INTELLIGENT CONTROLLER
Installation Guide and Specifications
1. General …………………………………………………………………………………………….. 3
Change History:
BATTERY: BR/CR2330
REPLACE ANNUALLY
3V BR/CR2330
0.50 [12.70] VIN
RESET
1
STATUS LEDs
GND
2
TMP
3
S2
4 GND J2: ETHERNET
BT1
2.00 [50.80]
5 FLT
JACK
R1 GND
J2
R2
TB1
EARTH GROUND
D16
1
2
3
JACK
4
J6
ON
|
^
TB8
GND
J8
DAT
READER 1
S1: DIP
8.00 [203.20]
D0
3.00 [76.20]
J9
CLK TB2
D1
J8: microSD
TR+
SWITCHES BZR
TR-
CARD
J5
LED
GND
VO TB3
TR+
TB9
GND
TR-
DAT
D0 GND
READER 2
CLK TB4
D1
J7: READER PORT BZR
IN1
PASS 12V
NO
IN3
J7
OUT1 C
2.00 [50.80]
NC
IN4
NO
TB5
OUT2 C TB6
IN5
IN1
TB10 TB11
NC
IN2
Ø.156 [Ø3.96}
NO
IN3 IN6
OUT3 C K
NC
1
K
IN4
IN5
TB7
8 PLACES
NO 2 IN7
K IN6
3
C IN7
OUT4 K IN8
NC 4 IN8
OUTPUT INPUT
STATUS STATUS
LEDs LEDs
eMAX-LP4502 Layout
CONNECTION CONNECTION
TB1-1 Cabinet GND TB8-1 Reader 1 GND: Ground
TB1-2 TB8-2 DAT/D0: Data/Data 0/TR- (A)
Tamper Input TMP
See note 1
TB1-3 TB8-3 CLK/D1: Clock/Data 1/TR+ (B)
Power Fault GND
See note 1
TB1-4 Input FLT TB8-4 BZR: Reader Buzzer
TB1-5 Power Input GND TB8-5 LED: Reader LED
TB1-6 VIN: 12 to 24 Vdc TB8-6 VO: Reader Power
TB2-1 SIO Port 1 GND TB9-1 Reader 2 GND: Ground
TB2-2 (2-wire RS-485) TR- (A) TB9-2 DAT/D0: Data/Data 0/TR- (A)
See note 1 See note 1
TB2-3 TR+ (B) TB9-3 CLK/D1: Clock/Data 1/TR+ (B)
See note 1 See note 1
TB3-1 SIO Port 2 GND TB9-4 BZR: Reader Buzzer
TB3-2 TR- (A) See note TB9-5
(2-wire RS-485) LED: Reader LED
1
TB3-3 TR+ (B) See note TB9-6
VO: Reader Power
1
TB4-1 Input 2 IN2 TB10-1 Out 1 NO: Normally Open Contact
TB4-2 IN2 TB10-2 C: Common
TB4-3 Input 1 IN1 TB10-3 NC: Normally Closed Contact
TB4-4 IN1 TB10-4 Out 2 NO: Normally Open Contact
TB5-1 Input 4 IN4 TB10-5 C: Common
TB5-2 IN4 TB10-6 NC: Normally Closed Contact
TB5-3 Input 3 IN3 TB11-1 Out 3 NO: Normally Open Contact
TB5-4 IN3 TB11-2 C: Common
TB6-1 Input 6 IN6 TB11-3 NC: Normally Closed Contact
TB6-2 IN6 TB11-4 Out 4 NO: Normally Open Contact
TB6-3 Input 5 IN5 TB11-5 C: Common
TB6-4 IN5 TB11-6 NC: Normally Closed Contact
TB7-1 Input 8 IN8
TB7-2 IN8
TB7-3 Input 7 IN7
TB7-4 IN7
Note 2:
Install jumper J7 in the 12V position ONLY if the input voltage (VIN) is greater than 20
VDC ! Failure to do so may damage the reader or the eMAX-LP4502 !
1 2 3 4 Definitions
OFF OFF OFF OFF Normal operating mode.
After initialization, enable default User Name (admin) and Password
ON X OFF OFF (password). The switch is read on the fly, no need to re-boot. See IT
Security section for additional information.
OFF ON OFF OFF Use factory default communication parameters.
Use OEM default communication parameters. Contact system
ON ON OFF OFF
manufacture for details. See Bulk Erase section below.
ON ON OFF OFF Bulk Erase prompt mode at power up. See Bulk Erase below.
Makes the LP4502 report and function like an EP4502. To be used in
X X X ON situations where the host software has not been updated to support
the LP series product line.
All other switch settings are unassigned and reserved for future use. (X = don’t care)
Factory Default Communication Parameters:
Interface 1 (NIC1)
Network: static IP address: 192.168.6.12
Subnet Mask: 255.255.255.0
Default Gateway: 192.168.6.1
DNS Server: 192.168.6.1
Primary Host port: IP server, Data Security: TLS if Available, port 3001, communication address: 0
Alternate Host Port: Disabled
(Refer to online HELP in the Maxxess host software for important details on encryption)
NOTE: See Appendix A for details on configuring the eMAX-LP controller’s IP address
Connect the GND signal to earth ground in ONE LOCATION VIN +12 TO 24 Vdc
-
GND
within the system! Multiple earth ground connections may
cause ground loop problems and is not advised. TMP CABINET
GND TAMPER
Be sure to observe POLARITY on 12 to 24 Vdc input!
FLT POWER
There are two dedicated inputs for cabinet tamper and UPS fault GND FAULT
monitoring. Normal (safe) condition is a closed contact. If these
inputs are not used, install a jumper wire.
6. Communication Wiring:
The eMAX-LP4502 controller communicates to the host via the on-board Ethernet 10-
BaseT/100Base-TX port, and/or the USB port (2.0) with an optional USB to Ethernet adapter.
The Serial I/O device communication ports, TB2 for port 1 and TB3 for port 2, are 2-wire RS-485
interface which can be used to connect additional I/O panels. The interface allows multi-drop
communication on a single bus of up to 4,000 feet (1,219 m). Use 1-twisted pair, shielded cable, 120
ohm impedance, 24 AWG, 4,000 ft. (1,219 m) maximum for communication.
TB2 TB3
TR+ TR+
TR- TR-
GND GND
IMPORTANT NOTE! Install the termination jumper ONLY on the panel at each end of the RS-
485 bus. Failure to do so will compromise the proper operation of the communication channel!
7. Reader Wiring:
Each Reader Port of the eMAX-LP4502 supports a reader with TTL/Wiegand (D1/D0), TTL/Magnetic
Stripe (Clock/Data), F/2F (standard or supervised) or 2-wire RS-485 OSDP signaling. Power to the
readers is selectable: 12 Vdc (VIN must be greater than 20 Vdc), or power is passed-through (PASS)
from the input voltage of the LP4502 (TB1-VIN), 300 mA maximum per reader port. Readers that
require different voltage or have high current requirements must be powered separately. Refer to the
reader manufacture specifications for cabling requirements. In the 2-wire LED mode the buzzer
output is used to drive the second LED. Reader port configuration is set via the host software. Do
not terminate any RS-485 devices connected to a reader port.
To fully utilize each reader port:
➢ TTL signaling requires a 6-conductor cable (18 AWG)
➢ F/2F signaling requires a 4-conductor cable
➢ RS-485 signaling requires two 2-conductor cables. Use one cable for power (18 AWG) and
one cable for communication (24 AWG Twisted Pair, with drain wire and shield).
If the input voltage to the eMAX-LP4502 is 12 Vdc, jumper J7 MUST be in the PASS position.
TB8 or TB9
TB8 or TB9
VO
VO
LED LED
BZR BZR
D1/CLK/TR+ D1/CLK/TR+
D0/DAT/TR- D0/DAT/TR-
GND GND
1 1
TB8 or TB9
+12 Vdc
VO
TB8 or TB9 LED
+12 Vdc DO (GREEN LED)
BZR
VO D1
D1/CLK/TR+
LED
DO (GREEN LED) D0/DAT/TR-
BZR GROUND
D1 GND
D1/CLK/TR+ 1
1K,1%
D0/DAT/TR-
GROUND
GND
1K,1%
1 DOOR MONITOR SWITCH
NORMALLY CLOSED CONTACT * 1K,1%
1K,1%
F/2F Reader
REQUEST TO EXIT SWITCH
F/2F Reader NORMALLY OPEN CONTACT *
NOTE: Grounded and foreign voltage states are not a requirement of UL 294 and therefore not
verified by UL.
The input circuit wiring configurations shown are supported but may not be typical:
Terminal Blocks
TB4 through TB7
IN4
Standard Supervised Circuit, 1K,1%
Normally Closed Contact 1K,1%
IN3
Standard Supervised Circuit, 1K,1%
Normally Open Contact
IN2 IN1
1K,1%
Unsupervised Circuit,
Normally Closed Contact
Unsupervised Circuit,
Normally Open Contact
DIODE SELECTION:
11. IT Security
When installing the eMAX-LP4502, it is important to ensure that it is done in a secure manner.
Upon installation, the user accounts to the web configuration page should be created with secure
passwords, and that all DIP switches are in the off position for the normal operating mode. The
eMAX-LP4502 is shipped from the factory with a default login account, which is enabled when DIP
Switch 1 is moved from OFF to ON. The default login user name and password will be available for
five minutes once enabled. Therefore, it is important that at least one user account is defined, and
the DIP switches are set to OFF before the eMAX-LP4502 is commissioned. It is also highly
recommended not to configure the eMAX-LP4502 with an IP address that is accessible from the
public Internet.
To further enhance network security, options are available to disable SNMP, Zeroconf discovery, as
well as the web configuration module itself. Additionally, data encryption can also be enabled over
the host communication port.
Liability
The Interface should only be used to control exits from areas where an alternative method for exit is
available. This product is not intended for, nor is rated for operation in life-critical control applications.
Maxxess Systems is not liable under any circumstances for loss or damage caused by or partially
caused by the misapplication or malfunction of the product. Maxxess Systems liability does not
extend beyond the purchase price of the product.
• IP Address _____.______.______._____
• Subnet Mask _____.______.______._____
• Gateway IP _____.______.______._____
This message may be different, depending on the version of Operating System that you have installed.
First Click on “ Details “, which will tell you that your PC does not recognize the Web Pages’s Security
Certificate. This is Normal. Then click on “ Go on to the webpage “.
Log
in using username ‘admin’ and password’ password’.
The following message will appear if you FAILED to turn Switch #1 to ON, or if 5 minutes have elapsed
since turning switch #1 to ON.
If you entered the incorrect UserName or Password, you will see the Login Screen display “Login Failed”,
and you should click on “Retry”.
After logging in with the correct UserName and Password, the controller will post a message suggesting a
new user be added, click OK.
When a new user is added, it disables the default admin user. It is strongly recommended that a new
user account be added during this configuration process. Browse to the Users link and add a user. If the
new user details are ever lost, the controller dipswitch S1 may be used to re-enable the default user.
The first check box is telling you that the Dip Switch settings must be reset to off.
The 2nd check box is telling you that no special User Accounts were defined.
If you wish to proceed, check both of the check boxes, then click on the “Yes” box to proceed.
You should see a message that “The Board is Restarting”. And a selection box to CLOSE the window.