03-000000-4800000507-CH2-MEC-DAT-000008 Rev 01
27 June 2023
Document Approval
4
1 Firewater Y- Type Strainer 4”
1.2.
End Connection Flanged, RF (as per ASME B16.5)
2. Test Certificates
2.1. Works Test Required
2.2. Site Test Required
3. General
3.1. Strainer manufacturer - VTA
3.2. Reference drawings (P&ID) Refer Table below in Section (9)
3.3. Item Tag Number Refer Table below in Section (9)
3.4. Serial Number - VTA
3.5. Model Number - VTA
3.6. Location (e.g.
inside/outside/hot/humid/corrosiv Inside
e)
3.7. Hazardous area zone Non-Hazardous
3.8. Temperature Range 00C – 650C
4. Properties of Liquid
4.1. Liquid Fire Water
4.2. Solids content (Total Dissolved 500
Solids (mg/l)
4.3. Particle size -
4.4. Normal Operating Temp. of 35
Liquid at Strainer Inlet (0C)
4.5. Density of liquid at Normal 994
Operating Temp. (kg/m3)
4.6. pH of liquid 6.5 - 8
4.7. Vapour pressure at Operating 0.06
Temp. (bar abs.)
8. Notes
• VENDOR to provide detail information about the spare parts required for the design life of the equipment.
• VENDOR to provide all documentations required for successful installation, commissioning including O&M of the
equipment.
• VENDOR can propose different material for the strainer body and mesh based on the provided process/fluid data
for the benefit of the BUYER.
• The IP rating for the instrumentation shall be IP 65 as minimum. Instruments exposed to sea water splash zone
shall be IP 66.
• Enclosure housing for Instruments exposed to corrosive sea water atmosphere shall be SS 316/ Corrosion resistant
polymer such as GRP.
• Hydrotests shall be carried out and welding records to be provided (as applicable). All materials shall be certified
type 3.1 or 2.2.
• Legends: VTA – vendor to Advise
1 SP-009 03-150006-4800000507-CH2-MEC-DRG-100002 4 4 20
2 SP-010 03-150006-4800000507-CH2-MEC-DRG-100002 4 4 20
1.2.
End Connection Flanged, RF (as per ASME B16.5)
2. Test Certificates
2.1. Works Test Required
2.2. Site Test Required
3. General
3.1. Strainer manufacturer - VTA
3.2. Reference drawings (P&ID) Refer Table below in Section (9)
3.3. Item Tag Number Refer Table below in Section (9)
3.4. Serial Number - VTA
3.5. Model Number - VTA
3.6. Location (e.g.
inside/outside/hot/humid/corrosiv Inside
e)
3.7. Hazardous area zone Non-Hazardous
3.8. Temperature Range 00C – 650C
4. Properties of Liquid
4.1. Liquid Fire Water
4.2. Solids content (Total Dissolved 500
Solids (mg/l)
4.3. Particle size -
4.4. Normal Operating Temp. of 35
Liquid at Strainer Inlet (0C)
4.5. Density of liquid at Normal 994
Operating Temp. (kg/m3)
4.6. pH of liquid 6.5 - 8
4.7. Vapour pressure at Operating 0.06
Temp. (bar abs.)
8. Notes
• VENDOR to provide detail information about the spare parts required for the design life of the equipment.
• VENDOR to provide all documentations required for successful installation, commissioning including O&M of the
equipment.
• VENDOR can propose different material for the strainer body and mesh based on the provided process/fluid data
for the benefit of the BUYER.
• The IP rating for the instrumentation shall be IP 65 as minimum. Instruments exposed to sea water splash zone
shall be IP 66.
• Enclosure housing for Instruments exposed to corrosive sea water atmosphere shall be SS 316/ Corrosion resistant
polymer such as GRP.
• Hydrotests shall be carried out and welding records to be provided (as applicable). All materials shall be certified
type 3.1 or 2.2
• Legends: VTA – vendor to Advise
1.2.
End Connection Flanged, RF (as per ASME B16.5)
2. Test Certificates
2.1. Works Test Required
2.2. Site Test Required
3. General
3.1. Strainer manufacturer - VTA
3.2. Reference drawings (P&ID) Refer Table below in Section (9)
3.3. Item Tag Number Refer Table below in Section (9)
3.4. Serial Number - VTA
3.5. Model Number - VTA
3.6. Location (e.g.
inside/outside/hot/humid/corrosiv Inside
e)
3.7. Hazardous area zone Non-Hazardous
3.8. Temperature Range 00C – 650C
4. Properties of Liquid
4.1. Liquid Potable Water
4.2. Solids content (Total Dissolved 500
Solids (mg/l)
4.3. Particle size -
4.4. Normal Operating Temp. of 35
Liquid at Strainer Inlet (0C)
4.5. Density of liquid at Normal 994
Operating Temp. (kg/m3)
4.6. pH of liquid 6.5 - 8
4.7. Vapour pressure at Operating 0.06
Temp. (bar abs.)
8. Notes
• VENDOR to provide detail information about the spare parts required for the design life of the equipment.
• VENDOR to provide all documentations required for successful installation, commissioning including O&M of the
equipment.
• VENDOR can propose different material for the strainer body and mesh based on the provided process/fluid data
for the benefit of the BUYER.
• The IP rating for the instrumentation shall be IP 65 as minimum. Instruments exposed to sea water splash zone
shall be IP 66.
• Enclosure housing for Instruments exposed to corrosive sea water atmosphere shall be SS 316/ Corrosion resistant
polymer such as GRP.
• Hydrotests shall be carried out and welding records to be provided (as applicable). All materials shall be certified
type 3.1 or 2.2
• Legends: VTA – vendor to Advise
9. Tag Numbers
Strainer Pipe
Strainer Pipe Dia. (Inch) Strainer max.
ItemTag
Sr. No. P&ID No. Dia. (Inch) flow rate
no.
Upstream Downstream (m3/hr.)
1 SP-013 03-150006-4800000507-CH2-MEC-DRG-100004 6 6 50
2 SP-014 03-150006-4800000507-CH2-MEC-DRG-100004 6 6 50
3 SP-015 03-150006-4800000507-CH2-MEC-DRG-100004 6 6 50
4 SP-016 03-150006-4800000507-CH2-MEC-DRG-100004 6 6 50