can feed to cooling tower
Cooling tower #3 (Factory 2): With COC of 43, Total Hardness and M-Alkalinity in cooling tower #3 were higher
than standard. High tends of Scale. Slime also is developing
Cooling tower #5 (factory 2): With COC of 64, Total Hardness and M-Alkalinity in cooling tower #5 were very high
(800 mg/l and 470 mg/l). Depositing Scale is occurring in system.
Figure 2: Inside cooling tower #3 (factory 2) Figure 3: Outside cooling tower #1 (factory 1)
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 6 of 17
Cycle of concentration *2 18 15
(hour/day) 24 24
(month/year) 12 12
Remark: *1 – Data given by Suheung Vina’s staff. for 1 unit cooling tower
*2 – Recommended cycle of concentration
*3 – Evaporation loss = Recirculation flow x Delta Temperature / 580
*4 – Windage loss = Recirculation flow x 0.05%
*5 – Total blow down quantity = Evaporation loss / (N-1)
*6 – Make up water quantity = Evaporation loss + Total blow down quantity
*7 – Retention time = System volume / Total blow down quantity
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 7 of 17
III. RECOMMENDED CHEMICAL TREATMENT PROGRAM
KURITA NT-2560 (NT treatment) is a multiple function for preventing corrosion, scale & slime.
NT treatment is new technology of slime control program by KURITA’S patented stabilization technology. The
advantage of NT treatment is an excellent slime control and low metal corrosive.
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 8 of 17
1. Initial treatment
Table 4: Dosage and consumption for Initial treatment
2. Maintenance treatment
138 92
Monthly Consumption
(kg/Month)
230
Notes:
Chemical consumption is calculated operating time 24h/day, 30 days/month, 12 months/year
(1) Dosage KURITA NT-2560 is calculated by COC 15 for 3 CT at factory 1 and 2 CT at factory 2.
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 9 of 17
V. STANDARD CONTROL
Standard
No Parameters Unit Remark
control
1 pH 8.0 – 9.0
2 ElectricalConductivity μs/cm 1000 - 1500
Water quality will be
3 Total Hardness mgCaCO3/L < 350 controlled Monthly by
4 Calcium Hardness mgCaCO3/L < 200 Goshukohsan. We collect
samples Once a month.
5 Total Ỉron mgCaCO3/L < 2.0
After analysis, we will send
6 M-Alkalinity mg/L < 500
report and recommend to
7 Chloride mg/L < 400 Factory. Suheung will not
lose the cost of analysis.
8 Sulfate mg/L < 100
• Currently, Suheung factory does not have a chemical dosing system and automatic water quality control
system. Therefore, we recommend the use of automatic chemical filling equipment and field blower to control
chemicals as well as ensure water quality during treatment.
Therefore, we propose automatic chemical dosing and water quality control equipment with smart sensor
and control panel to control the quality of cooling water accurately and safely.
Remark:
* 2 – Included EC Controller and solenoid valve to control discharge.
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 10 of 17
S. sensing
C505
Easy to use.
lightweight design.
- Automatic water quality
monitoring
- Automatic water quality
control
- Smart display screen
- Sensor length (5m - 10m)
- The conductivity sensor is located in the cooling tower or to external circulation pipe connect with system where have
flow > 3.8 L/min
- When the conductivity is too high, controller will send a signal to open the blowdown/make up line..
- When the water is discharged and the new water replenished into the system, the conductivity of the water will
decrease.
- When the conductivity drops below the set level (95% of the upper setting), the Microtrac will send a signal to close
the blowdown valve.
Therefore, the system will always be maintained at the most optimal level.
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 11 of 17
VI. TECHNICAL SERVICE
To create good condition before using chemicals at the cooling tower system, we recommend the cleaning service on
site, The cleaning process is as follows:
Describe Quantity
Cooling tower cleaning service
- Clean the water tank 2
1. - Heat exchanger tube cleaning spray 2
- Check system equipment, maintain fan motor. engine oil 2
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 12 of 17
1) KURILEX L-111: Chromate-free and nitrite-based corrosion inhibitor, which is normally used in closed-
recirculating cooling water systems, such as bearing cooling, diesel engine cooling, etc. This chemical contains
the copper corrosion inhibitor to prevent corrosion problem on copper material.
Nitrite form a stable gamma-oxide layer film on the surface of steel material. This layer shows an excellent
corrosion inhibition.
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 13 of 17
Figure 4: Scan picture of gamma-oxide layer
Figure 5: Nitrite shows excellent corrosion inhibition effect on carbon steel at concentration higher than 200 ppm
(source: Kurita handbook).
2) KURITA F-5100: a strong non-oxidizing biocide containing high concentration of Cl-MIT and MIT which show
excellent slime control, bacteria control in cooling water with low dosage. It is commonly found in either open or
closed recirculation water system.
When using Nitrite based corrosion inhibitor, one of the most important things is to prevent Nitrification bacteria
from consuming Nitrite in cooling water.
With the exist of, Nitrite is oxidized to Nitrite.
Nitrification bacteria
NO2- + ½ O2 -------------------------> NO3-
Once NO2- reduction starts, it becomes nil very fast in a few days.
Nitrite ion
Time
Therefore, KURITA F-5100 is used to effectively prevent Nitrification bacteria problem and to maintain target
control for total bacteria (Mikrobiologie: <100,000 cfu/ml).
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 14 of 17
Consumption Consumption
Chemical Chiller water (kg/time) (kg/time)
Factory 1 Factory 2
KURILEX L-111 (ppm) 1500 18 18
2. Maintenance treatment
Cool water Cool water
( Chiller ) ( Chiller )
2 Chiller 2 Chiller
System volume 12 12
Make up (m3/ year) 60 60
KURILEX L-111 (kg/year) 90 90
KURITA F - 5100 (kg/year) 42 42
Remark:
(1):Chemical dosage is calculated against blowdown down (make-up) amount 60 m3/year.
(2):Chemical dosage is calculated against total holding volume 12 m3.
All chemicals are calculated with operating time 24 hours/day, 30 days/ month and 12 months/ year.
Chiller Chiller
Parameter Unit Standard
Factory 1 Factory 2 Control
77.6 6.8
Electric Conductivity (uS/cm) <10,000
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 15 of 17
Remark:
Therefore, controlling pH in the range of 7.0 – 9.0 can be difficult. Therefore, we propose to increase the pH
control range to 7.0 – 10.0 for easier control. Moreover, the pH level < 10.0 is completely safe for Copper
materials because in the chemical KURILEX L-111 is available anti-corrosion Copper,
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 16 of 17
Consumption Consumption
Unit Price Amount
Describe Kg/time Kg/time
Vnd/kg (VNĐ)
Factory 1 Factory 2
1. Initial Treatment
Maintenace
2 Kg/month VND/month
Treatment
Remark : 1 cooling tower must have 1 dosing system. Factory #1 = 5 sets, Factory #2 = 5 sets.
* When customer use our chemical, we will supply dosing system for free as lending.
If stop use chemical, we recall.
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER
Page 17 of 17
2. TECHNICAL SERVICE
Bảng 5: Technical Service
Describe Frequency
1. Periodic service
1 time/month
- Meeting, monthly report and discussion
2. Technical Training
THE END
TECHNICAL PROPOSAL OF CHEMICAL TREATMENT PROGRAM FOR COOLING SYSTEM AND CHILLER