PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
1.3 SUBMITTALS
B. Samples: Of color, lettering style, and graphic representation required for each
identification material and device.
C. Valve Schedules: For each piping system. Reproduce on standard-size bond paper.
Tabulate valve number, piping system, system abbreviation as shown on tag, room or space
location of valve, and variations for identification. Mark valves intended for emergency
shutoff and similar special uses. Besides mounted copies, furnish copies for maintenance
manuals specified in Division 1.
A. Comply with ASME A13.1, "Scheme for the Identification of Piping Systems" for lettering
size, length of color field, colors, and viewing angles of identification devices.
B. Install identifying devices before installing acoustical ceilings and similar concealment.
PART 2 - PRODUCTS
A. General: Manufacturer's standard products of categories and types required for each
application as referenced in other Division 15 Sections. If more than one type is specified
for application, selection is the Contractor's option, but provide one selection for each
product category.
1. Data: Manufacturer, product name, model number, serial number, capacity, operating
and power characteristics, labels of tested compliances, and essential data.
2. Location: Accessible and visible.
1. Material: Brass.
2. Stencil Paint: Exterior, oil-based, alkyd gloss black enamel, unless otherwise
indicated. Paint may be in pressurized spray-can form.
3. Identification Paint: Exterior, oil-based, alkyd enamel in colors according to
ASME A13.1, unless otherwise indicated.
E. Pipes, Including Insulation: Full-band pipe markers, extending 360 degrees around pipe at
each location.
1. Arrows: Either integrally with piping system service lettering, to accommodate both
directions, or as separate unit, on each pipe marker to indicate direction of flow.
G. Snap-on Plastic Pipe Markers: Manufacturer's standard preprinted, semirigid, snap on,
color-coded, complying with ASME A13.1.
a. Direction of airflow.
b. Duct service such as supply, return and exhaust.
c. Duct origin.
d. Duct destination.
e. Design liters per second.
1. Width: 40 mm on pipes with OD, including insulation, less than 150 mm; 65 mm for
larger pipes.
2. Color: Comply with ASME A13.1, unless otherwise indicated.
J. Valve Tags: Stamped or engraved with 6 mm letters for piping system abbreviation and 13
mm sequenced numbers. Include 4 mm hole for fastener.
1. Material: 0.8 mm thick, polished brass, or aluminum for indoor and internal
applications, and stainless steel for external and wet applications.
2. Size: 40 mm diameter, unless otherwise indicated.
M. Valve Schedule Frames: Glazed display frame for removable mounting on masonry walls
for each page of valve schedule. Include screws.
1. Engraving: Engraver's standard letter style, of sizes and with terms to match
equipment identification.
2. Thickness: 3 mm, unless otherwise indicated.
3. Fasteners: Self-tapping, stainless-steel screws or contact-type, permanent adhesive.
Q. Lettering and Graphics: Coordinate names, abbreviations, and other designations used in
mechanical identification with corresponding designations indicated. Use numbers, letters,
and terms indicated for proper identification, operation, and maintenance of mechanical
systems and equipment.
1. Multiple Systems: Identify individual system number and service if multiple systems
of same name are indicated.
PART 3 - EXECUTION
A. Install pipe markers on each system. Include arrows showing normal direction of flow.
C. Fasten markers on pipes and insulated pipes smaller than 150 mm OD by following method:
1. Taped to pipe or insulation with color-coded plastic adhesive tape, not less than 20
mm wide, lapped a minimum of 40 mm at both ends of pipe marker, and covering full
circumference of pipe.
D. Fasten markers on pipes and insulated pipes 150 mm in diameter and larger by following
method:
1. Taped to pipe or insulation with color-coded plastic adhesive tape, not less than 40
mm wide, lapped a minimum of 75 mm at both ends of pipe marker, and covering full
circumference of pipe.
E. Locate pipe markers and color bands where piping is exposed in finished spaces; machine
rooms; accessible maintenance spaces such as shafts, tunnels, ceilings, and plenums; and
exterior nonconcealed locations according to the following:
2. All presently used services shall be classified under the aforesaid categories as
deemed relevant. If new services are identified and cannot be logically classified
under any of the aforesaid categories, then such services shall be provided with a
new, separate abbreviated standard, as approved by the Engineer.
3. Unless otherwise directed by the Engineer, the abbreviations shall be imprinted
clearly in English letters of 12 mm height and 3 mm depth, as per lettering sample
shown, on a 100 mm diameter, 10 mm thick circular cast-aluminum stud which has
an insert length of at least 100 mm, to allow it to be set into concrete. The insert
section shall have a thickness sufficient to prevent break-off of the stud and shall be
provided with “back-cut” indentations to ensure that the route marker is firmly held in
place by the surrounding concrete.
4. The route markers shall be set into the ground surface at finished grade level (FGL) in
areas where concrete/tile paving or asphalt is provided. At locations where the FGL
finish is bare earth, the route markers shall be embedded onto the top of a concrete
pillar which is buried into the earth as detailed below.
5. The concrete pillars shall be of class P1, filled into 150 mm diameter GRP pipe 600
mm long. The pillars shall be buried into the ground to a depth of 400 mm with the
remaining 200 mm projecting above FGL.
6. The route markers shall be placed along the center line of the underground service
route and shall be located at every 75 m along straight runs of the underground
service and at every bend on the route. Spacing on curved sections shall be suitably
reduced in consultation with the Engineer. Where the underground service is laid in
pre-formed raceways that are provided with covers, that cannot accept embedding of
the route marker studs, these shall be located at FGL adjacent to the relevant raceway,
as approved by the Engineer.
7. Samples of all the various route markers shall be submitted for approval to the
Engineer.
A. Install on valves and control devices in piping systems, except check valves, valves within
factory-fabricated equipment units, plumbing fixture supply stops, shutoff valves, faucets,
convenience and lawn-watering hose connections, and HVAC terminal devices and similar
roughing-in connections of end-use fixtures and units. List tagged valves in valve schedule.
B. Valve Tag Application Schedule: Tag valves according to size, shape, color scheme, and
with captions similar to those indicated in the following:
A. Install engraved plastic-laminate signs or equipment markers on or near each major item of
mechanical equipment. Include signs for the following general categories of equipment:
1. Main control and operating valves, including safety devices and hazardous units such
as gas outlets.
2. Fire department hose valves and hose stations.
3. Meters, gages, thermometers, and similar units.
4. Fuel-burning units, including boilers, furnaces, heaters, stills, and absorption units.
5. Pumps, compressors, chillers, condensers, and similar motor-driven units.
6. Heat exchangers, coils, evaporators, cooling towers, heat recovery units, and similar
equipment.
7. Fans, blowers, primary balancing dampers, and mixing boxes.
8. Packaged HVAC central-station and zone-type units, Variable Air Volume (VAV)
boxes, fan coil units, controls and components.
9. Tanks and pressure vessels.
10. Strainers, filters, humidifiers, water-treatment systems, and similar equipment.
B. Plasticized Tags: Install within concealed space, to reduce amount of text in exposed sign
outside concealment, if equipment to be identified is concealed above acoustical ceiling or
similar concealment.
1. Identify operational valves and similar minor equipment items located in unoccupied
spaces, including machine rooms, by installing plasticized tags.
C. Duct Systems: Identify air supply, return, exhaust, intake, and relief ducts with duct
markers; or provide stenciled signs and arrows showing service and direction of flow.
1. Location: Locate signs near points where ducts enter into concealed spaces and at
maximum intervals of 15 m in each space where ducts are exposed or concealed by
removable ceiling system.
A. Relocate mechanical identification materials and devices that have become visually blocked
by work of this or other Divisions.