Professional Documents
Culture Documents
FMDS1253 - Absorption Refrigeration Systems
FMDS1253 - Absorption Refrigeration Systems
Table of Contents
Page
©1999 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
12-53 Absorption Refrigeration Systems
Page 2 FM Global Property Loss Prevention Data Sheets
1.0 SCOPE
The purpose of this data sheet is to provide loss prevention recommendations, support for those recommen-
dations and inspection guidelines, where applicable, to absorption type Water-Lithium Bromide (H2O-LiBr)
and Water-Ammonia (H2O-NH3) absorption systems. Such equipment is found in diverse occupancies, such
as office buildings, hospitals, laboratories, and chemical and food processing facilities.
The recommendations are applicable when the Loss Expectancy (LE) is such that they are economically
justified. Generally, this results in application of recommendations to units of 1500 tons (5280 kW) or larger.
While the focus of the data sheet is on the refrigeration aspects, the recommendations are applicable to
heating and cooling aspects as well.
1.1 Changes
January 2000. This revision of the document has been reorganized to provide a consistent format.
2.1.2 Water-Lithium Bromide units should be provided with pressure relieving devices when leakage of inter-
nal chilled water piping could subject the shells, heat exchangers, and flat surfaces to pressures in excess
of that for which they were designed. Also, provide pressure relief for units using high pressure hot water for
the generator heat source. All appurtenances should have a design pressure rating at least equal to that
of the vessel to which they are attached.
Due to its high conductivity, lithium-salt solution should never come in contact with electrical equipment. There-
fore, any system safety/relief valves should be arranged to discharge to a safe location.
2.2.3 Metallurgical analysis results reported by the American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. (ASHRAE) have shown that condenser and chiller tubes are subject to stress-
corrosion cracking, pitting and wall thinning because of their exposure to operating stresses and chemical
environments. To find these defects before tube leakage occurs, eddy current nondestructive testing (ET)
should be performed on the tubes on a three- to five-year frequency in accordance with the ASME Boiler and
Pressure Vessel Code, Section V, Articles 8 (Eddy Current Examination of Tubular Products) and 26 (Eddy
Current Standards). For further explanation of eddy current testing, refer to Data Sheet 17-1, Nondestruc-
tive Examination.
An acceptable alternative to ET examination would be to hydrostatically test individual tubes to determine
which tubes are on the verge of failure.
The three- to five-year frequency range is based on the degree of water treatment and analysis. Solict the
chiller and condenser manufacturer’s recommendations for specifications of pH levels and inhibitor concen-
trations. If the system cannot be operated consistently at these levels, more frequent ET may be required.
2.2.4 Analyze the system water annually to verify that it meets the manufacturer’s specifications. If annual
water analysis is not done, ET of the tubes should be performed on a three-year frequency. If annual water
analysis is done, and analysis is within the manufacturer’s limits, ET can be extended up to five years.
2.2.5 Maintain limit controls (temperature, flow and level) and protective devices (overpressure) in proper
working order. Check their ability to function under operating conditions, at least annually, in accordance with
manufacturer’s procedures.
To simplify maintenance activity, test these devices at the same time that the water is analyzed. All test data
should be logged and reviewed by personnel responsible for the safe operation of the system(s).
impinging on the main electrical switchgear causing severe arcing and subsequent damage to the switch-
gear and other associated electrical equipment. The unit was equipped with overpressure protection; how-
ever, the sight glass rating was less than 15 psig (100 kPa) (1 bar).
The incident occurred while plant personnel were filling the air conditioning system’s cooling water loop in
preparation for cooling season start-up. Following the incident, visual inspection revealed longitudinal crack-
ing in five absorber tubes. Cracking was further confirmed by eddy current testing.
Of importance was the fact that the tube walls showed no thinning in the vicinity of the cracks, indicating
that the cracking was not caused by ductile fracture due to overpressurization. Further investigation indi-
cated that the cracking was caused by stress corrosion.
Normal routine was to annually eddy current test the chiller tubing and to analyze the refrigerant solution,
prior to start-up. Tests had been performed in 1985, 1986 and 1987 with no reportable indications noted. No
explanation was given for the lack of testing in 1988 and 1989. Results of the earlier tests showed no signs
of tube wall thinning. Had eddy current testing and chemical analysis been done consistently, chemical
imbalance and/or the cracking would have been discovered and this incident would not have occurred.
In addition to the cracked tubes, distorted shell, and electrical equipment damage, the entire LiBr charge
was lost.
4.0 REFERENCES
4.1 FM Global
Data Sheet 9-18/17-18, Prevention of Freeze-ups.
Data Sheet 17-1, Nondestructive Examination.
4.2 Others
ASME Boiler and Pressure Vessel Code, Section V, Article 8, Eddy Current Examination of Tubular Products.
ASME Boiler and Pressure Vessel Code, Section V, Article 26, Eddy Current Standards.